You are on page 1of 29

Reaffirmed IEEE 1982 ANSI/IEEE C37.

90-1978
Reaffirmed ANSI 1983 (Revision of ANSI C'37.90-1971)

adopted by the relays an'd relay systems


DEPARTMENT
OF
DEFENSE associated with
electric power apparatus
see acceptance notice on
inside front cover

,...,
00

...6en
en
,...:
M
U
W

-
W
W

C/)
Z
4:

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
A N S I / I E E E C37.90-1978
18 J u l y , 1983

Acceptance Notice

This n o n - G o v e r n m e n t d o c u m e n t w a s adopted o n 18 July, 1983, and is approved for use by the D o D . T h e indicated indus­
try group has furnished t h e c l e a r a n c e required by existing regulations. Copies o f the d o c u m e n t a r e stocked b y the D o D
Single Stock Point, N a v a l P u b l i c a t i o n s and F o r m s Center, Philadelphia, P A , 19120, for issue to D o D activities only. Con­
tractors and Industry g r o u p s must o b t a i n copies directly from I E E E , 345 East 47th Street, N e w Y o r k , N Y 10017.

Title of D o c u m e n t : IEEE Standard Relays and Relay Systems


Associated with Electric Power Apparatus

Document No: ANSI/IEEE C37.90-1978

D a t e o f Specific Issue A d o p t e d : 23 June, 1978

R e l e a s i n g Industry G r o u p : The Institute of Electrical and


Electronics Engineers, Inc

Custodians: Military C o o r d i n a t i n g A c t i v i t y :
Army — ME Navy — Y D
Navy — Y D
A i r Force — 8 5 Project N u m b e r : 6110-0258

Review Activity:
Army — ME
A i r Force — 9 9
Navy — SH
GLA — GS

N O T I C E : W h e n reaffirmation, a m e n d m e n t , revision, o r cancellation of this standard is initially proposed, the industry


group responsible for this standard shall inform t h e Military C o o r d i n a t i n g A c t i v i t y of the proposed c h a n g e and request
their participation.

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978
(Revision o f
ANSI C37.90-1971)

An American National Standard

IEEE Standard Relays and


Relay Systems Associated with
Electric Power Apparatus

Sponsor

Power System Relaying Committee of the


IEEE Power Engineering Society

Secretariat

Electrical and Electronics Technical Advisory Board

Approved September 9, 1 9 7 6
Reaffirmed March 1 1 , 1 9 8 2

IEEE Standards Board

Approved June 2 3 , 1 9 7 8
Reaffirmed April 4 , 1 9 8 3

American National Standards Institute

© Copyright 1978 by

The Institute of Electrical and Electronics Engineers, Inc


345 East 47th Street, New York, NY 10017, USA
No part of this publication may be reproduced in any form,
in an electronic retrieval system or otherwise,
without the prior written permission of the publisher.

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
IEEE Standards documents are developed within the Technical Com­
mittees of the IEEE Societies and the Standards Coordinating Commit­
tees of the IEEE Standards Board. Members of the committees serve
voluntarily and without compensation. They are not necessarily mem­
bers of the Institute. The standards developed within IEEE represent
a consensus of the broad expertise on the subject within the Institute
as well as those activities outside of IEEE which have expressed an in­
terest in participating in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to pro­
duce, test, measure, purchase, market, or provide other goods and ser­
vices related to the scope of the IEEE Standard. Furthermore, the view­
point expressed at the time a standard is approved and issued is subject
to change brought about through developments in the state of the art
and comments received from users of the standard. Every IEEE Stan­
dard is subjected to review at least once every five years for revision
or reaffirmation. When a document is more than five years old, and has
not been reaffirmed, it is reasonable to conclude that its contents,
although still of some value, do not wholly reflect the present state of
the art. Users are cautioned to check to determine that they have the
latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE. Sug­
gestions for changes in documents should be in the form of a proposed
change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the mean­
ing of portions of standards as they relate to specific applications. When
the need for interpretations is brought to the attention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since
IEEE Standards represent a consensus of all concerned interests, it is
important to ensure that any interpretation has also received the con­
currence of a balance of interests. For this reason IEEE and the mem­
bers of its technical committees are not able to provide an instant re­
sponse to interpretation requests except in those cases where the matter
has previously received formal consideration.
Comments on standards and requests for interpretations should be ad­
dressed to:
Secretary, IEEE Standards Board
3 4 5 East 47th Street
New York, N Y 1 0 0 1 7
USA

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
Foreword

(This F o r e w o r d is n o t a part o f A N S I / I E E E C 3 7 . 9 0 - 1 9 7 8 , A m e r i c a n National Standard R e l a y s and R e l a y S y s t e m s


Associated with Electric Power Apparatus.)

This revision of A N S I C 3 7 . 9 0 - 1 9 7 1 (IEEE Std 3 1 3 - 1 9 7 1 ) contains three major changes in content


and organization as described below.
( 1 ) The section on definitions of relay terms has been eliminated on the basis that these defini­
tions also appear in A N S I C 3 7 . 1 0 0 - 1 9 7 2 , Definitions for Power Switchgear. In the future, A N S I
C 3 7 . 1 0 0 will be the principal reference source for definitions of relay terms in the power switchgear
field.
( 2 ) A new section describing the Surge Withstand Capability ( S W C ) test has been added. The
description of this test was first published in 1 9 7 4 as A N S I C 3 7 . 9 0 a - 1 9 7 4 (IEEE Std 4 7 2 - 1 9 7 4 ) ,
Guide for Surge Withstand Capability ( S W C ) Tests (supplement to A N S I C 3 7 . 9 0 - 1 9 7 1 , IEEE Std
3 1 3 - 1 9 7 1 ) . A n y further revision of C 3 7 . 9 0 a - 1 9 7 4 will take precedence over Section 9 , Surge With­
stand Capability Tests.
(3) Clauses and tables have been added to the section on ratings to show performance data which
should be provided by a manufacturer in published information on auxiliary relays.
In addition to these changes, other significant changes have been made in Section 6, Ratings and
in Section 8 , Dielectric Tests.
In preparing this standard, consideration has been given to the work of other committees, and
especially to international standards which have been published or which are under preparation by
Technical Committee 4 1 of the International Electrotechnical Commission (IEC).
The major work in preparing the material for this revision was carried out by the Relay Standards
Subcommittee of the Power System Relaying Committee of the Power Engineering Society of the
Institute o f Electrical and Electronics Engineers.
Suggestions for improvement of this standard will be welcome. They should be sent to the Amer­
ican National Standards Institute, 1 4 3 0 Broadway, N e w York, N . Y . 1 0 0 1 8 , with a copy to the
Secretary, IEEE Standards Committee, Institute of Electrical and Electronics Engineers, Inc, 3 4 5
East 4 7 t h Street, N e w Y o r k , N . Y . 1 0 0 1 7 .
Membership of the Relay Standards Subcommittee during the period of revision of this document
consisted of:

C. A . Mathews, Chairman

J. W. C h a d w i c k R . J. K ü h r F. N . Meissner
D . Dal asta W. A . Lewis W. K . M o r r i s o n
R. E. Dietrich J. R . Linders M. Rosen
C. M . G a d s d e n J. W . L i p n i t z R . J. Sullivan
G. E . H e i d e n r e i c h G. L o k k e n F. V o n R o e s c h l a u b
J. A . I m h o f G . J. Marieni C. L . Wagner

The Subcommittee on Protective Relays of American National Standards Committee C 3 7 on


Power Switchgear was directly responsible for the revision and approval of this document as an
American National Standard. A t the time it completed its review of the standard, it had the follow­
ing personnel:

G. J. Marieni, Chairman

J. W. C h a d w i c k J. R . Linders Μ. B. Purvis
R . J. F e l t o n J. W. L i p n i t z M. Rosen
C. H . Griffin G. L o k k e n R. J. Sullivan
J. L . K o e p f i n g e r C. A . M a t h e w s F. V o n Roeschlaub

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
W h e n the I E E E Standards Board approved this standard on September 3 , 1 9 7 6 , it had the follow­
ing membership:

William R. Kruesi, Chairman Irvin N . Howell, Jr, Vice Chairman

Ivan G. Easton, Secretary

William E. A n d r u s Irving K o l o d n y William J. N e i s w e n d e r


Jean Jacques A r c h a m b a u l t Benjamin J. L e o n Gustave Shapiro
Dale R . C o c h r a n A n t h o n y C. Lordi Ralph M . S h o w e r s
Warren H . C o o k J o h n P. M a r k e y Robert A. Soderman
L o u i s Costrell T h o m a s J. Martin L e o n a r d W. T h o m a s , Sr
Jay F o r s t e r D o n a l d T . Michael Charles L. Wagner
Joseph L. Koepfinger Voss A. Moore William T . W i n t r i n g h a m f
William S. M o r g a n

t Deceased

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
Contents

SECTION PAGE

1. Definition of a Relay 7

2 . Scope 7

3 . Purpose 7

4 . Classification of Relays, Relay Systems, and Related Terminology 7


4 . 1 Classification of Relays b y Functions 7
4 . 2 Classification of Relays b y Input 8
4 . 3 Classification of Relays by Operating Principles or Structures 8
4 . 4 Classification of Relays by Performance Characteristics 8
4 . 5 Terminology Relating to Relay Operating and Performance Characteristics 9
4 . 6 Terminology Relating to Structural Components 9
4 . 7 Terminology Relating to Relay Environment 9
4 . 8 Terminology Relating t o Protective Methods and Systems and Their Performance 10

5. Service Conditions 10
5.1 Usual Service Conditions 10
5.2 Unusual Service Conditions 10

6. Ratings 11
6 . 1 Standard Current and Voltage Ratings for Relays 11
6.2 Allowable Variation from Rated Voltage 11
6 . 3 Maximum Design Voltage and Current for Relays 11
6 . 4 Range of Operating Voltage for Auxiliary Relays and other Functions 11
6 . 5 Test for Operation at Minimum Voltage — Auxiliary Relays 11
6 . 6 Make and Carry Ratings for Tripping Contacts 12
6.7 Published Data for Auxiliary Relays 12

7 . Heating (Temperature Limitations) 12


7 . 1 Limits of Temperature Rise for Coils 12

8. Dielectric Tests 14
8.1 General 14
8 . 2 Standard Test Voltages 14
8 . 3 Duration and Application of Test Voltage 14
8.4 Dielectric Tests at Point of Manufacture 14
8 . 5 Dielectric Tests by Users 14
8 . 6 Temperature at which Dielectric Tests are to be Made 14
8.7 Points of Application of Voltage 14
8 . 8 Frequency and Waveshape of Test Voltage 14
8 . 9 Measurement of Test Voltage 14

9. Surge Withstand Capability (SWC) Tests , 14


9 . 1 Introduction 14
9.2 General 14
9.3 Surge Withstand Capability (SWC) Waveshape and Characteristics 15
9.4 Equipment to be Tested 15
9.5 Application of Test Wave 17

FIGURES
Fig 1 General Makeup of a Relay System with Communications or Computer Interface,
or both, Showing Points to be Subjected t o the S W C Test 15
Fig 2 General Makeup of a Relay System Without Communications or Computer Interface
Showing Points to be Subjected to the SWC Test 16

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
FIGURES PAGE
Fig 3 Application of the C o m m o n M o d e Test 17
Fig 4 Application of the Transverse Mode Test 17
TABLES
Table 1 Maximum Design Voltage for dc Auxiliary Relays 11
Table 2 Limits of Temperature Rise for Coils 12
Table 3 Contact Rating for All Relays 12
Table 4 Operating Data for All Relays 13
Table 5 Operating Data for Relays with Intermittent Ratings 13
Table 6 Test Requirements for the Various External Connection Groups of a Relay System . . .18
APPENDIXES
A P P E N D I X A S W C Test Supporting Evidence and Bibliography 21
A l Supporting Evidence 21
A 2 Bibliography 22
APPENDIX FIGURES
Fig A l Typical SWC Test Circuit 21
Fig A 2 Control Circuit Transient Data 22

APPENDIX Β Graphical Illustrations of Relay Terminology 25

APPENDIX FIGURES
Fig B l (a) Operating Characteristic of Distance Relays; (b) Operating Characteristics
of Distance Relays that are Inherently Directional 25
Fig B 2 Relationship of Relay Operating Time for Electromechanical Relays 26
Fig B 3 Typical Operating Characteristic Curve Shapes of Various Inverse-Time Relays 26

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
An American National Standard
IEEE Standard Relays and
Relay Systems Associated with
Electric Power Apparatus

1. Definition of a Relay tions of relay terms. 1

Relay terminology covers a wide area from


A n electric device designed to respond to in­ the detailed relay structural principles through
put conditions in a prescribed manner and complex power system relay applications. The
after specified conditions are met to cause con­ terminology in this field can be classified in
tact operation or similar abrupt change in as­ several different manners. The following is be­
sociated electric control circuits. lieved to be the most comprehensive.

NOTES: 4 . 1 Classification of Relays b y Functions. The


( 1 ) Inputs are usually electrical b u t m a y b e m e c h a n ­
following basic areas of power system relay ap­
ical, thermal, o r o t h e r quantities, o r a c o m b i n a t i o n o f
quantities. L i m i t switches and similar simple devices plications provide a convenient method of re­
are n o t relays. lay classification.
(2) A relay m a y c o n s i s t o f several relay units, e a c h
4 . 1 . 1 Protective Relay. A protective relay
responsive t o a s p e c i f i e d i n p u t , with the c o m b i n a t i o n
o f unite p r o v i d i n g the desired overall p e r f o r m a n c e may be classified according to its input quan­
characteristic o f the relay. tities (see 4 . 2 ) , operating principles (see 4 . 3 ) ,
or performance characteristics (see 4 . 4 ) .
4 . 1 . 2 Regulating Relay. Regulating relays can
2.Scope be classified according to 4 . 2 , 4 . 3 , or 4 . 4 .
4 . 1 . 3 Monitoring Relay. Typical monitoring
This standard applies only to relays and re­ relays include:
lay systems used to control power switchgear.
It does not cover relays of types designed alarm relay
fault detector relay
primarily for industrial control, for switching
network phasing relay
of communication or other low-level signals,
synchronism-check relay
or any other equipment not intended for the
verification relay.
control of power equipment.
4 . 1 . 4 Programming Relay. Typical program
relays include:
3 . Purpose
accelerating relay
initiating relay
The purpose of this standard is to specify
network master relay
standard service conditions, standard ratings,
phase-selector relay
and requirements for testing of relays and re­
reclosing relay
lay systems associated with power apparatus.
synchronizing relay.

4 . 1 . 5 Auxiliary Relay. Typical auxiliary re­


4. Classification of Relays, Relay lays include:
Systems, and Related Terminology
blocking relay
closing relay
Definitions of relay terms are not included
in this standard. Refer to A N S I C 3 7 . 1 0 0 - 1 9 7 2 , 1
Illustrations o f s o m e o f the basic definitions are
Definitions for Power Switchgear, for defini­ s h o w n in A p p e n d i x B.

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

control relay 4 . 4 Classification of Relays by Performance


lockout relay Characteristics. Protective and other relays
receiver relay may be identified by their performance char­
seal-in relay acteristics, often represented graphically. Re­
timing relay lays included in this classification are listed
trip-free relay. below. [See Figs B l ( a ) , B l ( b ) , and B 2 . ]
4 . 2 Classification of Relays b y Input. Protec­
tive and other relays may be identified by the
input to which the relay responds. Relays in­ NOTES:
( l ) T h e general p e r f o r m a n c e term " o v e r " indicates
cluded in this classification are listed below.
that the relay o p e r a t e s f o r values o f the i n p u t quantity
N O T E : " O v e r " a n d " u n d e r " are qualifying terms t h a t in e x c e s s o f a p r e d e t e r m i n e d v a l u e ; similarly " u n d e r "
m a y b e u s e d t o prefix m a n y o f the i n p u t quantities, indicates that the relay o p e r a t e s f o r values o f the in­
t h e r e b y classifying the relay o n a p e r f o r m a n c e basis. p u t q u a n t i t y less than a p r e d e t e r m i n e d value. In s o m e
" G r o u n d , " " r e s i d u a l , " and " n e u t r a l " f o r m a n o t h e r cases a relay o p e r a t e s f o r values o f i n p u t quantity b o t h
t y p e o f qualifying term that m a y be used t o prefix greater than a n d less than the p r e d e t e r m i n e d value, and
m a n y o f the i n p u t quantities t o indicate a perfor­ are referred t o as " o v e r - a n d - u n d e r ( i n p u t ) r e l a y s . "
m a n c e l i m i t e d b y the m e t h o d o f c o n n e c t i o n t o the ( 2 ) T h e p e r f o r m a n c e o f relays m a y be significantly
p o w e r s y s t e m . T h e m o r e c o m m o n relays identified b y affected b y the m e t h o d o f c o n n e c t i o n t o the p o w e r
such qualifying terms are i n c l u d e d in 4 . 4 . s y s t e m . This is i n d i c a t e d b y such qualifying terms as
current relay " g r o u n d , " "residual," "differential," and others.

flow relay
frequency relay
blinder relay
power relay
conductance relay
pressure relay
definite minimum-time relay
temperature relay
definite-time relay
vibration relay
differential relay
voltage relay.
directional-overcurrent relay
4 . 3 Classification of Relays by Operating Prin­ directional-power relay
ciples or Structures. Protective and other relays
directional relay
may be identified by reference to operating
distance relay
principles or structural features. Relays classi­
frequency relay
fied in this way include:
ground relay
balance relay high-speed relay
current-balance relay impedance relay
electrically reset relay inverse-time relay
electromagnetic relay lens relay
electromechanical relay linear-impedance relay
gas-accumulator relay m h o relay
gas-pressure relay modified-impedance relay
hand-reset relay negative-phase-sequence relay
harmonic-restraint relay neutral relay
latching relay open-phase relay
mechanically reset relay overcurrent relay
multirestraint relay overexcitation relay
notching relay overload relay
percentage-differential relay overvoltage relay
phase-sequence relay phase-balance relay
product relay phase comparison relay
replica temperature relay phase relay
restraint relay phase-reversal relay
self-reset relay phase-undervoltage relay
solid-state relay positive-phase-sequence relay
static relay power relay
sudden-pressure relay rate-of-change relay
thermal relay. reactance relay

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH ELECTRIC POWER A P P A R A T U S C37.90-1978

residual relay torque control


resistance relay transient blocking
reverse-current relay transient response
sector-impedance relay travel
susceptance relay voltage restraint.
time-overcurrent relay
undercurrent relay
undervoltage relay 4.6 Terminology Relating to Structural Com­
zero-phase-sequence relay. ponents. Relays employ structural components
that may be unique or used in a unique manner
4.5 Terminology Relating to Relay Operating or that are infrequently found in other devices.
and Performance Characteristics. In addition to The following list of terms, relating to such
classifying relays according to their basic per­ structural components, may apply to both
formance characteristics, many terms are re­ static and electromechanical designs of relays.
quired to describe fully the detailed operation
and performance of a relay (see Fig B 3 ) . A
auxiliary relay driver
vocabulary of c o m m o n words with specialized
back contact
definitions that describe these relay operating
balance beam
and performance characteristics includes:
block-spike element
block block-block element
calibration card extender
calibration error comparer
contact opening time contact
critical impulse contact converter
critical impulse time *
critical overtravel time differentiator
critical travel front contact
dropout induction cup
dropout ratio induction disk
dropout time integrator
harmonic restraint level detector
impulse (time) margin operation indicator
input relay armature
relay element
instantaneous
relay unit
memory action
sequence network
offset
squaring amplifier
operating characteristic
squelch circuit
operating time
target
overtravel
telephone-type
phase delay
time dial
phase-sequence reversal protection
time lever
pickup
polarization transactor
polyphase tripping contact.
pulse
4.7 Terminology Relating to Relay Environ­
reach
ment. This terminology has c o m m o n usage
reset
with other electric apparatus. Some of the
reset time
more significant terms are:
response
setting drip-proof
setting error driptight
setting limitation dustproof
spike dusttight
startup explosionproof

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

fume-resistant overspeed protection


gasproof permissive
gastight phase-comparison protection
moisture-resistant phase-failure protection
submersible phase-sequence reversal protection
vaportight phase-undervoltage protection
watertight. pilot protection
primary protection
rate-of-change protection
4 . 8 Terminology Relating to Protective Meth­ reliability
ods and Systems and Their Performance. In remote backup
addition to the terminology described above
remote trip
pertaining to individual relays, there is also
security
significant terminology related to the applica­
selectivity
tion of protective relays and relay systems; this
time-undervoltage protection
includes:
transfer trip
applied-fault tripping trip
backup protection underfrequency protection
blocking underreaching protection
breaker-failure protection undervoltage protection
carrier-current-pilot protection voltage phase-balance protection
correct relaying system performance wire-pilot protection
correct relay operation zone
correct tripping zone-comparison protection
current phase-balance protection zone of protection.
dependability
differential protection 5 . Service Conditions
directional-comparison protection
directional-overcurrent protection 5.1 Usual Service Conditions. Relays and relay­
distance protection ing devices conforming t o this standard shall be
electrical center suitable for operation under the following
failure to trip conditions.
false tripping 5 . 1 . 1 The ambient temperature of the air
fault bus protection immediately surrounding the relay case or
ground protection other enclosure (for example, rack-mounted
guard signal units) shall be within the limits of —20° to
incorrect relaying system performance + 5 5 ° C , subject t o the requirements of 7 . 1 .
incorrect relay operation 5 . 1 . 2 The altitude shall not exceed 1 5 0 0 m
line tap ( 5 0 0 0 ft).
line terminal
5.2 Unusual Service Conditions. The use of re­
load restoration
lays and relaying devices at higher or lower
load shedding
ambient temperatures or at higher altitudes
local backup
than specified in 5.1 shall be considered as
loss of excitation
special conditions.
low-voltage protection
There are further unusual conditions that
microwave-pilot protection
may require special construction or opera­
open-phase protection
tion, and these shall be brought to the atten­
out of step
tion of those responsible for the application,
overcurrent protection
manufacture, and operation of relays and re­
overload protection
laying devices. A m o n g such unusual condi­
overpower protection
tions are exposure t o :
overvoltage protection
overreach ( 1 ) Damaging fumes or vapors
overreaching protection ( 2 ) Excessive moisture or dripping water

10

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH ELECTRIC POWER A P P A R A T U S C37.90-1978

( 3 ) Excessive dust, abrasive dust, or magnetic 6 . 3 . 3 The maximum design voltage or cur­
dust rent for all relays except as noted in 6 . 3 . 4 shall
( 4 ) Steam be equal to the rated voltage or current of the
( 5 ) Explosive mixtures of dust or gases relay.
( 6 ) Salt air 6 . 3 . 4 The maximum design voltage for dc
( 7 ) Abnormal shock, vibration, and seismic auxiliary relays, and for any power supply or
disturbances auxiliary relay circuits with dc voltage ratings,
( 8 ) Unusual transportation or storage condi­
tions
( 9 ) Extreme temperature or sudden change in
Table 1
temperature
Maximum Design Voltage for dc
( 1 0 ) Oil vapors
Auxiliary Relays
( 1 1 ) Extreme variations of supply voltage.

Rated Volts M a x . Design V o l t s

24 28
6 . Ratings
48 56
125 140
6 . 1 Standard Current and Voltage Ratings for 250 280
Relays. The standard current and voltage rat­
ings for relays shall be as follows:

shall be as shown in Table 1. The maximum


Voltage Current
design voltage for ac auxiliary relays shall be
(V) (A)
1 1 0 percent of the rated voltage.

Alternating Alternating 6 . 4 Range of Operating Voltage for Auxiliary


Current Current Relays and other Functions. Direct current
(rms) (rms) auxiliary relays which may be continuously
energized for indefinite periods, dc power
120 supplies, and auxiliary relay circuits with dc
240 voltage rating, shall be able to withstand the
480 maximum design voltage without exceeding the
temperature rises shown in Table 2 . These re­
lays shall operate successfully over a range
from 8 0 percent of rated voltage to the maxi­
6 . 2 Allowable Variation from Rated Voltage
m u m design voltage.
for Protective Relays. Protective relays which
are designed to be energized continuously N O T E : Generally, relays w h i c h operate at 8 0 percent
with ac voltage shall operate without damage o r less o f rated voltage w h e n h o t (see 6 . 5 ) will o p e r a t e
at 7 2 p e r c e n t o r less o f rated voltage w h e n c o l d .
at rated frequency with voltage not more than
1 0 percent above the rated voltage, but not Alternating current auxiliary relays which
necessarily in accordance with the temperature- may be continuously energized for indefinite
rise limits established for operation at rated periods shall be able to withstand 1 1 0 percent
voltage. of rated voltage without exceeding the tem­
perature rises shown in Table 2. These relays
6 . 3 Maximum Design Voltage and Current
shall operate successfully over a range from
for Relays
8 5 — 1 0 0 percent of rated voltage.
6 . 3 . 1 Maximum design voltage is the highest
rms alternating or direct voltage at which 6 . 5 Test for Operation at Minimum Voltage —
apparatus is designed to be energized con­ Auxiliary Relays. For successful operation at
tinuously. the minimum voltage for continuous duty,
6 . 3 . 2 Maximum design current is the highest the auxiliary relay coil should be subjected to
rms alternating or direct current at which ap­ the normal line voltage until constant tempera­
paratus is designed to be energized contin­ ture is reached, and then tested for successful
uously. closing at the minimum voltage.

11

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

Table 2 2 0 ° C ) with the relay in its case and with its


Limits of Temperature Rise for Coils cover (if any) in position.
One duty cycle shall consist of the following
Limits o f Observable T e m p e r a t u r e sequence: 2 0 0 ms on, 3 0 0 ms off, 2 0 0 ms on,
Rise A b o v e 55° C A m b i e n t 1 5 s off, 2 0 0 ms on, 3 0 s off, 2 0 0 ms on, ap­
Temperature
Method o f
proximately 2 min off. This duty cycle shall be
Temperature Class 1 0 5 Class 1 3 0 Class 1 8 0 repeated 5 0 0 times to obtain 2 0 0 0 operations.
Determination Insulation Insulation Insulation (Current is interrupted by independent means
at the end of each "on" interval.)
Thermometer
method 40 65 115
6.7 Published Data for Auxiliary Relays. Tables
Applied thermo­
couple method 45 70 120 3 , 4 , and 5 show the information concerning
Resistance contact ratings, operating time, pickup and
method 50 75 125
dropout values, etc, which should be provided
by the manufacturer in literature describing
these relays. It is also recommended that the
Relays may be tested cold with proper allow­
format shown in these tables be used as a guide
ance for increase in impedance due t o tempera­
when publishing this information. Numbers in
ture rise as established by temperature tests
parentheses refer to notes following Table 5 .
on duplicate relays.

6 . 6 Make and Carry Ratings for Tripping Con­


tacts 7. Heating (Temperature Limitations)
6 . 6 . 1 Definition of tripping contacts: relay
contacts designed for the purpose of energizing 7.1 Limits of Temperature Rise for Coils. The
power circuit breaker trip coils. temperature rise of relay coils as installed in a
6 . 6 . 2 Tripping contacts shall meet the follow­ relay case or other enclosure and tested at the
ing specifications for contact performance: maximum design voltage or current per usual
The contacts shall make and carry 3 0 A for service conditions (see 5 . 1 ) shall not exceed the
at least 2 0 0 0 operations in a duty cycle as de­ value given in Table 2 .
scribed below. The load shall be resistive for
N O T E : F o r the p u r p o s e o f m e e t i n g this requirement,
both dc and ac and the current shall be inter­ certain existing e l e c t r o m e c h a n i c a l relay designs m a y
rupted by independent means. The voltage have a 15° C rise greater than the values s h o w n in Table
value applied will be one of the standard volt­ 2 if the application is s u b j e c t t o the r e q u i r e m e n t that
the average a m b i e n t temperature that the relay is sub­
age ratings. Design tests to prove this rating j e c t e d t o t h r o u g h o u t its Ufe d o e s n o t e x c e e d 40° C
shall be made at room ambient (not less than w i t h a m a x i m u m o f 5 5° C.

Table 3
Contact Rating for A l l Relays

Contact Interrupting Rating ( A ) ( 1 ) Short


Circuit Time
(V) Resistive Inductive ( 2 ) Rating Continuous
— (1 min) Rating
Single Double (3) Single Double ( 3 ) (A) (A)
DC Contact Contacts Contact Contacts (4) (4)

24
48
125
250

60 Hz
120
240
480

12

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH E L E C T R I C P O W E R A P P A R A T U S C37.90-1978

Table 4
Operating Data for A l l Relays

Coil
Circuit Coil T y p i c a l Operating T i m e Operating ( V ) ( 6 ) ( 7 )
Volts Circuit (me) ( B ) ( 6 )
DC ( Ω ) Must Must
DC (25°C) Pickup Dropout Pickup Dropout

24
48
125
250

60Ηζ(Ω)(8)

Armature Armature
60Hz Open Closed

120
240
480

Table 5
Operating Data for Relays with Intermittent Ratings

DC Coil Coil Series Pickup


Circuit Rated (Ω) Resistor Withstand Time (9)
(V) (V) 25°C (if used) (s) (ms)

Notes concerning information in Tables 3, 4, and 5.


( 1 ) Interrupting rating s h o u l d b e based o n at least 1 0 0 o p e r a t i o n s at rated value, using s u d d e n l y applied ( o r re­
m o v e d ) rated v o l t a g e , w i t h n o e x t e n s i v e burning o f c o n t a c t s .
( 2 ) I n d u c t i v e rating s h o u l d b e based o n tests using standard i n d u c t a n c e L/R = 0 . 0 4 for d c and c o s φ = 0.4 for ac.
( 3 ) Interrupting rating c o l u m n h e a d e d " D o u b l e C o n t a c t s " means t w o c o n t a c t s in series.
( 4 ) S h o r t - t i m e and c o n t i n u o u s ratings are based o n t e m p e r a t u r e rise in c o n t a c t m e m b e r s and s u p p o r t i n g parts.
Limiting temperatures are t o b e d e t e r m i n e d b y manufacturer.
( 5 ) All operating times are measured w i t h rated v o l t a g e s u d d e n l y applied o r r e m o v e d .
( 6 ) Operating t i m e values and p i c k u p / d r o p o u t values in T a b l e 4 are measured w i t h relay " h o t " — energized at
rated v o l t a g e until thermal e q u i l i b r i u m has b e e n reached at r o o m a m b i e n t ( 2 0 — 2 5 ° C ) .
( 7 ) Operating v o l t a g e data c o l u m n s in T a b l e 4 have the f o l l o w i n g m e a n i n g : ( a ) " M u s t P i c k u p " means that actual
p i c k u p is less than value given, and applied voltage s h o u l d b e greater than this value for reliable o p e r a t i o n ; and ( b )
" M u s t D r o p o u t " means that actual d r o p o u t is greater than value given, and applied v o l t a g e s h o u l d b e less than this
value f o r reliable d r o p o u t .
( 8 ) I m p e d a n c e data for a c relays s h o u l d i n c l u d e o h m s and phase angle.
( 9 ) Operating t i m e values in T a b l e 5 are measured with relay " c o l d " — c o i l at r o o m a m b i e n t ( 2 0 — 2 5 ° C ) b e f o r e
m e a s u r e m e n t is m a d e .
( 1 0 ) F o r current o p e r a t e d auxiliary relays, substitute amperes f o r volts in a b o v e tables.
( 1 1 ) R e l a y c o n t a c t s s h o u l d have b o t h ac and d c c o n t a c t ratings at all applicable standard voltages.
( 1 2 ) S o m e relays will have i n f o r m a t i o n in all three tables.

13

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 RELAYS A N D R E L A Y SYSTEMS ASSOCIATED

8.7 Points of Application of Voltage. The test


8. Dielectric Tests
voltage for insulation to ground and between
circuits shall be applied successively between
8.1 General. Dielectric tests between circuits,
each electric circuit and all other electric cir­
and dielectric tests between circuits and relay
cuits, and between each electric circuit and the
frame, shall be considered as routine tests. Di­
metal frame of the relay. The test voltage
electric tests across open contacts shall be con­
across open contacts shall be applied to the
sidered as design tests. Dielectric tests are not
relay terminals which connect to the contacts.
required across contacts with surge-suppression
For relays with adjustable contact gap, the con­
components, nor across solid-state output cir­
tact spacing shall be not less than that recom­
cuits; when these are used, the Surge Withstand
mended by the manufacturer.
Capability ( S W C ) test (Section 9 ) should be
substituted for the dielectric test. 8 . 8 Frequency and Waveshape o f Test Voltage.
The test voltage shall have a frequency value
8 . 2 Standard Test Voltages. Relays rated 6 0 0 V
and waveshape conforming to good commercial
and below shall withstand for 1 min a low-
practice. Experience has shown that, with the
frequency test of the following values:
comparatively low test voltage used for relays,
( 1 ) Insulation to ground and between cir­
moderate variations in waveform or frequency
cuits: twice rated voltage plus 1 0 0 0 V rms,
have no appreciable influence on the effect
with a minimum of 1 5 0 0 V rms.
of the test voltage.
( 2 ) Across normally open contacts: twice
rated voltage plus 1 0 0 0 V rms with a minimum 8 . 9 Measurement of Test Voltage. The volt­
of 1 5 0 0 V rms meter method shall be used. In measuring the
voltage with a voltmeter, the instrument should
8 . 3 Duration of Application of Test Voltage.
derive its voltage from the high-voltage circuit
The test voltage for all relays shall be applied
either directly or through a potential trans­
continuously for a period of 6 0 s.
former, or by means of a voltmeter coil placed
As an alternate, to be made at the point of
in the testing transformer.
manufacture only, it is permissible to test any
relay for 1 s at a value 2 0 percent higher
than the standard 6 0 s test voltage.
9. Surge Withstand Capability (SWC) Tests 2

8 . 4 Dielectric Tests at Point of Manufacture.


Dielectric tests shall be made at the point of
9 . 1 Introduction. The Surge Withstand Capabil­
manufacture in accordance with this standard.
ity (SWC) test is a design test for relay systems,
8 . 5 Dielectric Tests b y Users and in particular static relay systems. The pur­
8 . 5 . 1 Dielectric tests, in accordance with the pose of this test is to apply to the terminals
standard, may be made by the user on new re­ of the relay system a standardized test wave­
lays only to determine whether specifications shape that is representative of surges observed
are fulfilled. N e w relays for the purpose of this and measured in actual installations. Points of
test are defined as those which have n o t been application to systems under test are described
in service, which are not more than one year in detail. In order to pass this test, relay sys­
old from the date of shipment, and which have tems must be able to withstand the applied
been suitably stored to prevent deterioration. surge without damage to components and with­
8 . 5 . 2 Additional dielectric tests may be out operating incorrectly.
made, using 7 5 percent of the test voltage
9 . 2 General. Surges and how they relate to pro­
determined in accordance with 8 . 2 , at the
tective relay systems can be divided into two
point of installation to determine the prac­
categories: first, the control of the surges pre­
ticality of placing or continuing equipment in
sented to the relay systems, and second, the
service.
ability of the relay systems to withstand the
surges. The surges presented to the relay sys-
8.6 Temperature at Which Dielectric Tests Are
to be Made. Dielectric tests shall be made at
the temperature assumed under normal opera­ 2
T h i s s e c t i o n represents a c o n d e n s e d version o f sup­
p l e m e n t A N S I C 3 7 . 9 0 a - 1 9 7 4 . A n y further revision o f
tion or at the temperature attained under the
A N S I C 3 7 . 9 0 a - 1 9 7 4 will take p r e c e d e n c e over this
condition of commercial testing. section.

14

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH ELECTRIC POWER A P P A R A T U S C37.90-1978

tems can be generated either within the cir­ pedance of the surge generator used to produce
cuits to the system or induced into the circuits. the test wave shall be 1 5 0 Ω + 5 percent. The
Certain construction practices can be followed test wave is to be applied to a test specimen at
which will minimize the surges impressed upon a repetitive rate of not less than 5 0 tests per
the relay. Both the user of static relay equip­ second for a period of not less than 2 . 0 s.
ment and the manufacturers have a given area
N O T E : ( 1 ) All v o l t a g e and time values refer t o the
of responsibility relating to surge protection o p e n circuit c o n d i t i o n o f the surge generator. ( 2 )
of relay systems. T i m e p e r i o d a n d r e p e t i t i o n rate have been c h o s e n t o
c o v e r e q u i p m e n t w h i c h is u s e d o n 5 0 H z as well as 6 0
9.3 Surge Withstand Capability ( S W C ) Wave­ Hz systems.
shape and Characteristics. The S W C test wave
A schematic diagram of a typical surge gen­
is an oscillatory wave, with a frequency range
erator is shown in Fig A l .
of 1.0 M H z to 1.5 M H z , voltage range of 2 . 5
kV to 3.0 kV crest value of the first half cycle 9.4 Equipment to be Tested. Equipment to be
peak, and envelope decaying to 5 0 percent of subjected to the SWC test is described below in
the crest value of the first peak in not less than general terms and is shown in Figs 1 and 2 . Be­
6 μη from the start of the wave. The source im­ cause of variations in relay engineering nomen-

Figl
General Makeup of a Relay System with Communications or Computer
Interface, or both, Showing Points to be Subjected
to the SWC Test

RELAY SYSTEM

TRI Ρ 1
RECLOSE BLOCK ^RCUITS
RELAY BREAKER FAILUREJ
INPUT LOGIC
CURRENT<
CIRCUITS ζ

ζ
2N
DC

< > SIGNAL CIRCUITS


INPUT ω COMMUNICATIONS
VOLTAGE s AND/OR COMPUTER
CIRCUITS INTERFACE

ι _ H POWER SUPPLY

POINTS SUBJECTED
TO SWC T E S T
+ - +
STATION OTHER
BATTERY POWER SUPPLY
(IF USED)
(INPUT POWER SUPPLY CIRCUITS)

15

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

RELAY SYSTEM

TRIP
IOUTPUT
R E C L O S E BLOCK (CIRCUITS
RELAY B R E A K E R FAILURE ) '
INPUT
CURRENT< LOGIC
CIRCUITS 3
O
Ζ
rr

<
ÜJ
INPUT
VOLTAGE
CIRCUITS > SIGNAL CIRCUITS

POWER SUPPLY

POINTS S U B J E C T E D
+ - + - T O SWC T E S T
STATION OTHER
BATTERY POWER SUPPLY
(IF USED)
(INPUT POWER SUPPLY CIRCUITS)
Fig 2
General Makeup of a Relay System without Communications
or Computer Interface Showing Points to be Subjected
to the SWC Test

clature, equipment definitions in this section consisting of measuring units, relay logic, com­
illustrate b y example the intent of this test. munications interfaces, computer interfaces,
9.4.1 General. Transient voltages usually are and necessary power supplies (as shown in Fig
capacitively or magnetically coupled from a 1 or 2 ) .
high voltage source of electrical noise into sec­ 9 . 4 . 2 . 4 Signal Circuit. A n y circuit other
ondary circuits or control wiring. Since these than input voltage circuits, input current cir­
voltages may appear unsuppressed across con­ cuits, power supply circuits, or those circuits
nection points of components associated with which directly or indirectly control power
the protective relay system, it must be deter­ circuit breaker operation.
mined that they will not cause a failure or a 9 . 4 . 2 . 5 Common Mode Voltage. The volt­
misoperation of the system. age c o m m o n to all conductors of a group as
9.4.2 Nomenclature and Definitions. measured between that group at a given loca­
9 . 4 . 2 . 1 Communications Interface Equip­ tion and an arbitrary reference (usually earth).
ment. A portion of a relay system (shown in 9.4.2.6 Transverse (Differential) Mode
Fig 1 ) which transmits information from the Voltage. The voltage at a given location be­
relay logic to a communications link, or con­ tween two conductors of a group.
versely to logic, for example, audio tone equip­ 9.4.3 Devices to be Tested. The S W C test is
ment, a carrier transmitter-receiver when an a design test of a relay system. It is the intent
integral part of the relay system. of the SWC test to prove that a given relay sys­
9 . 4 . 2 . 2 Computer Interface Equipment. A tem can operate satisfactorily without failure
device which interconnects a protective relay or misoperation when subjected to high voltage
system to an independent computer, for ex­ transients. The components which make up a
ample, a scanner, a buffer amplifier. relay system vary, depending on the require­
9 . 4 . 2 . 3 Relay System. As assembly usually ments of the user or the system as designed by

16

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH ELECTRIC POWER A P P A R A T U S C37.90-1978

the manufacturer. The user, the manufacturer, ISOLATING R E A C T O R T E R M I N A L S OF R E L A Y


or both must therefore decide what consti­ IF S P E C I F I E D S Y S T E M UNDER T E S T

L
(I0A, 370μΗ, 2500 V)
tutes the relay system to be tested. T w o typical
arrangements of relay systems are shown in
Figs 1 and 2 . The points of application, as de­
scribed in 9 . 5 . 2 , of all components of a relay
system shall be subjected to the SWC test.

N O T E : Design tests m a y b e m a d e o n s e l e c t e d speci­


m e n s during p r o d u c t i o n at t h e r e q u e s t o f the purchaser COUPLING CAP
IF S P E C I F I E D
w h e n s p e c i f i e d a n d agreed u p o n .
TEST R E F E R E N C E GROUND
9.5 Application of Test Wave GENERATOR

9.5.1 Conditions of the Test. The tests shall N O T E : Use s h o r t lead lengths o r c o a x i a l c a b l e .
be made under usual service conditions. These
tests shall be made at the temperature attained Fig 3
under the condition of commercial testing. Application of the C o m m o n Mode Test
9 . 5 . 1 . 1 Since the S W C test is a design test
external connection groups are shown in Table
of the relay system, it is important to duplicate
6. Details of the recommended method of ap­
as nearly as feasible the actual in-service condi­
plying the c o m m o n mode and transverse mode
tions. Where portions of the relay system are
tests are shown in Figs 3 and 4 , respectively,
manufactured by someone other than the relay
and are discussed in 9 . 5 . 3 .
manufacturer and assembled by the user, those
9.5.3 Connection Groups. Each of the five
portions may be simulated for the relay system
groups is tested with system conditions as
test. In this case, the user shall be responsible
specified in 9 . 5 . 1 . 4 .
for tests on the complete relay system.
9 . 5 . 3 . 1 Signal Circuit Tests. Signal circuits
9 . 5 . 1 . 2 The purpose of the test is t o deter­
shall be tested as follows:
mine: ( 1 ) that no component failures occur,
9 . 5 . 3 . 1 . 1 Common Mode Test. The com­
and ( 2 ) that no incorrect outputs occur, such
mon mode test is required on all connection
as trip, auxiliary output, or target lamps.
groups. For this test, one terminal of the test
9 . 5 . 1 . 3 All external connections to the
generator shall be connected to each input con­
relay system shall be considered in one of the
nection, or logical group of connections,
following five groups:
through coupling capacitors if specified in
(1) Signal circuits Table 6 , as shown in Fig 3. The other terminal
(2) Input current circuits of the test generator shall be connected to the
(3) Input voltage circuits surge reference of the system.
(4) Input power supply circuits 9 . 5 . 3 . 1 . 2 Transverse (Differential Mode)
(5) Output circuits Test. Transverse tests are preferred; their exclu­
sion shall be stated in writing by the manufac­
9 . 5 . 1 . 4 For the duration of the test, the
turer. When required, the terminals of the test
relay system, or simulated system, is to be con­
generator shall be connected to the terminals
nected and energized in its normal configura­
of a signal pair as shown in Fig 4 .
tion. The input voltage circuits are to be ener­
gized at 1 0 0 percent rated voltage. Input cur­ Fig 4
rent circuits are t o be energized at 7 5 percent Application of the Transverse Mode Test
of nominal C T rating and essentially in-phase
with the respective input circuit voltage. Input TERMINALS OF RELAY
SYSTEM UNDER TEST
voltage to power supply circuits must be within
specified limits.
9.5.2 Points of Application of SWC Test. In
block diagram format, Figs 1 and 2 shows speci­
fic points of application as related to the relay TEST
system configuration. Tests at these points of GENERATOR
application are considered the minimum re­
quirements for equipment used in relay sys­
tems. The test requirements for the various

17

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

Table 6
Test Requirements for the
Various External Connection Groups of a Relay System

C o m m o n M o d e Test
( R e q u i r e d o n all Circuits)

Reactors Required Coupling Caps


Connection Group Yes No Yes No

I n p u t / O u t p u t Signal Circuits X X
I n p u t Current X X
Input Voltage X X
Input Power Supply(s) X X
O u t p u t Circuits
(a) Thyristor* X X
( b ) Contacts X X

* Includes a n y o u t p u t w h i c h is s w i t c h e d b y a thyristor o r s o m e o t h e r elec­


tronic type device.

9 . 5 . 3 . 2 Current Circuit Tests. With system test, one terminal of the test generator shall be
conditions as specified in 9 . 5 . 1 . 4 , all like input connected with suitable coupling (for example,
current circuits shall be surge tested as a unit. a 1 0 0 0 V , 0.1 μ¥) capacitors to each power
This is a test of the c o m m o n mode surge pro­ supply terminal. The other terminal of the test
tection of the system. For this test, the in­ generator shall be connected to the surge ref­
put current circuits of a like group (that is, erence of the system. An isolating inductor (for
phase 1, phase 2 , phase 3 ) should be connected example, an R F choke rated 1 0 A , 2 5 0 0 V , 3 7 0
via suitable coupling to one terminal of the test μ Η ) shall be inserted in each source lead. Each
generator as shown in Fig 3. The other terminal power supply shall be tested if there is more
of the test generator shall be connected to the than one.
surge reference of the system. If the current 9 . 5 . 3 . 4 . 2 Transverse Mode Tests. For this
circuit has provision for the circuit residual test, the terminals of the test generator shall be
current to pass through an electrically separate connected to power supply terminals using
circuit of the relay, then these connections suitable ( 1 0 0 0 V , 0.1 /zF) coupling capacitors.
shall also be treated as an input current circuit An isolating inductor ( 1 0 A , 2 5 0 0 V , 3 7 0 μ Η )
and tested in a similar manner. Likewise, each shall be inserted in each source lead. Each pow­
group of input current circuits, such as polariz­ er supply shall be tested if there is more than
ing circuits, shall be tested. one.
9 . 5 . 3 . 3 Voltage Circuit Tests. With system
conditions as specified in 9 . 5 . 1 . 4 all like input 9 . 5 . 3 . 5 Tests on Output Circuits. With sys­
voltage circuits shall be surge tested as a unit. tem conditions as specified in 9 . 5 . 1 . 4 output
This is a test of the c o m m o n mode surge pro­ circuits shall be tested as follows.
tection of the system. For this test, the input 9 . 5 . 3 . 5 . 1 Common Mode Test. For this
voltage circuits of a like group (that is, phase 1, test, one terminal of the test generator shall be
phase 2 , phase 3) shall be connected via suit­ connected to each output connection, or
able coupling to one terminal of the test gen­ logical group of connections. The other
erator. The other terminal of the test generator terminal of the test generator shall be con­
shall be connected to the surge reference of the nected to the surge reference of the system.
system. In a similar manner, each group of 9 . 5 . 3 . 5 . 2 Transverse Mode Test. For this
input voltage circuits, such as polarizing cir­ test, one terminal of the test generator shall be
cuits, shall be tested. connected to one output connection of a pair
9 . 5 . 3 . 4 Input Power Supply Tests. With or logical group and the other terminal of the
system conditions as specified in 9 . 5 . 1 . 4 , each test generator shall be connected to another
input power supply circuit shall be surge tested output connection of a pair or logical group.
as a unit. The test shall be repeated for other pairs until
9.5.3.4.1 Common Mode Tests. For this each pair has been tested.

18

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH ELECTRIC POWER A P P A R A T U S C37.90-1978

N O T E : S o m e o u t p u t circuits (that is, relay c o n t a c t s ) and in some applications carrier bursts, car­
m a y n o t require surge p r o t e c t i o n ; h o w e v e r , t h e y shall
rier interruptions.
b e tested e v e n t h o u g h their o n l y link t o the s y s t e m
is through c o u p l i n g t o adjacent wiring and c o m p o n e n t s .
N O T E : S q u e l c h o p e r a t i o n is n o t c o n s i d e r e d false o r
erroneous information.

9 . 5 . 5 Test Data. A copy of the n o load wave­


9 . 5 . 4 Acceptance. A test is successful when form, details of the surge generator circuit, and
no erroneous output is present, no component a description of the tests conducted shall be
failure occurs, and there is no change in calibra­ supplied upon request.
tion exceeding normal tolerances. A n er­ 9 . 5 . 6 Equipment Changes. SWC tests shall be
roneous output is one that presents false in­ required following significant equipment de­
formation, such as target lights, trip pulses, sign changes.

19

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
Appendix A

( T h i s A p p e n d i x is n o t a part o f A N S I / I E E E C 3 7 . 9 0 - 1 9 7 8 , A m e r i c a n National Standards R e l a y s and R e l a y Systems


A s s o c i a t e d with Electric P o w e r A p p a r a t u s . )

SWC Test Supporting Evidence


and Bibliography

A l . Supporting Evidence
the equipment to a continuous voltage for a
longer time, and, therefore, is potentially more
The purpose of this section is to provide
damaging to equipment.
background information on the choice of
Arguments favoring the oscillatory test are
values for the surge withstand capability
based on the observation that most field test
(SWC) test waveform.
data show clear evidence of oscillatory tran­
There were four fundamental questions
sients.
which affected the working group's final
Furthermore, stray coupling of high frequen­
choice of values for the SWC test. These were:
cy oscillatory transients can produce inter­
(1) Are typical surges unidirectional or os­
ference with equipment operation more readily
cillatory?
because of the more rapid rates of change of
(2) If surges are oscillatory, what frequen­
currents and voltage produced. Therefore, it
cies are typical?
is claimed, it should be more effective in caus­
(3) What practical value of crest voltage
ing possible false tripping of static relays.
should be specified?
Finally, several members expressed the
(4) What source impedance should the gen­
opinion that the major concern is surges origi­
erator have?
nating external to the control circuits. Ex­
The following summarizes the salient points
perience has shown that these sources tend to
of the working group's discussions on each of
induce only oscillatory transients, whereas
these questions.
surge sources within the control circuits pro­
Al.l Unidirectional or Oscillatory? Opinion duce both oscillatory and unidrectional surges
was somewhat divided on this point. A minor­ depending on circuit conditions. Hence, the
ity was in favor of a unidirectional impulse emphasis on oscillatory surges.
type waveform similar to the 1.2 X 5 0 μβ im­
pulse used for high voltage insulation tests. A 1 . 2 What Frequency? It appears that the pro­
The British Electrical and Allied Manufacturers posed 1.5 M H z figure was first suggested by
Association ( B E A M A ) surge test uses an im­ W. K. Sonnemann in June 1 9 6 4 . Apparently,
pulse waveform. Reasons supporting this posi­ he had measured 1 2 5 0 V crest at this frequen­
tion are that it represents a more energetic cy during field tests on a 1 6 1 k V system. The
source than the oscillatory test and it subjects measurements reportedly were made on the

Fig A l
Typical SWC Test Current

5kVGAP 300 Λ

120 V CI - ± - · 0 | 5
>"τ TEST
Ll JO.TSijH •300Λ SPECIMEN
60 Hz
loo * a l o w
•VW
120 V - 7 2 0 0 V

Τ s 6 — 1 0 MS t o Vi value
Ci = m i c a t y p e
L i =; 3 turns Vi in c o p p e r t u b i n g o r equivalent o n 2Vi in
diameter f o r m

N O T E : S o u r c e i m p e d a n c e equals o p e n circuit v o l t a g e divided b y short circuit current, o r 1 5 0 Ω .

21

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 RELAYS A N D R E L A Y SYSTEMS ASSOCIATED

secondary circuits of capacitor potential de­ more data became available, it became evident
vices during disconnecting switch operations. that a higher value was desirable and it was
In June 1 9 6 6 , Η . T. Seeley endorsed the 1.5 thought important t o coordinate this value
MHz figure in correspondence with R . E . with secondary circuit insulation rating. A
Dietrich. value of 2 5 0 0 V received general approval. This
Data on control circuit surges reported in figure was based on these considerations. Tech­
various technical papers give frequencies from nology is now available to design circuitry ex­
5.0 k H z to several megahertz. Most of these ternal to the relay to limit surges impressed on
surges were induced from various kinds of E H V the relays to a maximum of 2 . 5 k V . This value
switching operations external to the control has a crest which is slightly in excess of the
circuits. There have been some indications that relay 1.0 min dielectric test.
switching phenomena in the control circuits Actual test data shown in Fig A 2 exceed 2 . 5
themselves produce even higher frequencies, kV by substantial amounts. Because these
many megahertz, in addition to unidirectional levels would present hazards to secondary
surges. However, no data to support this indica­ cables and apparatus insulation as well as to
tion have been published. the relays it becomes obvious that other
Reliable data on surge waveforms are scarce. means would need to be taken to minimize
If one extracts data from the dozen or so pub­ their magnitude to conform with equipment
lished papers on field measurements, less than insulation ratings. It does not make sense
100 data points are obtained. Nevertheless, then to specify a relay surge test voltage
these data are useful in obtaining a general pic­ above insulation ratings.
ture of the range of surge characteristics. Fig
A1.4 Test Source Impedance? The first re­
A 2 is a plot of such data. Crest voltage is
corded discussion of the test source imped­
plotted versus frequency, one point for each
ance occurred in January 1 9 6 7 , when the
test in which both parameters were reported.
working group was considering three sub­
The coordinates of the proposed S W C test are
mitted values, 5 0 , 1 5 0 , and 3 0 0 Ω . It was also
also plotted for comparison.
brought to the group's attention that the
A1.3 What Crest Voltage? Early proposals for B E A M A unidirectional test specified 4 9 5 Ω .
the SWC test originated from W. K. Sonne- After some deliberation, the value of 1 5 0 Ω
mann's suggestion of 1 2 5 0 V at 1.5 M H z . As was selected as representing a realistic com­
promise.
Fig A 2 Data on this factor are rather meager and
Control Circuit Transient Data are based on measurements made at lower
frequencies, 0.1 to 0.2 M H z . They show values
Ιθ5 ranging from 5 0 to 1 0 0 Ω . Only one reference
has been found which gives data at 1.5 M H z
o ° <9 which may pertain to this question. This is a
oo oo a report by J. H . Bull of the Electrical Research
0
ft o Association, which shows data on the mea­
SP sured surge impedance of various low voltage
o ° indoor power wiring systems over the fre­
> 100 1\
quency range 0 . 0 0 1 to 1 0 . 0 M H z . Average
values at 1.5 M H z ranged from 5 0 to 1 0 0 Ω . If
10
these systems can be compared to usual station
control circuit wiring systems, then it would
0.OOI 0.01 0.1 I 10 100 seem that the 1 5 0 Ω value is a little on the high
FREQUENCY, MHz side, but not overly so.
O PUBLISHED DATA
Β PROPOSED SWC T E S T (BOX SHOWS
APPROXIMATE RANGES)
A2. Bibliography
N O T E : This is a p l o t o f v o l t a g e m a g n i t u d e versus fre­
q u e n c y as d i s p l a y e d o n field test c a t h o d e - r a y o s c i l l o ­ [1] B L U M E , L. F., and B E W L E Y , L. V .
grams. O n l y t h o s e data are indicated f o r w h i c h b o t h
parameters are o b t a i n e d f r o m the o s c i l l o g r a m o f the Switching Surges with Transformer
surge w a v e f o r m . Load-Ratio Control Contactors. AIEE

22

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
WITH ELECTRIC POWER A P P A R A T U S C37.90-1978

Transactions, vol 5 6 , pp 1 4 6 4 — 1 4 7 5 , Journal of Japan, vol 7 , no 2 , 1 9 6 2 , pp


December 1 9 3 7 . 65-72.
[2] T A Y L O R , J. R . , and R A N D A L L , C. E. [13] D I E T R I C H , R . E., and G I L L I E S , D . A .
Voltage Surges Caused by Contactor Shielding Measuring Circuits from Fast
Coils. Proceedings of the Institution of Rise Voltages and Currents. AIEE
Electrical Engineers ( L o n d o n ) , 1 9 4 2 . Conference Paper for Special Technical
[3] G R O V E R , F. W. Inductance Calcula­ Conference on Extra High Voltage
tions — Working Formula and Tables. Communications, Control and Relay­
New Y o r k : Dover Publications Incor­ ing, March 1 9 6 2 , Dallas, Texas.
porated, 1 9 4 6 . [14] W A L L A C E , J. B. A Study of Surge
[4] H A L M A N , T. R . , and H A R R I S , L. K. Voltages Occurring on the Control Bus
Voltage Surges in Relay Control Cir­ at Walton Station. Presented at the
cuits. AIEE Transactions, vol 6 7 , pp AIEE Special Technical Conference,
1693-1701, 1948. Dallas, Texas, March 1 9 6 2 .
[5] A n A I E E Committee Report. Insula­ [15] C A L L O W , J. Α . , and M A C K L E Y , K. W.
tion Level of Relay Control Circuits. Impulsive Overvoltages on Secondary
AIEE Transactions, vol 6 8 , pp 1 2 5 5 — Circuits of 3 3 0 k V Capacitor Voltage
1257,1949. Transformer. Snowy Mountain Hydro­
[6] G O O D I N G , F. H . , and S L A D E , Η. B. electric Authority, C I G R E , 1 9 6 2 , Re­
Shielding of Communication Cables. port 1 3 6 .
AIEE Transactions (Communication [16] G I L L I E S , D . Α . , and R A M B E R G , H. C.
and Electronics), vol 7 4 , pp 3 7 8 — 3 8 6 , D I E T R I C H , R. E . , and S C H A U F E L -
July 1 9 5 5 . B E R G E R , F. G. Field Switching Surge
[7] V O N B E R G E R , K. Necessity and Pro­ Instrumentation and Results of T w o -
tective Value of Metallic Secondary Step Switching Tests Conducted by the
Cable Sheaths in High Voltage Installa­ Bonneville Power Administration. IEEE
tions and in High Mountain Applica­ Transactions on Power Apparatus and
tions as Example of Protective Action Systems (Special Supplement 1963),
of Faraday Screens. Zurich SEV Bulle­ pp 2 5 8 - 2 7 9 .
tin, vol 5 1 , no 1 1 , June 4 , 1 9 6 0 , pp [17] S O N N E M A N N , W. K. A Laboratory
549-563. Study of High-Voltage High-Frequency
[8] A R M S T R O N G , H. R . , and M I L L E R , Transients. Presented at the Texas
B. D . A Surge-Impedance Analog of A&M Protective Relay Conference,
a Large Generating Plant Switchyard. April 1 9 6 5 .
AIEE Transactions (Power Apparatus [18] G I L L I E S , D . A . , and R A M B E R G , H.C.
and Systems), vol 7 9 , pp 1 0 5 0 — 1 0 5 4 , The Effects of Transient Voltages on
February 1 9 6 1 . Measurements Within a Switchyard.
[9] S E E L E Y , Η . T . Protection of Control Pacific Northwest Instrumentation
Circuit Rectifiers Against Surges from Conference, I S A , April 1 9 6 5 .
DC Coil Interruption. AIEE Transac­ [19] M O R R I S O N , R . Shielding and Ground­
tions (Power Apparatus and Systems), ing for Instrumentation Systems. Elec­
vol 8 0 , pp 8 7 1 - 8 7 9 , December 1 9 6 1 . tromechanical Design, February 1 9 6 6 ,
[10] I D A , E . S. Reducing Electrical Inter­ pp 5 6 - 5 9 .
ference. Control Engineering, February [20] O N S A G E R , R . W . Power Supply Re­
1 9 6 2 , pp 1 0 7 - 1 1 1 . quirements for Computers. Proceedings
[11] S O N N E M A N N , W. K. Transient Volt­ of the American Power Conference,
ages in Relay Control Circuits. AIEE vol X X V I I I , 1 9 6 6 , pp 1 0 3 4 - 1 9 4 8 .
Transactions (Power Apparatus and [21] T U R N E R , J. A . Voltage Surges in Re­
Systems), vol 8 0 , pp 1155—1161, lay Control Circuits. Interim Report
February 1 9 6 2 . IEEE Surge Phenomena Subcommittee
[121 Y A M A M U R A , Y . , and others. On the of Power System Relaying Committee,
Voltage Induced in the Interconnected IEEE Conference Paper no 31PP66-
Earth Network and the Control Circuit 3 1 4 . Presented at the 1 9 6 6 Summer
by Impulse Current. Electrotechnical Power Meeting.

23

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

[22] S M I T H , L. E. Voltages Induced in Con­ [33] G A R T O N , H. L., and S T O L T , Η. K.


trol Cable from Arcing 5 0 0 k V Field Tests and Corrective Measures
Switches. IEEE Conference Paper, n o for Suppression of Transients on Solid
3 1 P P 6 6 - 4 6 7 . Presented at the 1 9 6 6 State Devices in E H V Stations. Pro­
Summer Power Meeting. ceedings of the American Power Con­
[23] Recommended Transient Voltage Tests ference, vol 3 1 , 1 9 6 9 , pp 1 0 2 9 - 1 0 3 8 .
Applicable to Transistorized Relays. [34] K O T H E I M E R , W. C. The Influence of
British Electrical and Allied Manufac­ Station Design on Control Circuit
turers Association ( B E A M A ) , Publica­ Transients. Proceedings of the Amer­
tion no 2 1 9 , November 1 9 6 6 . ican Power Conference, vol 3 1 , 1 9 6 9 ,
[24] S L A D E K , N . J. Electromagnetic Inter­ pp 1 0 2 1 - 1 0 2 8 .
ference Control. Science and Engineer­ [35] B U D Z I L O V I C H , P. N. Electrical Noise,
ing Series, Electro-Technology, no 9 5 , its Nature, Causes, Solutions. Control
November 1 9 6 6 . Engineering, May 1 9 6 9 .
[25] S O N N E M A N N , W . K., and M A R I E N I , [36] M O O R E , L. E . , and C H U N G , Η. Y .
G. J. A Review of Transient Voltages Transient Effects on Solid State Relays
in Control Circuits. Presented at the for E H V Lines. Presented at the Mid­
Relay Committee Meeting, Pennsylvania west Power Symposium, Minneapolis,
Electric Association, February 1 9 6 7 . Minnesota, October 1 9 6 9 .
[26] G I L L I E S , D . Α . , R O G E R S , E. J., and [37] S E E L E Y , Η . T . , a n d E M M E R L I N G , E.J.
R A M B E R G , H. C. Transient Voltages The W h y and H o w of Surge Control in
— High Voltage Capacitor Switching. Station Relaying. Proceedings of Amer­
Presented at the Texas A & M Protective ican Power Conference, vol 3 2 , 1 9 7 0 ,
Relay Conference, April 1 9 6 7 . pp 1 0 4 6 - 1 0 5 3 .
[27] G I L L I E S , D . Α . , and R A M B E R G , H. C. [38] D I E T R I C H , R . E., R A M B E R G , H. C ,
Methods for Reducing Induced Volt­ and B A R B E R , J. C. B.P.A. Experience
ages in Secondary Circuits. IEEE Trans­ with EMI Measurement and Shielding
actions on Power Apparatus and Sys­ in E H V Substations. Proceedings of the
tems, vol PAS-86, pp 9 0 7 — 9 1 6 , July American Power Conference, vol 3 2 ,
1967. 1 9 7 0 , pp 1 0 5 4 - 1 0 6 1 .
[28] K O T H E I M E R , W. C. Control Circuit [39] S U T T O N , H. J. Transient Pickup in
Transients in Electric Power Systems. 5 0 0 k V Control Circuits. Proceedings
Presented at the Texas A & M Protec­ of the American Power Conference,
tive Relay Conference, April 1 9 6 8 . vol 3 2 , 1 9 7 0 , pp 1 0 6 2 - 1 0 6 9 .
[29] S O N N E M A N N , W. K . , and F E L T O N , [40] C H A D W I C K , J. W . , Jr. Proposed IEEE
R. J. Transient Voltage Measurement Surge Withstand Capability Test for
Techniques. IEEE Transactions on Solid State Relays. Proceedings of the
Power Apparatus and Systems, vol American Power Conference, vol 3 2 ,
P A S - 8 7 , pp 1 1 7 3 - 1 1 7 9 , April 1 9 6 8 . 1 9 7 0 , pp 1 0 7 0 - 1 0 7 5 .
[30] D I E N N E , G., and W E R Y , R . Induced [41] S U T T O N , H. J. Transients Induced in
Interference in Wiring Feeding Pro­ Control Cables Located in E H V Sub­
tective Relays. Progress Report of station. IEEE Transactions on Power
Study Committee no 4, Appendix 2, Apparatus and Systems, vol PAS-89,
C I G R E , 1 9 6 8 , Report 3 1 - 0 1 . pp 1 0 6 9 - 1 0 8 1 , July/August 1 9 7 0 .
[31] B I R C H , F. H . , B U R R O W S , C. H., and [42] HICKS, R . L. Control of Transient
T U R N E R , H. J. Investigation into Interference on Station Wiring. On­
Transient Overvoltages in Secondary tario Hydro. PEA Relay Committee
Wiring at Switching Stations. C I G R E , Minutes, October 1 9 7 0 .
1 9 6 8 , Report 3 1 - 0 4 . [43] HICKS, R . L., and JONES, D . E.
[32] P A D D I S O N , E. Protection of Relays Transient Voltages on Power Station
Against Surges and Overvoltages. Pre­ Wiring. IEEE Transactions on Power
sented at the Symposium on Distance Apparatus and Systems, vol PAS-90,
Protection, University of Manchester, pp 2 6 1 - 2 6 9 , January/February 1 9 7 1 .
England, September 1 9 6 8 .

24

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
Appendix 6

(This Appendix is not a part of A N S I / I E E E C 3 7 . 9 0 - 1 9 7 8 , American National Standard Relays and Relay Systems
Associated with Electric Power Apparatus.)

Graphical Illustrations of Relay Terminology

MODIFIED IMPEDANCE RELAY

ft

(b)

FigBl
(a) Operating Characteristic of Distance Relays; (b) Operating
Characteristics o f Distance Relays that are Inherently Directional

25

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.90-1978 R E L A Y S A N D R E L A Y SYSTEMS ASSOCIATED

r NORMAL MOVEMENT OF
RELAY WHEN CURRENT
G R E A T E R T H A N PICKUP
IS A P P L I E D

U CRITICAL IMPULSE TIME »JCRJTICAL OVERTRAVEL TIME [·—

[ • — — C H A R A C T E R ι S T IC O P E R A T I N G TIME • *L RESET TIME -

Fig B 2
Relationship of Relay Operating Time for
Electromechanical Relays

C MODERATELY INVERSE

6 VERY INVERSE

G EXTREMELY INVERSE

Fig B 3
Typical Operating Characteristic Curve Shapes of
Various Inverse-Time Relays

26

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
C 3 7 . 4 2 - 1 9 8 1 S p e c i f i c a t i o n s for Distribution Cutouts C 3 7 . 6 3 - 1 9 6 9 ( R 1 9 7 4 ) R e q u i r e m e n t s for A u t o m a t i c
and Fuse Links ( A N S I ) Line Sectionalizers for Alternating-Current Systems,
(includes s u p p l e m e n t C 3 7 . 6 3 a - 1 9 7 3 ) ( A N S I )
C 3 7 . 4 4 - 1 9 8 1 S p e c i f i c a t i o n s for Distribution Oil Cut­
outs and Fuse Links ( A N S I ) C 3 7 . 6 6 - 1 9 6 9 ( R 1 9 7 4 ) R e q u i r e m e n t s for Oil-Filled
C a p a c i t o r Switches for Alternating-Current Systems
C 3 7 . 4 5 - 1 9 8 1 S p e c i f i c a t i o n s for Distribution Enclosed
(ANSI)
Single-Pole Air Switches ( A N S I )
C 3 7 . 8 5 - 1 9 7 2 ( R 1 9 7 8 ) Safety R e q u i r e m e n t s for X -
C 3 7 . 4 6 - 1 9 8 1 S p e c i f i c a t i o n s for P o w e r Fuses and Fuse
R a d i a t i o n Limits f o r A C High-Voltage P o w e r V a c u u m
D i s c o n n e c t i n g Switches ( A N S I )
Interrupters Used in P o w e r Switchgear (includes sup­
C 3 7 . 4 7 - 1 9 8 1 S p e c i f i c a t i o n s for Distribution Fuse Dis­ plement C 3 7 . 8 5 a - 1 9 7 2 ) ( A N S I )
c o n n e c t i n g Switches, Fuse S u p p o r t s , and Current-
C 3 7 . 9 0 - 1 9 7 8 ( R 1 9 8 2 ) R e l a y s and R e l a y Systems As­
Limiting Fuses ( A N S I )
s o c i a t e d with Electric P o w e r Apparatus ( A N S I / I E E E )
C 3 7 . 4 8 - 1 9 6 9 ( R 1 9 7 4 ) G u i d e for A p p l i c a t i o n , Opera­
C 3 7 . 9 0 a - 1 9 7 4 ( R 1 9 7 9 ) G u i d e for Surge Withstand Ca­
tion, and Maintenance o f Distribution C u t o u t s and
pability ( S W C ) Tests ( S u p p l e m e n t t o A N S I / I E E E
Fuse Links, S e c o n d a r y Fuses, Distribution E n c l o s e d
C37.90-1978) (ANSI/IEEE)
Single-Pole Air S w i t c h e s , P o w e r Fuses, Fuse D i s c o n ­
necting S w i t c h e s , and A c c e s s o r i e s ( A N S I ) C 3 7 . 9 1 - 1 9 6 7 ( R 1 9 7 9 ) G u i d e for Protective R e l a y A p ­
C 3 7 . 4 8 a Trial-Use Standard A p p l i c a t i o n o f Fuses in p l i c a t i o n s t o P o w e r Transformers ( A N S I / I E E E )
Enclosures ( R e v i s i o n o f S e c t i o n 8, A N S I C 3 7 . 4 7 - C 3 7 . 9 3 - 1 9 7 6 G u i d e f o r Protective R e l a y A p p l i c a t i o n s
1969) (ANSI/IEEE) o f A u d i o T o n e s o v e r T e l e p h o n e Channels ( A N S I /
C 3 7 . 5 0 - 1 9 7 3 Test P r o c e d u r e s f o r L o w - V o l t a g e A C IEEE)
P o w e r Circuit Breakers Used in Enclosures, (includes C 3 7 . 9 5 - 1 9 7 3 ( R 1 9 7 9 ) G u i d e f o r Protective Relaying
supplements C 3 7 . 5 0 a - 1 9 7 5 and C 5 7 . 5 0 b - 1 9 7 5 ) ( A N S I ) o f Utility-Consumer I n t e r c o n n e c t i o n s ( A N S I / I E E E )
C 3 7 . 5 1 - 1 9 7 9 C o n f o r m a n c e Testing o f Metal-Enclosed C 3 7 . 9 6 - 1 9 7 6 G u i d e f o r A C M o t o r P r o t e c t i o n (super­
L o w - V o l t a g e A C P o w e r Circuit Breaker Switchgear As­
sedes C 3 7 . 9 2 - 1 9 7 2 and C 3 7 . 9 4 - 1 9 7 2 ) ( A N S I / I E E E )
semblies ( A N S I )
C 3 7 . 9 7 - 1 9 7 9 G u i d e for Protective R e l a y A p p l i c a t i o n s
C 3 7 . 5 2 - 1 9 7 4 Test P r o c e d u r e s for L o w - V o l t a g e A C
t o P o w e r S y s t e m Buses ( A N S I / I E E E )
P o w e r Circuit P r o t e c t o r s Used in Enclosures ( A N S I )
C 3 7 . 9 8 - 1 9 7 8 Standard f o r Seismic Testing o f Relays
C 3 7 . 6 0 - 1 9 8 1 R e q u i r e m e n t s f o r Overhead, Pad M o u n t e d ,
(This standard c o m p l e m e n t s A N S I / I E E E 3 4 4 - 1 9 7 5 )
Dry Vault, and Submersible A u t o m a t i c Circuit R e ­
(ANSI/IEEE)
closers and Fault Interrupters f o r A C Systems ( A N S I /
IEEE) C 3 7 . 9 9 - 1 9 8 0 G u i d e f o r the P r o t e c t i o n o f Shunt Capa­
c i t o r Banks ( A N S I / I E E E )
C 3 7 . 6 1 - 1 9 7 3 G u i d e for the A p p l i c a t i o n , O p e r a t i o n ,
and Maintenance o f A u t o m a t i c Circuit R e c l o s e r s C 3 7 . 1 0 0 - 1 9 8 1 Definitions for P o w e r Switchgear ( A N S I /
(ANSI/IEEE) IEEE)

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.
Related Standards in the C37 Series

C 3 7 . 0 4 - 1 9 7 9 Rating Structure for A C H i g h - V o l t a g e C 3 7 . 1 6 - 1 9 7 9 Preferred Ratings, R e l a t e d R e q u i r e m e n t s


Circuit Breakers R a t e d o n a S y m m e t r i c a l Current Basis f o r and A p p l i c a t i o n R e c o m m e n d a t i o n s for L o w -
( C o n s o l i d a t e d e d i t i o n , Including s u p p l e m e n t s C 3 7 . 0 4 a , V o l t a g e P o w e r Circuit Breakers and A C P o w e r Cir­
C 3 7 . 0 4 D , and C 3 7 . 0 4 c ) , ( A N S I / I E E E ) cuit P r o t e c t o r s (revision o f C 3 7 . 1 6 - 1 9 7 3 ) ( A N S I )
C 3 7 . 0 6 - 1 9 7 9 Preferred Ratings and R e l a t e d R e q u i r e d C 3 7 . 1 7 - 1 9 7 9 T r i p Devices f o r A C and General Purpose
Capabilities f o r A C H i g h - V o l t a g e Circuit Breakers D C L o w - V o l t a g e P o w e r Circuit Breakers ( A N S I )
R a t e d o n a S y m m e t r i c a l Current Basis ( C o n s o l i d a t e d
edition, ANSI) C 3 7 . 1 8 - 1 9 7 9 Standard Field Discharge Circuit Breakers
C 3 7 . 0 9 - 1 9 7 9 Test P r o c e d u r e for A C H i g h - V o l t a g e Used in Enclosures f o r R o t a t i n g Electric Machinery
Circuit Breakers R a t e d o n a S y m m e t r i c a l Current (ANSI/IEEE)
Basis ( C o n s o l i d a t e d e d i t i o n , A N S I / I E E E )
C 3 7 . 2 0 - 1 9 7 4 Switchgear A s s e m b l i e s , Including Metal-
C 3 7 . 0 1 0 - 1 9 7 9 Application Guide for A C High-Voltage E n c l o s e d Bus ( i n c l u d e s s u p p l e m e n t C 3 7 . 2 0 a - 1 9 7 0 ,
Circuit Breakers R a t e d o n a S y m m e t r i c a l Current C37.20b-1972, C37.20c-1974, C37.20d-1978) (Con­
Basis ( C o n s o l i d a t e d e d i t i o n , A N S I / I E E E ) solidated edition, A N S I / I E E E )
C 3 7 . 0 1 1 - 1 9 7 9 A p p l i c a t i o n G u i d e f o r Transient R e ­
C 3 7 . 2 3 - 1 9 7 0 ( R 1 9 7 7 ) G u i d e f o r Calculating Losses in
c o v e r y V o l t a g e f o r A C H i g h - V o l t a g e Circuit Breakers
Isolated-Phase Bus ( A N S I / I E E E )
R a t e d o n a S y m m e t r i c a l Current Basis ( C o n s o l i d a t e d
edition, ANSI/IEEE) (Revision o f C 3 7 . 0 7 2 1 - 1 9 7 1 ) C 3 7 . 2 4 - 1 9 7 1 ( R 1 9 7 6 ) G u i d e f o r Evaluating the Effect
C 3 7 . 0 1 2 - 1 9 7 9 A p p l i c a t i o n G u i d e f o r C a p a c i t a n c e Cur­ o f Solar R a d i a t i o n o n O u t d o o r Metal-Clad Switchgear
rent S w i t c h i n g o f A C H i g h - V o l t a g e Circuit Breakers (ANSI/IEEE)
R a t e d o n a S y m m e t r i c a l Current Basis, ( C o n s o l i d a t e d
edition) (ANSI/IEEE) (Revision o f C 3 7 . 0 7 3 1 - 1 9 7 3 ) C 3 7 . 2 6 - 1 9 7 2 ( R 1 9 7 7 ) Guide for Methods o f Power
F a c t o r Measurement f o r L o w - V o l t a g e Inductive Test
C 3 7 . 0 8 1 - 1 9 8 1 G u i d e for S y n t h e t i c Fault Testing o f A C Circuits ( A N S I / I E E E )
H i g h - V o l t a g e Circuit Breakers R a t e d o n a S y m m e t r i c a l
Current Basis ( A N S I / I E E E ) C 3 7 . 2 7 - 1 9 7 2 A p p l i c a t i o n G u i d e for L o w - V o l t a g e A C
Non-Integrally F u s e d P o w e r Circuit Breakers (Using
C 3 7 . 1 - 1 9 7 9 Standard D e f i n i t i o n , S p e c i f i c a t i o n and
Separately M o u n t e d Current-Limiting Fuses) ( A N S I /
Analysis o f Manual, A u t o m a t i c , and Supervisory Sta­
t i o n C o n t r o l and D a t a A c q u i s i t i o n ( A N S I / I E E E ) IEEE)
C 3 7 . 2 9 - 1 9 7 4 Standard f o r Low-Voltage A C Power
C 3 7 . 2 - 1 9 7 9 Standard Electrical P o w e r S y s t e m D e v i c e
Circuit P r o t e c t o r s Used in Enclosures ( A N S I / I E E E )
Function Numbers (ANSI/IEEE)
C 3 7 . 4 - 1 9 5 3 ( R 1 9 7 6 ) Definitions and Rating Struc­ C 3 7 . 3 0 - 1 9 7 1 Definitions and R e q u i r e m e n t s for High-
ture for A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a V o l t a g e A i r S w i t c h e s , Insulators, and Bus Supports
T o t a l Current Basis [ i n c l u d e s s u p p l e m e n t s C 3 7 . 4 a - (ANSI/IEEE)
1 9 5 8 ( R 1 9 6 6 ) and C 3 7 . 4 b - 1 9 7 0 ( R 1 9 7 1 ) (reaffirmed
with c h a n g e in t i t l e ) ] ( A N S I ) and C 3 7 . 4 c - 1 9 8 0 ( A N S I / C37.30a-1975 Supplement to C37.30-1971, (ANSI/
IEEE) I E E E ) ( s o l d separately)

C 3 7 . 5 - 1 9 7 9 G u i d e f o r Calculation o f Fault Currents C 3 7 . 3 1 - 1 9 6 2 ( R 1 9 6 9 ) Electrical and Mechanical Char­


f o r A p p l i c a t i o n o f A C H i g h - V o l t a g e Circuit Breakers acteristics o f I n d o o r Apparatus Insulators ( A N S I )
R a t e d o n a T o t a l Current Basis ( A N S I / I E E E )
C 3 7 . 3 2 - 1 9 7 2 S c h e d u l e s o f Preferred Ratings, Manu­
C 3 7 . 6 - 1 9 7 1 ( R 1 9 7 6 ) S c h e d u l e s o f Preferred Ratings facturing S p e c i f i c a t i o n s , and A p p l i c a t i o n G u i d e for
f o r A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a T o t a l H i g h - V o l t a g e Air S w i t c h e s , Bus S u p p o r t s , and Switch
Current Basis ( A N S I ) Accessories ( A N S I )

C 3 7 . 7 - 1 9 6 0 ( R 1 9 7 6 ) (reaffirmed with change in title) C37.33-1970 ( R 1 9 7 6 ) R a t e d C o n t r o l V o l t a g e s and


Interrupting Rating F a c t o r s for R e c l o s i n g Service their Ranges for High-Voltage Air Switches ( A N S I )
for A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a T o t a l
C 3 7 . 3 4 - 1 9 7 1 ( R 1 9 7 7 ) Test C o d e for High-Voltage Air
Current Basis ( A N S I )
Switches ( A N S I / I E E E )
C 3 7 . 9 - 1 9 5 3 ( R 1 9 7 6 ) (reaffirmed w i t h c h a n g e in title) C37.34a-1975 supplement to C37.34-1971, sold
Test C o d e f o r A C H i g h - V o l t a g e Circuit Breakers R a t e d separately
o n a T o t a l Current Basis [ i n c l u d e s s u p p l e m e n t C 3 7 . 9 a -
1970 ( R 1971)] (ANSI) C 3 7 . 3 5 - 1 9 7 6 G u i d e f o r the A p p l i c a t i o n , Installation,
O p e r a t i o n , and Maintenance o f H i g h - V o l t a g e Air Dis­
C 3 7 . 1 1 - 1 9 7 5 R e q u i r e m e n t s f o r Electrical C o n t r o l f o r c o n n e c t i n g and L o a d Interrupter Switches ( A N S I )
A C High V o l t a g e Circuit Breakers R a t e d o n a S y m ­
metrical Current Basis a n d a T o t a l Current Basis C 3 7 . 3 7 - 1 9 7 9 L o a d i n g G u i d e f o r A C High-Voltage Air
(ANSI) Switches (In Excess o f 1 0 0 0 V o l t s ) (revision o f C 3 7 . 3 7 -
1971) (ANSI/IEEE)
C37.12-1969 ( R 1 9 7 4 ) Guide Specifications for A C
H i g h - V o l t a g e Circuit Breakers R a t e d o n a S y m m e t r i c a l C 3 7 . 4 0 - 1 9 8 1 Service C o n d i t i o n s and Definitions for
Current Basis and a T o t a l Current Basis ( A N S I ) High-Voltage Fuses, Distribution E n c l o s e d Single-Pole
Air S w i t c h e s , Fuse D i s c o n n e c t i n g Switches, and A c ­
C 3 7 . 1 3 - 1 9 8 1 L o w - V o l t a g e A C P o w e r Circuit Breakers cessories ( A N S I / I E E E )
Used in Enclosures ( A N S I / I E E E )
C 3 7 . 4 1 - 1 9 8 1 Design Tests for High-Voltage Fuses,
C 3 7 . 1 4 - 1 9 7 9 L o w - V o l t a g e D C P o w e r Circuit Breakers Distribution E n c l o s e d Single-Pole Air S w i t c h e s , Fuse
Used in Enclosures ( A N S I / I E E E ) D i s c o n n e c t i n g S w i t c h e s , and A c c e s s o r i e s ( A N S I / I E E E )

Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 29,2016 at 03:53:00 UTC from IEEE Xplore. Restrictions apply.

You might also like