Professional Documents
Culture Documents
REGSys
Operating Manual
Issue: 2007-02-21_01
Controller _______________
REG-DPA
with optional
Current Injection
REG-DPA a-eberle
Operating manual
Edited by:
Tel.: 0911 / 62 81 08 - 0
Fax: 0911 / 66 66 64
e-mail: info@a-eberle.de
Internet: www.a-eberle.de
The company A.Eberle Gmbh & CoKG cannot be held liable for any damages or losses emitting from
printing errors or changes in this operating manual.
Furthermore, A.Eberle Gmbh & CoKG does not assume responsibility beyond the guarantee period for any
damages and losses resulting from deficient devices or from devices changed by the applicant.
2 Druml: BA_REG-DPA_e_2007_01_01_012.doc
REG-DPA a-eberle
Table of Content
Druml: BA_REG-DPA_e_2007_01_01_012.doc 3
REG-DPA a-eberle
3.6.2 AC - voltage inputs .................................................................................................................. 68
3.6.3 AC - current inputs................................................................................................................... 68
3.6.4 Binary inputs ............................................................................................................................ 68
3.6.5 Binary outputs: relays ............................................................................................................. 69
3.6.6 Controller for Current Injection ( CCI )..................................................................................... 70
3.7 Current Injection CI using CCI ......................................................................................................... 75
3.7.1 Principal schemas.................................................................................................................... 75
3.7.2 Indoor version .......................................................................................................................... 77
3.7.3 Outdoor version ....................................................................................................................... 77
3.7.4 19" version ............................................................................................................................... 78
3.7.5 Example for outdoor motor-drive version ................................................................................ 79
3.7.6 Example for 19" rack mounted indoor version......................................................................... 80
4 REG-DP(A) .............................................................................................................................................. 81
4.1 Indication and Operation Elements ................................................................................................. 81
4.1.1 LCD Display ............................................................................................................................. 82
4.1.2 Keys ......................................................................................................................................... 83
4.1.3 Plug Connection at the Front ................................................................................................... 83
4.2 Human-Machine Interface (HMI) ..................................................................................................... 84
4.3 Selection of the Display Mode ......................................................................................................... 86
4.3.1 <F1> Resonance Curve.......................................................................................................... 87
4.3.2 <F2> Detail Display ................................................................................................................ 87
4.3.3 <F3> Current Injection Measurement...................................................................................... 88
4.3.4 Operation-mode Recorder ....................................................................................................... 89
4.3.5 Statistics................................................................................................................................... 91
4.4 SETUP ............................................................................................................................................. 93
5 Commissioning ........................................................................................................................................ 97
5.1 WinEDC ........................................................................................................................................... 97
5.1.1 Installation................................................................................................................................ 97
5.1.2 Shortcuts of WinEDC............................................................................................................... 99
5.1.3 Physical connection ................................................................................................................. 99
5.1.4 Assumed settings on the REG-DP(A) ..................................................................................... 99
5.2 Firmware Update REG-DP(A) ....................................................................................................... 100
5.3 REG-DP(A) R: Send the Standard Parameterization Set to device ............................................. 103
5.4 Check of Communication REG-DP(A) <=> CCI .......................................................................... 106
5.5 Calibration of the coil ..................................................................................................................... 107
5.6 Linearization of the coil .................................................................................................................. 110
5.7 Check of Current Injection ............................................................................................................. 111
5.7.1 Requirements for Test of CI................................................................................................... 111
5.7.2 Check of the Current Injection ............................................................................................... 112
5.8 Check of Digital- and Analogue Inputs .......................................................................................... 119
5.9 Check of Signalling on the Panel and to SCADA .......................................................................... 120
5.10 Second Controller for example: REG-DP(A) V:............................................................................. 122
5.11 System voltage unequal to 20 kV .................................................................................................. 123
6 Parameterization Software: WinEDC .................................................................................................... 125
6.1 General Functions of WinEDC ...................................................................................................... 125
6.1.1 Parameterization.................................................................................................................... 126
6.2 REG-DP(A) .................................................................................................................................... 132
6.2.1 General .................................................................................................................................. 132
6.2.2 Communication ...................................................................................................................... 136
6.2.3 Control ................................................................................................................................... 138
6.2.4 Commissioning ...................................................................................................................... 156
6.2.5 Options................................................................................................................................... 180
6.2.6 Recorder ................................................................................................................................ 182
6.2.7 Logfile .................................................................................................................................... 183
6.3 Panel.............................................................................................................................................. 185
6.4 Terminal ......................................................................................................................................... 187
6.5 Logfile ............................................................................................................................................ 191
6.5.1 General .................................................................................................................................. 191
6.5.2 REG-DP (DAN) ...................................................................................................................... 193
7 FAQ........................................................................................................................................................ 195
7.1 REG-DP(A) .................................................................................................................................... 195
4 Druml: BA_REG-DPA_e_2007_01_01_012.doc
REG-DPA a-eberle
7.2 Current Injection CI........................................................................................................................ 195
8 Background Programming REG-L......................................................................................................... 197
8.1 The programming language REG-L .............................................................................................. 197
8.2 List of the REG-L / ECL-Interpreter-commands ............................................................................ 197
9 SCADA................................................................................................................................................... 199
9.1 Data Point list for IEC 870-5-103................................................................................................... 199
10 Maintenance and Current Consumption............................................................................................ 203
10.1 Cleaning information...................................................................................................................... 203
10.2 Changing fuses.............................................................................................................................. 203
10.3 Changing battery ........................................................................................................................... 203
10.4 REG-DPA Current Consumption ................................................................................................... 205
10.5 Replacing the device ..................................................................................................................... 206
10.6 Storage Information ....................................................................................................................... 206
Druml: BA_REG-DPA_e_2007_01_01_012.doc 5
REG-DPA a-eberle
6 Druml: BA_REG-DPA_e_2007_01_01_012.doc
REG-DPA a-eberle
1.1 Warnings
The P-coil regulator REG- DPA is exclusively designed for implementation in systems and equipment for
power systems. Only trained experts are permitted to carry out all required work. Experts are persons who
are familiar with the installation, mounting, commissioning and operation of these type of products.
Furthermore, experts have qualifications which correspond with the requirements or their field of work.
The P-coil regulator REG-DPA left the factory in a condition that fulfils all relevant safety regulations. To
maintain this condition and to ensure safe operation, the following instructions and warnings in this operating
manual must be observed.
¾ The REG-DPA Petersen-Coil controller has been designed to comply with IEC 10110 / EN61010
(DIN VDE 0411), protection class I and was tested according to this standard before delivery.
¾ The REG-DPA Petersen-Coil controller must be earthed via a protective earth conductor. This
condition is fulfilled when the controller is connected to an auxiliary voltage with a protective earth
conductor (European power supply system). If the auxiliary voltage power supply system does not
have a protective earth conductor, an additional connection must be established from the protective
earth conductor terminal to earth.
¾ The upper limit of the permissible auxiliary voltage UH respectively UAUX may not exceeded, nether
permanently nor for a short period of time.
¾ Before changing the fuse, separate the REG-DPA controller completely from the auxiliary voltage.
The use of the fuses other than those of the indicated type and rated current is prohibited.
¾ A REG-DPA controller which displays visible damage or clear malfunctioning must not be used and
has to be secured against unintentionally being switched on.
¾ Maintenance and repair work on a REG-DPA controller with an open door may only be carried out by
authorised experts.
Warning signs
Please familiarise yourself with the nominal insulation voltage of the controller before connecting the
device
Ensure that the voltages are connected via a disconnecting mechanism, and that the current
transformer path can be shortened externally, to enable problem-free device replacement in case of
a device-fault.
When wiring, please ensure that the conductors are either bound short or kept sufficient short so that
they cannot touch the boards of level II or III.
If a fault occurs ( connection becomes loose), no line that carries a voltage that is dangerous when
touched (>50 V) or line to which a nominal isolation voltage larger than 50 V is assigned, may come
into contact with the touchable circuits in level II and III.
1 Parameterisation software
1 Nullmodem cable
1 Spare fuse
2 tools ( 7 mm Allen key and special screwdriver for the terminals on level II and III )
2 Application
The P-coil regulator REG-DP is a component of the Measuring, Control, Regulation and Registration system
REGSys™.
REGSys™ - Overview
E-LAN
IEC 61850
et
rn
IEC 60850-5-101/103/104
32
85
he
L
WinEDC / WinREG
S2
S4
MODBUS,SPABUS,
LW
Et
R CPR-D a-eberle
Windows NT Reset
COM1
Reset
COM1
Reset
COM1
Reset
COM1
Reset
COM1
Windows 2000
Windows XP CPR-D EOR-D
E-LAN
E-LAN
COM3 PQI-D a-eberle
Reset
COM1
km
BIN-D ANA-D
N
BIN-D ANA-D PQI-D REG-BO
LA
5
<
E-
E-LAN
RS485 S
Rteuflte
ns
c
h
a
lth
e
rlte
te
ig rn
P AN- D a-eberle REG-D a-eberle MMU-D a-eberle a-eberle REG-DP a-eberle
REG-DPA L
S us
fe u
ng
s
c
s
c
h
a a
rr
lte
Betrieb Lauflampe Störung Status F1 Status Status F1
<U <U
Störung Phasenfall Störung Display F2 Display F2
>U >U
< U1 Auslösung >I X = 81,15 >I X = 81,15
y = 76,95 F3 y = 76,95 F3
> U2 NOT-AUS B = 67,818 mm B = 67,818 mm
REG-PC
AUTO ESC MENU COM1 AUTO ESC MENU COM1 COM1 AUTO ESC MENU COM1
REG/ST
The REG-DPA regulator is part of the REGSys™ regulation system and can therefore be connected to a
REG-D / PAN-D voltage regulator or a PQI-D power quality interface without any problems. An important
feature of REGSys™ is that all components that are connected to each other via the E-LAN system bus can
be parameterised or connected to the control system via a single interface. This means that the
measurement values and parameters of all connected devices are available to the control system, and that
they can be read and altered there. Conversions according to IEC 60870-5-103 (VDEW) and IEC 60870-5-
101 (balanced und unbalanced mode), MODBUS, SPABUS or IEC 61850 are available.
If multiple devices are connected via the E-LAN system bus, any bus station can be parameterised or read
by connecting a PC to the interface (COM1, COM2) or any other bus station.
Furthermore, multiple PCs can simultaneously access individual stations (Multimaster).
2.1 Notation
For the suppression of the arc the Petersen coil should be well tuned within limits, which are described in
[1] for the different insulation levels. The increase in the cable lengths of distribution networks brings about
that on the one hand the level of the neutral-to-earth voltage is decreasing and on the other hand the
resonance curves become sharper. The reason for the reduction of the neutral-to-earth voltage level is
mainly due to the reduced capacitance tolerances of the new cables. Furthermore, the cables have smaller
losses compared to equivalent overhead lines. This is why, the damping of the network is reduced and the
resonance curves become sharper.
A first idea to meet these demands on the control of Petersen coils is to make the measurement of the
neutral-to-earth voltage more sensitive. But in this chapter it will shown that with this idea the results doesn't
satisfy. The main reason for this is that the disturbances caused by the system due to, e.g. geometrically
asymmetric of installed cables, are higher than the measurement noise. Therefore the reasons for the
different disturbances of the neutral-to-earth voltage will be elaborated on the next pages. Finally, a new
approach for finding the resonance point also for smaller neutral-to-earth voltage levels will be presented.
In medium-voltage (MV) and high-voltage (HV) networks with “resonant grounding” the current over the
fault location in the case of a single line-to-earth-fault is reduced by the use of the Petersen-Coil. For this the
Petersen coil is adjusted during the healthy operation of the network to compensate the capacitive current
over the fault location by an inductive current. Fig. 2.2 shows the simplified equivalent circuit used for a faulty
distribution system where we assume ideal symmetrical three-phase voltage sources and negligible line
resistances and inductances.
The phasor diagram of Fig. 2.3 for a SLE with ZF = 0 Ω is depicted in Fig. 2.3a. The situation of different
coil positions of the Petersen coil and the resulting current IF over the fault location are shown in Fig. 2.3b.
2 3
IF IGp IC2+IC3
ILp 1 IC2+ IC3
IGp IP ILp
IC3 IC2 over- under-
Earth compensation compensation
full-compensation
a) b)
Fig. 2.3: a) Phasor diagram for a single line-to-earth-fault (SLE).
b) Reduced phasor diagram
For the derivation of the mathematical model the following assumptions will be made (see Fig. 2.2):
with
YU = ΔG + jωΔC unbalance of the fault location
YW = 3G + G P wattmetric part of YO
BC = ω 3C capacitive part of YO
1
BL = inductive part of YO .
ωL P
The equivalent circuit of eq. (1.14) is depicted in Fig. 2.5. This circuit is valid for low ohmic single line-to-
U1
YW BC BL
Fig. 2.5: Single phase equivalent circuit for the “resonant grounding”.
In the following subsections the dependence of Une and IF on the tuning of the Petersen coil under the two
major operation conditions will be discussed.
In the case of a low ohmic earth-fault the capacitive unbalance jBC is negligible. On the other hand the
ohmic admittance ΔG is very high. As a result of these conditions the voltage on the resonance circuit Une is
more or less constant (see also Fig. 2.5). Fig. 5 shows the absolute value and Fig. 2.6 the locus diagram of
the current IF over the fault location as a function of the Petersen-Coil position Ipos = BLU1 for a typical 20
kV network ( BCU1 = 150 A, YWU1 = 5 A and 1/YU = 1 Ω ).
Fig. 2.6: Absolute value of the current IF over the fault location
Fig. 2.7: Locus diagram of the current IF over the fault location
In this case the ohmic admittance ΔG is normally negligible compared to the capacitive unbalance jBC of
the network. As a consequence the current IF is more or less constant (see Fig. 2.5). In analogy to the
previous subsection Fig. 2.8 shows the absolute value and Fig. 2.9 the locus diagram of the neutral-to-earth
voltage Une at the fault (unbalance) location as a function of the Petersen-Coil position Ipos = BLU1 for a
typical 20 kV network (BCU1 = 150 A, YWU1 = 5 A and 1/YU = 40 kΩ ).
The resonance curve of the sound network can be described by the following three parameters:
These parameters can be determined from the resonance curve in an easy way. At the resonance point
( BC = BL ) eq. (1.14) simplifies to
YU (1.15)
U res = − U1 .
YU + YW
In order to explain the meaning of the current Iw, let us consider the point of the resonance curve from Fig.
U ne 1
2.8 or Fig. 2.9 where the relation = holds. Thus, under the assumption YU << YW the
U res 2
corresponding coil position Ipos,W = BL,WU1 can be calculated from eq. (1.14) in the form
(1.16)
U ne 1 1 1
= = ≈
U res 2 j ( BC − BL ,W ) j ( BC − BL ,
1+ 1+
YU + YW YW
or equivalently
( BC − BL ,W ) = YW . (1.17)
Thus, eq. (1.18) says that the difference between the coil position at the resonance point Ires and the coil
position Ipos,W where the voltage Une is reduced to U res / 2 is equal to the wattmetric current IW.
For the explanation of the control algorithm it will be useful to consider the absolute value and the locus
diagram of the inverse of the neutral-to-earth voltage
1 Y + Y + j ( BC − BL ) (1.19)
=− U W
U ne YU U1
The controller makes all necessary recording for the estimation of the resonance point during its tuning.
The controller shows the result directly on the screen.
According to the already evaluated curve of the value of the fault-current over the fault location, it is
possible to define the current during the healthy network in advance.
Fig. 2.12: Absolute value of the current IF over the fault location
The current will be in any case a minimum at the resonance point Ires. In this case the capacitive current from
the healthy phases and the current through the Petersen-Coil have the same size, but opposite directions.
The resulting current is only the wattmetric part IW of IF, which is also calculated during the tuning operation.
With the detuning-parameter v the additional reactive part of the fault current can be defined.
Uen
IF IW ICE = Ires
ILp
over- under-
compensation compensation
full-compensation
The value of the reactive current over the fault location may be calculated either as 'absolute value' or as
'relative value'. The following equations are describing both variants of calculation:
Ipos[ A] − Ires[ A]
Detuning in %: v[%] = *100 (1.21)
Ires[ A]
160 − 150
v= * 100 = 6,66%
150
The controller tunes the coil to a position, that the reactive current over the fault location is always of the
same size, independent of the network size,
The reactive current is equal for small and large systems. Furthermore, no fix coils installed in the same
system have to be evaluated and taken into account for the calculation of the detuning. Most of the time, it is
not easy to define how many fix-coils and of witch size are included in the same system. Additional problems
arise from the possibilities to inform the controller of the actual sum-value of these coils. The result of the
tuning is always a clear statement on the value of the 50 Hz component of the reactive current over the fault
location.
In case of a detuning in per cent, the expected reactive current IV in A over the fault location is calculated
according to the following equation:
( I res + I fix ) ∗ v
Iv = (1.22)
100
With a compensation in per cent, very large systems the resulting fault current can exceed the recommended
value for the self-extinguishing of the arc. (up to 20 kV: 60A, at 110kV approx. 132 A).
The expected touch voltage in the case of an earth fault should be taken into consideration according to the
DIN VDE 0101 as a further very important criteria for selecting the compensation. For this calculation the
earthing impedances must be known or estimated.
1. High noise levels in the measurement of Une due to, e.g. inductive and capacitive coupling on the line
from the measurement winding of the Petersen coil to the controller. This effect can be reduced, by using
twisted and shielded measurement lines.
2. Resolution of the A/D converter. The resonance maximum in cable networks is often less than 0.5 % of
U1. Thus, in order to identify a resonance curve the resolution should be in the range of 0.01 % of U1.
3. Harmonics in the zero-sequence system. They are filtered out by the controller.
4. Unbalance of the voltage (dU1) coupled from the HV.
5. Unbalance of the voltage (dU1) due to manufacturing tolerances of the transformer in the range less than
1 %. As a result a completely balanced HV-system generates an unbalanced system on the MV side.
6. An asymmetric load of the auxiliary system on the tertiary winding of the earthing-transformer (zig-zag)
also generates an unbalance of the voltage (dU1).
7. Capacitive unbalance of the lines due to, e.g. the geometrical arrangement of the phases in overhead
lines or due to the manufacturing tolerances of cables.
8. Coupling of the load current over the normally negligible line resistances and reactances (symmetric and
asymmetric values).
9. Coupling of the load current over the normally negligible mutual coupled line reactances (symmetric and
asymmetric values).
10. Measurement of the neutral-to-earth voltage Une using the open delta winding at the busbar instead of
the auxiliary winding of the Petersen coil results in a constant amplitude and phase error. This is caused
by the different accuracy classes of the open delta winding and the transformer.
11. Non-linearity between the measured coil position and the real susceptance of the Petersen coil. The
sensor for the coil position is a linear potentiometer, which gives a signal proportional to the air gap. But
the susceptance of the Petersen coil is a non-linear function of the air gap.
12. Capacitive coupling from parallel lines of different voltage levels on the same lattice tower. To reduce the
required ground floor, lines with different voltage levels are installed on the same lattice tower. Due to
this, changes in the balance of one system are capacitively coupled to the second system.
13. Combination of the disturbances mentioned above where unbalanced loads are important.
In order to get an impression of the quantitative influence of some of these disturbances on the neutral-to-
earth voltage Vne, in particular 4 to 9, we will subsequently investigate a simple 20 kV network.
dU1
Une YP Y1 Y2 Y3
IP
I1 I2 I3
Earth
Fig. 2.16: Simple equivalent circuit for the investigation of some disturbances on Une.
For the sake of clarity, we further assume without restriction of generality that unbalances of the transmission
line only occur in phase 1.
The disturbances described in the items 4 to 9 can be reduced to the following three coupling effects, which
will be discussed in more detail on the basis of the network of Fig. 2.16:
Under the assumption that all components of the network are symmetrical except for the unbalanced
voltage dU1 we get the following relation between Une and dU1
U ne YLYC
=− (1.23)
dU1 3YLYC + YP (YL + YC )
with
The important information of eq. (1.23) is that even in a network with ideal symmetrical components (line
resistances, line reactances, mutual coupling, line-to-earth capacitances and loads) an unbalance
dU1 will produce a non-zero neutral-to-earth voltage Une. In addition, the amplitude of this voltage
depends on different network parameters and has its maximum in the case when the Petersen coil is
adjusted. The relation U ne / dU1 as a function of the coil position for the network of Fig. 2.16 is shown in
Fig. 2.17.
For this investigation we assume that dU1 = 0 and that there is only an unbalance ΔYC in the line-to-earth
capacitance in phase 1. Then the following relation
U ne 3Y 2 ΔY
=− L C
U1 3Yn1 + Yn 2
U ne 3Y 2 ΔY (1.24)
=− L C
U1 3Yn1 + Yn 2
1
YLoad =
Z Load
ΔYC = jωΔC.
The natural unbalance in the line-to-earth capacitance ΔYC also brings about a non-zero neutral-to-earth
voltage Une. But now Une also depends on the load YLoad and hence on the load current due to the
serial impedance of the line. As it can be seen from eq. (1.24) and eq. (1.25) this dependence is even
present if both the serial line impedance and the load are symmetrical. If there are additional asymmetries in
the serial impedances, e.g. due to asymmetrical mutual coupling of the overhead lines, the coupling effect
can be worse. Fig. 2.18 depicts the relation U ne / U1 as a function of the load current in the case of an
adjusted Petersen coil for the network of Fig. 2.16.
Fig. 2.18: Neutral-to-earth voltage due to a capacitive unbalance and non-zero serial impedances in the line.
For this calculation the assumption dU1 = 0 and a symmetrical network except for an asymmetry of 5% in ZL
of phase 1 is made. Since the formulas are rather complex only the graph of the relation U ne / U1 in Fig.
2.19 as a function of the load current in the case of an adjusted Petersen coil for the network of Fig. 2.16 is
presented.
Fig. 2.19: Neutral-to-earth voltage due to an unbalance of the serial impedances in the line
The important result is that there is an increasing neutral-to-earth voltage Une depending on the load
current. If the load current is zero Une results from the capacitive current of the line itself. In some networks
the neutral-to-earth voltage is zero in the case of no-load operation of the network. The coupled voltages of
the capacitive unbalance and of the unbalance of the serial impedances are compensating themselves. But
as it can be seen in Fig. 2.19 the neutral-to-earth voltage Une is increasing depending on the load.
The asymmetry of a line may be caused for example by the kind of laying the cables, as shown in Fig.
2.20a. If the cables are laid in a triangle (see Fig. 2.20b) the mutual coupling of the three phases is obviously
the same. A similar situation can be found for overhead lines where an improvement can be made, by
transposing the phases.
Z M13 2
Z M12 Z M23
1 2 3 Z M12 Z M23
1 3
2r
Z M13
a a
a
a) b)
Fig. 2.20: a) Single conductor cables in parallel
b) Single conductor cables in triangle.
The following figures shows the change of Une and Ipos over one week. The coil position was more or less
the same during the whole period.
2005-04-06 01:33:53
3
Uo / V sek
0
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00
2005-04-04 16:36:19:
250
240
Ipos / A
230
220
210
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00
In this industrial network, there was no switching operation during the whole week.
During the working hours of the week a remarkable increase of the zero-sequence voltage can be detected.
The small peeks in the zero-sequence voltage are results from the search operation of the Petersen-Coil
controller.
2.5
2
sek
Uo / V
1.5
0.5
0
00:00:00 03:00:00 06:00:00 09:00:00 12:00:00 15:00:00 18:00:00 21:00:00 00:00:00
t/d
The change of the load during the morning break and the lunch time is recognizable in the behavior of Une.
Also the working period from 7:00 to 17:00 can be recognized. The end of television between 21:00 and
24:00 result in a slow change of Une.
The problem in this network is, that the zero-sequence-voltage Une is only about 0.2 % in the night and
increases during the day up to 1.5%. This is a special challange for the controller.
The parameter of the controller are set correct, if the controller is tuning not more than 10 times per day in a
comparable system.
Controller Petersen-Coil
L
R1 m otor high
R2 m otor low
N
+U H
E1 endswitch high
E2 endswitch low
-U H
+ Pot
V en
V en V en = 0...100VAC
The task of the controller is to detect a change of the network configuration and to adjust the Petersen coil to
the new resonance point or to a predefined over- or under-compensated value. In the simplest version the
change of the absolute value of the neutral-to-earth voltage Une is used as an indication of a switch operation
in the network. With this approach not all changes of the network configuration can be detected. An
improvement can be made, by investigating the change of the neutral-to-earth voltage Une in the complex
plane. To calculate the resonance curve parameters it is necessary to change the value of the Petersen-Coil
and to measure the corresponding variation of the neutral-to-earth voltage Une. As shown in the sections
before, the voltage Une is corrupted by different disturbances. Summarizing the objectives, the controller has
¾ to distinguish between a “real” resonance point and a “fictitious” resonance point, in particular in the case
of small neutral-to-earth voltages and
It has turned out that by means of a least-squares approach the parameters Ures, Ires and IW of the
resonance curve of fig. 7 can be obtained in a robust way. The Petersen-Coil needs in its fastest operation
mode about 60 s from one end-switch to the other. This requires that during the tuning operation about every
0.5 s a new estimation is accessible. To avoid too high computational consumption the non-linear parameter
estimation problem is transformed to a linear one.
2
U ne 1 1
= 2
= 2 2
U1 T ⎛ YW ⎞ ⎛ BC − BL ⎞ (1.26)
⎜1 + ⎟ +⎜ ⎟
⎝ YU ⎠ ⎝ YU ⎠
or equivalently
2
0 = YU + 2YU YW + YW + BC − 2 BC BL − YU T + BL .
2 2 2 2 2
(1.27)
2
Since T and BL can be measured, we can rewrite eq. (1.27) for n different measurement points in the form
1
⎡− 2 BL − T 2 1 ⎤ ⎡− B 2 ⎤
⎢ ⎥ ⎡ x1 ⎤ ⎢ L ⎥
⎢ ... ... ...⎥ ⎢ ⎥ ⎢ ... ⎥
⎢ ... x =
...⎥ ⎢ 2 ⎥ ⎢ ... ⎥
(1.28)
...
⎢ ⎥ ⎢x ⎥ ⎢ ⎥
⎢− 2 B − T 2 1 ⎥ ⎣ 3 ⎦ ⎢⎣− BL 2 ⎥⎦
n ⎣ L ⎦
with the abbreviations
x1 = BC (1.29)
x2 = YU
2
(1.30)
x3 = YU + 2YU YW + YW + BC .
2 2 2 (1.31)
Eq. (1.28)can be solved with a classical least squares approach in order to obtain BC, YU and YW and
from this the parameters Ures, Ires and IW for the construction of the resonance curve. It is worth mentioning
that for the sake of computational efficiency an on-line version of the least-squares algorithm is implemented.
However, some further steps in the preprocessing of the signals have to be taken to gain additional
robustness against disturbances.
As an example Fig. 2.24 shows the estimated inverse resonance curve (see eq. (19) and Fig. 2.10), by using
only the marked samples from the measured values for the computation of the parameters. The real
resonance point of the network is at 100 A.
Fig. 2.24: Inverse resonance curve estimated from the sampled values.
In the past, different control algorithms were developed. Most of these algorithms are based on the
necessity to move the Petersen-Coil. The development of today's distribution networks is characterized on
one side by an increase of symmetrical cables, which results in smaller usable zero-sequence-voltages
and, on the other side, in an increase of the crosstalk of the positive sequence of the load current to
the zero-sequence system. With the decreasing zero-sequence voltage the controller must be set much
more sensitive. Due to the crosstalk of the load current to the zero-sequence voltage, each change of the
load current can release a tuning operation, which is, in most of the actual algorithms, combined with a
physical movement of the Petersen-Coil. Due to the disturbances the state and parameter estimation of the
network is much more difficult and results in a necessary movement of the Petersen-Coil over a longer
distance. Nevertheless, sometimes a correct tuning is impossible.
One problem arises because the motor-drive of the Petersen-Coil is only designed for few tuning operations
per day. The other problem arises because of the longer detuning time. This is caused by the increase of
tuning cycles, respectively by wrong tuning positions.
Therefore on the next pages a method will be presented, which is able to find the correct tuning position,
even if the natural zero-sequence voltage is zero, respectively if the disturbances in the zero-sequence
voltage are not negligible. Additionally, the number of necessary moving operations is reduced.
Up to now, mainly the following algorithms are used to determine the network parameters respectively to
tune the Petersen-Coil. The relative change of the zero-sequence voltage is normally used as the criterion
for the detection of a switching operation in the network.
4. Locus Diagram of U0
This method is based on the fact that a circle can be constructed with only three points. This method
assumes that the third point of the circle is the origin of the complex plane. A short detuning can be achieved
for example by switching a capacity in parallel to the Petersen-Coil. This switching results in a second point
of the locus diagram of UNE. Measuring the voltage with amplitude and angle it is possible to construct the
locus diagram.
5. 50 Hz Current Injection
This algorithm is based on the idea to inject an artificial current into the neutral point of the system if there
is no unsymmetrical current from the natural asymmetry. The influence of the natural unbalance can be
partly compensated by using a differential measurement from two time points. Eq.
Fehler! Verweisquelle konnte nicht gefunden werden. in combination with the coil position enables to
determine the network parameters.
d I CI
Y CI = ≈ YW + j ( BC − BL ) (1.32)
dU NE
Principle
All the existing algorithms are based on the fact, that the residual voltage is generated either by the natural
unbalance of the network or by an artificial 50 Hz current injection. These methods are assuming, that there
is no change in the network respectively no change of the crosstalk of the load current during the calculation
period. Please pay attention that the calculation period can last from several seconds up to several
minutes.
In reality there are a lot of situations where these assumptions are not valid, for example in the sphere of
heavy industry with symmetrical networks but heavy changes of load.
The new CIF-algorithm (Control by Injecting Frequencies) suppresses the 50 Hz crosstalk from the load
current by using frequencies unequal to 50 Hz for the measuring and for the parameter estimation.
The simplified equivalent circuit with a current injection according to Fig. 2.25
Fig. 2.26: Simple equivalent circuit with current injection unequal to 50 Hz.
For the frequency fn the admittance, seen from the current injection, can be described as:
I CI _ fn 1
Y CI _ fn = = Y U + YW + j (ωn C − ) (1.33)
U NE _ fn ωn L
I CI _ fn 1
Y CI _ fn = ≈ YW + j (ωn C − ) (1.34)
U NE _ fn ωn L
Using two different frequencies f1 and f2 one gets two complex equations with three variables, which leads to
the following solution:
⎧⎪ I f 1 ⎫⎪
Y W = real ⎨ ⎬ (1.35)
⎪⎩ U NE _ f 1 ⎪⎭
imag (Y CI _ f 1 ) ω1 − imag (Y CI _ f 2 ) ω2
C= (1.36)
ω12 − ω22
1
L= (1.37)
ω1 (−imag (Y CI _ f 1 ) + ω1C )
Assuming a linear system enables the current injection of two frequencies and evaluation of the
corresponding YCI_fn at the same time. This results in very fast measurement possibilities and depends more
or less on the used frequencies and filter algorithms. The duration of the measurement is usually in the range
of 240 ms.
The following items list the main advantages of this new CIF-algorithm:
Additional requirements
Depending on the resonance curve and the normal operation philosophy of the network, there arise some
additional requirements for the current injection.
1) The injected current should be variable in the amplitude to enable adaptation to the losses of different
switching states of the network.
One of the most used criteria for the earthfault detection is the zero-sequence voltage. In small networks
On the other side, in case of situations with a large detuning a small injected current will not deliver a
reliable measurement of the residual voltage UNE_fn .In this case a higher injected current is recommended.
3) Using a current injection with variable frequencies, it is possible to select the injected frequencies in such
a way, that these frequencies are near to the resonance of the network. In this case small injected
currents result in large values of the residual voltage. The accuracy of the parameter estimation is
increased, especially for systems with a large standard detuning.
Operation philosophy
Depending on the operation philosophy the current injection can be activated only for a short time after the
detection of an essential relative change of the zero-sequence voltage, to check if a new tuning of the
Petersen-Coil is necessary. In symmetrical networks the current injection can be switched on continuously,
to detect any switching operation in the network immediately. Combinations of these two philosophies are
possible, for example to check every 10 min the actual network parameters in symmetrical networks.
In Fig. 2.25 a connection of the Petersen-Coil to the neutral point of the transformer is shown. For a more
accurate calculation of the network including a Petersen coil, as shown in Fig. 2.25 , it is necessary to use a
more precise equivalent circuit as depicted in Fig. 2.28.
Fig. 2.27: Wiring diagram of the Petersen Coil with current injection and wattmetric increase Rp
ICI UCI
Cu ICu
ZPC_leakage I2 N ZoTr A I0_Tr IU
IGu IU1
IP IP IC IG I Lext Gu
I0_Fix
ZP UP RFe LPC UX
UNS U0d_Tr UU
ZPC Cnet Gnet Lnet
RFix
LFix
S ZFix
I0_fix
USE UNE
RS1
I0_S
Fig. 2.28: Simplified zero-sequence equivalent circuit of one transformer, one ASC and one Fix-Coil
(red currents and blue voltages can be measured)
Using frequencies unequal to 50 Hz enables now an accurate measurement of the following components
during normal operation of the network
The parameter estimation of the network can be extended for each feeder by measuring the injected currents
in each feeder of interest either with the Holmgreen-Circuit (summation CT) or with the core-balance
transformer.
As the crosstalk from 50 Hz is suppressed, the measurement of U0D can be used for the calculation of the
essential parameters for each line.
It is possible to calculate the capacitive part BCx, the losses YWx and the size of distributed coils BLx seen on
feeder x, with the same method as explained above. By using additionally the 50 Hz components at the
same time, the actual unbalance of the network can be determined and supervised.
The advantage of this algorithm is, that all measurements are made at the same time. The usual problem to
check for a switching operation is removed. The determination of the network parameter is included in the
algorithm directly.
The most simple way is to use a standard frequency converter (FC) in the mode of a current source as
shown in Fig. 2.30. To reduce the disturbances on the 400 V side, a frequency converter with a power factor
correction module (PFC) is recommended. The coil L1 respectively the parallel circuit L1//L2 is used to
convert the pulsed voltage to an impressed current. The size of L1//L2 defines the maximum available
injected current. The auxiliary winding of the Petersen-Coil is usually designed for 500 V, which makes
necessary, in these cases, an additional transformer for the adaptation. With this type of current injection two
currents with individual amplitude, frequency and phase can be injected very easy. On the other side the
physical realisation is not the cheapest one.
Fig. 2.30: Current injection with AC-switch for three frequencies (AC-1)
If the requirement for variable frequencies is cancelled, a much cheaper version to generate a current with
more frequencies is available, as shown in Fig. 2.31
Fig. 2.31: Current injection with AC-switch for three frequencies (AC-1)
The following figure shows one possible pattern of pulses for the current injection.
0.8
0.6
0.4
0.2
I/A
-0.2
-0.4
-0.6
-0.8
-1
41.67 : 0.34724
0.5
0.4
I/A
0.3
0.2
0.1
0
0 50 100 150 200 250
f / Hz
The major disadvantage of this type of current injection is that the main spectrum of the injected current is 50
Hz. This can be avoided by the following type of thyristor-switch, where it is possible to invert the direction of
the current during the previous pause time.
Fig. 2.34: Current injection with AC-switch for two frequencies (AC-2)
0.8
0.6
0.4
0.2
I/A
-0.2
-0.4
-0.6
-0.8
-1
Depending on the pulse pattern and the number of periods different frequencies are available. The previous
figures show a 100 % phase-firing. The amplitude can be reduced by a reduced phase-firing, as for example
depicted in Fig. 2.37. This AC-switch (AC-2) can also be used to generate the pattern for three frequencies
like shown in Fig. 2.32.
25.00 : 0.28292
0.4
I/A
0.3
0.2
0.1
0
0 50 100 150 200 250
f / Hz
0.8
0.6
0.4
0.2
I/A
-0.2
-0.4
-0.6
-0.8
-1
¾ Tuning of the Petersen Coil only with zero-sequence voltage by changing the coil position
¾ Enough zero-sequence voltage must be available
¾ Zero-sequence voltage should be used from the Petersen Coil ( With known L0Tr the influence of this
impedance could be taken into account for the display of Cnet )
The algorithm uses the measurement according to the simplified schema from Fig. 2.28
In most cases it is sufficient to use the simplified algorithm with ICI and U0D respectively UNS
The resistors Rs1 and Rs2 normally doesn't exist. In this case UNS = UNE
ICI ; ; ;
I0_S ;
I0_fix ;
Steps of CIF:
Characteristics of CIF:
¾ Up to two frequencies
¾ Frequencies near to the resonance frequency
¾ Parameters:
o Maximal allowed current injection: |ICI | < 25 A
o Maximal value of u0 due to current injection: u0(t) < 5%
¾ Continuous injection with reduced current for supervisory of the network
¾ Switch off or reduction of the current injection during coil movement
¾ Very fast, as the calculation is within one filter cycle ( 240 ms)
¾ For supervision of the network in case of very small U0 the current-injection can be selected to be
continuous or periodically
¾ During continuous injection switch operation are detected immediately
¾ Injection and move of the coil at the same time is not required, but possible
¾ Size of current injection is changed by the controller. Max of 20 A on the 220 V side
( 10 A on the 500 V side )
¾ Maximal allowed value of u0(t) < 5% caused by Current Injection. The current injection is supervising
u0(t) and limits its actual injection if necessary.
spindle Imax
higher
lower Imin
fixed core
The primary winding is connected on one side to the high voltage system and on the other side to ground.
According to some specifications also the grounded side must be isolated to ground for the full voltage. In
this case both bushings on the top of the Petersen-Coils have the same isolation level and the customer can
select which one will be grounded.
The Power-Auxiliary-Winding (PAW) is normally designed for 500 V with variation of ± 10% over the tuning
range. Due to the variation of the distance d of the air-gap the coupling from the primary winding to the PAW
is not constant. The PAW is normally designed for an additional load-current of about 10% of the specified
maximum of the inductive current Ip_max. This current can be ohmic, inductive or capacitive. For the design of
the Petersen-Coil the maximum duration of this additional current must be specified and depends on the use
of this PAW.
In most cases for the measurement of the UNE few Measurement Windings (MW) are added to deliver about
100 V in case of a solid earthfault. Also the accuracy of this winding is only in the range of 10%. The
accuracy of this measurement depends on the location and distribution of these windings. Sometimes their
arrangement is concentrated and asymmetric as shown in Fig. 2.39: Petersen Coil with PAW. Another
solution implements the winding on the return limp of the magnetic circuit. There are lot of additional different
solutions to get better results for the measurement and they can be optimized for a class of coils with a
nominal power.
Alternative solutions generate the 100 V via a simple autotransformer connected to the PAW. As long there
is not wattmetric-increase connected to the PAW the measurement is relative acceptable.
To improve he accuracy of the voltage measurement some designs uses a small voltage transformer under
oil connected directly to the primary voltage. With this solution the accuracy depends only on the accuracy of
the voltage transformer.
For the current injection the Petersen Coil is not more an ideal transformer. The coupling between the three
windings is a function of the coil position and is nonlinear.
The use of the current injection, as a simple method, can be made more complicate if the current injection
should be used in combination with an older Petersen-Coil without a PAW.
In this case the Petersen Coil is used as a transformer. The major influence on the accuracy is depending on
the constancy of the transfer-function of the injected current on the secondary side to the resultant current on
the primary side. This transfer-function should be constant over the whole tuning range of the Petersen coil.
Additionally the voltage measurement should reflect the primary voltage and not the voltage on the PAW.
U0d
ICI_3
UNE_2 UNE_3
RS
IS
In this case, an additionally small single phase transformer as a replacement of the PAW is necessary,
connected parallel to the primary side of the Petersen-Coil. The power rating of this transformer can be
designed for about 10 A continuous current on the low voltage side. The ratio of the windings is normally
designed to produce 500 V on the low-voltage side. The short circuit impedance of the transformer should
be as small as possible.
If figures are shown in the following tables, they assume a 20 kV network, an injection transformer with a
ratio of 11550/500, a natural unbalance of < 5%, a network with Ice of about 300 A and a maximal injection
current of 10 A on the low voltage side.
ICI_2 , UNE_1 ✓ -- -- -- -
ICI_2 , UNE_2 -- ±3% ±10% -- 2
ICI_2 , UNE_3 -- ±3% ±3% -- 1.5
ICI_2 , U0d -- ±3% ±3% -- 1
IS , UNE_1 ✓ -- -- -- --
IS , UNE_2 -- -- ±10% ±3% Bad condition of IS 8
IS , UNE_3 -- -- ±3% ±3% Bad condition of IS 6
IS , U0d -- -- ±3% ±3% Bad condition of IS 6
2.9 Literatur
[1] DIN VDE 0228, Maßnahmen zur Beeinflussung von Fernmeldeanlagen durch Starkstromanlagen,
1987.
[2] Doemeland Wolfgang, Handbuch Schutztechnik, Grundlagen – Schutzsysteme – Inbetriebsetzung,
VDE Verlag GmbH, Berlin-Offenbach, 7.Auflage, 2003
[3] Druml G., Kugi A., Parr B., Control of Petersen Coils, XI. International Symposium on Theoretical
Electrical Engineering, 2001, Linz
[4] Schossig Walter, Netzschutztechnik, VDE Verlag GmbH, Berlin, 2001
[5] Druml G., "EDCSys Operation Manual - Earthfault Detection and Control System", A-
Eberle GmbH&CoKG, 2004, Nürnberg, Germany
Error message when a break or short circuit occurs in the sensor and/or when the voltage of the slider lies outside the
measurement range.
Protection class I
Pollution level 2
Overvoltage category II, III
III II
Input circuits of the current and Control circuits(DC),
voltage transformers Analogue inputs,
power supply Analogue outputs,
ELAN’s, COM’s
50 V 150 V 230 V
E-LAN, Voltage inputs Power supply,
COM1...COM3, Current inputs Binary inputs (E1 ... E16),
Analogue outputs Relay outputs (R1 ...R13)
Analogue inputs
Hous. COM2
Test voltage Uh BO BI AI AO UE IE
COM1 COM3
Housing/COM1 Hous./COM1 - 2.2 0.35 1.35 1.35 0.35 0.35 1.35 1.35
Auxiliary voltage Uh 2.2 - 3.7 2.9 2.9 3.7 3.7 2.6 2.6
COM2/3 /IEC / DNP_ COMx 0.35 3.7 - 2.3 2.3 0.5 0.5 2.8 2.8
Binary Outputs BO 2.0 2.9 2.3 - 2.0 2.3 2.3 2.6 2.6
Binary Inputs(250V) BI 2.0 2.9 2.3 2.0 - 2.3 2.3 2.6 2.6
Analogue Inputs AI 0.35 3.7 0.5 2.3 2.3 - 0.5 2.8 2.8
Analogue Outputs AO 0.35 3.7 0.5 2.3 2.3 0.5 - 2.8 2.8
Input voltage UE 1.35 2.6 2.8 2.6 2.6 2.8 2.8 - 2.2
Input current IE 2.0 2.6 2.8 2.6 2.6 2.8 2.8 2.2 -
Notes: All test voltages are AC voltages in kV, which may be applied for 1 minute.
E-LAN, COM2, COM3 are tested against each other with 0.5 kV.
Emitted interference
Conducted and EN 61326 Table 3 and
radiated emissions EN 61000-6-4
Magnetic fields with heavy IEC 61000-4-8 100 A/m (50 Hz), continuous
electrical frequencies 1000 A/m (50 Hz), 1 s
Feature H1 H2
AC (intern) - -
AC 85 ... 264 V -
DC 88 ... 280 V 18 .. 72 V
Power consumption ≤ 15 VA ≤10 Watt
Frequency 50 Hz / 60 Hz
Fuse T2 250V T2 250V
Function supervision (Status) In each controller, the battery, the operation of the process (Watchdog) and
the operation voltage are supervised.
Sending and receiving devices are available for glass and plastic fibre optic cables.
In addition, it can be choose between various mechanical connection possibilities (ST or FSMA connection).
Features V13 to V19 give an overview of the various possibilities
Logic level of receiving output: CMOS (Uhmin : > 0.9VCC, Ulmax < 0.1VCC @ Io = 1mA)
Logic level of transmitting input: CMOS (Uhmin : > 0.7VCC, Ulmax < 0.3VCC), Schmitt trigger
Mass ≤ 3 kg
Degree of protection IP 54
REG-DPA
SERVICE
BLOCKED F1
F2
F3
F4
F5
LOCAL
281 x 209
ACK
307
REGSys™ www.regsys.de
12
18 87 250
Panel mounting
Rear view
Cutout
282 x 210 mm
Panel
6.5
surface / wall-mounting
328 Rear view
252
200
270
Level III
Level II
Level I
Level I :
The auxiliary voltage, input voltage and currents, as well as the relay outputs, binary inputs, etc. are connected to this
Level.
Level II :
The hardware for all the control system connections is contained on Level II. The appropriate connection elements on
Level II must be used for RS232 or RS485 connections. If an Ethernet connection is used, the corresponding connection
on Level II is also available (must be connected for IEC 61850 or IEC 60870-5-104!).
The connection elements for fibre-optic cables (send and receive diodes as ST or FSMA connection) are mounted
directly on the flange plate and can be connected there without having to open the device.
Furthermore, additional binary inputs and outputs as well as mA inputs and outputs can also be accommodated on Level
II.
In total, two connection points are available and they can be equipped with the following modules:
Level III : contains the connections for the individual COM, E-LAN, the analogue inputs and outputs
Rx -
Tx -
E-
E-
CTS
CTS
RXD
TXD
Rx +
TxD
Tx +
E+
E+
RxD
RTS
GND
RTS
GND
EA -
EA -
EA +
EA +
REG-DPA
85 84 86 83 82 81 80 79 78 77 69 70 71 72 73 74 75 76 FSMA
ST
COM1 IEC IEC opens R13
COM2 COM3 E-LAN E-LAN DNP 3.0 Life contact
LON
RS232 1 2 3 4 5 RS232 RS485 L R LON (Status)
DNP 3.0
6 7 8 9 MODBUS SPABUS closes
AUTO R12
L / (L 1) U Comm. MAN. / AUTO
U sync
1 2
N / (L 2)
MANUAL
Comm. R6...R11
4
n U R11 progr.
Une
Relay outputs
5
e
7
k I
Ip R8 progr.
9
l
R7 progr.
I
R6 progr.
56 55 54 59 58 57 53 47 48 49 50 51 52
I
F1 UH
L / (+)
µP
LED
21 22
N / (-)
Display
LCD
3.5 Blockdiagram of the REG-DPA
R1 Motor
high
96 97 98
Relay outputs
R3 progr.
AC / DC 48...250V
Characteristic E 91...99
Level
Additional Binary inputs E1 ... E8 Binary inputs E9 ... E16
Analogue inputs and outputs R4 progr.
inputs and outputs AC / DC 50...230V AC / DC 50...230V
Double module Characteristic C01 ... C09
*
A1 A2 A3 A4 (See pin assignment R5 progr.
Level II on page 11)
46 45 44 43 42 41 40 39 38 37 36 35 34 33
+ - + - + - + -
E3
E4
E5
E6
E7
Legend:
+ mA input
- mA input
optional
E16 progr.
E9 progr.
E10 progr.
E11 progr.
E12 progr.
E13 progr.
E14 progr.
E15 progr.
progr.
progr.
progr.
progr.
progr.
E8 progr.
E1 endsw. high
- input or output
+ input or output
- input or output
+ input or output
- input or output
+ input or output
E2 endsw. lower
Comm. E3...E8
Comm. E1...E2
Comm. E13...E16
Comm. E9...E12
Level III II I
a-eberle
Druml: BA_REG-DPA_e_2007_01_01_012.doc
REG-DPA a-eberle
REG-DA a-eberle
SERVICE
BLOCKED F1
Display-Maße F2
67,8 x 67,8 mm
F3
X = 114,5
Y = 88,5 F4
F5
LOCAL
ACK
Level III
1 5
6 9
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 81 83 84 85 86
COM1
100101 102103 104105 106 107108 109 110 111112113 87 88 89 90 91 92 93 94 Ethernet Level II
(IEC 61850, IEC 60870-5-104)
1 2 3 4 5 6 7 8 9
Level I
11 12 13 14 15 16 17 18 19 20
23 24 25 26 27 28 29 30 31 32
Binary inputs
21 22 90 91 92
ON
1 2 3 4
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
Binary inputs
Relay outputs
Potentiometer input
3.5.1 Level I
Signals with non touchable voltages are connected first of all on level I.
All of the circuits on level I have a nominal insulation voltage of > 50 V and are therefore considered to be
non touchable in accordance with VDE 0110.
Please take into account this condition, even if low voltages are connected to the relay-contacts or the binary
inputs.
The protection earth must be connected first, because the REG-DPA is a device with protection class I.
A plug-in shoe ( 6.3 x 0.8 mm) is provided in the lower part of the housing for the connecting the protective
earth.
Flat-plug
connection for
protective earth
The auxiliary voltage is supplied via the twin connector block (terminals 21 and 22).
No Function
21 L /(+)
Level I
UH Auxiliary voltage
22 N /(-)
For the tuning of the Petersen-Coil a voltage of 230 V AC is necessary at the motor drive. Without this
voltage a tuning is impossible. Therefore also for the controller a power supply of 230 V AC is enough. It is
not necessary to connect the controller to the uninterruptible power supply of the protection system. The
parameters and data of the recorders are buffered by a battery and will be not lost by an voltage dip or an
longer power supply interruption.
If 230 VAC is used as the power supply, it is preferred to use this voltage also for the Usync to enable the
angle measurement of the phasors.
Feature H1 H2
AC (intern) - -
AC 85 ... 264 V -
DC 88 ... 280 V 18 .. 72 V
Power consumption ≤ 15 VA ≤10 Watt
Frequency 50 Hz / 60 Hz
Fuse T2 250V T2 250V
No Function
1 L /(L1) Synchronisation voltage Usync
2 N /(L2) ( 100 V or 230 V)
3
4 n
Zero-Sequence voltage Une
5 e
6
Level I
7 k
Current Input Ip
8 l
9
Usync:
To enable the angle measurement of the phasor, the controller needs a reference voltage with a minimum
amplitude of 40 VAC. As reference any synchronised voltage can be used. The 230 V AC of the auxiliary
power supply is the preferred solution, due to the simplified connection. If the 230 VAC is not available, the
100 V of U12 of the busbar voltage measurement can be used.
For the control with the standard algorithm the voltage measured at the Petersen Coil should be used. For
the standard algorithm the voltage of the open delta winding is not applicable due to the complex offset
voltage of this type of measurement, especially at very low zero-sequence-voltages. The measurement of
the open delta would be identical to the measurement at the Petersen Coil only, if the VT's would model
exact the power transformer.
If the controller is using the current injection system, the open delta measurement is the preferred solution.
Normally the measurement winding at the Petersen-Coil is designed to deliver 100 VAC in case of a solid
grounded earthfault.
N n REG-DP(A)
n
UNE Une
E e e
The following picture shows the measurement, using the open delta winding
n REG-DP(A)
Une
e n
U X u
u x u x
L1
V Y v
v y v y
L2
W Z w
w z w z
L3 n
N n n
Fig. 3.51: Une measured via the open delta winding at the busbar
With this analogue input the real current through the Petersen-Coil or any other current can be measured.
The current Ip is not used by the algorithm. Due to the large air-gap the Petersen-Coil is more or less a linear
element. If the actual coil-position and the zero-sequence voltage is known, the corresponding current
through the coil can be calculated immediately.
...
EspBIFV
End-switch U read & write(t)
E16 E16 Endschalter L
EspBI
read &
write(t)
Assignment Output-Function
Output-Function:
Motor H
EspRelFV
R2 R2 Motor L write &
read
...
Uo > Uerd
Uo > Umax
R9 R9
EspRel
read
Fig. 3.52:Functional diagram for binary I/O with visualization of possible access by the background
programming (H-Program)
No Function
11 Binary input 1 End-switch high
12 Binary input 2 End switch low
13 Common BI_1…BI_2
14 Binary input 3 Free programmable
15 Binary input 4 Free programmable
16 Binary input 5 Free programmable
17 Binary input 6 Free programmable
18 Binary input 7 Free programmable
Level I
No Function
23 Binary input 9 Impulse Auto
24 Binary input 10 Impulse MANUAL
25 Binary input 11 Free programmable
26 Binary input 12 Free programmable
27 Common BI_9...BI_12
28 Binary input 13 Free programmable
29 Binary input 14 Free programmable
30 Binary input 15 Free programmable
Level I
The two inputs for the endswitches high and low have additional capacitive components to reduce the
ac-crosstalk.
Binaryl Input
A more detailed description of the possible assignment can be found on page 159
The binary outputs are free programmable. The minimum assignments are shown in the following tables
No Function
33 R5 Free programmable
34
35 R4 Free programmable
36
37 R3 Free programmable
38
39 R2 Motor lower
40
41
42
43 R1 Motor higher
Level I
44
45
46
No Function
47 R11 Error sum
48 R10 Une > Uearth
49 R9 Une < Umin
50 R8 tuned
51 R7 tuned, not compens.
52 R6 Free programmable
53 Common R6...R11
54 Closes in case of error
55 R13 STATUS
56 Opens in case of error
57 MANUAL
Level I
58 R12
59 AUTO
60
.
A more detailed description of the possible assignment can be found on page 161
3.5.1.5 Potentiometer
No Function
96 Pot +
Level I
97 Slider
98 Pot -
SW_ 1: 'on' 1 mA
SW_2: 'on' 5 mA
SW_3: 'on' 10 mA
SW_4: 'on' 20 mA
To get correct amplification in the 'current source-mode' only one of the DIP-switches SW_1 … SW_4 is
allowed to be in the 'on' position at the same time. For the 'standard potentiometer-mode' all switches SW_1
… SW4 must be in the 'off' position. The 'wire-break-detection' is in the current source mode not possible.
In the 'potentiometer-mode' the wire-break-detection can be enabled by putting SW_5 into the 'on' position.
Z_Line P+ +5V
Protection
& Filter
I_act
Z_Line S 51 kΩ A
SW_1
SW_2
SW_3
SW_4
D
10 mA
20 mA
1 mA
5 mA
Imin
Z_Line P-
Selectable Range by
DIP-switches:
20 mA : SW 4
10 mA : SW 3
5 mA : SW 2
1 mA : SW 1
The use of a current source, for example 4…20 mA is an alternative for the three wire configuration.
+ 5,5 V Isolation-
amplifier
SW_5
Z_Line S 51 kΩ A
SW_1
SW_2
SW_3
SW_4
D
+
10 mA
20 mA
1 mA
5 mA
-
Z_Line P-
Selectable Range by
DIP-switches:
20 mA : SW 4
10 mA : SW 3
5 mA : SW 2
1 mA : SW 1
The next alternative describes a two wire configuration. In this case only one part of the potentiometer is
used.
Z_Line P+ +5V
Protection
& Filter
amplifier
I_aktuell
Z_Line S 51 kΩ A
SW_1
SW_2
SW_3
SW_4
D
10 mA
20 mA
1 mA
5 mA
Imin
P-
Selectable Range by
DIP-switches:
20 mA : SW 4
10 mA : SW 3
5 mA : SW 2
1 mA : SW 1
The following table defines for the last picture the equivalent current source mode. According to the possible
resistance of the potentiometer the equivalent current source mode must be selected via the DIP-switches.
The comparison of the three methods should take into account the normally very long distance between the
controller and the Petersen-Coil. The temperature gradient of the potentiometer and of the long line delivers
In the second configuration the temperature gradient of the line can be ignored. The temperature gradient of
the converter coil-position to mA is the major problem.
In the third configuration all temperature gradients influences the actual coil position.
The first version is the best solution, especially if the resistance of the potentiometer is much higher, than the
impedances of the connecting wires.
All available input signals and some calculated signals can be assigned to the analogue outputs.
For the REG-DP(A) the values of Une and Ipos are used most of the time.
The modules can be configured using the menu or via the WinEDC software.
Ip
+ R_Temp
A3 A8
-
Fig. 3.57: Functional diagram for analog outputs with visualization of possible access by the background
programming ( H-Program )
No Function
61 + A2
20mA input or output
62 - A2
63 + A1
20mA input
64 - A1
65 + A3 double
Level III
Different types of transfer characteristics can be very easy defined, for example:
mA y [%]
20 100
4 20
0 0
0 100 Uen [V] 0 100 Uen [V]
mA y [%]
10 50
8 40
0 0
0 10 100 Uen [V] 0 10 100 Uen [V]
3.5.2.2 ELAN
No Function
69 E-
70 E+
E-LAN Left
71 EA -
72 EA +
73 E-
Level III
74 E+
E-LAN Right
75 EA -
76 EA +
No Function
77 Tx +
Level III
78 Tx -
COM 3 (R2485)
79 Rx +
80 Rx -
No Function
81 +12V
82 TxD
83 RxD
Level III
COM 2 (RS232)
84 RTS
85 CTS
86 GND
The COM1 is on mounted on the Level III of the controller. The pinning of COM1 allows to connect the
controller with the PC direct with a standard null modem cable
SubminD-No Function
1 DCD
2 Rx
3 Tx
4 (DTR) not used
5 GND
6 (DSR) not used
Level III
7 RTS
8 CTS
9 RI
D-Sub Stiftleiste
frontseitig
1 2 3 4 5
6 7 8 9
GND
DCD
RTS
CTS
RxD
TxD
RI
COM 1
RS232
For the connection between the PC and the device the following null modem cable is necessary:
Level II is not equipped in the standard version of the controller. However, a large number of additional
inputs and outputs can be provided via this connection level, if necessary.
The following different modules are available, which can be used also in combination:
Feature C01
6 additionally binary inputs 48 ... 250 V AC/DC
No Function
100 Binary input 17
101 Binary input 18
102 Binary input 19
Module 1
Feature C02
12 additionally binary inputs 48 ... 250 V AC/DC
No Function
100 Binary input 17
101 Binary input 18
102 Binary input 19
Module 1
No Function
100 R14
101 R15
102 R16
Module 2
103 R17
Level II
104 R18
105 R19
106 Common R14...R19
Feature C04
12 additionally relay (NO conntacts)
No Function
100 R14
101 R15
102 R16
Module 2
103 R17
104 R18
105 R19
106 Common R14...R19
107 R20
108 R21
109 R22
Module 2
110 R23
Level II
111 R24
112 R25
113 Common R20...R25
Feature C05
6 additionally binary inputs 48 ... 250 V AC/DC
6 additionally relay (NO conntacts)
No Function
100 Binary input 17
101 Binary input 18
102 Binary input 19
Module 1
110 R23
Level II
111 R24
112 R25
113 Common R20...R25
Feature C06
2 additional analogue 20 mA inputs
No Function
100 + AI 10
20mA analogue input
Module 3
Level III
101 - AI 10
102 + AI 11
20mA analogue input
103 - AI 11
Feature C07
4 additional analogue 20 mA inputs
No Function
100 + AI 10
20mA analogue input
Module 3
101 - AI 10
102 + AI 11
20mA analogue input
103 - AI 11
104 + AI 12
20mA analogue input
Module 3
Level III
105 - AI 12
106 + AI 13
20mA analogue input
107 - AI 13
Feature C08
2 additional analogue 20 mA outputs
No Function
100 + AO 10
20mA analogue output
Module 4
Level III
101 - AO 10
102 + AO 11
20mA analogue output
103 - AO 11
Feature C09
4 additional analogue 20 mA inputs
No Function
100 + AO 10
20mA analogue output
Module 4
101 - AO 10
102 + AO 11
20mA analogue output
103 - AO 11
104 + AO 12
20mA analogue output
Module 4
Level III
105 - AO 12
106 + AO 13
20mA analogue output
107 - AO 13
The following figure shows a standard connection between REG-DPA and the P-Coil. In the figure also the
standard connections to the SCADA are shown. Especially the last items depends on the requirement of the
utility.
REG - DPA
+UH
R12 AUTO
MANUAL
R11 Error_Sum
R10 Earth-fault
R9 Umin Petersen-Coil
L
R1 Motor higher
R2 Motor lower
N
+UH
BI_1 Endswitch higher
BI_9 AUTO
BI_10 Manual
UH BI_x Binary inputs
Rx Relay
+UH Auxilliary power +
-UH Auxilliary power -
PE PE
AC Version
Nominal Un: 110-230 VAC/VDC
Overload permanent: 1,3 Un
Overload for 1s 2 Un
DC Version
J 22
LWL
J 21
GND
+5V
LED 11
1 2 3
1
J 01
LED
LED 13
LED 12
J 23
J 24
J 02
COM1 J 03
J 04
1 J 05
J 06
J 07
2
128 mm
J 34
J 35
J 36
3
J 32a
J 32b
J 33a
J 33b
Reset
1 1 1 1 1 1
PE -X5 -X6 -X7 -X8 -X9 -X10
360 mm
3.6.6.2 Connectors
3.6.6.2.1 PE
L1 / +110 +5 V =>+12V
0
N / -110 -5 V
L1
DSP
N
DSP_Capture
L2
DSP
N
L3
DSP
N
> 30 > 45 0 0
> 30 < 30 0 red
< 15 > 45 red 0
< 15 < 30 red red
3.6.6.4 Jumper
The configuration of the Jumper as shown in Fig. 3.62 is the standard ex factory.
The Nominal input-range of the analogue measurements can be selected with the following jumpers:
Jumper Function
Connection 1-2
32a
500 V 100 V
32b
33a
500 V 100 V
33b
34 30 A 6A
35 30 A 6A
36 30 A 6A
REG-DPA Petersen-Coil
+ Pot
+ Uh endswitch
high
B_9 Auto BI_1
low
BI_2
BI_10 Manual
- Uh
- Uh
- Uh
Une Une 0...100 VAC
R7
X1:10 L1
L1 X1:15
X1:11 L2
(L2) X1:12 L3 AC-S2
(L3) X1:16
PAW U0d_Tr
X1:8 N
N
Ip
k l
PE
22 kΩ X1:29 30
k K
l L
PE
REG-DPA Petersen-Coil
+ Pot
+ Uh endswitch
high
B_9 Auto BI_1
low
BI_2
BI_10 Manual
- Uh
- Uh
- Uh
Une Une 0...100 VAC
R7
X1:10 L1
L1 X1:15
X1:11 L2
(L2) X1:12 L3 AC-S2
(L3) X1:16
PAW U0d_Tr
X1:8 N
N
Ip
k l
PE
22 kΩ X1:29 30
k K
l L
PE
10 mm 760 mm 300 mm
R4
N1 (ICC) N1
R3
N3 X3 N3
Q1
Q1+ Q2+ Q2
K3 F1
K1 K2 F1
760 mm
R1+R2
X1 Übergabeklemmen R1/R2
L1/L2
Kabelabfangschiene
L1 L2
N1 (ICC) N1
R3
N3 N3
K3 Q1+ Q2+ K4 Q1
810 mm
F1 E3 Q2
K1 K2 F1
760 mm
R1+R2
R1/R2
X1 Übergabeklemmen
L1/L2
L1 Kabelabfangschiene L2
Q1
N3 Q1+ Q2+ N3 Q2
F1
K1 K2 F1
N1 (ICC) N1
R1+R2 R1/R2
L1/L2
L1 L2
X1 Übergabeklemmen
Kabelabfangschiene
210
max. high
mounting area: 1000 x 440 mm (HxB) incl. mounting plate
The following figure shows the current injection included on the left side of a motor-drive for a Petersen Coil.
The dimension of the current injection is 470 x 670 x 260 mm ( width x high x depth )
Fig 3.1: Dimension for the current injection with a depth of 260 mm
Under construction
4 REG-DP(A)
REG - DP LED
LCD - display
Status F1
M
F2 Function-key
F3
F4
F5
Escape
LED's:
- Status and Error LED are
separated
- 18 LED's instead of 12 LED's
Keyboard:
- Remote and Local are separated
- New button: ACK
LCD-display
LED's
Status green Status of the controller
Error_sum
The keys for the menu are still available. It is also still possible to navigate in the menu, to display and to
modify parameters.
ESC (Escape)
Note:
The keys will only be active, if the controller is switched to operation mode 'MANUAL'.
ENTER
to confirm a changed parameter in the 'SETUP' menu.
Repeat function
If a key is pressed for quite some time, the function of the key will at first be repeated every second. After
approx. 10s, the repeat frequency will be increased.
If controller parameters should be set or changed, the following operation principle applies:
¾ With every push of the key <local / remote> there will be a change to the other operation status
( Key <F1> or key <⇒> would list the next page of possible operation modes )
¾ Turn pages with the keys <F1> to <F5> and the horizontal arrow keys until the required parameter is
reached.
For example, with the sequence <F2><F2><F3> the parameter for the threshold level can be
reached
¾ With the horizontal arrow keys < ⇐ > and < ⇒ > the value of the increments resp. decrements
in the right column may be changed. Therefore it is possible to navigate very quickly, even within
very big number ranges.
¾ <F3> resp. <F5> are used for special functions in some 'SETUP'- menus.
¾ If the modification of a value is finished, the changed value must be confirmed by the key <ENTER>.
Additionally, with the confirmation the display is changing back to the previous menu level.
¾ Leaving the setting menu without changing the value: short striking of <ESC > (abort)
¾ Leaving the parameterization and return to the initial display mode for example resonance curve:
long pressing of key <ESC> ( ESC++ )
¾ In the operation mode "AUTO", the keys "Higher" and "Lower" are locked
If any error occurs, this is displayed with a short information in the status line. More detailed information can
be found with:
<MENU>
<F5: Help>
1. Line:
From the 2nd line down the following items are shown:
¾ Une the actual measured 50 Hz zero-sequence component with amplitude and angle
¾ Icomp the actual compensation current of the whole network
¾ v the last calculated detuning v in % resp. in A
¾ Ice capacitive current of the whole network, referred to the bus bar
¾ Iw losses of the zero-sequence system, expressed in A
¾ Ifix value of the fix-coil assigned to this controller
¾ Iext all external coils
¾ small analogue graphic display of the actual coil position
¾ Usync Synchronisation voltage for the CCI, amplitude and phase (primary value)
¾ Uci Voltage at the current injection point ( primary value )
¾ Uns Voltage at the Petersen-Coil ( primary value)
¾ Uod Voltage at the open delta at the bus bar ( primary value )
¾ Ici Injected current ( primary value )
¾ Is Current through Rs ( primary value )
¾ If Current through the fix-coil ( primary value )
On the display, the temporal characteristic of the coil position Ipos and of the zero-sequence-voltage Une is
shown as a line diagram. In the left diagram, the linearized coil position Ipos is displayed in [A] and in the
right diagram the zero-sequence-voltage Une is displayed logarithmically in [V], in a range of three decades
which corresponds to the range of 0.1 V ... 100 V.
In the diagram, the actual values are on top of the diagram. These actual values are marked with small
arrows, which are symbolizations for writing pens. In order to permit a more accurate reading of the values,
the measured values are also displayed digitally.
Above the numerical display of the actual measurements, the actual state of the controller is displayed. Thus,
even in the operation mode 'recorder' it is possible to recognize the actual status of the controller.
The actual transportation speed is shown in the right corner at the bottom of the screen and can be changed
by pressing the keys <F4> and <F5> in the following steps:
• 12 s / Div,
• 1 min / Div
• 5 min / Div
• 10 min / Div
Using the keys <F1> and <F2> it is possible to switch to the mode 'History' and to search for the interesting
events in the memory, according to the arrow directions.
Pressing the key <F3> changes to a submenu in which additional parameters for the recorder may be set.
Scrolling:
By this parameter, the different transport-rates for the keys <F1:ñ> and <F2: ò> may be set for the search in
the history- buffer. The following step sizes per key strike are selectable:
1 Pixel
1 Div
3 Div
5 Div
1 min
1h
Time search:
To enable a faster search in the history-buffer, it is possible to insert the date and clock-time of the
interesting point of time directly. This point of time corresponds to the position of the pens.
The values to be changed can be selected by means of key <F3> or by means of the arrow- keys < ⇐ > and
< ⇒ >. Using the keys <F1>, <F2> resp. <F4>, <F5> the value may be changed.
< ESC> aborts the modification, whereas <ENTER> accepts the actual value.
Fill Level:
The actual fill level of the recorder is shown here in % resp. in days.
Method of recording:
It is checked every second, if the measured value, which should be recorded, has changed by a defined
threshold. If the variation exceeds this threshold value in positive or negative direction, a complete set of
data is stored in the recorder. By this method a very compressed recording occurs.
The buffer is organized as a ring-buffer, i.e. as soon as the buffer is full, the oldest data is overwritten.
The standard settings of the thresholds are fixed in such a way, that the three channels may be stored over a
period of approx. two weeks, assuming that there are only usual changes within the system.
Start / Stop:
By means of this key, the recording may be frozen so that, for example, the data can be transmitted to a PC
later
The assignment and the thresholds of the measured values, which should be recorded, are freely selectable:
Key <F3> may set the 'Resolution' for the trigger for a new recording. After the recording, the actual value is
used as the new reference value for the calculation of the threshold.
The zero-sequence voltage is stored and displayed logarithmically. This type of recording enables also for
very small voltages a good resolution.
Channel 3 , ( invisible ):
In this channel, an additional information may be stored, e.g. the phase angle of the zero-sequence-voltage
Une.
Caution:
If the assignment of a recording channel is changed, all data stored in the recorder will be deleted.
4.3.5 Statistics
The statistics is displayed either as sum statistics (sum) or as statistics per calendar week (w). Key <F3>
permits the change between the different display methods. A turn of the page can be made by key <F1>
resp. by the arrow keys < ⇐ > and < ⇒ > .
Parameter Description
AUTO Sum time of the operation mode 'AUTO':
cleared when reached 100 000 h
Automatig range selection of days: d
Motor On Sum time of the commands "Higher" and "Lower"
Also the input Mot_run of the P-Coil is considered.
GND fault Sum time of the earth faults including transient earth fault
Curr Inj. Sum time of the Current injection active
GND transient Number of the transient earth faults ( Only number of earth faults with
shorter duration, than the defined 'transient earthfault time')
earth faults Number of permanent-earth faults (without transient earth fault)
Iw - incr Number of increased wattmetric component ( Counts of the R_on)
>Threshold Number of exceeding the tolerance range
The data can also be read out using e.g. the terminal program included in the WinEDC with the following
REG-L commands. The results can be transferred to other programmes as, for instance, Excel or Word, with
Cut-and-Paste
Statistics
Auto MotorOn GNDfault CurrInj. Search Tuned Tuned NC TuneUmin GNDTrans GND-Perm Iw-Incr >Thresh.
w40/2004 0:11:15 0:03:15 0:00:00 0:30:51 2 1 0 0 0 0 0 0
w41/2004 26:32:57 0:06:23 0:00:00 3:04:02 95 74 1 0 0 0 0 11
w42/2004 14:25:41 0:06:24 0:00:00 1:57:05 18 12 0 0 0 0 0 0
w43/2004 0:03:21 0:02:49 0:01:43 0:00:00 0 0 0 0 3 2 0 0
w44/2004 0:03:27 0:02:53 0:00:00 0:00:00 0 0 0 0 0 0 0 0
---------
sum 41:16:41 0:21:44 0:01:43 5:31:58 115 87 1 0 3 2 0 11
EspSTATIST 40 44 = 0
<P>
Sum-statistic from:
<P>espstatist
Statistics
Auto MotorOn GNDfault CurrInj. Search Tuned Tuned NC TuneUmin GNDTrans GND-Perm Iw-Incr >Thresh.
sum 41:16:42 0:21:46 0:01:43 5:31:59 115 87 1 0 3 2 0 11
since 01.01.90
EspSTATIST = 0
<P>
4.4 SETUP
The standard parameterization is discussed more in detail in the REG-DP (DAN) section of the WinEDC
The following screens shows only, that it is possible to see the actual status of the binary inputs and to make
all assignments of the digital inputs in front of the controller.
To modify the assignment or the inversion, the function key near to the digital input must be pressed. This
opens a submenu, where it is possible to select a new assignment or to invert the logical signal.
With <RETURN> the actual values will be accepted and stored for further use. With <ESC> the parameter
will be cancelled.
For the output functions and the relays a similar screen exists, for example:
Also here it is possible to make a new assignment or to invert logically the output signal.
Another block of information's can be found in the submenu status which can be reached with the following
sequence:
<MENU>
<F3: SETUP>
<F5: System>
<F1: next page>
<F5: Status>
5 Commissioning
During the commissioning the following items should be done
5.1 WinEDC
Details see chapter 6 Parameterization Software: WinEDC on page 125
5.1.1 Installation
An installation is not necessary. The actual exe-file and the database with the extension .mdb must be
copied to a user selectable directory.
Transfer the actual selected parameter-set from the device into the PC ( read out )
For the connection between the PC and the device the following null modem cable is necessary:
WinEDC/Terminal:
<V>ver
REG-DP: Version 2.3.11 vom 20.12.05
Alternative on REG-DP(A)
Menu/Setup/System/Status
For a 'Firmware Update' connect the serial interface of the PC to COM1 on the front of the REG-DP(A).
Start WinEDC
Check the standard settings for the WinEDC:
and
Test the connection to the REG-DP(A) with the WinEDC terminal program
<Menu>
<F3: Setup>
<F5: System>
<F1: next page>
<F5: Status>
<F1> press for more than 5 sec, until the screen is changing to ‘Urlader’
Comments:
- xxxx represents the firmware version
- mot is the ‘Motorola S-record format’
- moc is the ‘compressed Motorola S-record format’
After the reboot all Parameter can be reset to factory values with
Sysreset = 590
WinEDC/Terminal:
<R>ver
REG-DP: Version 2.3.11 vom 27.10.06
<R>merkmale
FEATURE SE = 1
<R>
If the features are not set, they can be set with the following commands:
sysopen
merkmal se = 1 170303
The setting is necessary, to transfer all parameters from the WinEDC to the REG-DP(A)
Comments:
AA: ... Connected controller, ID of this controller is not used.
R: ... ID of the controller, used in the template
Later on the data for the Petersen-Coil should be transferred only on request.
For verification of the transferred data see chapter 6.1.1.2 on page 127.
This item is only necessary, if the LED 'CI_alive' is not on. (A correct parameterisation is assumed.)
Response to
<R>DevModID *
DevMODID 0 = 0 ---
DevMODID 1 = 0 ---
DevMODID 2 = 0 ---
DevMODID 3 = 0 ---
DevMODID 4 = 0 ---
DevMODID 5 = 0 ---
DevMODID 6 = 0 ---
DevMODID 7 = 0 ---
DevMODID 8 = 0 ---
DevMODID 9 = 0 ---
DevMODID 10 = 0 ---
DevMODID 11 = 0 ---
DevMODID 12 = 0 ---
DevMODID 13 = 0 ---
DevMODID 14 = 0 ---
DevMODID 15 = 74 ICC
<R>
Possible errors:
- CCI is switched off
- Connection REG-DP(A) <-> MCI
- Connection must be:
REG-DP(A) CCI
Tx+ <=> Rx+
Tx - <=> Rx -
Rx+ <=> Tx+
Rx - <=> Tx -
The menu can be found in the <F4: P-Coil> menu with <F3: Poti Calibration>
The coil will be moved to the lower end-switch, than to the upper end-switch. The end-switches and the
corresponding potentiometer-positions are automatically recorded and stored for the further operations.
From the upper position, the coil is moved near to the middle position, where the system is automatically
checked from the controller for the following parameters:
- lost motion
- mechanical play
- after running
If this evaluation is successful, the coil is moved to the lower end-switch, to be prepared for the coil
linearization.
Run-time L->H
Operation time, which were needed from the Petersen-Coil to move from the end-switch low to the
end-switch high.
After-running
Time delay expressed in A of the equivalent coil movement from the beginning of a stop-signal to the
Petersen-Coil and detection of no movement of the Petersen-Coil. This parameter is used during
normal operation to improve the reach ability of exact compensation points. Depending on this value
the motor is stopped before the target compensation point.
Lost motion
Due to mechanical play there is difference between the real air-gap of the iron core and the signalled
potentiometer position. This difference depends on the direction of the movement.
The REG-DP(A) evaluates this mechanical play during the commissioning and uses it to compensate
the displayed values during normal operation. The compensation is only working, if the commands to
the Petersen-Coil is generated by the controller. It can not compensate if the coil is moved by the
buttons in front of the Petersen-Coil.
Poti- linearity
During the commissioning the values of the potentiometer-slider is recorded. Normally this should be
a linear function of the time. The displayed value is the deviation from the linear time interpolation
from the minimum to the maximum coil position. This value should be below 2%. Higher values
indication problems with the potentiometer or with the connection from the controller to the Petersen-
Coil.
With <RETURN> the actual values will be accepted and stored for further use. With <ESC> the calibration is
aborted and the results cancelled.
Possible errors:
- Motor drive supply is switched off
- Wiring of motor up / down commands
- Wiring of end-contacts
- Wiring of potentiometer
- Sequence of the potentiometer wiring.
To compensate the nonlinear function of the inductive current through the Petersen-Coil depending on the
air gap, it is possible to insert in the controller up to 8 interpolation points.
The menu can be found in the <F4: P-Coil> menu with <F4: Poti Linerization>
The following procedure is recommended for the linearization, starting in the lower end-position:
¾ Selection of 8 interpolation points. It is recommended to use more interpolation points in the lower
part of the P-Coil, as the nonlinearity is in this part usually higher.
There should be used only that interpolation points, which have a mark on the mechanical indication
on the P-Coil. To reduce the influence of the mechanical play, the interpolation points should be
approached only from one side.
¾ Repeat the last 4 steps until all 8 values are set or until Imax has been reached.
With <RETURN> the actual values will be accepted and stored for further use. With <ESC> the linearization
is aborted and the results cancelled.
¾ Check of correct connection of N in the motor drive and grounding of auxiliary winding
<MENU> ???
<F3: SETUP>
<F3: Initial operation>
<F4: P-Coil>
<F2: Data of P-coil>
Fig. 5.4: Simplified zero-sequence equivalent circuit of one transformer, one ASC and one Fix-Coil
(red currents and blue voltages are measured)
Show Magnitude
Values are displayed either as Magnitude or Magnitue/ 2
Secondary values
Select primary or secondary values
CI channels
Enables to select the displayed values in the phasor-diagram
CI mode
Enables to select test the different operation modes of the current injection.
For the commissioning the manual mode is important.
After pressing the button <modify> the value of injection can be selected either by typing the value or
with the slider. Although the frequency can be selected. Possible values for ‘f 1‘are
{ -11, -10, -9, -6, 6, 9, 10, 11, 12}. The frequency f2 is calculated directly.
The active channel must be set via the radio-button in the middle.
By pressing the <apply> button, the parameter-set and the values are send to the CCI via the DAN.
In this section also the binary inputs on the CCI and the output’s are displayed. Most of them can
also be modified by selecting the corresponding checkbox.
After few seconds the currents should be shown in the table and the phasor diagrams should be available.
Please check:
After this test set the injected current of the 'manual operation' to 0%
The following figure shows an example for a Petersen Coil without connection to the net.
For all the following steps the coil must be connected to the net. The net should have such a size, that
the resonance point is within the tuning range. The resonance maximum should be as large as possible.
REG-DP(A): The Uns respectively Une is measured directly at the Petersen Coil, the vector group of the
connection of the Petersen Coil to the bus-bar influences the angle of the measured Uns
Current Injection: The Uns is measured directly in the motor drive. The vector group of the distribution
Transformer influences the angle of the measured Uns
U ne _ REG − DP ≈ U ne _ CCI
∠ (U ne _ REG − DP ) ≈ ∠ (U ne _ CCI )
and
U ne _ CCI ≈ U od _ CCI
∠ (U ne _ CCI ) ≈ ∠ (U od _ CCI )
REG-DP/Menu/Commisioning/Current_Injection/Measurement/Phase_angle_of_Usync
- press <modify>
- select radio button of 'Manual Operation'
- set injected current in 'Manual Operation' to 100% with slider or by typing
- set apply
Check:
- angle(Ici_f1, Uns_f1): depends of tuning position. The voltage should be always in sector 1 o 4
- under compensation
- resonance angle(Ici_f1, Uns_f1) ≈ - angle(Ici_f2, Uns_f2)
- over compensation
Possible errors:
- Polarity of Ici
- Polarity of Is
- Polarity of Uod
- Shorting jumper of Is not removed
- Shorting jumper of If not removed, if Fixcoils are used
During the tuning the estimated Icomp and Iw should be always near to the real value.
7: 2006-10-02 13:18:13:
13:23:00
13:22:00
1
0.8
13:21:00
Uo / Vsek
0.6
0.4
13:20:00
0.2
0
13:19:00
t / min
400 350 300 250 200 150 100 13:18:00
50
Ipos / A
Ires _ new
kni _ Is _ new = kni _ Is
Ires _ estimated
Possible errors:
- kni of Is in the CCI for small signals
- Current limiting coil
Also the assignments, which are displayed to the right side of the LED's, are always read out from the
controller. It doesn't use the information from the actual opened configuration file.
The states of the LED's are reflecting the actual physically input.
Additionally all the important analogue inputs of the REG-DP are shown in the middle area of the service
page of the REG-DP.
The right area of this page is used for the test of the current injection controller CCI
With marking the checkbox of the LED's and relays inverts the actual output.
In this way it is easy to check the displayed LED's and to check all connections from the controller to the
SCADA.
For experts an additional function is available, with witch it is also possible to override the results of the
control process for some minutes. This function is only available, if the box 'Override' ,below the analogue
measurements, is marked.
With the second 'Override' it is possible to override also the analogue values to check if the transfer and
display in the SCADA system is ok. It is not more necessary to use an external current respectively voltage
source.
...
EspBIFV
End-switch U read & write(t)
E16 E16 Endschalter L
EspBI
read &
write(t)
Assignment Output-Function
Output-Function:
Motor H EspRelFV
R2 R2 Motor L write &
read
...
Uo > Uerd
Uo > Umax
R9 R9
EspRel
read
Fig. 5.6:Functional diagram for digital I/O with visualization of possible access by the background
programming (H-Program)
In case of using the 'Override', the connection between the 'control process' and {Relays, LED's and
Analogue I/O} are disconnected for 10 minutes. During this time it is possible to set or clear manually the
binary output functions. With this feature, also the test of background programs can be done.
Druml: BA_REG-DPA_e_2007_01_01_012.doc 5.9 40BCheck of Signalling on the Panel and to SCADA 121
REG-DPA a-eberle
The check of the current injection must be done equivalent to the steps in the first controller.
<V>ver
REG-DP: Version 2.3.11 vom 20.12.05
Alternative on REG-DP( A)
Menu/Setup/System/Status
WinEDC/REG-DP:
WinEDC/REG-DP:
Select:
- including: Communication parameters
- including: Coil Data
- including: Name and Identifier
¾ Panel mode
Remote handling of the components via serial interface, modem or internet in the same way, as if
the user would be in front of the EDCSys
¾ Terminal mode
In the Terminal mode the language REG-L can be used directly, written and transferred to the
modules. This programs are called as background-programs ( H-program).
With this background-program it is simple to expand the standard functionalities of the modules with
user specified functions.
¾ Logbook
In each controller respectively earthfault detection system there is a logbook included, where the
events are recorded. It is possible to reduce the recorded data by using an event-filter.
This logbook can be read out and administrated with the WinEDC
¾ Recorder
Depending on the application there are different recorders available.
Also this records can be read out and administrated with the WinEDC
¾ Service mode
This is an additionally tool, to simplify the commissioning
6.1.1 Parameterization
The administration for the parameter-sets must be done for each device separately!!
6.1.1.1 Shortcuts
Transfer the actual selected parameter-set from the device into the PC ( read out )
6.1.1.2 Menu
File
Read
Transfer of the parameters from the device to the PC
Before the start of the transfer, an additionally menu is opened with a list of all devices on the E-LAN.
Via the E-LAN it is possible to read out, parameterize, program etc. all devices on the E-LAN via
only one serial port.
Send
Transfer of the parameter from the PC to the device.
For the REG-DP (DAN) it is possible to select, which parameters should be transferred.
Verify
The verify offers different possibilities to compare the different parameter sets available from the
device, a file, the standard configuration and the actual version under work in the WinEDC
New
Load
With this parameter the standard MS file-open dialog is opened. It is now possible to select a
previous configuration and to reload it.
Save As
The actual configuration can be stored, using a new file-name
Save Cntrl + S
The actual configuration will be saved under the actual file name
Language
Selection of the desired language.
Print
Print of the parameter-set.
Exit
Exit and close the WinEDC
COM
In this menu all parameters for the connection via the serial interface can be set.
The selected COM on the PC must be set to the same parameters than the COM1 on the device.
COM Settings
This selection opens the standard menu from MS to set up the parameters of the serial interface.
Normal communication
Disconnect On Deactivate
If checked, the actual connection will be disconnected if no communication is detected.
Modem
Connection
The following possibilities exist:
- An existing station can be selected
- A new station can be defined
- An existing station can be removed
- The name of an existing station can be modified directly
Phone number
Only numbers are accepted.
Special symbols like ‘-‘, ‘ ‘ and ‘/’ are accepted to make the phone-number more readable.
Modem
The selection out of
- Standard-modem
- Standard-modem with private branch exchange
modifies the proposed beginning of dial-string
at
Enables the selection of the COM. This can be a direct connection to an external modem, an internal
modem or an COMServer reachable via an internal network
Dial string
As a result of the previous selections a dial string is proposed.
This dial string can be modified directly in this field.
Connect
By pressing this button the dial string will be send to the selected modem. The responses of the
modems will be shown in the status window. (The cursor should be inside the window ‘Modem
Connection’ until the connection is completed.)
Hookup or Hang up
This button ended an existing connection. The corresponding command sequence is send to the
connected modem
Close
Closes the window ‘Modem Connection’.
Before it can be closed the modem must be hanged up !!
>>
Clicking on this symbols an additional option window is opened.
Modem initialization
The modem on the PC-side and the modem on the controller side must be initialized with different
strings.
For some modems there exist predefined init-strings. In this window it is possible to add, remove and
modify init strings.
Send
With this button the init string is send to the selected COM.
To init the modem for the controller, the modem must be connected to the selected COM. In most
cases the COM selection must be done in advance, as the modems have auto-baud detection.
The ‘save to firmware’ of the modem is included in the init string.
To simplify the transfer from one PC to another, a simple exchange program is included to export
and import telephone numbers.
6.2 REG-DP(A)
6.2.1 General
General
version of parameter database
Version of the 'config' database, which includes all parameters and their description (read only)
Special name: AA: In this case it is not necessary to know the identification of the controller in the
network. It is always that controller used to which the PC is connected directly.
Name
Name of the station; maximum length is 8 characters
The name is used for automatic generation of file-names for the logbook and the recorder. Therefore
it is preferred not to use special characters like ‘\’.
Due to the automatic generation of the names, it is preferred to include the name of the substation.
This simplifies the handling of controllers in a larger count of substations.
Language
Selected language for the LCD-Display on the controller:
- Deutsch
- English
- Italian
- Czech
- Russian
- Polish
- Finnish
Software version
Version of the installed REG-DP(A) “firmware”; (read only)
Will be detected after first parameter transfer from the REG-DP to the PC.
Hardware Type
installed hardware version of the Une measurement hardware
Possible selections:
unknown
LPER(Reg-DE) Hardware of the first controller generation
NTZ2(Reg-DP) Standard Hardware
Date
Date of the parameter set. The date depends on the transfer to or from the controller.
Time
Time of the parameter set.
Time zone
used time zone for correct time adjustment of the Greenwich time
Hemisphere
ENEL menu
If selected, the menu is reduced to the functions which are necessary for ENEL
Features
The enabling of the features can be done only in the terminal mode and with direct connection to the
controller. The structure of the parameter-menu is adaptive to these settings, so it is necessary to set
up or read from the device the correct feature settings. The feature can be deactivated by setting the
value to 0.
The change of some feature items results in a complete reconstruction of the dynamic menu-tree. In
case of a reconstruction the WinEDC changes to the highest menu-node. It is necessary to go back
to the page 'General.'
In the following, the activating command in the terminal mode is shown in italic letters
PP_NO_COMM
If selected, the feature for the tuning of a network without communication over a SCADA System is
available ( Parallel Petetersen-Coil_controllers with No Communication )
CI
If selected, the extended functions for the current injection are available
EOR
If selected, the REG-DP(DAN) assumes an existing EOR_DM(MCI). The communication to the
EOR-DM is supervised and failures will be signalled.
ENEL
If selected, the extended function for the calculation of the capacitive current of the network is
available. This extended calculation takes also the zero-sequence-impedance of the transformer into
account.
CBR
If selected, the display is expanded by an additionally circuit breaker schema and a modified resistor
control
CORR_TAB
enables the display of the earth-fault correction table
6.2.2 Communication
These parameters are send from the PC to the directly and only to the connected device AA:. The transfer is
started by pressing the button: < Send to AA:>.
The Real Time Clock displays the actual PC-Time. By pressing the button <AA:> the time is send only to the
directly connected controller. By pressing the button <all> the time is send to the directly connected controller
and to all other controllers in the network connected via E-LAN
Device Identification
Same parameters, than on the previous page
Serial Communication
Parameter setting of the two serial ports. COM1 is in front of the controller. COM2 is accessible on
the rear of the Controller and can be used for example for the connection via a modem or for the
connection to a SCADA interface for example REG-P, REG-PE or REG-PM
Mode
Possible selections for the used protocol:
Parity
Possible selections:
None
Odd
Even
Handshake
Possible selections:
None
Xon / Xoff
RTS / CTS
PC-COMx
The parameters configured for the COM in the controller is used for the setting of the COM in the
PC. This improves the handling of the serial interface of the PC in case of necessary changes of the
communication parameters.
E-LAN
Mode
Possible selections:
2-wire
4-wire
Baud
Possible selections:
15 600
31 200
62 500
125 000
375 000
Termination
If selected, the ELAN is terminated in the device by a resistor.
6.2.3 Control
General
The threshold range of the circle 3 is defined as a relative value referring to the reference voltage
Une_ref . If the phase-measurement is not accessible, only the relative amplitude of Une_ref is used.
imag(Une)
1
Threshold range:
3 modul + angle
2
Une_ref
real(Une)
Threshold range:
absolut
Standard value: 15 %
Delay of search
The calculation is only started, if the actual zero-sequence-voltage is permanent out of the threshold
area during this defined time. If the voltage is coming into this threshold area, the timer is reseted.
Standard value: 5 s
Tuning position
With the following parameters the type and size of detuning of the Petersen-Coil can be defined.
The calculation sequence of the controller evaluates the capacitive zero-sequence-current of the
network. Taking the following parameters into account the Petersen-Coil is tuned to the new coil
position.
For the calculation of the new tuning position the following possibilities exists:
Absolute detuning in A
The detuning ΔI CE _ abs is directly defined in A.
I COMP = I CE + ΔI CE _ abs
Relative detuning in A
The detuning ΔI CE _ rel is defined in % of the whole capacitive zero-sequence current of the network.
For a correct calculation of I CE all fixcoils in the network must be taken into account.
ΔI CE _ rel
I COMP = I CE
100
Kind of detuning
Possible selections:
relative
absolute
Relative detuning
Absolute detuning
Search method
The method for the evaluation of the whole capacitive zero-sequence current I CE can be selected
with this parameter.
Possible selections:
Move Coil
Current Injection
Standard value: 5 %
Standard value: ;
Follow-up of Uref
To reduce the number of search operation, slow changes Une can be accepted. If the voltage never
cross the previous defined threshold during the time defined in this parameter, the actual value of Une
at the end of this period will be used as a new reference voltage for the calculation of the new
threshold. Therefore the Une_ref follows slow changes of Une.
A value of 0 deactivates the function
Standard value: ;
Position tolerance
Accepted tolerance for the coil position after coil-movement.
Standard value: 1 %
Search abort
Under some condition the search of the new tuning position respectively the calculation of the I CE is
aborted:
If it is not possible to reach the desired coil position within the predefined cycles the search is
aborted and the coil is moved to a predefined position. The type of the predefined position can be
selected via an parameter.
To protect the Petersen-Coil also against continuous movement, which can overstress the
mechanical components, there is also a parameter for a maximal time of coil movement. In the
controller a counter is incremented during an active movement of the coil and is decremented with
the same speed only during the state “tuned”. If the counter exceeds the preseted value the coil is
stopped.
Standard value: 15
Value Description
Homeposition The P-Coil will be moved to the predefined ‘Home Position’
Tuning Position The P-Coil is moved to the latest successfully tuning position.
Home position
Must be defined and depends on the network size
General
CI-algorithm
Depending on the accessible measurement points according toFig. 5.4: Simplified zero-sequence
equivalent circuit of one transformer, one ASC and one Fix-Coil, different calculation algorithm can
be used.
Measurement Description
Uns Voltage on the Petersen-Coil.
Uod Zero-sequence voltage of the open delta measured on the bus bar
Ici Current of the current injection
Is Current flowing over Rs
If Current flowing over the fix-coil
Value Description
Uod Ici
Uns Ici Simplest algorithm
Uns Uod Ici
Uns Uod Is If Standard ENEL algorithm
If the parameter is set to zero, there will be no extra check of the tuning state. In this case only the
change of the zero-sequence voltage will result to a new calculation cycle.
Standard value: ;
Possible selections:
NO
YES
Possible selections:
Value Description
OFF Continuous current injection is always switched off
ON Continuous current injection is always switched on
autom. Continuous current injection is always switched on according to the
following two parameters
Earth fault
If the zero-sequence voltage exceeds the defined maximal voltage Uearth the current injection and a
coil-movement is aborted.
Uearth threshold
Definition of the maximal zero-sequence voltage Uearth. If Uns exceeds this voltage, it is defined that
the network has an earthfault.
The value should be few percent less than the selected value of Uearth for the protection relays.
Standard value: 30 %
Standard value: 7 s
If the duration exceeds the preset time, a calculation of the actual tuning is initiated in any case.
Standard value: 7 s
change to MANUAL
During an earthfault the calculation of the resonant point and the moving of the Petersen coil is
switched off. After the end of the earthfault a new calculation of the resonant point and the estimation
of the network-parameter is normally initiated. If this parameter is set, the controller changes from
state 'Automatic' to 'Manual'. Therefore the new search operation after the end of the earthfault is
Standard value:
Possible selections:
abs(IF)
A
ICE Ipos
ICE_2 ICE + A
Idetuning
a)
b)
c)
Remark: Each change on the binary input function for the selection of dIc generates a new search
operation
Umax threshold
Definition of the maximal zero-sequence voltage Umax. If Uns respectively Une exceeds this voltage, a
moving of the coil is stopped immediatly. This limit should prevent an earthfault signalisation during
the search operation. Therefore this value should be about 5% less than Uearth .
Standard value: 25 %
Umax delay
Delay for the Umax -state and its signalisation.
Standard value: 0 s
Umax end
For the 110 kV network it is possible to define a value which should not be exceeded for continuous
operation. For the short time, during the search operation, this value can be exceeded.
v ICE_max
1
10
Une / %
Uearth
0 Umax
10
Uend
-1
10
-2
10
0 20 40 60 80 100
Coilposition Ipos / %
The controller searches the minimum position, to fulfil all three boundary values.
If Une is below the Umin threshold the controller searches the whole tuning range of the Petersen Coil
for a value larger than this Umin. If the controller cannot find any peak value above Umin, the controller
moves the coil to a predefined coil position. After a defined time ( 'Message delay') , this situation is
signalled. If there is no change of Une to exceed Umin, the search operation can be restarted
automatically.
In case of using a current injection, a moving of the Petersen Coil is not started. Only a current
injection is started to get new estimation for the network-parameters. The Petersen Coil will be
moved only if the Coil is not at the predefined detuning position.
Umin threshold
Une below this Umin will be treated as disturbances.
End position
Value Description
Home position The P-Coil will be moved to the same position as defined for the
abort in case of exceeding the number of search operations.
Tuning-Pos The P-Coil is moved to the latest successfully tuning position.
Message delay
If there is now voltage change larger than Umin and larger than the Une-threshold during this
'message delay' time the actual situation will be signalled.
change to MANUAL
If this checkbox is selected, the controller changes to 'Manual' mode after reaching the selected
homeposition. For a new tuning operation, the controller must be switched back to 'Automatic' mode
either with SCADA or with the button 'Automatic'
Standard value:
Resistor control
The resistor control is a complete independent task running parallel to the control task for tuning the
Petersen coil. The state 'Manual' or 'Automatic' of the Petersen coil control has no influence to the
resistor control.
Due to the parallel operation, the reachable maximal resolution is about 0,1s. Therefore this resistor
control has some limitations for very fast KNOSPE with a time resolution of less than 0,1s. For
KNOSPE with reduced currents, for example 300 A and time resolutions in the range of 1 s, this
resistor control is a preferred application.
To improve the resistor control, a thermal equivalent of the resistor is calculated as a function of
switching on time and actual Une.
SCADA
+U
H
Binary Inputs (BI)
R_auto_on
R_auto_off
R_block
R_start
Binary Outputs (BO or Rel)
-UH
+U
H
R_auto_on
R_block
-UH
L Resistor
R_on
Resistor on
N
In the REG-DP(A) the following binary input functions (BIF) are available for the resistor control:
The following binary output functions (BOF) are available for the resistor control:
Une
Relay Ron
T_idle
T_Trans
n x repetion-cycle
t
The Time T_Trans is the ' Transient faults <' parameter from the parameter set Uearth, Umax, Umin.
The resistor control starts normally after the final recognition of the earthfault with suppression of
transient faults. The duration of the transient faults is defined in the parameter sets of
{Uearth,Umax,Umin}. With the parameter 'Suppression of transients ' this transient delay can be
suppressed, so that T_delay0 starts with the rising edge of the earthfault detection.
T_delay0 is only active, if the resistor is switched on during normal operation. In this case the voltage
Une is less than the Uearth threshold. The RC is in the idle state and waits for the recognition of an
earthfault.
For some requirements the initial value of R_on can be defined (' Idle state at Une < Uearth '). With
this parameter the situations with continued switched on resistor for damping of the unsymmetry
during normal operation can be solved. The parameter T_delay0 defines how long the resistor
should be in the on state after the first recognition of the earthfault.
The first cycle of the RC can be defined with T_delay1 and T_R_on.
The following 'repetition-cycle' can be defined with T_Rdelay2 and T_R_on2. With the parameter
'Repetition cycles' the count n of this repetition-cycle can be defined.
Using different combinations of these parameters the most requirements can be fulfilled.
Warning: Rp_on, Rs1, Rs2, Rs12 can be used only in the ENEL configuration
active
Activates the resistor control
Standard value:
Repetition cycles n 0
Repetition delay T_delay2 0 0s
Repetition on-time T_R_on2 1 0s
Suppression of transients
If activated, the time T_delay0 starts immediately with the recognition of an earthfault. Some
switching operations in the network could start the whole sequence.
Standard value:
Value Description
OFF During normal operation the resistor is switched off
ON During normal operation the resistor is switched on
This time is only used, if the previous parameter 'Idle state at Une<Uearth' is 'ON'.
Standard value: 1s
Possible selections:
Value Description
OFF The resistor automatic is disabled after the end of the earthfault.
ON The resistor automatic is on, but no automatic start of a cyle with the
beginning of the earthfault. The cycle must be started via SCADA or via
the menu.
autom. One cycle is started automatically with the beginning of an earth-fault
The advantage of this thermal model is on one side, that for higher ohmic faults the number of
possible manual triggers is increased. On the other side, if the resistor is to hot and the RC is
active
Activates the use of the exponential thermal equivalent of the resistor
Standard value: ;
Standard value: 10 s
Temperature max
For the calculation of the thermal capacity of the resistor the rated maximal temperature of the
resistor must be defined with this parameter
Cooling time
Necessary time to cool down the resistor from the maximum temperature to 60° with an ambient air
temperature of 50°
Display Description
R:10 Resistor control is active; 10 times of Rp_on is possible at solid
grounded earthfaults
*R:10 The Wattmetric increase is actual active. During the whole Rp_on time
the star is displayed.
R:0 The resistor is too hot. An additional switching on of the resistor can be
started when the counter is increased to the minimum value 1 ( R:1). The
over-temperature of the resistor can also signalled with a relay.
[R:10] The squared brackets represents a blocked resistor control
Parallel Operation
For the parallel operation the following parameters are available:
Parallel program
Possible selections:
Value Description
OFF Parallel operation is not used
Master / Slave Master / Slave function; Information exchange via the ELAN is possible.
The coupling information of the bus-bar is available via an digital input.
The ability for detection of an external coupling is defined by another
parameter.
No Comm Must be set if the parallel operation should be done without
communication between the controllers.
active
Possible selections:
Value Description
OFF Parallel operation is never recognized used
ON Parallel operation is always on
BB-Coupling If the coupling of the bus bar via circuit breaker or external over the
network is recognized, the selected parallel operation mode will be
activated.
Value Description
… No slave
M1 According to the identifications A: … Z4:
Value Description
No If the coupling is detected, the coil of the slave is blocked immediately
tuning If the coupling is detected by the controller, the slave coil is moved, if the
master is not able to do a successfully tuning with his own coil. The
master will move the coil of the slave to such a position, that he has
enough space for his own tuning.
def. position The coil of the slave will be moved to a predefined home-position, before
the master is tuning his own coil. The home position is defined with the
next parameter.
Value Description
Stop In case of Umin the slave stops at actual position
Home position The slave is moved to his defined home-position, before the master
starts with his tuning
Tuning Position The slave is moved to his last successful tuned position, before the
master starts with his tuning
Homeposition, if slave
Definition of the home position. This parameter must be activated with the previous parameter.
EOR-DM ID
ID of the EOR-DM ( MCI )
External CI blocked
Possible selections:
Value Description
NO The CI of the controller is always available for the MCI
Manual The CI is not available for the MCI, if the controller is in the manual
operation state
always The CI is always blocked for the MCI. There is no limitation for the DAN
to access the CI.
6.2.4 Commissioning
The Commissioning is splitted up into three parts according to the components of the earthfault
compensation controller:
- REG-DP (DAN)
- Petersen Coil
- Current Injection (CI)
REG-DP(A)
Measurement
Inverse polarity
The polarity of the measurement can be changed with this parameter. It is not necessary to change
the real wiring.
Current transformers
Nominal current I1
This is the nominal input current of the internal CT_1 which is connected to the REG-DP (DAN)
knI1 = Iprim/Isek
knI is the nominal ratio of the current transformer
inverse polarity
The polarity of the current transformer can be modified
assignment of I1
Possible selections:
Value Description
OFF No assignment
NER Used by the feature NER
Nominal current I2
This is the nominal input current of the internal CT_2 which is connected to the REG-DP (DAN)
knI2 = Iprim/Isek
knI is the nominal ratio of the current transformer
inverse polarity
The polarity of the current transformer can be modified
assignment of I2
The same assignments as for CT_1 can be defined.
- Additionally all digital inputs can be read and all outputs are programmable by the user with background
programming ( H-Prog)
...
EspBIFV
End-switch U read & write(t)
E16 E16 Endschalter L
EspBI
read &
write(t)
Assignment Output-Function
Output-Function:
Motor H EspRelFV
R2 R2 Motor L write &
read
...
Uo > Uerd
Uo > Umax
R9 R9
EspRel
read
Fig. 6.12:Functional diagram for digital I/O with visualization of possible access by the background
programming (H-Program)
Binary Inputs
The threshold level for the inputs must be defined during the order.
As input signal DC or AC signals are accepted. The voltage input is converted to a logical signal.
This logical signal can be inverted using the following table. Additionally each physical input can be
assigned to the ‘binary input function’ ( BIF)
Gray ‘binary input functions’ ( BIF’s) are fixed and cannot be changed by the user.
In the field 'user name' each binary input can be assigned with an user selectable name with a length
of 8 characters. These user names are used in the panel mode and on the service page.
20 Start_search The rising edge of this signal starts a new search cycle of the controller.
21 R_start The rising edge of this signal starts with the switch on of the resistor the
cycle for the ‘wattmetric increase’
22 R_auto_on SCADA pulse => REG-DP: Activating of the Resistor control
23 R_auto_off SCADA pulse => REG-DP: Deactivating of the Resistor control
24 R_auto_onoff SCADA pulse => REG-DP: Change of Activating / Deactivating of the
Resistor control
25 R_block Blocking of the switching on of the resistor by an external signal. For
example by an external temperature supervision of the resistor.
26 Pulse:CI_on SCADA pulse => REG-DP: Switch on of the current injection
27 Pulse:CI_off SCADA pulse => REG-DP: Switch off of the current injection
28 reserved Reserved for future use
29 Coupling Static signal => REG-DP: The bus bars are coupled via a sectionalizing
circuit breaker or via a bus coupler. The parallel operation mode of the
controller is activated.
30 Fixcoil on Static signal => REG-DP: A fix coil is switched on. This information is
specially used for the calculation of an relative compensation.
31 Quit error Quit of the controllers error state
32 EarthF_corr1 Static signal => REG-DP:
33 EarthF_corr 2 In case of an earthfault the P-Coil is moved according this table.
34 EarthF_corr 3
35 EarthF_corr 4
36 R_enabled The raising edge is ending the self-blocking function of the resistor control.
The resistor control is waiting for a new trigger at the next earthfault.
37 CI_block Static signal => REG-DP: blocking of the current injection
38 Rp_on The resistor Rp is switched on
39 Rs2_on The relay for Rs2 is energized => Rs2 is switched off (CRs)
40 Rs12_on The relay for Rs12 is energized => Both resistors Rs1 and Rs2 are
switched off ( CCRs)
41 CBR_S1 Status of the switch S1 for the CB-schema
42 CBR_S1inv Two information’s are required for 00, 01, 10, 11
43 CBR_CB1 Status of the switch CB1 for the CB-schema
44 CBR_CB1inv Two information’s are required for 00, 01, 10, 11
45 CBR_S2 Status of the switch S2 for the CB-schema
46 CBR_S2inv Two information’s are required for 00, 01, 10, 11
47 CBR_CB2 Status of the switch CB2 for the CB-schema
Also here the signals can be assigned with user names to make the display on the panel and service page
more readable.
15 Tuned_nC Signal ‘tuned but not compensated’: The desired compensation has been
not reached. The controller has moved the coil as much as possible, but
the desired compensation point cannot be reached by the controller taking
the predefined boundary conditions into account. One example is that the
desired compensation point is outside the tuning range of the Petersen-
Coil.
16 Umax_nC Signal ‘Umax reached and not compensated’.: Due to the level of Umax it
was not possible to reache the desired compensation point.
17 Block Signal ‘Block’: The controller is in the operating mode ‘AUTO’ but blocked
by an event or command via the digital inputs.
18 HomePos1 Signalling: The coil has reached his home-position.
This home-position is selected if:
- no successful search over the whole tuning range, because Une < Umin
- abort of search or abort of calculation.
19 HomePos2 Reserved.
20 Remote Signalling: The controller is switched to ‘remote’. On the controller the
buttons <motor high>, <motor lower>, <MANUAL> and <AUTO> are
blocked by the software. A physical disconnection of the binary signals
doesn’t occur. The menu of the controller and all parameters are still
available.
21 Fixcoil on Signalling: The fixcoil is switched on an is used for the calculation of the
desired compensation.
22 Coupling Signalling: Parallel operation of the controller is active. This signal is a
routed signal of the digital input function (29) for coupling.
23 R_auto_on Signalling: Resistor control is active
24 R_block Signalling: Resistor control is deactivated
25 R_on Command: The resistor for the wattmetric increase is switched on.
26 R_T>> Signalling: Resistor is to hot.
27 PotiWarning A gap in the potentiometer was detected.
28 SIM Internal simulation of the network is active
29 Alarm Common alarm signalling:
- Exceeding of the maximum allowed time for search ( 45 min )
(38:T_MotOn)
Alarm:
- Exceeding of search time ( 45 min ) ( 38:T_MotOn)
- Exceeding of number of searches ( 37:n>search)
Error:
- Motor fault
o No movement detection on actuator command (33:E:Move)
o Wrong direction (32:E:Dir)
- Potentiometer fault
o Broken conductor (39:Pot_???)
- Both end switches detected at the same time
- Positioning error
- Error signalling from the P-Coil (DIF 10:E:Error )
Status:
- All internal errors for example:
o RAM
o ELAN
o battery
o ...
37 >n_Search Signalling: within n search respectively calculation cycles it was not
possible to make an successful tuning of the Petersen-Coil
38 >T_MotOn Signalling: The predefined maximum of the motor run time was exceeded.
39 PotiError Signalling: An error on the measurement of the coil-position via the
potentiometer was recognized; for example a broken conductor
40 Une_?? Signalling: An error on the measurement of the zero-sequence voltage
was identified, for example a value > 120% of the predefined nominal
zero-sequence voltage
41 E:MANUAL Signalling: Routed signal of the digital input ‘E-Manual’
42 E:ERROR Signalling: Routed signal of the digital input ‘E-Error’
43 CoupleSignal Replication of the input signal 'coupled'
44 CoupleViaNet External coupling in the network was detected.
45 ELAN Error Signalling: Common signalling for errors on the E-LAN
46 U12<< Reference voltage is less than 35 VAC => The measurement of angles is
impossible. The controller switches over to the calculation method using
only the amplitude
47 R_armed Resistor control is waiting for the next earthfault
48 SearchDelay True, if the zero-sequence voltage is outside the tolerance range of the
zero sequence voltage. The controller has not started with the calculation
Alarm delay
Alarm messages will be signalled only if the duration of the alarm is longer than this predefined time.
Error delay
Error messages will be signalled only if the duration of the error is longer than this predefined time.
Notation:
Empty not used
+1 used as normal OR
-1 inverted signal is used for the OR
For each user BOF an individual signalisation delay can be defined in the column 'Delay'.
Analogue I/Os
Ip
+ R_Temp
A3 A8
-
Fig. 6.13: Functional diagram for analogue outputs with visualization of possible access by the background
programming ( H-Program )
mA y [%]
20 100
4 20
0 0
0 100 Uen / V 0 1 Uen
mA y [%]
10 50
8 40
0 0
0 10 100 Uen / V 0 0,1 1 Uen
The function and correct parameterisation in combination with the SCAD system can be checked very easy
on the service page. In the 'Override mode' the analogue values can be overwritten for some minutes with
direct input via the keyboard.
Petersen Coil
Petersen Coil
I_min
Value of the Petersen coil in the lower position at the ‘end switch lower current’.
This current will flow through the Petersen coil in case of an solid earthfault.
I_max
Value of the Petersen coil in the higher position at the ‘end switch higher current’.
This current will flow through the Petersen coil in case of an solid earthfault.
15 kV network:
If the coil is designed for 20 kV and the operation voltage is only 15 kV the reduction-factor is 0,75.
All the current-values must be defined for the nominal voltage of 20 kV.
Possible selections:
This function can be used to limit the active range of the Petersen Coil. During search operation the
controller will not leave the selected range.
I_min
Simulated lower endswitch of the Petersen Coil. The decision is evaluated from the coil Position
measured with the potentiometer. Normal successful calibration is assumed.
I_max
Simulated higher endswitch of the Petersen Coil. The decision is evaluated from the coil Position
measured with the potentiometer. Normal successful calibration is assumed.
Potentiometer
Plausibility check for poti gaps
Enables the function
Us / V
+5,5V
Us_end switch
high
Interpolated values
Ipos= f( motor movment, calibration)
Us_end switch
low
If there are problems with the potentiometer, the parameter for the gap can be increased, but during
one of the next services, the potentiometer in the Petersen Coil should be changed
For some situation, the gap can be set to 100%. In this case the controller assumes that no
potentiometer exists and all values must be interpolated. It is not a recommended version, but
Results of Calibration
The following parameters are results from the coil-calibration. They are only displayed and cannot be
changed by the user
End-switch Low
Value of the potentiometer ratio, where the ‘End-switch Low’ was detected. In case of no end-
switches at this position there was no coil-movement detected for more than 15 s.
End-switch High
Value of the potentiometer ratio, where the ‘End-switch High’ was detected.
Run-time L->H
Operation time, which were needed from the Petersen-Coil to move from the end-switch low to the
end-switch high.
After-running
Time delay expressed in A of the equivalent coil movement from the beginning of an stop-signal to
the Petersen-Coil and detection of no movement of the Petersen-Coil. This parameter is used during
normal operation to improve the reach ability of exact compensation points. Depending on this value
the motor is stopped before the target compensation point.
Lost motion
Due to mechanical play there is difference between the real air-gap of the iron core and the signalled
potentiometer position. This difference depends on the direction of the movement.
The REG-DP evaluates this mechanical play during the commissioning and uses it to compensate
the displayed values during normal operation. The compensation is only working, if the commands to
the Petersen-Coil is generated by the controller. It can not compensate if the coil is moved by the
buttons in front of the Petersen-Coil.
Linearity error
During the commissioning the values of the potentiometer-slider is recorded. Normally this should be
a linear function of the time. The displayed value is the deviation from the linear time interpolation
from the minimum to the maximum coil position. This value should be below 2%. Higher values
indication problems with the potentiometer or with the connection from the controller to the Petersen-
Coil.
Linearization Table
One item of the calibration operation is the linearization of the Petersen-Coil. During this operation
the nonlinear function of the coil-current from the air-gap due to the nonlinear magnetization is
measured and transferred in this table. These values are used by the controller to compensate the
nonlinearity for the display, transfer over 20 mA transducers and for the serial transfer to SCADA
systems.
Fix-Coil
The information of the fix-coil is used to calculate the capacitive current of the whole network.
This information is also necessary if the calculation of the desired compensation is using the relative
compensation.
If there is no information on the external fix-coils, it is easier to use the absolute compensation.
Depending of the parameter ‘Use fix-coil value’ the predefined or the measured value and quality
factor of the fix-coil is used.
Fix-Coil control
If the tuning range of the Petersen-Coil is to small it depends on this parameter, if the controller is
allowed to switch on / off an additionally fix-coil.
Possible selections:
Value Description
OFF The fix-coil will never switched on by the controller.
ON The fix-coil is always switched on, from the controller
AUTO The controller is allowed to switch on/off the fix-coil according to the
requirements to reach the compensation point.
Value Description
Parameter The predefined values are used for the calculation. They are only used, if
also the ‘digital input function’ is true (DIF 30:Fixcoil)
Measured During the current injection the parameters of the fix-coil are measured.
This values are used for the calculation of the compensation current and
the compensation point. The status of the digital input function DIF
30:Fixcoil is not used
Some values are measured directly by the current injection controller. The connection to the CCI is
via an isolated RS485 and it is not necessary to transfer all values in analogues to the REG-DP.
Parameter sets
The size and frequency of the injected current can be set to different values for the following states:
- Manual current injection
- Calculation with current injection
- Continuous current injection
- External CI request ( from MCI for example)
Additionally the maximal zero-sequence-voltage due to the injected current can be set. The injected current
is limited by the controller in such a way, that the zero-sequence voltage does not exceed the preset value.
This occurs according the following equation:
Frequency
Possible selections:
Current
Ratio of the maximal injected current.
This current depends on the number of installed current-limiting coils in the motor drive.
Due to the current injection the zero-sequence voltage is increased, respectively modulated. To
prevent the earth fault detection for tripping, the maximum of une is supervised and if necessary the
current injection reduced.
The previous parameter takes care on the maximal absolute value of Une due to the current
injection. This parameter takes care on the maximal relative change of Une due to the current
injection.
The assignment for the voltages and currents is free. For a better resolution for lower values an additional
jumper is implemented.
Possible selections:
Value Description
OFF Not used
Usync Synchronisation voltage. This is the reference voltage for all the other
five channels. ( normally 230 V )
Uns_P-Coil Zero-sequence voltage measured on the Petersen-Coil. This does not
include the voltage drop on the Rs. ( normally 100 V )
Uod_BB Zero-sequence voltage measured on the bus bar using the open-delta
winding ( normally 100 V)
Uci Voltage measured at the current injection point. Can be up to 500V.
For each input the nominal value and the ratio of the VT in front of this input must be defined.
Possible selections:
Value Description
OFF Not used
Ici Injected Current
Is Current over Rs.
If Current over Fix-Coil
For each input the nominal value and the ratio of the CT in front of this input must be defined.
Digital I/O
The same scope of digital input functions and digital output functions are available as for the internal digital
inputs, relays and LED’s.
Additional Components
With the following parameters it is possible to use either predefined values or measured values of
the zero-sequence components of the transformer. The measurement is done with two frequencies
near to 50 Hz, so that the problems of disturbances from 50 Hz are eliminated.
Used Ro, Xo
Possible selections:
Value Description
Parameter The predefined values are used for the calculation.
Measured During the current injection the parameters of the serial zero-sequence-
impedance of the transformer is measured.
Ro_Tr
Real (watt metric) part of the transformer zero-sequence-impedance R0 _ Tr = real ( Z 0 _ Tr )
Xo_Tr
Imaginary part of the transformer zero-sequence-impedance X 0 _ Tr = imag ( Z 0 _ Tr )
Value Description
OFF Rp is requested for always switched off
ON Rp is requested for always switched on
AUTO Rp is requested according to the requirement in the network
- One Rp is always requested to be switched off during parallel
operation
- The second Rp is also requested to be switched off, if the coil
position of the master is higher than the predefined value
Rp value
Value of the installed resistor in Ohm
Rp ON if Ipos <
If Ipos goes below the predefined value, the second Rw will be requested to be switched on in the
parallel operation mode
Value Description
OFF The R12 relay is always de-energized. Rs1 is never shortened.
ON The R12 relay can be energized and switched off
Rs1 value
Value of the resistor Rs1 in Ohm
SCADA
6.2.5 Options
Local / Remote
active
If checked, the local / remote function is active. The keys in the orange area are not available for the
user in front of the controller.
EspLockBIFV ….
EspLockKB
EspLockRegL
Local/Remote state
xxx
Options
Controller state after reset
Possible selections:
Value Description
unchanged The R12 relay is always de-energized. Rs1 is never shortened.
MANUAL The R12 relay can be energized and switched off
Display
Une display in
Value Description
% Percentage of the nominal value
V In V; the voltage refers to the secondary side of the VT
kV In kV; the voltage refers to the primary side of the VT
Parameter
Possible selections:
value description
k_v_d k … unbalance of the network in %
v … detuning
d … damping of the network in %
Une_Ir_Iw Une … Zero-sequence voltage in V,%,kV
Ir ……. Resonant point in A
Iw …… Watt-metric part of the network
Display of current
With this parameter the scaling of the x-axis is defined.
Possible selections:
Value Description
+Ifix Value of the own coil plus the value of the own fix-coil
+Ifix+Islave Value of the own coil plus all additionally coils seen in the network
only_Ipot Only the value of the own coil.
LCD Saver ON
If this box is checked, the backlight is switched of after 15 min, if now key is pressed within this time.
After one hour also the graphic is switched off.
LCD contrast
The contrast of the display can be modified.
Simulation
Net models
The parameter for three net-models can be defined. The networks can be defined by 4 parameters:
Parameter Description
Ires Resonantpoint in A
Iu Unbalanced current. Defines the maximal resonant voltage
Iw Wattmetric current. Influences the steepness of the resonance curve.
Smaller values defines sharp curves and high values results in flat
curves
phi defines the direction of Ures in reference to phase L1
Coil simulation
Parameter Description
Run Time Time for the movement of the coil from the lower endposition up to the
higher endposition
End switch low End switch low defined in % of maximal value of the potentiometer
End switch high End switch high defined in % of maximal value of the potentiometer
CI simulation
In future
6.2.6 Recorder
The Resolution is selected in % in most of the cases the reference is the actual value and not the maximal
value!
6.2.7 Logfile
BI Binary Input
BO Binary Output, respectively Relay
The signal number represents the bit position in the 4 Byte word and is designed for the maximum
configuration.
The 'x' activates the recording of the change of the signal respectively of the function.
6.3 Panel
In the Panel mode the connection to the controller is via the serial interface. Additionally there can be
also included a modem link.
The serial link is to one controller, which is also identified with the ID AA:
From this Controller, it is possible also to select any other controller, which is connected to the same
ELAN. It is not necessary to remove the serial link and to reconnect to another controller. The
accessibility of all controllers on the E-LAN via one controller is one of the features of the E-LAN
concept.
The possibilities with the panel are the same as the user would be in front of the controller.
Freeze
The actual display is frozen. It is possible to analyze the displayed data without stress.
Copy Panel
With this command the panel is copied to the clipboard and can be used from other programs.
Copy Display
With this command only the LCD display is copied to the clipboard and can be used from other
programs
6.4 Terminal
The Terminal is with some exceptions an ASCII terminal.
It can be used to communicate with the controller via the REG-L language.
It can also be used to write programs in REG-L directly on the controller or to transfer a REG-L
program from the PC to the controller.
Font…
The font, which is used in the terminal, can be selected via the standard MS – font selection tool
Convert OEM-Font
Converts the OEM Font for Windows to enable correct display of special characters like äöü.
Commandline Mode
If checked, the command line mode is active. In this case the whole string is collected in the PC-
buffer and is send to the controller after <return> is pressed.
Initial Return
If checked, each command send to the controller starts with an <return>
RegSys Terminal
Accepts and generates all special combinations, which are specified within REGSys
The selection can include more than one file. The selection is according to Windows-specifications
either with Cntrl for definitive selected files or with shift for a range of files.
Before the transfer the controller must be brought into the boot-loader mode.
This can be done in the following way:
REG-DP ( DAN )
< Menu>
< F3 > Setup
< F5 > System
< F1 > next page
< F5 > Status
< F1 > continuous for 5 s
=> change to the boot loader mode includes also the change of the COM1 settings to
EOR-D
Pressing the <Reset> for 10 s until all LED’s starts to blink.
The Firmware update can be started immediately.
EOR-DM
Pressing the <Reset> for 10 s until the status LED’s begins to blink..
The Firmware update can be started immediately.
In parallel the functions find and find next are also accessible over the menu.
Find…
Find next
Datenlogger
With the data logger it is possible to send REG-L commands to the controller and to store the results
in a file. This can be stored in such a way, that it can be directly used by other programs like excel.
Output File
Directory and name of file
Format
Selection of the type of separation between the data:
- tab tabulator
- CSV comma separated values
Timestamp
If checked, the PC-timestamp is added in each line
Append
If checked, the next data will be appended to the selected file.
Autoincrement
If checked, each new <RUN> starts with an check if the file name already exist. If the file name
exists an index is appended and incremented. This index is incremented on each following <RUN>
command.
Repetition time
For long time recordings, it is possible to define a repetition time for the read out.
Run
Pressing this button starts the logging.
Stop
Pressing this button stops the logging.
6.5 Logfile
6.5.1 General
Font…
The font, which is used in the terminal, can be selected via the standard MS – font selection tool
Find….
Find Next
This two functions enables to search text within the Logfile
If there are connected more devices connected via the E-LAN, it is possible to select the desired
device out of a list.
Before the download starts, it is possible to select a logbook on the PC. If it is from the same device,
only the new data's will be transferred.
Split Logfile…
Existing Logfiles can be split up in two files
Merge Logfile…
Two existing files can be merged
The native format, based on the CSV format, includes some additionally information, which can be
used during the evaluation process.
To reduce the stored data and enable to restore a init state the following data are written in the
Logfile:
- each change of DI,DO,DIF,DOF
- cyclic distributed over more lines: actual status of DIF, DOF, DI, DO, Une, UnePhi and Ipos
7 FAQ
7.1 REG-DP(A)
Clear Logbook
WinEDC/Terminal:
EspLogClear = 0
Clear Recorder
WinEDC/Terminal:
RecCLEAR = 0
WinEDC/Terminal:
merkmale *
FEATURE PP_NO_COMM = 0
FEATURE ENEL = 1
FEATURE SE = 1
FEATURE CBR = 0
FEATURE EOR = 1
FEATURE COM2FIX = 0
FEATURE CORR_TAB = 0
FEATURE SE_OFFSET = 0
Statistic
Statistics
Auto MotorOn GNDfault CurrInj. Search Tuned Tuned NC TuneUmin GNDTrans GND-Perm Iw-Incr >Thresh.
w40/2004 0:11:15 0:03:15 0:00:00 0:30:51 2 1 0 0 0 0 0 0
w41/2004 26:32:57 0:06:23 0:00:00 3:04:02 95 74 1 0 0 0 0 11
w42/2004 14:25:41 0:06:24 0:00:00 1:57:05 18 12 0 0 0 0 0 0
w43/2004 0:03:21 0:02:49 0:01:43 0:00:00 0 0 0 0 3 2 0 0
w44/2004 0:03:27 0:02:53 0:00:00 0:00:00 0 0 0 0 0 0 0 0
---------
sum 41:16:41 0:21:44 0:01:43 5:31:58 115 87 1 0 3 2 0 11
<P>EspSTATIST 40 44 = 0
Only sum-statistic:
<P>EspStatist
Statistics
Auto MotorOn GNDfault CurrInj. Search Tuned Tuned NC TuneUmin GNDTrans GND-Perm Iw-Incr >Thresh.
sum 41:16:42 0:21:46 0:01:43 5:31:59 115 87 1 0 3 2 0 11
since 01.01.90
EspSTATIST = 0
<P>
The language leans on the programming languages Forth and BASIC which had been developed for a fast
close-to-the-machine control. Forth permits a simple summary of command series to new commands. Forth
uses the “Reversed Polnish Notation” (UPN) which is well-known from the scientific HP-calculators.
The programming of the REGSys and EDcSys devices may be made by any ASCII - terminal. The
programme lines are edited as text in the device and stored by <Return> when all is typed in.
The programme lines are read from the interpreter in the device and worked through cyclically in the
'background'.
The list of REG-L commands can be readout with any ASCII terminal.
? General list
? Esp* List of all REG-DP specific commands
? EspI* List of groups of commands starting with EspI
? EspVo List of the group including EspVo
More Details to the REG-L language can be found on the home-page of a.eberle
9 SCADA
Druml: BA_REG-DPA_e_2007_01_01_012.doc 9.1 52BData Point list for IEC 870-5-103 199
REG-DPA a-eberle
Binary Input 5 Bit TK1 160/12
Binary Input 6 Bit TK1 160/13
Binary Input 7 Bit TK1 160/14
Binary Input 8 Bit TK1 160/15
Binary Input 9 Bit TK1 160/16
Binary Input 10 Bit TK1 160/17
Binary Input 11 Bit TK1 160/18
Binary Input 12 Bit TK1 160/19
Binary Input 13 Bit TK1 160/20
Binary Input 14 Bit TK1 160/21
Binary Input 15 Bit TK1 160/22
Binary Input 16 Bit TK1 160/23
Druml: BA_REG-DPA_e_2007_01_01_012.doc 9.1 52BData Point list for IEC 870-5-103 201
REG-DPA a-eberle
If the inside becomes dirty due to improper use, it is recommended that you send the device back to the manufacturer.
If a large amount of dust has accumulated on the terminal blocks, the insulator coordination could fail. Dust particles are
generally hygroscopic and can bridge creepage distances.
For this reason we recommend operating the device with the doors closed. Furthermore, in dusty environments it is
particularly important to ensure that the cable connections are correctly mounted.
A replacement fuse can be found in the plastic container at the bottom of the housing.
Fuse
Caution!
Before changing the battery it is essential that the REG-DPOA voltage regulator
is disconnected from the power supply!!
If for certain reasons this is not possible, the following precautionary measures should be carried out: all the parameters
should be saved using WinREG, the recorder should be read out and the log book and the statistics unit should be
backed up.
Battery
The battery holder should then be removed and the connection plug should be unplugged.
The new battery can now be inserted and the device can be closed again. The steps listed above should then be carried
out in the reverse order.
REG-DPA
Measurement results:
If a REG-DA voltage regulator must be replaced, the device must first be disassembled.
If the device is defective, we recommend sending it to the company headquarters together with a short description of the
fault.
An Allen key is provided so that the disassembly can be carried out easily. It can be used to loosen the flange plate on
the bottom of the device.
After undoing the four screws, the flange plate can be shifted approximately 5 mm to the left, so that the entire wiring
including the connector blocks can be removed through the bottom of the device.
A replacement device can then replace the defective one and can be put into operation within a few minutes.