You are on page 1of 4

TEST CERTIFICATE

Issued To: Dhanvantri Hospital Report No: 18-20180510-20


Vasant vihar, Naubasta Report Date 10/05/2018
Kanpur , Uttar Pradesh Sample Received On Onsite test
Sample by AES Labs
Description Compressed Air Purity Analysis Start Date 10/03/2018
Analysis End Date 10/03/2018
Page 1 of 1

RESULTS
. Compressed Air for Medical and Related Purpose as per ANSI/AAMI/ISO : 8573-1:2010
Parameter Source Air/Ga Results Unit Limits
Chemical Contaminants

Oxygen 21.4 PASS Volume % 19.5 – 23.5


Carbon Monoxide <0.5 PASS Ppmv 5
Carbon Dioxide 384 PASS Ppmv 1000
Oil Mist & Particulate <0.1 N/A Mg/m3 2
Oil Mist <0.1 PASS Mg/m3 N/A
Particulate <0.1 N/A Mg/m3 N/A
Water <1 PASS Ppmv 24
Total Nomethane Volatile <1 PASS Ppmv 25
Organic Hydrocarbons
Methane 0.9 PASS Ppmv N/A
Odor No PASS Pronounced or unusual No
Nitrogen 78.2 PASS Volume % 75 – 81

AUTHORIZED SIGNATORY
TEST CERTIFICATE

Issued To Dhanvantri Hospital Report No: 18-20180510-20


Vasant Vihar, Naubasta Report Date 10/05/2018
Kanpur , Uttar Pradesh Sample Received On Onsite test
Sample by AES Labs
Description RO Water Sample Analysis Start Date 10/05/2018
Analysis End Date 18/05/2018
Page 1 of 3

RESULTS
. Water For Portable and Related Purpose as per ANSI/AMI/ISO : 13959 : 2009
Parameter Test Method Result Unit Limits
Chemical Contaminants

Aluminium (as AI) APHA 3113 (B) ND (<0.003) mg/l Max 0.01
Chlorine APHA 4500 C C ND (<0.02) mg/l Max 0.1
Copper (as Cu) APHA 3111 (B) ND (<0.02) mg/l Max 0.1
Fluoride (as F) APHA 4500 F D ND (<0.1) mg/l Max 0.2
Lead (as Pb) APHA 3113 (B) ND (<0.005) mg/l Max 0.005
Nitrate (as N) APHA 4500 NO3 E 1.4 mg/l Max 2.0
Sulphate (SO4) APHA 4500 SO4 E 1.6 mg/l Max 100
Zinc (as Zn) APHA 3111 (B) ND (0.05) mg/l Max 0.1
Calcium (as Mg) APHA 3500 Ca B <1.0 mg/l Max 2
Magnesium (as Mg) APHA 3111 (B) <1.0 mg/l Max 4
Potassium (as K) APHA 3500 K B <1.0 mg/l Max 8
Sodium (as Na) APHA 3500 Na B 32 mg/l Max 70
Antimony (as Sb) USEPA 200 9 ND (<0.004) mg/l Max 0.006
Arsenic (as As) APHA 3114 (B) ND (<0.005) mg/l Max 0.005
Barium (as Ba) APHA 3113 (B) ND (<0.01) mg/l Max 0.01
Beryllium USEPA 200 9 ND (<0.0001) mg/l Max 0.0004
Cadmium (as Cd) APHA 3113 (B) ND (<0.0005) mg/l Max 0.001
Chromium Total (as Cr) APHA 3113 (B) ND (<0.0005) mg/l Max 0.014
Mercury (as Hg) APHA 3112 (B) ND (<0.0002) mg/l Max 0.0002
Selenium (as Se) APHA 3114 (C) ND (<0.01) mg/l Max 0.09
Silver (as Ag) APHA 3113 (B) ND (<0.00025) mg/l Max 0.005
Thallium USEPA 200 9 ND (<0.0005) mg/l Max 0.002

AUTHORIZED SIGNATORY
TEST CERTIFICATE

Issued To: Dhanvantri Hospital Report No: 18-20180510-20


Vasant Vihar, Naubasta Report Date 10/05/2018
Kanpur , Uttar Pradesh Sample Received On Onsite test
Sample by AES Labs
Description Water Tank Sample Analysis Start Date 10/05/2018
Analysis End Date 18/05/2018
Page 2 of 3

RESULTS
. Water For Portable and Related Purpose as per ANSI/AMI/ISO : 13959 : 2009
Parameter Test Method Result Unit Limits

Microbiological Requirements
Total Viable Count IS 13959:2009 (E) 91 cfu/ml Max 100
Bacterial Endotoxin LAL Test Gel Clot Method <0.25 EU/ml Max 0.25

Total Pareameters: 24

Remarks: The tested parameters meet the specified limits

Note(s): ND means not Detected. The value enclosed in brackets are the detection limits of the mentioned test methods.
The above remarks are computer generated.

AUTHORIZED SIGNATORY
TEST CERTIFICATE

Issued To: Dhanvantri Hospital Report No: 18-20180510-20


Vasant Vihar, Naubasta Report Date 10/05/2018
Kanpur , Uttar Pradesh Sample Received On Onsite test
Sample by AES Labs
Description Borewell Tank Sample Analysis Start Date 10/05/2018
Analysis End Date 18/05/2018
Page 3 of 3

RESULTS
. Water For Portable and Related Purpose as per ANSI/AMI/ISO : 13959 : 2009
Parameter Test Method Result Unit Limits

Microbiological Requirements
Total Viable Count IS 13959:2009 (E) 92 cfu/ml Max 100
Bacterial Endotoxin LAL Test Gel Clot Method <0.25 EU/ml Max 0.25

Total Pareameters: 24

Remarks: The tested parameters meet the specified limits

Note(s): ND means not Detected. The value enclosed in brackets are the detection limits of the mentioned test methods.
The above remarks are computer generated.

AUTHORIZED SIGNATORY