You are on page 1of 12

HOTEL

Fire Sprinkler Reports

for

Abdullah Aldhashy For Construction

King Abdul Aziz Road - Alshefaa


Riyadh City

Prepared By:

Eng / Ayman Elghrieb

Drwazah Engineering Consultant & Safety

King Abdul Aziz Road - Riyadh

Riyadh City

06/03/17

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 2

General Project Data Report (Inputs may have changed)

General Data

Project Title: Hotel Project File Name: hotel..fiw


Designed By: Eng / Ayman Elghrieb Date: 06/03/17
Code Reference: NFPA 13 - NFPA 14 Approving Agency: Civil Defence
Calculations Done According to ordinary Hazard
Client Name: Abdullah Aldhashy For
Phone:
Construction
Address: King Abdul Aziz Road - Alshefaa City, State Zip Code: Riyadh City
Company Name: Drwazah Engineering Consultant &
Representative:
Safety
Company Address: King Abdul Aziz Road - Riyadh City And State: Riyadh City
Phone:
Building Name: Abdullah Aldhahashy For
Hotel Building Owner:
Construction
Contact at Building: Phone at Building:
Address Of Building: King Abdul Aziz Road - Alshefaa City, State Zip Code: Riyadh City

Project Data

Description Of Hazard: Light Hazard Sprinkler System Type: Wet


Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 225 ft²
Default Sprinkler K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: Vk Model: Viking
Size: 1/2 Temperature Rating: 155 F

Water Supply Test Data

Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 431.63 gpm Calculated Inflow Residual Pressure: 168.79 psi

Calculation Project Data

Calculation Mode: Demand


HMD Minimum Residual Pressure: 24.00 psi Minimum Desired Flow Density: 0.10 gpm/ft²
Maximum Water Velocity: 27.00 ft/s Maximum Frictional Loss / 100 feet: 0.00 psi
Number Of Active Nodes: 25
Number Of Active Pipes: 24 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 12 Number Of Inactive Sprinklers: 0

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 3

Fire Sprinkler Input Data

Node Input Data (Inputs may have changed)

Sprinkler Pressure Node Elev (ft) Non-Sprinkler


Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Sprinkler ---- 5.65 24.00 127.95 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 24.00 127.95 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 25.62 128.00 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 38.35 127.95 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 35.96 127.95 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 35.96 127.95 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 46.67 127.95 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 42.42 127.95 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 59.29 128.00 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 52.02 128.00 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 48.87 127.95 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 48.87 127.95 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 35.05 128.00 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 30.63 128.00 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 76.25 128.00 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 62.38 128.00 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 49.06 128.00 0.00


17
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 60.17 128.00 0.00


18 Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
---- 0.000 0.0 ---- 0.0 0.00
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)

Sprinkler Pressure Node Elev (ft) Non-Sprinkler


Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)
No Discharge ---- N/A 97.15 128.00 0.00
19
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 97.15 128.00 0.00


20
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 100.01 121.39 0.00


21
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 108.69 127.95 0.00


22
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 121.46 104.00 0.00


23
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 167.49 0.00 0.00


24
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 168.79 0.00 0.00


25
---- 0.000 0.0 ---- 0.0 0.00

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 5

Fire Sprinkler Input Data

Pipe Input Data (Inputs may have changed)

Nominal Nominal Fitting Total CFactor


Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inc
Node Node Group Data
(inch) (feet) (feet) (feet) h-psi)

1 3 SCHED 40 WET STEEL 1.000 0 E 4.92 2.00 6.92 120

2 3 SCHED 40 WET STEEL 1.000 0 E 4.92 2.00 6.92 120

5 4 SCHED 40 WET STEEL 1.000 0 E 4.92 2.00 6.92 120

6 4 SCHED 40 WET STEEL 1.000 0 E 4.92 2.00 6.92 120

3 4 SCHED 40 WET STEEL 1.000 0 T 9.84 5.00 14.84 120

4 7 SCHED 40 WET STEEL 1.500 0 T 9.84 8.00 17.84 120

7 8 SCHED 40 WET STEEL 1.000 0 T 5.58 5.00 10.58 120

7 9 SCHED 40 WET STEEL 1.500 0 T 8.69 8.00 16.69 120

9 10 SCHED 40 WET STEEL 1.500 0 T 3.71 8.00 11.71 120

11 10 SCHED 40 WET STEEL 1.000 0 E 4.92 2.00 6.92 120

12 10 SCHED 40 WET STEEL 1.000 0 E 4.92 2.00 6.92 120

10 13 SCHED 40 WET STEEL 1.000 0 T 9.84 5.00 14.84 120

13 14 SCHED 40 WET STEEL 1.000 0 T 9.84 5.00 14.84 120

9 15 SCHED 40 WET STEEL 2.000 0 T 13.12 10.00 23.12 120

15 16 SCHED 40 WET STEEL 1.000 0 T 2.46 5.00 7.46 120

16 17 SCHED 40 WET STEEL 1.000 0 T 23.95 5.00 28.95 120

15 18 SCHED 40 WET STEEL 1.000 0 T 23.95 5.00 28.95 120

15 19 SCHED 40 WET STEEL 2.500 0 T 23.29 12.00 35.29 120

19 20 SCHED 40 WET STEEL 2.000 0 T 4.92 10.00 14.92 120

20 21 SCHED 40 WET STEEL 2.000 0 E 6.56 5.00 11.56 120

19 22 SCHED 40 WET STEEL 3.000 0 T 41.01 15.00 56.01 120

22 23 SCHED 40 WET STEEL 4.000 0 T 23.95 20.00 43.95 120

23 24 SCHED 40 WET STEEL 6.000 0 T 104.00 30.00 134.00 120

24 25 SCHED 40 WET STEEL 6.000 0 T 144.36 30.00 174.36 120

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 6

Fire Sprinkler Output Data

Overall Node Groupings Output Data (Inputs may have changed)

Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 3 0 0.00 27.68 0.00 0.00 24.00

2 3 0 0.00 27.68 0.00 0.00 24.00 0.00127

3 1 0 0.00 0.00 0.00 0.00 25.62


3 2 0 0.00
3 4 0 0.00

4 3 0 0.00 0.00 0.00 0.00 38.35


4 5 0 0.00
4 6 0 0.00
4 7 0 0.00

5 4 0 0.00 33.88 0.00 0.00 35.96 0.00229

6 4 0 0.00 33.88 0.00 0.00 35.96 0.00229

7 4 0 0.00 0.00 0.00 0.00 46.67


7 8 0 0.00
7 9 0 0.00

8 7 0 0.00 36.80 0.00 0.00 42.42 0.00331

9 7 0 0.00 0.00 0.00 0.00 59.29


9 10 0 0.00
9 15 0 0.00

10 9 0 0.00 0.00 0.00 0.00 52.02


10 11 0 0.00
10 12 0 0.00
10 13 0 0.00

11 10 0 0.00 39.50 0.00 0.00 48.87 0.00425

12 10 0 0.00 39.50 0.00 0.00 48.87 0.00425

13 10 0 0.00 33.45 0.00 0.00 35.05 0.00339


13 14 0 0.00

14 13 0 0.00 31.27 0.00 0.00 30.63 -0.00037

15 9 0 0.00 0.00 0.00 0.00 76.25


15 16 0 0.00
15 18 0 0.00
15 19 0 0.00

16 15 0 0.00 44.62 0.00 0.00 62.38 0.00655


16 17 0 0.00

17 16 0 0.00 39.57 0.00 0.00 49.06 0.00253

18 15 0 0.00 43.83 0.00 0.00 60.17 0.00509

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
19 15 0 0.00 0.00 0.00 0.00 97.15
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 7

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)

Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

20 19 0 0.00 0.00 0.00 0.00 97.15


20 21 0 0.00

21 20 0 0.00 0.00 0.00 0.00 100.01

22 19 0 0.00 0.00 0.00 0.00 108.69


22 23 0 0.00

23 22 0 0.00 0.00 0.00 0.00 121.46


23 24 0 0.00

24 23 0 0.00 0.00 0.00 0.00 167.49


24 25 0 0.00

25 24 0 0.00 0.00 0.00 0.00 168.79

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 8

Fire Sprinkler Output Data

Overall Pipe Output Data (Inputs may have changed)

q (gpm) F. L./ft Pipe-Len.


Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 5.65 127.95 27.68 24.00 1.00 0.00 0.23748 4.92 1.644


3 0.00 128.00 0.00 25.62 1.049 27.68 E 2.00 -0.022
SCHED 40 WET STEEL 120 10.28 0 6.92 1.622

2 5.65 127.95 27.68 24.00 1.00 0.00 0.23748 4.92 1.644


3 0.00 128.00 0.00 25.62 1.049 27.68 E 2.00 -0.022
SCHED 40 WET STEEL 120 10.27 0 6.92 1.622

3 0.00 128.00 0.00 25.62 1.00 0.00 0.85623 9.84 12.709


4 0.00 127.95 0.00 38.35 1.049 55.36 T 5.00 0.020
SCHED 40 WET STEEL 120 20.55 0 14.84 12.729

5 5.65 127.95 33.88 35.96 1.00 0.00 0.34521 4.92 2.389


4 0.00 127.95 0.00 38.35 1.049 33.88 E 2.00 0.000
SCHED 40 WET STEEL 120 12.58 0 6.92 2.389

6 5.65 127.95 33.88 35.96 1.00 0.00 0.34521 4.92 2.389


4 0.00 127.95 0.00 38.35 1.049 33.88 E 2.00 0.000
SCHED 40 WET STEEL 120 12.58 0 6.92 2.389

4 0.00 127.95 0.00 38.35 1.50 0.00 0.46643 9.84 8.323


7 0.00 127.95 0.00 46.67 1.610 123.12 T 8.00 0.000
SCHED 40 WET STEEL 120 19.40 0 17.84 8.323

7 0.00 127.95 0.00 46.67 1.00 0.00 0.40218 5.58 4.254


8 5.65 127.95 36.80 42.42 1.049 36.80 T 5.00 0.000
SCHED 40 WET STEEL 120 13.66 0 10.58 4.254

7 0.00 127.95 0.00 46.67 1.50 0.00 0.75666 8.69 12.632


9 0.00 128.00 0.00 59.29 1.610 159.91 T 8.00 -0.020
SCHED 40 WET STEEL 120 25.20 0 16.69 12.611

9 0.00 128.00 0.00 59.29 1.50 0.00 0.62087 3.71 7.269


10 0.00 128.00 0.00 52.02 1.610 143.70 T 8.00 0.000
SCHED 40 WET STEEL 120 22.65 0 11.71 7.269

11 5.65 127.95 39.50 48.87 1.00 0.00 0.45839 4.92 3.172


10 0.00 128.00 0.00 52.02 1.049 39.49 E 2.00 -0.022
SCHED 40 WET STEEL 120 14.66 0 6.92 3.151

12 5.65 127.95 39.50 48.87 1.00 0.00 0.45839 4.92 3.172


10 0.00 128.00 0.00 52.02 1.049 39.49 E 2.00 -0.022
SCHED 40 WET STEEL 120 14.66 0 6.92 3.151

10 0.00 128.00 0.00 52.02 1.00 0.00 1.14315 9.84 16.968


13 5.65 128.00 33.45 35.05 1.049 64.72 T 5.00 0.000
SCHED 40 WET STEEL 120 24.02 0 14.84 16.968

13 5.65 128.00 33.45 35.05 1.00 0.00 0.29763 9.84 4.418


14 5.65 128.00 31.27 30.63 1.049 31.27 T 5.00 0.000
SCHED 40 WET STEEL 120 11.61 0 14.84 4.418

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 9

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)

q (gpm) F. L./ft Pipe-Len.


Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

9 0.00 128.00 0.00 59.29 2.00 0.00 0.73381 13.12 16.968


15 0.00 128.00 0.00 76.25 2.067 303.61 T 10.00 0.000
SCHED 40 WET STEEL 120 29.03 0 23.12 16.968

15 0.00 128.00 0.00 76.25 1.00 0.00 1.85974 2.46 13.876


16 5.65 128.00 44.62 62.38 1.049 84.19 T 5.00 0.000
SCHED 40 WET STEEL 120 31.25 0 7.46 13.876

15 0.00 128.00 0.00 76.25 1.00 0.00 0.55566 23.95 16.086


18 5.65 128.00 43.83 60.17 1.049 43.82 T 5.00 0.000
SCHED 40 WET STEEL 120 16.27 0 28.95 16.086

16 5.65 128.00 44.62 62.38 1.00 0.00 0.46009 23.95 13.320


17 5.65 128.00 39.57 49.06 1.049 39.57 T 5.00 0.000
SCHED 40 WET STEEL 120 14.69 0 28.95 13.320

15 0.00 128.00 0.00 76.25 2.50 0.00 0.59210 23.29 20.898


19 0.00 128.00 0.00 97.15 2.469 431.63 T 12.00 0.000
SCHED 40 WET STEEL 120 28.92 0 35.29 20.898

19 0.00 128.00 0.00 97.15 2.00 0.00 0.00000 4.92 0.000


20 0.00 128.00 0.00 97.15 2.067 0.00 T 10.00 0.000
SCHED 40 WET STEEL 120 0.00 0 14.92 0.000

20 0.00 128.00 0.00 97.15 2.00 0.00 0.00000 6.56 0.000


21 0.00 121.39 0.00 100.01 2.067 0.00 E 5.00 -2.862
SCHED 40 WET STEEL 120 0.00 0 11.56 -2.862

19 0.00 128.00 0.00 97.15 3.00 0.00 0.20558 41.01 11.515


22 0.00 127.95 0.00 108.69 3.068 431.63 T 15.00 0.020
SCHED 40 WET STEEL 120 18.73 0 56.01 11.535

22 0.00 127.95 0.00 108.69 4.00 0.00 0.05473 23.95 2.405


23 0.00 104.00 0.00 121.46 4.026 431.63 T 20.00 10.370
SCHED 40 WET STEEL 120 10.88 0 43.95 12.776

23 0.00 104.00 0.00 121.46 6.00 0.00 0.00744 104.00 0.997


24 0.00 0.00 0.00 167.49 6.065 431.63 T 30.00 45.033
SCHED 40 WET STEEL 120 4.79 0 134.00 46.030

24 0.00 0.00 0.00 167.49 6.00 0.00 0.00744 144.36 1.297


25 0.00 0.00 0.00 168.79 6.065 431.63 T 30.00 0.000
SCHED 40 WET STEEL 120 4.79 0 174.36 1.297

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 10

Fire Sprinkler Output Data

Overall Sprinkler Output Data (Inputs may have changed)

Flowing Sprinkler Residual Flowing Sprinkler


Area Group Sprinkler Flowing
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) Area (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

1 5.65 127.95 24.00 225.00 0.123 27.68


Sub Totals For Non-Group 225.00 0.123 27.68

2 5.65 127.95 24.00 225.00 0.123 27.68


Sub Totals For Non-Group 225.00 0.123 27.68

5 5.65 127.95 35.96 225.00 0.151 33.88


Sub Totals For Non-Group 225.00 0.151 33.88

6 5.65 127.95 35.96 225.00 0.151 33.88


Sub Totals For Non-Group 225.00 0.151 33.88

8 5.65 127.95 42.42 225.00 0.164 36.80


Sub Totals For Non-Group 225.00 0.164 36.80

11 5.65 127.95 48.87 225.00 0.176 39.50


Sub Totals For Non-Group 225.00 0.176 39.50

12 5.65 127.95 48.87 225.00 0.176 39.50


Sub Totals For Non-Group 225.00 0.176 39.50

13 5.65 128.00 35.05 225.00 0.149 33.45


Sub Totals For Non-Group 225.00 0.149 33.45

14 5.65 128.00 30.63 225.00 0.139 31.27


Sub Totals For Non-Group 225.00 0.139 31.27

16 5.65 128.00 62.38 225.00 0.198 44.62


Sub Totals For Non-Group 225.00 0.198 44.62

17 5.65 128.00 49.06 225.00 0.176 39.57


Sub Totals For Non-Group 225.00 0.176 39.57

18 5.65 128.00 60.17 225.00 0.195 43.83


Sub Totals For Non-Group 225.00 0.195 43.83

Totals For All Groups 2700.00 0.160 431.65

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 11

Fire Sprinkler Output Summary (Inputs may have changed)

Hydraulically Most Demanding Sprinkler Node

HMD Sprinkler Node Number: 2


HMD Actual Residual Pressure: 24.00 psi
HMD Actual GPM: 27.68 gpm

Sprinkler Summary

Sprinkler System Type: Wet


Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.100 gpm/ft²
Application Average Density: 0.288 gpm/ft²
Application Average Area Per Sprinkler: 125.00 ft²
Sprinkler Flow: 431.65 gpm
Average Sprinkler Flow: 35.97 gpm

Flow Velocity And Imbalance Summary

Maximum Flow Velocity ( In Pipe 0 - 0 ) 0.00 ft/sec


Maximum Velocity Pressure ( In Pipe 0 - 0 ) 0.00 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0089 psi
Actual Average Nodal Pressure Imbalance: 0.0030 psi
Actual Maximum Nodal Flow Imbalance: 0.0066 gpm
Actual Average Nodal Flow Imbalance: 0.0014 gpm

Overall Network Summary

Number Of Unique Pipe Sections: 24


Number Of Flowing Sprinklers: 12

Pipe System Water Volume: 421.92 gal

Sprinkler Flow: 431.65 gpm


Non-Sprinkler Flow: 0.00 gpm

Minimum Required Residual Pressure At System Inflow


168.79 psi
Node:
Demand Flow At System Inflow Node: 431.63 gpm

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Hotel
Hell Page 12

Fire Sprinkler Output Data (Inputs may have changed)

Hydraulic Supply/Demand Graph

200

180
169

160

140

120

100
Pressure psi

80

60

40

20

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 168.79 psi
Calculated Flow Rate: 431.63 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 55.42 psi

Printed by BoltPDF (c) NCH Software. Free for non-commercial use only.

You might also like