You are on page 1of 48

SA3000 Door Access SyStem

Installation Guide
CONTENTS

1 SA3000 Door Access System


1 System Overview
2 SA3000 Model Numbers
2 SA2000 System Upgrades
3 Installation Overview
4 Installation Planning Considerations

5 SA3000 Controller Unit Installation


5 Installation Overview
6 SA3000 Installation
6 Mount the Power Supply/Enclosure
6 Install Conduit and Pull Wire
6 Connect Power to Power Supply/Enclosure
7 Install the Controller Boards
8 Connect to the Network
8 Connect Card Readers
8 Connect Door Accessories
8 Configure Controller Unit

9 Card Readers
11 SE3/CS Installation
11 Mount and Wire the SE3/CS using Narrow Mounting Plate
12 Mount and Wire the SE3/CS using Wide Mounting Plate
14 SE3/CSPP Installation
14 Mount and Wire the SE3/CSPP
16 Proximity Reader Installation
16 Wire the Proximity Reader(s)
18 Wiring to Existing SACS and SASPP
18 Wiring the SACS
19 Wire the SASPP

20 Door Accessories
20 Door Monitor Contacts
20 Wire Door Monitor Contacts
21 Request-to-Exit Devices

Document 988 SA3000 Installation Guide i


January 28, 2008
21 Wire Request-to-Exit Device
22 Door Locking Mechanisms
23 Wire the Door Locking Mechanism
25 Local Alarm
25 Powering the Local Alarm
25 Wire Local Alarm

27 Controller Unit Configuration


27 Configure Controller Boards (using switches)
29 Configure Controller Boards
(using RS-232 config port)
30 Configure Controller Boards (using Telnet)
31 Restore Default Settings

32 Annual Maintenance & Testing


33 Card Reader Testing

34 Troubleshooting
34 Master Controller
35 Door Controller
37 Card Readers

38 SA3000 Security Access System Features

39 Specifications

40 Terminal Block Descriptions

Document 988 SA3000 Installation Guide ii


January 28, 2008
List of Tables

Table 1: SA3000 Component Model Numbers................................................................. 2


Table 2: Maximum Wire Distance ..................................................................................... 4
Table 3: Master Controller TB2: Host Network RS-485 Connections............................ 8
Table 4: SA3000 Supported Card Reader Combinations ............................................... 9
Table 5: SE3/CS Card Reader Accessories ................................................................... 11
Table 6: SE3/CSPP Card Reader Accessory ................................................................. 14
Table 7: Proximity Reader Model Numbers ................................................................... 16
Table 8: Door Controller TB1 Proximity Reader Signals .............................................. 17
Table 9: Door Controller TB2 Proximity Reader Signals .............................................. 17
Table 10: RS-232 Config Port Connection ....................................................................... 30
Table 11: Master Controller LCD Line 4 Messages ......................................................... 34
Table 12: Abnormal Condition Messages ........................................................................ 35
Table 13: Door Controller Input Status LEDs .................................................................. 36
Table 14: Door Controller Error Indicators ...................................................................... 36
Table 15: Electrical Specifications ................................................................................... 39
Table 16: Master Controller TB2: Host Network & SM8 RS-485 Connections.............. 41
Table 17: Door Controller TB1: Card Reader Connections ............................................ 41
Table 18: Door Controller TB2: Card Reader Connections ............................................ 41
Table 19: Door Controller TB3: Door Accessory Connections...................................... 42
Table 20: Door Controller TB4: Door Accessory Connections...................................... 42
Table 21: Door Controller TB5: Tamper and Other Connections................................... 42

Document 988 SA3000 Installation Guide iii


January 28, 2008
List of Figures

Figure 1: Typical Installation/Wiring Plan...............................................................4


Figure 2: Controller Unit: Controller Boards + Power Supply/Enclosure ...........5
Figure 3: Power Supply Installation........................................................................6
Figure 4: Power Supply Assembly..........................................................................6
Figure 5: Controller Boards Installation .................................................................7
Figure 6: SE3/CS and SE3/CSPP.............................................................................9
Figure 7: SE3PROXLR and SE3/PROXMR..............................................................9
Figure 8: SE3/CS Installation (Narrow Mounting Plate) ......................................11
Figure 9: SE3/CS Mounting (Wide Mounting Plate).............................................12
Figure 10: SE3/CS Mount w/ Shroud & Visor.........................................................13
Figure 11: SE3/CS Wiring ........................................................................................13
Figure 12: SE3/CSPP Mounting Diagram ...............................................................14
Figure 13: SE3/CSPP Wiring....................................................................................15
Figure 14: SACS Wiring ...........................................................................................18
Figure 15: SASPP Wiring .........................................................................................19
Figure 16: Door Locking Mechanisms Wiring .......................................................24
Figure 17: Local Alarm Wiring (powered by Controller Unit) ...............................25
Figure 18: Controller Configuration Switches .......................................................28
Figure 19: Master Controller Configuration Flowchart .........................................28
Figure 20: Door Controller Configuration Flowchart ............................................29
Figure 21: Controller Unit Configuration Menu .....................................................29
Figure 22: Controller Boards...................................................................................40

Document 988 SA3000 Installation Guide iv


January 28, 2008
Blackboard Inc. SA3000

Tested To Comply
With FCC Standards

FOR HOME OR OFFICE USE

UL Considerations:

Attention to Installers: All field wiring/cabling connections made to


the Controller need to use shielded cable with one of the shielded
ends connected to earth ground.

SACS/SASPP Card Readers have not been evaluated by UL.

Document 988 SA3000 Installation Guide 1


January 28, 2008
SA3000 D O O R A C C E S S S Y S T E M

System Overview
This manual provides instructions for selecting, installing and configuring SA3000 Security Access
System. Recommendations on selecting an installation location and selecting Door Accessories, used
to monitor and control access at a door, are included. Wiring diagrams show how to connect the
SA3000 system.

The SA3000 Door Access System, designed to work with Blackboard Transaction System (BbTS), consists
of:
• SA3000 Controller (page 2)
• Power Supply and Enclosure (page 2)
• Card Readers (page 2)
• Door Accessories (page 3)

SA3000 CONTROLLER

The SA3000 Controller boards process card information to determine access


privileges defined in its local cardholder database. Transactions are stored in
non-volatile memory until transferred to BbTS. This architecture allows the
SA3000 to operate normally when offline.

POWER SUPPLY AND ENCLOSURE

New installations must be ordered with a Power Supply and Enclosure. The
Enclosure has a hinged, locking door and a tamper switch.

“Controller Unit” refers to the SA3000 Controller, Power Supply, and Enclosure.

CARD READERS

In addition to the Controller Unit, one or more Card Readers must be installed.

Card Readers are ordered separately from the SA3000 Controller Unit, allowing flexibility in Card Reader
selections to meet the application requirements.

Document 988 SA3000 Installation Guide 2


January 28, 2008
DOOR ACCESSORIES

in addition to the Controller Unit and Card Readers, Door Accessories are required to complete the
SA3000 System to monitor and control access at the door. Door Accessories include door locking
mechanisms, door monitor contacts, request-to-exit switches, alarms, etc.

Door Accessories are not available through Blackboard. Ask a door hardware dealer about locking
mechanism options and compliance issues.

SA3000 Model Numbers

Model numbers for SA3000 system components available through Blackboard are listed in the following
table:
Table 1: SA3000 Component Model Numbers
Componenta Model Number Description UL Category
Controllers SA3004 Controller boards - 4,000 cardholder database
SA3032 Controller boards - 32,000 cardholder database Access Control Sys-
tem Subassembly
Power Supplies SE3/PS24ENCL Power Supply with Enclosure, 24 volt Access Control Sys-
tem Power Supply
Card Readers SE3/CSb Magstripe Card Reader
Access Control Sys-
SE3/CSPP Magstripe Card Reader with Pin Pad
tem Accessories
SE3/PROXMR Proximity Reader - Medium Range (HID ProxPro 5355)
SE3/PROXLR Proximity Reader - Long Range (HID MaxiProx 5375)
Card Reader SE3/MPN Narrow Mounting Plate for the SE3/CS n/a
Accessories SE3/MPW Wide Mounting Plate for the SE3/CS
SE3/DS Decorative Shroud (optional)
SE3/VISOR Protective Visor (optional)

a. Configurations using a Controller, Power Supply and Card Reader(s) listed in this table are UL rated.
b. Requires mounting plate, either a SE3/MPN or SE3/MPW

SA2000 System Upgrades1

SA2000 Systems can be upgraded to SA3000. Legacy Card Readers can be used with minor wiring
changes at the Controller Unit. Reference Wiring to Existing SACS and SASPP (page 19). (The SACS
and SASPP have not been evaluated by UL.)

The SA2000 upgrade requires:


• SA3004 or SA3032 Controller
• SE3/PS24V Power Supply

1. SA2000 System upgrades (using SA3000 Controller boards) are not UL rated.

Document 988 SA3000 Installation Guide 3


January 28, 2008
Installation Overview

1 Installation Planning Central


Electronics
Closet
AC mains
BbTS

Considerations (page 5) or
Drop
Ceiling

Conduit

Local
Alarm
Bypass
Cable Key Output

Belden 8723
(or equivalent)
2 pair, 22AWG
0.165”OD Door Monitor
Contacts
Belden 8719
(or equivalent)
1 pair, 16AWG
0.310”OD
continuous electric
hinge or electronic
power transfer

Reader

Crash bar w/
Request to Exit
switch
Electric
Strike

2 Install SA3000 Controller Unit


Installation (page 6)

3 Install Card Readers (page 10)

4 Install Door Accessories


(page 21)

5 Controller Unit
Configuration (page 28)

Document 988 SA3000 Installation Guide 4


January 28, 2008
Installation Planning Considerations

Careful planning of hardware purchases, cable routing, power supplies and reader placement will simplify
a successful implementation of the SA3000 System. Consider the following before ordering hardware:

AC mains Comply with all regulatory,


Network
electrical and safety codes.
Communications
Central
Electronics
Closet
HARDWARE SELECTIONS
or
Drop •Readers
Ceiling Inbound/outbound, number of doors, PIN,
Proximity, SA2000 legacy readers
•Door Accessories
Conduit Locks, contacts, request-to-exit, alarm,
automatic door, bypass output, external
power needed for Door Accessories
•Backup Power in case of failure

Local CONTROLLER PLACEMENT (CENTRAL CLOSET


Alarm OR NEAR DOOR)

Cable Key •AC power availability


•Network communications availability
Belden 8723
Door Monitor
•Multiple Controller Units (power load)
(or equivalent)
2 pair, 22AWG Contacts •Ease of cable routing to readers
0.165”OD
•Wiring distance limitations
Belden 8719 Table 2: Maximum Wire Distance
(or equivalent)
1 pair, 16AWG continuous electric RS-485 Communications 4000' total per loop
0.310”OD hinge or electronic 10-1000Base-T Communications 300'
power transfer SE3/CS, SE3CSPP to Controller 4000' total
Unit
Reader Other Readers & Door see manufacturer’s
Accessories specs
Crash bar w/
Request to Exit READER PLACEMENT
switch
Electric •Cardholder safety
Strike
•Weather protection
•Cardholder convenience
•Cable routing
Figure 1: Typical Installation/Wiring Plan •Installation height regulations

Document 988 SA3000 Installation Guide 5


January 28, 2008
SA3000 C O N T R O L L E R U N I T I N S TA L L A T I O N

Installation Overview

The SA3000 Controller Unit


consists of the following
components:
• Controller
Master
• Power Supply and Enclosure Controller

There are two Controller boards:


the Master Controller and the Door
Controller.

The Master Controller circuit board


contains the Cardholder database
and the interface circuitry to Door
communicate with the host system. Controller
It also has a serial interface for
communicating with the Door
Controller.

The Door Controller circuit board Controller Enclosure Power Supply


controls and monitors Door
Accessories and Card Readers. Figure 2: Controller Unit:
Removable terminal blocks provide Controller Boards + Power Supply/Enclosure
wiring connections to Readers and
Door Accessories.

The Power Supply has a toggle switch and terminal blocks for connecting to the AC Mains. The Enclosure
has a hinged, locking door and tamper switch.

Installing the Controller Unit involves the following tasks:

• Mount the Power Supply/Enclosure (page 7)


• Install Conduit and Pull Wire (page 7)
• Connect Power to Power Supply/Enclosure (page 7)
• Install the Controller Boards (page 8)
• Connect to the Network (page 9)
• Connect Card Readers (page 9)
• Connect Door Accessories (page 9)

Document 988 SA3000 Installation Guide 6


January 28, 2008
SA3000 INSTALLATION

SA3000 I NSTALLATION

Mount the Power Supply/Enclosure


AC Power knockout
1 Protect Power Supply from debris while
mounting the enclosure.
Mounting
2 Remove knockouts from the Enclosure holes
that will be used for wiring. accept
AC Power should enter the Enclosure’s 1/4"
hardware
upper-left corner to help provide 1/4”
separation from other wiring.
3 Secure the Enclosure to a wall using
hardware appropriate for the wall LNG
material.
Mounting holes accept up to 1/4”
hardware.

Install Conduit and Pull Wire

1 Install conduit from Controller for Power,


Card Readers, Door Accessories, and
network communications.
2 Pull wire through conduit.

Figure 3: Power Supply Installation


Connect Power to Power Supply/Enclosure

Disconnect external AC power when installing any wiring.


LNG

Connect to 120 VAC @ 60 Hz. Connect only to a 20A


maximum branch circuit protection or equivalent.

1 Strip back the insulation on the AC wire .28" so no bare wire is Power
exposed when installed in the AC terminal block. Switch
2 Install the appropriate wires into the AC terminal block, as
shown in Figure 4, and tighten the screws to 5 - 7 in-lbs.
3 Re-connect external AC power.

Maintain 1/4" separation from AC wiring to other wiring.


Figure 4:Power Supply Assembly

Document 988 SA3000 Installation Guide 7


January 28, 2008
SA3000 INSTALLATION

Install the Controller Boards

Power Supply switch must


be OFF. power
plug LNG

1 Secure the Master


Controller board onto the top
four standoffs and secure it J1

RX485+
TX485+
232 TX

RX485-
TX485-
232RX
GND

GND
with four ¼" standoffs from Master TB3
485+

Controller
GND

the hardware kit.


485- VDC
GND
485+ VAC
TB1
485- VAC
GND J7
485+
485-
GND
TX485+

2 Secure the Door Controller ribbon


TX485-
GND
RX485+

board onto the lower four cable


RX485-
TX485+
TX485-

jumper
GND

standoffs and secure it with RX485+


RX485-
TB2

four ¼" standoffs from the DEC INC ENTER CLEAR


MASTER

hardware kit.

MASTER
VDS 485-
GND 485+
485+ TB6 GND
485- RX232

TAMPERTAMPERAUX
D1/CLK TX232
TB1
D0/DATA NO
SW1
GLED

3 Connect the short ribbon


COM
RLED IN+
BEEP IN-

cable jumper included in the power TAMP


VCS+
GND
FS1
TB5
ACFAILBATLOW IN+
IN-
IN+

hardware kit from the J5 LEDs SASPP TX


SASPP RX
D1/CLK
TB2
GND
IN-

D0/D ATA GND


INPUT POWER

connector of the Master Door GLED


RLED
BEEP
VDC

VAC

Controller
TB3 TB4

Controller to J2 of the Door


TAMP VAC
LOCK LATMON AUX ALARMREQEXBYPASSDOOR SPARE
VDC+
COM

COM

COM

COM
GND

IN+

IN+

IN+

IN+
NO

NO

NO

NO
NC

NC
IN-

IN-

IN-

IN-

Controller.
These are the 2x3 power plug tamper inputs
connectors directly adjacent tamper switch
from each other on the
Figure 5: Controller Boards Installation
boards.

4 Connect one of the 5-position power plugs from the Power Supply to the Master Controller power
connector J7.
Seat the plug on the connector so the retaining latch engages.

5 Connect the other 5-position power plug from the Power Supply to the Door Controller power
connector J4.
Seat the plug on the connector so the retaining latch engages.

6 Using a 10-position terminal block from the hardware kit, connect the two wires from the Enclosure’s
tamper switch to the Tamper inputs (Door Controller TB5, pins 7 and 8).

7 Set the power switch to the ON position, verifying power LEDs illuminate.
There may be a delay of up to 5 seconds.

8 Turn the power switch OFF.

Document 988 SA3000 Installation Guide 8


January 28, 2008
SA3000 INSTALLATION

Connect to the Network

The Master Controller board provides both 10/100 Base-T TCP/IP (J1) and RS-485 (TB2) connections for
communications with BbTS (NP, Network Processor). Choose a connection based on the local network.
The host connections, J1 and TB2 are for supplementary use only.

Once connected to the network, the Controller must be configured for the network type.
Reference Controller Unit Configuration (page 28) for information on configuring the
Controller Unit.

10/100 Base-TX: Install Cat5 cable with an RJ-45 plug connector into the J1 connector on the Master Controller
board.
The RJ-45 plug connector must be terminated per EIA/TIA-568B patch cable specifications.
The J1 connector exits at the top of the board.
RS-485: Install wiring from the Master Controller TB2 terminal block to the local RS-485 network using Belden
8273 cable or equivalent. Terminate connections per Table 3:

SA3000 Controllers communicating in RS-485 mode to a Universal Edition Host require an IP


Converter. See the SA3000 UE Migration Quick Start guide for more Details.

Table 3: Master Controller TB2: Host Network RS-485 Connections


Connection Wire Color (Belden 8723) Signal Name
TB2-6 RED RX485-
TB2-7 BLACK RX485+
TB2-8 SHIELD GND
TB2-9 WHITE TX485-
TB2-10 GREEN TX485+

Terminal Block Descriptions (page 41) details Door Controller Terminal Block connections.

Connect Card Readers


Card Readers (page 10) includes wiring instructions for Door Controller TB1 and TB2 terminal blocks
to Card Readers.

Connect Door Accessories


Door Accessories (page 21) includes wiring instructions for Door Controller board TB3, TB4 and TB5
terminal blocks to Door Accessories.

Configure Controller Unit


Controller Unit Configuration (page 28) describes configuring the Controller Unit interface to the
attached Card Reader(s), once wiring has been completed.

Document 988 SA3000 Installation Guide 9


January 28, 2008
SA3000 INSTALLATION

CARD READERS

MAGSTRIPE READERS

Two magstripe reader models are available in the SA3000 System.


Both have rugged metal construction and tamper and weather
protection to withstand the abuse of high-traffic environments. Readers
mounted outdoors can be further protected from weather with an
optional visor.

The SE3/CS is a single-function Card Reader with a vertical


continuous swipe-through card slot. The narrow design allows
mounting to a door frame or mullion.

The SE3/CSPP Reader can be configured to require users to enter a


PIN with a card swipe for enhanced security. It mounts to a single gang
box or a wall.

Figure 6:SE3/CS and SE3/CSPP


PROXIMITY READERS

Two models of Proximity Readers are also available for the SA3000
System.

Proximity Readers are only supported on SA3000 series


controllers in BbTS Universal Edition.

EXISTING SA2000 READER SUPPORT

The SA3000 Controller Unit supports the SACS and SASPP legacy Card
Readers. See Wiring to Existing SACS and SASPP (page 19).
Figure 7: SE3PROXLR and
CARD READER COMBINATIONS SE3/PROXMR

The following Card Reader combinations are supported by the SA3000 Controller Unit:
Table 4: SA3000 Supported Card Reader Combinations
Inbound Outbound 1 Outbound 2
Inbound
Optional Optional Optional
SE3/CS or SE3/CSPP SE3/PROX (LR or MR) SE3/CS or SE3/CSPP SE3/PROX (LR or MR)
SE3/PROX (LR or MR) SE3/PROX (LR or MR)
SE3/PROX (LR or MR) SACS♦
SACS♦ SE3/PROX (LR or MR)
SACS♦ SACS♦
SASPP♦ SE3/PROX (LR or MR) SACS♦
SASPP♦ SE3/PROX (LR or MR) SE3/PROX (LR or MR)

♦ - denotes existing SA2000 Card Readers. These readers have not been evaluated by UL.

Document 988 SA3000 Installation Guide 10


January 28, 2008
SA3000 INSTALLATION

CARD READER OPERATION

Magstripe Readers require the user to swipe a card. Proximity Readers require the user bring a card into
range of the Reader. Both Readers read the encoded information on the card and transmit the information
to the Controller Unit.

BbTS Universal Edition Systems only support the 78-bit Proximity card format.

The Controller Unit compares the card information to its internal database to determine if the card has
access privilege at the door. If valid, the Card Reader turns on the VALID lamp. If invalid, the Card Reader
turns on the DENIED lamp. If an error is encountered while reading the card, the Card Reader turns on the
ERROR lamp. In this case, the user must re-swipe the card.

Both the SE3/CS and SE3/CSPP Readers can be configured to generate tones. If access is allowed, the
Reader generates a valid tone. If access is denied or in the case of an error, it generates a warble tone.

CARD READER MOUNTING CONSIDERATIONS

When selecting a location to mount the Card Reader, consider the following:

• Will a cardholder be injured if the door is opened while swiping a card?


• Where will the Card Reader get the most protection from the weather? Is a Protective Visor neces-
sary?
• Where is the most convenient place for the cardholder to swipe a card?
• How will electrical cables be routed from the Controller Unit to the Card Reader?
• Does installation height meet federal / local height requirements (such as ADA)?

Document 988 SA3000 Installation Guide 11


January 28, 2008
SE3/CS INSTALLATION

SE3/CS I NSTALLATION

The SE3/CS Card Reader can be installed on a door frame, mullion or wall, wherever space
constraints require a narrow Card Reader.

A decorative shroud is available for use with a surface mounted single gang box. Consider
installing a protective visor if the Card Reader will be exposed to inclement weather.

Two mounting plate models are available for this model and sold separately. The narrow
mounting plate has the same profile as the Reader (see page 12). A wide mounting plate
mounts to a single gang box, flush or surface mounted on a wall (see page 13). Either
mounting plate is used to mount a protective visor, although a wide mounting plate provides
more stability. If using a decorative shroud and a visor, two mounting plates are required (see
SE3/CS Mount w/ Shroud & Visor (page 14)).

The table below lists the model numbers of SE3/CS accessories.

Table 5: SE3/CS Card Reader Accessories


Model # Description
SE3/MPN Narrow mounting plate (for door mullion)
SE3/MPW Wide mounting plate (for single gang box)
SE3/DS Decorative shroud (conceals low profile surface mounted single gang box, requires SE3/MPW) *
SE3/VISOR Visor (for protection from inclement weather, requires SE3/MPN or SE3/MPW) a

a. If decorative shroud and visor are both used, a second wide mounting plate is required.

SE3/CS wiring requires Belden 8723 cable or equivalent from the SE3/CS to the Door
Controller. Cable length must not exceed 4000 feet.

Mount and Wire the SE3/CS using Narrow Mounting Plate


The narrow mounting plate is secured using three holes (two slotted and one regular) with #6 hardware
(Figure 8). Select hardware based on the mounting material.
1 Use the mounting plate as a template to mark mounting
holes and cable routing hole.
Put the cable hole near the center of the mounting plate
window.
2 Drill the holes for the mounting hardware (#6 screws) and
the cable. See Figure 8.
3 Secure the mounting plate with the chosen hardware.
If using a protective visor, install it behind the mounting
plate.
In outdoor installations, use a bead of silicone sealer
between the mounting plate and the installation surface to
protect the Reader from moisture.
4 Pull cable through hole and wire to 5-pin terminal block, per
Figure 11 on page 14. Figure 8: SE3/CS Installatio
(Narrow Mounting
A 5-pin terminal block is supplied in the hardware kit.

Document 988 SA3000 Installation Guide 12


January 28, 2008
SE3/CS INSTALLATION

5 Plug the terminal block onto the SE3/CS.


6 Place SE3/CS on mounting plate and slide up to engage screws into the tapered slots.
7 Tighten the screw at the bottom of the mounting plate to secure the Reader.

If a second SE3/CS or SE3/CSPP reader is installed, wire the Readers in parallel. Connect a
jumper wire across pins 2 and 5 of the terminal block to configure the second reader. The
jumper configures the Reader address to allow communication on a half-duplex RS-485 bus
so both will not transmit concurrently.

Mount and Wire the SE3/CS using Wide Mounting Plate


The wide mounting plate is secured to a single gang box using the center and lower holes (Figure 9).
The optional decorative shroud can only be used with the wide mounting plate.

1 Secure the mounting plate Remove Conduit Knockout


to the gang box using #6 Plate if Necessary

screws.
Conduit
If using a decorative shroud Decorative Shroud
(optional)

or protective visor, install it


behind the mounting plate.
If using both, see Figure
10.
Wide Mounting Plate
In outdoor installations, use
a bead of silicone sealer
between the mounting plate SE3/CS

and the installation surface Bower’s Box


to protect the Reader from 102-W Low Profile

moisture.
2 Pull cable through mounting
plate and connect to 5-pin VALID

terminal block, per Figure


DENIED

REREAD

11 on page 14. Decorative Shroud Measurements:


7.375" tall x 3" wide x 1.9" deep

A 5-pin terminal block is


supplied in the hardware kit.
3 Plug terminal block onto the
SE3/CS.
Figure 9: SE3/CS Mounting
4 Place SE3/CS on mounting (Wide Mounting Plate)
plate and slide up to
engage screws into the
tapered slots.
5 Tighten the screw at the bottom of the mounting plate to secure the Reader.

If a second SE3/CS or SE3/CSPP Reader is installed, wire the Readers in parallel. Connect a
jumper wire across pins 2 and 5 of the terminal block to configure as a second reader. The
jumper configures the reader address to allow communication on a half-duplex RS-485 bus so
readers do not transmit concurrently.

Document 988 SA3000 Installation Guide 13


January 28, 2008
SE3/CS INSTALLATION

Installing a shroud & visor requires


two wide mounting plates
(the Visor can use a narrow mounting
plate, but the wide provides more stability)

Figure 10: SE3/CS Mount w/ Shroud & Visor

11 2 35 4 510
10

RED
10 9 8 7 6 5 4 3 2 1

BLK & Shield GRN


10

1 2 3 4 5

WHT GRN WHT


GRN BLK
WHT RED
5
5

BLK

RED
1

Belden 8723 Cable


1

(5 conductor)
Second SE3/CS or SE3/CSPP
Wire in parallel with first reader and
Door Controller install jumper wire between
(TB1 only) pins 2 and 5

Mounting Plate
SE3/CS

Figure 11: SE3/CS Wiring

Document 988 SA3000 Installation Guide 14


January 28, 2008
SE3/CSPP INSTALLATION

SE3/CSPP INSTALLATION

The SE3/CSPP Card Reader provides a keypad in addition to the magstripe read head.

A PIN annunciator notifies the cardholder when a PIN must be entered after a card
swipe. The requirement to enter a PIN is configured in BbTS software. A mounting plate
is included with each SE3/CSPP, a protective visor is optional.

Table 6: SE3/CSPP Card Reader Accessory


Model # Description
SE3/VISOR Visor (for protection from inclement weather)

Mount and Wire the SE3/CSPP


The SE3/CSPP mounting plate holes in the plate align with the holes of a single gang box. The gang
box hardware can be used to attach the mounting plate.

Cable length between Card Reader and Controller Unit must not exceed 4000 feet.

1 Secure the mounting plate to


gang box with #6 screws
(Figure 12).
If using a visor, install it
10

12345

behind the mounting plate.


In outdoor installations, use
5

a bead of silicone sealer


1

between the mounting plate Pin Valid

and the installation surface 8723 Belden Cable


Error Denied

to protect the Reader from


moisture. 1 2
2 Pull cable through hole and
To Controller
3 4
wire to 5-pin terminal block, 5 6
per Figure 13 on page 16. 7 8
5-pin terminal block is 9
supplied in the hardware kit.
0
CLEAR ENTER
Figure 12: SE3/CSPP Mounting Diagram
3 Plug terminal block onto the
SE3/CSPP.
4 Place SE3/CSPP on mounting plate and slide up to engage screws into the tapered slots.
5 Tighten the two screws at the bottom of the mounting plate to secure the Reader.

If a second SE3/CS or SE3/CSPP reader is installed, wire the Readers in parallel. Install a
jumper wire across pins 2 and 5 of the terminal block to configure the second reader. The
jumper configures the Reader address to allow communication on a half-duplex RS-485 bus
so readers do not transmit concurrently.

Document 988 SA3000 Installation Guide 15


January 28, 2008
SE3/CSPP INSTALLATION

1 2 53 4 510
Note: Install Jumper wire between
GRN
pins 2 and 5 on secondaryWHT
SE3/CS
BLK
10

RED
10 9 8 7 6 5 4 3 2 1

10

12345
BLK & Shield RED
GRN

1
WHT
GRN
WHT
5
5

BLK
RED
1

8723
1

Belden Cable

TB1 ONLY
Door Controller

Mounting Plate SE3/CSPP (Back View)

Figure 13: SE3/CSPP Wiring

Document 988 SA3000 Installation Guide 16


January 28, 2008
PROXIMITY READER INSTALLATION

PROXIMITY READER I NSTALLATION

The SA3000 Controller Unit can support up to two Proximity Readers.


Proximity Reader ranges are dependent on the installation materials, as
described in the manufacturer’s installation manual. Model numbers for the
supported Proximity Readers are listed in the table below:

Proximity Readers are only supported on SA3000 series


controllers in BbTS Universal Edition.

Table 7: Proximity Reader Model Numbers


Model # Description
SE3/PROXMR Proximity Reader - Medium Range (HID ProxPro Model 5355)
SE3/PROXLR Proximity Reader - Long Range (HID MaxiProx Model 5375)

Reference the manufacturer’s manual for Proximity Reader installation and mounting
instructions.

MOUNTING CONSIDERATIONS
• Mount at least six inches away from any metallic surface 12" x 12" or larger
Large adjacent metals, especially iron, steel, or copper, diminish the card read range.
• Use a plastic gang box and conduit
• Do not use metal hardware within two inches of the back of the reader.
• Do not mount the Proximity Reader in areas of high vibration.

PROXIMITY READER SETTINGS


All DIP-switches in the readers should be set to the factory default positions. (Reference the
manufacturer’s manual for default settings.)

The TAMPER SELECT from the Proximity Reader must be configured as a Normally-Closed
contact.

Wire the Proximity Reader(s)


1 Mount Proximity Reader using manufacturer’s installation instructions.
In outdoor installations, use a bead of silicone sealer between the mounting plate and the installation
surface to protect the Reader from moisture.
2 Route wire from the Proximity Reader to the Controller Unit using Belden 9540 cable or equivalent.
The Weigand interface module required on the SA2000 System is no longer required.
3 Connect wiring between the Proximity Reader and the Door Controller TB1 and/or TB2 terminal block
using Table 8 and Table 9 as a guide for wire terminations.

TB1 and TB2 terminal blocks each support a single Proximity Reader. If two Proximity
Readers are installed, both TB1 and TB2 must be used.

Document 988 SA3000 Installation Guide 17


January 28, 2008
PROXIMITY READER INSTALLATION

The DC voltage supply from the Door Controller to the Reader is +12 VDC. If your
Proximity Reader requires +24 VDC, use an external power supply.

4 See Controller Unit Configuration (page 28) for configuring the Door Controller to operate with the
Proximity Reader(s).

TERMINATION TABLES

Signal names may vary on the Proximity Readers as changes are made to the models.

Table 8: Door Controller TB1 Proximity Reader Signals

Prox Reader 9540 Cable Door Controller


Signal Name Wire Color Position Signal Name
+DC RED TB1-1 VCS+
GROUND BLK TB1-2 GND
TAMPER COMMON BLU TB1-2 GND
DATA-1 WHT TB1-5 D1/CLK
DATA-0 GRN TB1-6 D0/DATA
GRN LED ORG TB1-7 GLED
RED LED BRN TB1-8 RLED
BEEPER YLW TB1-9 BEEP
TAMPER SELECT PUR TB1-10 TAMPER

Table 9: Door Controller TB2 Proximity Reader Signals

Prox Reader 9540 Cable Door Controller


Signal Name Wire Color Position Signal Name
+DC RED TB2-1 VCS+
GROUND BLK TB2-2 GND
TAMPER COMMON BLU TB2-2 GND
DATA-1 WHT TB2-5 D1/CLK
DATA-0 GRN TB2-6 D0/DATA
GRN LED ORG TB2-7 GLED
RED LED BRN TB2-8 RLED
BEEPER YLW TB2-9 BEEP
TAMPER SELECT PUR TB2-10 TAMPER

Document 988 SA3000 Installation Guide 18


January 28, 2008
WIRING TO EXISTING SACS AND SASPP

WIRING TO E XISTING SACS AND SASPP

SACS and SASPP Card Readers (not evaluated by UL) can be used when upgrading a SA2000 System to
use the SA3000 Controller boards. Some minor wiring changes are required, but these changes need only
be made at the Controller Unit. The existing Card Readers do not need to be removed. If Proximity
Readers were used with the SA2000 System, the Weigand interface module must be removed. The
SA3000 Controller Unit now interfaces directly with Proximity readers.

The Door Controller only supports one SASPP Reader.


SASPP Readers cannot be used in combination with SE3/CS or SE3/CSPP Readers.

Wiring the SACS


The new interface eliminates three wires originally used in the SA2000 System. The remaining wires
terminate at different positions on the Door Controller terminal block(s).
1 Rewire the original terminal block in the Controller Unit per the pertinent wiring diagram (Figure 14).
Wiring colors are shown for both Belden 9540 and 9541 cable. If different wiring was used, remove the
SACS Reader and compare the wiring on the terminal block.
2 Verify conductor connections are equivalent to those shown.
The signals for the SACS Reader are identical on the Door Controller’s TB1 and TB2 terminal blocks.

YLW

10
1 2 3 4 55 6 7 8 9 10
BLK
BLU
ORG
WHT
RED
GRN
GRY
BRN
PUR
10
5 6 7 8 9 10

BRN
PUR
GRY
RED
ORG Belden 9540 Cable (10 Conductor)
11 2 3 4 5

Note: Disregard silk screen on PC Board.


BLK It refers to wire colors for
YLW
9541 belden cable (15 conductor).
10

Belden 9540 Cable


5
1
10

WHT/BLK
1 2 3 4 55 6 7 8 9 10
11 2 3 4 55 6 7 8 9 10

10

ORG/BLK Belden 9541 Cable BLK


RED/BLK (15 conductor) BLU
GRN/BLK or ORG
RED WHT
ORG
Belden 9540 Cable
RED
(10 conductor) GRN
GRN/BLK
BLK
ORG/BLK
WHT/BLK
RED/BLK
1

Belden 9541 Cable


SACS
Mounting Plate Belden 9541 Cable (15 Conductor)

Door Controller TB1/TB2


Figure 14: SACS Wiring

Document 988 SA3000 Installation Guide 19


January 28, 2008
WIRING TO EXISTING SACS AND SASPP

Wire the SASPP


The new interface uses all four wires which were originally used on the SA2000 System. However, all
four wires terminate at different positions on the Door Controller terminal block.

1 Remove all SASPP wires from the SA2000 Controller Unit TB1 terminal block.

2 Terminate the wires in the Door Controller’s TB2, per the pertinent wiring diagram (Figure 14).
Wiring colors are shown for Belden 8723 cable. If different wiring was used, remove the SASPP
Reader and check the wiring on the terminal block.

3 Verify the conductors are connected in an equivalent method as those shown in Figure 15.
10

1 2 3 4 5 6 7 8 9 10

RED
BLK
WHT
GRN
5
1

Door Controller
TB2
10
1 2 3 4 5 6 7 8 9 10

RED

BLK

GRN

WHT
5

Belden 8723 Cable

Install a jumper from pin 2 to pin 6


1

Mounting Plate SASPP (Back View)

Figure 15: SASPP Wiring

Document 988 SA3000 Installation Guide 20


January 28, 2008
DOOR MONITOR CONTACTS

DOOR ACCESSORIES

This section covers wiring instructions for non-Blackboard Door Accessories.

The SA3000 System requires Door Accessories to provide access control and door monitoring. Door
Accessories selections are based on the requirements for each application. Door Accessories supported
by the SA3000 are:

• Door Monitor Contacts


• Door Locking Mechanism
• Request-to-Exit device
• Local Alarm

All Door Accessories must be UL listed to maintain UL compliance of the SA3000


System.

DOOR MONITOR CONTACTS

Door Monitor Contacts are used for door status or forced or held alarm reporting. The Door Monitor
Contacts signal the Controller Unit that the door is open or closed. There are several types of Door Monitor
Contacts commercially available. Purchase the Door Monitor Contacts that best suit the application and
install using the manufacturer’s instructions.

Wire Door Monitor Contacts

1 Route wire from Door Monitor Contacts to the Controller Unit.

2 Connect wires to Door Monitor Contacts.

3 At the Door Controller, test the contacts with an Ohm meter and verify the circuit is less than 100 Ohms
when the door is closed and an open circuit when the door is open.
The door contact wires cannot be connected to the Controller Unit while performing this test.

4 Connect the wires from the Door Monitor Contact to Door Controller TB4, positions 7 and 8.
Reference Figure 22: Controller Boards (page 41) for terminal block locations.

Document 988 SA3000 Installation Guide 21


January 28, 2008
REQUEST-TO-EXIT DEVICES

REQUEST - TO -EXIT DEVICES

Request-to-Exit devices signal the Controller Unit that a valid door opening will occur, preventing a forced
alarm. In cases where a separate Card Reader is used to exit and enter, an exit device is not required
because the Card Reader provides the exit detection functionality.

Common Request-to-Exit devices include:


• motion detectors
• crash bar with request-to-exit switch
• push-to-exit button

Purchase the Request-to-Exit device that best suits the application and install using the manufacturer’s
instructions.

The Request-to-Exit device must provide a Normally Open circuit which closes when
activated.

Wire Request-to-Exit Device

The Door Controller can supply 24VDC (Door Controller TB3, pins 1 and 2) to the
Request-to-Exit device, if required.

1 Route wire from Request-to-Exit device to the Controller Unit.

2 Connect wires to the Request-to-Exit device according to the manufacturer’s instructions.

3 At the Door Controller, test the device with an Ohm meter. Verify the circuit is less than 100 Ohms
when the Request-to-Exit device is active and an open circuit when not active.
The device cannot be connected to the Door Control board while performing this test.

4 Connect the wires from the Request-to-Exit device to Door Controller TB4, positions 3 and 4.
Reference Figure 22: Controller Boards (page 41) for terminal block locations.

Document 988 SA3000 Installation Guide 22


January 28, 2008
DOOR LOCKING MECHANISMS

DOOR L OCKING MECHANISMS

Door Locking Mechanisms are electronic hardware devices activated by the Controller Unit to lock/unlock
a door. Common Door Locking Mechanisms include:
• electric strikes
• magnetic locks
• crash bars and locksets with electronic latch retraction

Terms commonly associated with door locking mechanisms are:


• Fail-Safe means that the door locking mechanism is unlocked when there is no electricity available.
• Fail-Secure means that the door locking mechanism is locked when there is no electricity available.
• Normally-Open and Normally-Closed contacts are provided by the Door Controller for the Door
Locking Mechanism.

Verify compliance with all applicable codes before purchasing door hardware.

For lock circuitry that is installed and configured as "fail secure", UL-listed panic
hardware shall be used to allow emergency exit from the protected area.

Purchase the Door Locking Mechanism that best suits the application and install using the manufacturer’s
instructions.

POWERING THE DOOR LOCKING MECHANISM

The Controller Unit can supply 24VDC (Door Controller TB3, pins 1 and 2) to the Door Locking
Mechanism, if required. This output is fused by FS1. If the fuse must be replaced, install a 2AG style, 1.5
Amp Slo-blow. See “Specifications” on page 40. for maximum current rating of the 24 VDC output.

The combined current for ALL devices connected to the 24 VDC output must NOT
exceed the maximum 1 Amp current rating.

Devices that require more than 1.5 Amp current require an external power supply. An example of such a
device is a crash bar with electronic latch retraction. Wiring of this device can be seen in Figure 16.

Document 988 SA3000 Installation Guide 23


January 28, 2008
DOOR LOCKING MECHANISMS

Wire the Door Locking Mechanism

1 Route wire from Door Locking Mechanism to the Controller Unit.

2 Connect wires to the Door Locking Mechanism according to manufacturer’s installation instructions.
When wiring to an inductive device, such as an electric strike or magnetic lock, install a protection
diode across the wires as close as possible to the lock mechanism, as shown in Figure 16. The diode
protects the relay in the Door Controller and reduces EMI when the circuit is opened. Two diodes
(1N4003) are included in the hardware kit.

3 Connect the wires from the Door Locking Mechanism to the Door Controller.
Reference Figure 16 for wiring options.

Document 988 SA3000 Installation Guide 24


January 28, 2008
DOOR LOCKING MECHANISMS

Electric Strike Magnetic Lock

DOOR CONTROLLER DOOR CONTROLLER


CIRCUIT BOARD CIRCUIT BOARD

1 VCS+ 5 1 VCS+ 5
2 GND 4 2 GND 4
3 SASPP Tx 3 3 SASPP Tx 3
4 SASPP Rx 2 4 SASPP Rx 2
5 D1/CLK 1 5 D1/CLK 1
6 D0/DATA
GND 5 6 D0/DATA
GND 5
7 GLED VDC 4 7 GLED VDC 4
8 RLED 3 8 RLED 3
9
10
BEEP

TAMP
TB3 TB4
VAC
VAC
2
1
9
10
BEEP

TAMP
- VAC
VAC 1
2

TB2 LOCK RELAY L MON ALARM REQEX BYPASS DOOR SPARG TB5 TB2 LOCK RELAY L MON ALARM REQEX BYPASS DOOR SPARG TB5
2 VDC+

2 VDC+
1 GND

1 GND
4 NO

9 NO

2 NO

6 NO

4 NO

9 NO

2 NO

6 NO
10 NC

10 NC
5 NC

5 NC
TB3 TB4

-
8 +

8 +
4 +

10 +

4 +

10 +
-

-
7 +

7 +
-

-
3 C

8 C

1 C

5 C

3 C

8 C

1 C

5 C
6

9
ANODE

24VDC CATHODE
- +
ELECTRIC STRIKE 24VDC
MAGNETIC LOCK
IN4003
DIODE
-
=
+ READER CIRCUIT BO ARD
Crash Bar
(FRONT VIEW )
DOOR CONTROLLER
1 VCS+ 5
2 GND 4
3 SASPP Tx 3
4 SASPP Rx 2
5 D1/CLK 1
6 D0/DATA G ND 5
7 GLED V DC 4
8 RLED 3
9 BEEP VAC 2
10 TAMP VAC 1

The Controller Unit can provide a TB2 LOCK RELAY L M ON ALARM EXIT BYPASS DOOR TB5
2 +24V
1 GND

contact closure to activate an


4 NO

9 NO

2 NO

6 NO
10 NC
5 NC

TB3 TB4
8 +
4 +

10 +
-

-
-
7 +
3 C

8 C

1 C

5 C

external power source if the locking


6

9
mechanism does not require power
from the Controller (or the
Controller cannot supply enough
power).

110VAC

POW ER BO OSTER

Figure 16:Door Locking Mechanisms


Wiring
CRASH BAR W ITH ELECTRIC LATCH RETRACTION

Document 988 SA3000 Installation Guide 25


January 28, 2008
LOCAL ALARM

LOCAL ALARM

A Local Alarm can be connected to the Controller Unit to warn of a forced entry or a held condition. These
functions can be configured in BbTS software.

Normally-Open contacts are provided by the Door Controller for the Local Alarm. The Alarm output
terminals act as a simple switch to turn the siren on at the appropriate times.

Purchase the Local Alarm that best suits the application and install using the manufacturer’s instructions.

Powering the Local Alarm

The Controller Unit can supply 24VDC (Door Controller TB3, pins 1 and 2) to the Local Alarm, if required.
This output is fused by FS1. If the fuse must be replaced, install a 2AG style, 1.5 Amp Slo-blow. See
“Specifications” on page 40. for maximum current rating of the 24 VDC output.

The combined current for ALL devices connected to the 24 VDC output must NOT
exceed the maximum 1.5 Amp current rating.

TB2
Devices that require more than 1.5 Amp D0/DATA GND

current require an external power

INPUT POWER
GLED VDC
RLED
supply. BEEP VAC
TB3 TB4
TAMP VAC
LOCK LATMON AUX ALARM REQEX BYPASS DOOR SPARE
VDC+
COM

COM

COM

COM
GND

IN+

IN+

IN+

IN+
NO

NO

NO

NO
NC

NC
IN-

IN-

IN-

IN-
Wire Local Alarm

10
10
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9

1 Route wire from Local Alarm to the


Alarm Output

Controller Unit.
2 Connect wires to the Local Alarm
according to manufacturer’s
installation instructions.
3 Connect the wires from the Local
Alarm to the Door Controller.
- +
Reference Figure 17 for wiring
options.
Figure 17: Local Alarm Wiring
BYPASS OUTPUT (powered by Controller Unit)

Bypass Output (BYPASS) is used to bypass another security system during valid door openings. Connect
Door Controller TB4, positions 5 and 6 across the Door Monitor Contacts used by the other security
system.

AC Fail Input

AC Fail Input (ACFAIL) can be connected to an external monitoring device that detects when AC power is
lost. The external monitoring device must be located within the same room (within a maximum of 20 feet)

Document 988 SA3000 Installation Guide 26


January 28, 2008
LOCAL ALARM

as the Controller Unit to meet the requirements for a UL-294 rated configuration and must provide a
normally-closed output. Connect the monitoring device across the Door Controller's TB5 terminal block,
pins 3 and 4.

If not used, install a jumper wire across pins 3 and 4.

Battery Low Input

Battery Low Input (BATLOW) can be connected to an external monitoring device that detects when a
battery-backup system's battery is low. The external monitoring device must be located within the same
room (within a maximum of 20 feet) as the Controller Unit to meet the requirements for a UL-294 rated
configuration and it must provide a normally-closed output. Connect the monitoring device across the Door
Controller's TB5 terminal block, pins 5 and 6.

If not being used, install a jumper wire across pins 5 and 6.

Tamper Input

The Tamper Input (TAMPER) reports to the Host if the Enclosure’s door is open or closed. Connect the
wires of the plunger style switch mounted to the Enclosure to the Door Controller's TB5 terminal block, pins
7 and 8.

Tamper Relay Output

The Tamper Relay Output (TAMPER) can be connected to an alarm. The alarm must be located within the
same room as the Controller Unit to meet the requirements for a UL-294 rated configuration.

The normally-open output is activated when the TAMPER input is open, indicating the Enclosure door is
open, a serial card reader is not responding, or a proximity reader is indicating a tamper condition. The
Tamper Output is on the Door Controller's TB5 terminal block, pins 9 and 10.

Auxiliary Relay

The Auxiliary (AUX) Relay provides a mechanism to control a second lock (such as double doors with
separate locks) or to control an automatic door opener. It can be configured to operate in 'normal' or 'door
opener' mode. In 'normal' mode, the relay follows the state of the LOCK relay. In 'door opener' mode the
relay can be delayed, so the AUX relay is turned on after the LOCK relay is activated. This momentary
closure for activating a door opener can be configured (0.0 to 25.5 seconds). The length of time the AUX
Relay remains on, regardless of when the LOCK relay is turned off, can also be configured (0.0 to 25.5
seconds). The AUX Relay can be configured to activate for all card readers or for proximity readers only.
The AUX Relay outputs are located on Door Controller's TB3 terminal block, pins 8 (COM), 9 (NO) and 10
(NC).

Spare Input

The Spare Input (SPARE) will activate the Auxiliary Relay with a Door-Open-Request switch that provides
a normally-open contact. When the Spare Input is shorted, the LOCK and the AUX Relay will be activated.
This is useful with an automatic door opener. If the Request-to-Exit is activated without the Spare Input
being activated, the Auxiliary Relay will not cycle. The Spare Input is located on Door Controller's TB4
terminal block, pins 9 and 10.

Document 988 SA3000 Installation Guide 27


January 28, 2008
LOCAL ALARM

CONTROLLER UNIT CONFIGURATION

The Controller Unit must be configured to interface to BbTS and attached Card Readers. Configure the
Controller Boards using either the switches on the Master Controller board or the configuration port.

DEFAULT SETTINGS

The Controller Unit default settings are:


• DHCP enabled
• NP (host) IP address assigned by DHCP server
• One SE3/CS or SE3/CSPP Card Reader, tones enabled

CONFIGURATION METHODS

The Controller Unit configuration can be changed using one of three modes:
• Controller Board switches
• RS-232 using a RS-232 terminal (such as a computer and Hyperterminal software & configuration
cable)
• Telnet via IP if using Ethernet connections

Configure Controller Boards (using switches)


DEC and INC step through the options for each menu item.
ENTER captures the displayed option and sequences to the next menu item.
CLEAR aborts the configuration, and cancels all changes
To save all configuration changes, press ENTER at the ‘Hit ENTER to save’ message.

1 Press any switch to start configuration.

Document 988 SA3000 Installation Guide 28


January 28, 2008
LOCAL ALARM

2 At ‘Choose Menu’, use DEC or INC to scroll start configuration Master Controller
through the options, and press ENTER to scroll save selection (bottom left corner)
choose: settings
& advance menu
Master Config to configure the Master
Controller. A flowchart of configuration options
is in Figure 19.
Door Control Config to configure the Door
Controller. A flowchart of configuration options
is in Figure 20.
Show Status displays:
• abnormal conditions
• software versions
• reader status
Figure 18: Controller Configuration Switches
• number of cardholders in database

Master Config

MAC Address
IP Address
DHCP Status

RS-485
Com Mode Reader Address Baud Rate

Ethernet

Enabled
Enabled
DHCP NP DHCP

Disabled Disabled

IP Address
Telnet
LCD Contrast
Enable

Subnet Mask

NP IP Address Save
Deflt Router/Gateway

Figure 19: Master Controller Configuration Flowchart

Document 988 SA3000 Installation Guide 29


January 28, 2008
LOCAL ALARM

Door Control
Config

Serial Reader(s)
none Door Opener
1 SE3/CS or SE3/CSPP Aux Relay ON Delay
Aux Relay Mode
2 SE3/CS or SE3/CSPP
1 SASPP

Normal
Aux Reader on TB1
none Aux Relay ON Time
PROX
SACS

Aux Relay Triggers


PROX only
Aux Reader on TB2 All Readers
none
PROX
SACS

(Config Reader) Tones Save

Figure 20: Door Controller Configuration Flowchart

Configure Controller Boards Blackboard SA3032 Configuration


(using RS-232 config port)
Enter Password > ******* IPrdr4U
SA3032 V1.7
1 Connect a cable from a
computer’s serial port to Command Reference -
Master Controller J2 port. config - Configure master controller parameters
showconfig - Display master controller parameters
Cable connections are door - Configure door controller parameters
shown in Table . showdoor - Display door controller parameters
status - Display reader status
2 Open a terminal program ping <ip_addr> - Ping another IP device
(such as Hyperterminal) and netstats - Display network statistics
establish connection netclear - Clear network statistics counters
settings: password - Change config utility password
ipreboot - Reboot reader
• 9600 baud exit - Log out of session Figure 21:Controller
Unit
• 1 stop Type command, followed by 'Enter' key >
Configuration Menu

• no parity
• no flow control
3 Login using the default password: IPrdr4U.
The password is case sensitive. Consider changing the password.

Document 988 SA3000 Installation Guide 30


January 28, 2008
LOCAL ALARM

4 At the prompt, type one of the following commands and press ENTER to start configuration:
config to configure the Master Controller. A flowchart of the configuration options is in Figure 19.
door to configure the Door Controller. A flowchart of the configuration options is in Figure 20.
status displays:
• abnormal conditions
• software versions
• reader status
• number of cardholders in database

5 Disconnect cable from J2.

Other commands are available on the menu (see Figure 21).

Table 10: RS-232 Config Port Connection

Master Controller J2 PC Serial Port


Signal
(RJ-12) DB9 Connector

Pin 1 Pin 5 Ground

Pin 3 Pin 3 Receive (RX)

Pin 4 Pin 2 Transmit (TX)

Configure Controller Boards (using Telnet)

1 Open a Telnet session to the Controller Unit’s IP address.

2 Login using the default password: IPrdr4U.


The password is case sensitive. Consider changing the password.

3 At the prompt, type one of the following commands and press ENTER to start configuration:
config to configure the Master Controller. A flowchart of the configuration options is in Figure 19.
door to configure the Door Controller. A flowchart of the configuration options is in Figure 20.
status displays:
• abnormal conditions
• software versions
• reader status
• number of cardholders in database

Document 988 SA3000 Installation Guide 31


January 28, 2008
LOCAL ALARM

Other available commands are displayed on the menu (see Figure 21 on page 30).

Restore Default Settings

Forget your password? Reset the Controller Unit to the default factory settings and default
password.

1 Connect a computer to the Master Controller using steps 1 and 2 above.

2 Turn the Power Supply switch to ON.

3 Type xxx within 3 seconds after “Config Task Started” is displayed in the terminal program.
“Restoring to Factory Defaults” will display during reset.

Document 988 SA3000 Installation Guide 32


January 28, 2008
LOCAL ALARM

A N N U A L M A I N T E N A N C E & TE S T I N G

MAINTENANCE

Normally, the Controller Unit and Card Readers do not require maintenance. Magstripe reader heads may
be periodically cleaned using commercially available clean cards. Pin pads can be wiped with a damp
towel.

CONTROLLER UNIT TESTING

Normally, the Controller Unit does not require maintenance. Test the Controller Unit annually to verify
proper operation.

DOOR CONTACT SWITCH

The resistance of the Door Monitor Contact switch should be measured and verified to be less than 100
Ohms when the door is closed. When the door is open, the resistance should be greater than 100KOhms.
The Door Controller TB4 terminal block must be removed when taking the measurement. The
measurement must be taken across pins 7 and 8 of TB4.

REQUEST TO EXIT SWITCH

The resistance of the Request-to-Exit switch should be measured and verified to be less than 100 Ohms
when the switch is active. When inactive, the resistance should be greater than 100KOhms. The Door
Controller TB4 terminal block must be removed when taking the measurement. The measurement must be
taken across pins 3 and 4 of TB4.

TAMPER SWITCH

Verify the Tamper input switch is operating correctly by depressing and releasing the switch that contacts
the enclosure door. When depressed, the TAMPER indicator on the Door Controller board should be off.
When the switch is released, the indicator should be on. If an alarm is connected to the TAMPER output,
the alarm should be on when the door is open.

Document 988 SA3000 Installation Guide 33


January 28, 2008
CARD READER TESTING

CARD R EADER TESTING

Normally, Card Readers do not require maintenance. Test Card Readers monthly to verify proper
operation.

SE3/CS AND SE3/CSPP CARD READERS

The SE3/CS and SE3/CSPP Readers can be tested by swiping both a valid and invalid card.
• Swiping a valid card will turn on the green VALID annunciator.
• Swiping an invalid card will turn on the red DENIED annunciator.
• Swiping either card in the reverse direction, from bottom to top, will cause a read error and the yellow
ERROR annunciator will turn on.
• If tones are enabled, swiping a valid card will generate a constant tone.
• If tones are enabled, swiping a invalid card will generate a warble sound.
• If tones are enabled, a read error caused by swiping either card in the reverse direction, from bottom to
top, will generate a warble sound.
• The Power light, located near the bottom of the reader, should always be illuminated.
• The SE3/CSPP keypad should generate a tone after pressing each of the keys.

Document 988 SA3000 Installation Guide 34


January 28, 2008
MASTER CONTROLLER

TR O U B L E S H O O T I N G

The Blackboard SA3000 Door Access System provides several mechanisms to aid the installer in
troubleshooting problems. Both the Master Controller and Door Controller boards display status
information through the LED indicators and the LCD display. The Card Readers also have problem
indicators that can be used to pinpoint a problem if the system is not working properly. Error messages and
error indication for each device are covered below.

MASTER C ONTROLLER

The Master Controller board LCD displays status information. The LCD contains 4 lines.
1 Current time and date
2 Model number and the 6-character abbreviated name of the Controller Unit.
3 Blank
4 Messages (If blank, no detectable error exist).

Dynamic status messages are displayed briefly when card information is being processed (e.g. a card
swipe), including “Transaction Valid” and “Transaction Invalid”. Watch messages to verify the system is
active and processing card data.

Static messages, which can indicate an error condition, are displayed on line 4.

The following table lists messages and dispositions.


Table 11: Master Controller LCD Line 4 Messages
Message Description Disposition
Check status An abnormal condition exists See information below
FLASH program error Application code is corrupt Return unit to Blackboard for repair
Stored txn crc error Transaction record has a crc error Return unit to Blackboard for repair
Waiting for config Waiting for configuration information from NP Verify network connection or configuration
information has been entered in BbTS
TXN storage full Transaction storage memory is full Bring unit online to upload transactions
DC not responding Door Controller is not responding to poll requests Reference Door Controller in this section

CHECK STATUS MESSAGE

“Check Status” indicates an abnormal condition exists. To view the abnormal condition, press the INC key
on the Master Controller until the “Show Status” message is displayed. Press ENTER to select “Show
Status”, and continue to press ENTER to advance through status screens:
1 Number of cards loaded
2 Software versions of the Controller boards and Readers
3 Abnormal conditions which exist are displayed on subsequent screens.

Document 988 SA3000 Installation Guide 35


January 28, 2008
DOOR CONTROLLER

The list of possible abnormal conditions and dispositions are listed in the following table:
Table 12: Abnormal Condition Messages
Status Message Description Disposition
DHCP Not Received IP Address has not been assigned by DHCP Server (IP Mode, Verify network connection and DHCP
DHCP enabled) server configuration
NP IP Missing NP IP Address was not included in DHCP assignment Verify network connection and DHCP
server configuration
Hunting for NP NP has not responded Verify:
NP IP address configured properly in
Controller Unit
Network connection
Host running
Reader configured in Host
DC 0 Offline No Response from the Door Controller after a poll Refer to Door Controller
(page 36).
DC 0 BATLOW Active The BATLOW input, Door Controller TB5, is open Check wiring
DC 0 ACFAIL Active The ACFAIL input, Door Controller TB5, is open
DC 0 Ser 1 Offline Card Reader 1 is not responding
DC 0 Ser 2 Offline Card Reader 2 is not responding
DC 0 TB1 Rdr Tamper Prox reader on TB1 tamper output is active
DC 0 TB2 Rdr Tamper Prox reader on TB2 tamper output is active
DC 0 Enclosur Tamper Tamper Enclosure indicates door is open

DOOR CONTROLLER

NORMAL OPERATION

Each Door Controller relay has an associated LED that indicates when the relay is energized. The LEDs
are located in a row along the top of the board with a text legend identifying the associated relay. These
LEDs can be used to verify wiring is installed correctly. For example, the DOOR LED should be ON when
the door is in the open position.

Document 988 SA3000 Installation Guide 36


January 28, 2008
DOOR CONTROLLER

Door Controller input status LEDs are described in the following table:
Table 13: Door Controller Input Status LEDs
LED STATE DESCRIPTION
DOOR ON Door is Open
OFF Door is Closed
REQEX ON Request to Exit switch is pressed
OFF Request to Exit switch is not pressed
LATMON ON Latch Monitor input Closed
OFF Latch Monitor input Open
SPARE ON Spare input Closed
OFF Spare input Open
ACFAIL ON ACFAIL input Open
OFF ACFAIL input Closed
BATLOW ON BATLOW input Open
OFF BATLOW input Closed
TAMPER ON TAMPER input Open
OFF TAMPER input Closed
CSRX ON Packet being received from Serial Card Reader
OFF No Packet being received from Serial Card Reader
MAIN ON Packet being received from Master Controller
OFF No Packet is being received from Master Controller

ERROR INDICATORS

The Door Controller status LEDs indicate an error condition exists when blinking. Status LEDs are the
combination of blinking ACFAIL, BATLOW and TAMPER LEDs while the DOOR, REQEX, LATMON and
SPARE LEDs are all ON. Table 14 lists the combinations of blinking LEDS and the error condition
indicated.

Table 14: Door Controller Error Indicators


LEDs
Error Condition
ACFAIL BATLOW TAMPER
BLINKING OFF OFF No messages are being received from the Master Controller board
OFF OFF BLINKING No response from Card Reader (SECS/SECSPP/SASPP)
BLINKING BLINKING OFF Card Reader (SECS/SECSPP) Flash programming failure
BLINKING OFF BLINKING Door Controller Flash programming failure
BLINKING BLINKING BLINKING Switch SW1 must be set to address 0.

Document 988 SA3000 Installation Guide 37


January 28, 2008
CARD READERS

CARD R EADERS

The Card Readers (SE3/CS and SE3/CSPP) LED annunciators on the face of the unit will indicate an error
condition. Detectable error conditions and their identification are listed below:

VALID, DENIED AND ERROR ANNUNCIATORS BLINKING

The SE3/CS and SE3/CSPP Card Readers will flash the VALID, DENIED and ERROR annunciators
simultaneously when software has been corrupted in Flash memory. The Card Reader must be returned to
Blackboard for repair.

DENIED ANNUNCIATOR BLINKING

The SE3/CS and SE3/CSPP Card Readers DENIED annunciator blinks (approximately 1 second rate)
when communication is lost with the Controller Unit. If the DENIED annunciator is flashing, check the
following:
• Verify the Controller Unit has been configured to interface to the SE3/CS and SE3/CSPP Readers, ref-
erence Controller Unit Configuration (page 28).
• If two Card Readers are installed, verify one reader has a jumper wire installed across pins 2 and 5 of
its terminal block.
• Verify the wiring between the Door Controller board and the Card Reader is terminated as shown in
Figure 11: SE3/CS Wiring (page 14) or Figure 13: SE3/CSPP Wiring (page 16).

NO ANNUNCIATION AFTER CARD SWIPE

One annunciator will always turn on after a card swipe. If no annunciator turns on after a card swipe, the
Reader may have corrupted software or the read head is not operating correctly.

To check software integrity, cycle power to the Reader. The annunciators should turn ON and OFF in
sequence, followed by four tones, indicating the Reader has successfully executed its power-up
initialization code.

If the power-up initialization is successful, the read head may be damaged.

POWER INDICATOR IS OFF

If the Power indicator located near the bottom of the Reader remains off when power is applied, verify the
voltage being supplied to the Reader is +12 Volts (Pin 1 = +12V, Pin 2 = GND).

Document 988 SA3000 Installation Guide 38


January 28, 2008
CARD READERS

SA3000 S E C U R I T Y A C C E S S S Y S T E M F E A T U R E S

• Card Readers can be ordered separately from the Controller for more flexibility.
• Supports 10/100Base-T communication with the NP for faster HS downloads in addition to RS-485
Multi-drop.
• The SA3000 supports 2 Card Readers (with or without PIN pad) and 2 Proximity Readers. The
Weigand interface module is no longer required to support Proximity readers.
• The SA3000 Controller consists of 2 boards (Master Controller and Door Controller). The boards
include status LEDs and a 4x20 LCD for displaying configuration and status information (no DIP
switches).
• Supports legacy SACS and SASPP Readers, allowing SA2000 system upgrades without replacing
Card Readers.
• Supports multi-plans in the downloaded cardholder database for off-line operation.
• Allows continued operation while downloading a new cardholder database. It will continue to operate if
it goes off-line during an HS download.
• The SA3000 enclosure has a locking/hinged lid with a tamper switch.
• The new SE3/CS Card Reader (without PIN pad) is approximately 1.5” shorter than the SACS.
• New Card Readers can generate valid/denied tones. Tones can be enabled or disabled through config-
uration options.
• New Card Readers use a 4-wire interface to the Controller.
• Enhanced tamper reporting include Controller Enclosure OPEN and Card Reader TAMPERED/
REMOVED (SE3/CS, SE3/CSPP, SASPP and HID prox).
• All components (Master Controller, Door Controller, and SE3/CS, and SE3/CSPP card slots) are in-
system re-programmable for future enhancements.
• The SA3000 does NOT support “learn mode”. An HS download is the only way to add/delete/change
cards in the downloaded table for off-line operation.

Document 988 SA3000 Installation Guide 39


January 28, 2008
CARD READERS

SPECIFICATIONS

DIMENSIONS & WEIGHT

• SE3/PS24ENCL:13" H x 9" W x 4" D, 10.0 lbs.


• SE3/PS24V:9.75" H x 5.25" W x 2.4" D, 1.5 lbs.
• SE3/CS: 7.25" H x 1.5" W x 1" D, 1.0 lbs.
• SE3/CSPP: 4.5" H x 2.7" W X 1.4" D, 1.0 lbs.

Table 15: Electrical Specifications


Power Input Voltage Range 120VAC
Input Frequency 60Hz
Input Current 1.4A, max
Auxiliary Power Output Output Voltage 24VDC
(TB3-1 and TB3-2) Output Current 1A, max (fused by FS1)
Reader Power Supply Reader Output Voltage +12VDC
(VCS+ on TB1-1 and TB2-1) Reader Output Current 1A, max, combined all readers
Relays Alarm Relay 1A @ 30VDC
Auxiliary Relay 1A @ 30VDC
Bypass Relay 1A @ 30VDC
Lock Relay 1A @ 30VDC
Controller

Tamper Relay 1A @ 30VDC


Inputs DOOR 24VDC, max
REQEX 24VDC, max
LATMON 24VDC, max
SPARE 24VDC, max
ACFAIL 24VDC, max
BATLOW 24VDC, max
TAMPER 24VDC, max
Operating Environment Temperature 0 to +45C (+32 to +114F)
Relative Humidity 0 to 95 percent, non-condensing
Altitude 0 -10,000 feet
Non-Operating Environment Temperature -20 to +70 C (-4 to +158F)
Relative Humidity 0 to 95 percent, non-condensing
Altitude 0 - 35,000 feet

Power Input Voltage Range 6 – 26VDC


SE3/CS and SE3/CSPP

Input Current 100mA, max.


Operating Environment: Temperature -40 to +65C (-40 to +150F)
Relative Humidity 0 to 95 percent, non-condensing
Altitude 0 -10,000 feet
Non-Operating Environment Temperature -40 to +85C (-40 to +185F)
Relative Humidity 0 to 95 percent, non-condensing
Altitude 0 - 35,000 feet

Document 988 SA3000 Installation Guide 40


January 28, 2008
CARD READERS

TE R M I N A L B L O C K D E S C R I P T I O N S
not used
Host
10/100 Base-T Config Port
J1 J2 10 9 8 7 6 5 4 3 2 1

GND

GND
232RX
232 TX

TX485+
TX485-

RX485+
RX485-
1 TB4
2 485+ GND 5
3 485- VDC 4
4 GND 3 Power Input
not used 5 485+ VAC 2
TB1
6 485- VAC 1
7 GND TB3
8 485+
Power LED
9 485-
10 GND
TX485+ 10
TX485- 9 Host RS-485
GND 8
RX485+ 7
RX485- 6
TX485+ 5
TX485- 4
not used
GND 3
RX485+ 2
RX485- 1
TB2

DEC INC ENTER CLEAR


Ribbon Cable Jumper
MASTER

Input Status LEDa


1 VCS+
5
MASTER

Reader Power 485-


2 GND 485+ 4
3 485+ not used
TB6 GND 3
SE3/CS and SE3/CSPP
4 485- RX232 2
AUX

5 D1/CLK TX232 1
TB1
6 D0/DATA 10
ACFAIL BATLOW TAMPER TAMPER

NO
SW1
PROX or SACS 7 GLED
COM 9 Tamper Relay Output
8 RLED IN+ 8
9 BEEP 7 Tamper Input
IN-
10 TAMP IN+ 6
1 TB5 Low Battery Input
Reader Power VCS+ FS1 IN- 5
2 GND IN+ 4
AC Failure Input
3 SASPP TX IN- 3
SASPP 4 SASPP RX 2
5 D1/CLK GND 1 Power LED
6 TB2
D0/DATA GND 5
PROX or SACS 7
INPUT POWER

GLED VDC 4
Power Input
8 RLED 3
9 BEEP VAC 2
10 TAMP TB3 TB4
LOCK LATMON AUX ALARM REQEX BYPASS DOOR SPARE
VAC 1
VDC+
COM

COM

COM

COM
GND

IN+

IN+

IN+

IN+
NO

NO

NO

NO
NC

NC
IN-

IN-

IN-

IN-
10
10
1
2
3
4
5
6
7
8
9
1
2
3
Lock Relay 4
5
6
7
8
Auxiliary Relay 9

Use only
Auxiliary Power Output (+24)

Latch Monitor Input

Alarm Output

Request to Exit Input

Bypass Relay Output

Door Monitor Input

Spare Input

2AG 1.5A SLO-BLO Fuse


if replacement is required

Figure 22: Controller Boards

Document 988 SA3000 Installation Guide 41


January 28, 2008
CARD READERS

Table 16: Master Controller TB2: Host Network & SM8 RS-485 Connections
Position Wire Color (Belden 8723) Signal Name
TB2-1 (not used) RX485- (SM8)
TB2-2 (not used) RX485+ (SM8)
TB2-3 (not used) GND (SM8)
TB2-4 (not used) TX485- (SM8)
TB2-5 (not used) TX485+ (SM8)
TB2-6 RED RX485- (Host/Network)
TB2-7 BLACK RX485+ (Host/Network)
TB2-8 SHIELD GND (Host/Network)
TB2-9 WHITE TX485- (Host/Network)
TB2-10 GREEN TX485+ (Host/Network)

Table 17: Door Controller TB1: Card Reader Connections


Position Description
TB1–1 Voltage output for providing power to readers
TB1–2 Ground reference and power return for readers
TB1–3 RS-485 high-side for communication to SE3/CS and SE3/CSPP
TB1–4 RS-485 low-side for communication to SE3/CS and SE3/CSPP
TB1–5 Interface to Weigand Data 1 or to TA Strobe signal from the SACS
TB1–6 Interface to Weigand Data 0 or to TB Data signal from the SACS
TB1–7 Driver for Green LED on SACS or Proximity readers
TB1–8 Driver for Red LED on SACS or Proximity readers
TB1–9 Driver for Yellow LED on SACS or Beeper on Proximity readers
TB1–10 Tamper input for Proximity reader

Table 18: Door Controller TB2: Card Reader Connections


Position Description
TB2–1 Voltage output for providing power to readers
TB2–2 Ground reference and power return for readers
TB2–3 SASPP Transmitter output
TB2–4 SASPP Receiver input
TB2–5 Interface to Weigand Data 1 or to TA Strobe signal from the SACS
TB2–6 Interface to Weigand Data 0 or to TB Data signal from the SACS
TB2–7 Driver for Green LED on SACS or Proximity reader
TB2–8 Driver for Red LED on SACS or Proximity reader
TB2–9 Driver for Yellow LED on SACS or Beeper on Proximity reader
TB2–10 Tamper input for Proximity reader

Document 988 SA3000 Installation Guide 42


January 28, 2008
CARD READERS

Table 19: Door Controller TB3: Door Accessory Connections


Position Description
TB3–1 Ground reference and power return
TB3–2 Voltage output to provide power to door locking mechanism
TB3–3 LOCK relay Common (COM)
TB3–4 LOCK relay Normally Open (NO)
TB3–5 LOCK relay Normally Closed (NC)
TB3–6 Latch Monitor Input (-)
TB3–7 Latch Monitor Input (+)
TB3–8 AUXILLIARY relay Common (COM)
TB3–9 AUXILLIARY relay Normally Open (NO)
TB3–10 AUXILLIARY relay Normally Closed (NC)

Table 20: Door Controller TB4: Door Accessory Connections


Position Description
TB4–1 ALARM relay Common (COM)
TB4–2 ALARM relay Normally Open (NO)
TB4–3 Request to Exit Input (-)
TB4–4 Request to Exit Input (+)
TB4–5 BYPASS relay Common (COM)
TB4–6 BYPASS relay Normally Open (NO)
TB4–7 Door Monitor Input (-)
TB4–8 Door Monitor Input (+)
TB4–9 Spare Monitor Input (-)
TB4–10 Spare Monitor Input (+)

Table 21: Door Controller TB5: Tamper and Other Connections


Position Description
TB5–1 Ground reference
TB5–2 No Connect
TB5–3 AC Fail Monitor Input (-)
TB5–4 AC Fail Monitor Input (+)
TB5–5 Battery Low Monitor Input (-)
TB5–6 Battery Low Monitor Input (+)
TB5–7 Tamper Monitor Input (-)
TB5–8 Tamper Monitor Input (+)
TB5–9 TAMPER relay Common (COM)
TB5–10 TAMPER relay Normally Open (NO)

Document 988 SA3000 Installation Guide 43


January 28, 2008

You might also like