You are on page 1of 5

Voltage Sensorless Predictive Direct Power Control for

Renewable Energy Integration Under Grid Fault


Conditions
Y. K. Tao*, Q. H. Wu*†, Fellow, IEEE, W. H. Tang*, Senior Member, IEEE, and L. Wang*
*
School of Electrical Power Engineering, South China University of Technology, Guangzhou 510641, China.

Department of Electrical Engineering and Electronics, University of Liverpool, Liverpool L69 3GJ, U.K.
Corresponding author: Prof. W. H. Tang; E-mail address: wenhutang@scut.edu.cn.

Abstract—With the increasing penetration of distributed the increasing penetration of DG systems into the power grid,
generation (DG) systems based on renewable energies into the new and stricter grid codes are issued, which require the DG
power grid, the fault ride-through capability of them is stressed systems to maintain the active power delivery and reactive
by recent grid codes. Aiming to adapting this requirement, this power support during grid faults [2]ˈ [3]. During the last
paper proposes a voltage sensorless predictive direct power decade, a few works have been published to improve the
control (PDPC) for the grid-interactive DC/AC converter output property of the DC/AC interface belonging to DG
utilized in DG systems. In order to realize a voltage sensorless
systems. In the proposed control strategies, two important
operation independent of the grid frequency deviation, a second
order generalized integrator (SOGI)-based virtual flux (VF)
types can be identified: active power and reactive power
observer is adopted. Moreover, through specific fluctuating currents based [4]-[6] and fluctuating power compensation
power compensations calculated base on the estimated VF, the based [7], [8] schemes. In the former, active and reactive
proposed control strategy offers positive sequence current, power fluctuations are regulated by the corresponding
constant active and reactive power behaviors, respectively. components of currents. In the latter, the residual power
Simulation studies were conducted in MATLAB/Simulink under fluctuating components are directly added to the constant
gird fault conditions, including the grid frequency deviation, power reference values to manage the power ripples.
distorted grid voltage by negative sequence voltage and higher
Virtual flux (VF) based schemes are popular in voltage
harmonics. The simulation results verify that the proposed
voltage sensorless PDPC presents superior steady-state and
sensorless controller designs for the following two reasons.
transient performance against the foregoing grid faults. The application of VF remains the common advantages of
sensorless strategies, such as cost reduction, reliability and
Index Terms--Voltage sensorless control, predictive direct power generality improvement. Meanwhile, it eliminates the
control (PDPC), DC/AC converter, renewable energy limitation of the orientation point for the control system [9]
integration, grid fault condition. and enhances harmonic tolerance [10]. The most common VF
observer is designed based on a first-order low pass filter (LPF)
I. INTRODUCTION [11], however, it cannot emulate the pure integrator accurately.
Later, some varieties for it were proposed to overcome this
Recently, with the economic development and energy shortcoming [9]ˈ [12]. The above-mentioned observers are
demand increase, environmental problems have gradually all sensitive to grid frequency deviation. Literature [13]
become a heated issue. It forces human to look for a proposed a frequency-adaptive observer, whose behavior can
sustainable development way for power generation. On this be adjusted in time according to the grid frequency.
background, the distributed generation (DG) systems based on
renewable energies are attracting more and more attentions. This paper proposes a voltage sensorless predictive direct
From the researches carried out to date we may find that power control (PDPC) for the DC/AC converter interfacing
power electronic equipments appear as essential parts of the the DG systems with the utility network, which can operate
DG systems [1]. under grid fault conditions, involving the unbalance voltage
dip, grid frequency deviation and higher harmonic distortion.
Due to the existence of various grid disturbances, the After compensating for specific power fluctuating components,
power grid cannot keep up the ideal operation conditions. In positive sequence current, constant active and reactive power
these cases, several problems could lead a DC/AC converter to operations can be ensured, respectively. The rest of this paper
trip, such as DC link voltage oscillation, overcurrent, is organized as follows. Section II introduces the VF observer.
under/overvoltage and heavy imbalance at the AC side. With Then, the principles of the proposed control strategy are

The project is supported by Guangdong Innovative Research Team


Program (No. 201001N0104744201).
presented in Section III, and followed by simulation vs
verifications in Section IV. Finally, conclusions are drawn in DC link
Section V. R L
Distributed
Sources
II. VF OBSERVERS
As defined in [10], the grid voltage can be regarded as the vDC
ia ,b Virtual AC Motor
product of a VF. Thus, the relationship between the line S abc
voltage vector v and the VF vector \ can be described as v̂DE
iab iDE
abc Voltage uDE
\ ³ vdt  \ 0 (1)
S abc SDE
SCEs & p, q
Reference SVM
S abc

DE SVEs p , q
c c Calculation
where \ 0 is the initial value of the flux integral. The integral
initial value is essential for the VF estimation, as conducted in vDC p q
[14], nevertheless, which is not the issue concerned by this
paper. Figure 2. Block scheme of the proposed strategy.

Since the pure integrator could cause DC bias due to the A. Mathematical Model
unknown initial input signal and DC offset presented in
sampled signals, and integration drift problems [15], other Assuming that the grid voltage is constant at adjacent
approaches have been utilized to emulate the integral action in sampling instants and the differential operation is replaced by
(1). Thereinto, a ¿rst-order LPF [11] is the simplest and most the first order difference, the voltage sensorless PDPC can be
common method for VF observer designs. However, this modeled as [15]
method will introduce amplitude and phase errors in the VF
estimation. Although some varieties of it have eliminated ªuD (k ) º ª vˆD (k ) º L ª vˆD (k ) vˆE (k ) º
«u ( k ) » «vˆ (k ) »  2 « »
¬ E ¼ Ts (vˆD  vˆE ) ¬vˆE (k ) vˆD (k ) ¼
2
these errors, all of them suffer from estimation performance ¬ E ¼
degeneration when the grid frequency is different from the (2)
rated value, unless the grid frequency adaptive strategy is ª p app (k  1)  p (k ) º
˜« »
integrated in the observer. «¬ q app (k  1)  q (k ) »¼

where u is the converter terminal voltage reference, v̂


v  q\ denotes the estimated grid voltage , Ts represents the sampling
+ - Hv +
k - ³ y period and papp , qapp give the amended power reference
Ẑ valuesZKLFKDUHGH¿QHGDV
qv '
³ \
ª p app (k  1) º ª p (k  1)  K p H p (k ) º
SOGI
« » « »
«¬ q app (k  1) »¼ «¬ q (k  1)  K q H q (k ) »¼
(3)
ª 2 p (k )  p (k  1)  K p [ p (k )  p (k )]º
Figure 1. Frequency-adaptive VF observer based on a SOGI. « »
«¬ 2q (k )  q (k  1)  K q [q (k )  q (k )] »¼

Here, a frequency-adaptive VF observer (shown in Fig. 1)


is utilized, which is based on a second order generalized where K p , q are the delay compensation coefficients and H p , q
integrator (SOGI). As indicated in Fig. 1, the estimated grid are tracking errors. In (3  WKH ¿UVW 5+6 H[SUHVVLRQ p , q
frequency Ẑ is an explicit input, which can ensure the grid
represent the actual references, which are estimated using a
frequency-adaptive performance. A frequency-locked loop
(FLL) [16] is adopted in the following simulation verifications linear extrapolation. The second RHS expression, e.g. K p H p ,
to fulfill this estimation. There is another output of this is the delay compensation term.
observer q\ in addition to \ , which is in quadrature with \ ,
B. Power Analysis and Compensation Schemes During Grid
and can be utilized for sequence component extraction.
Faults
III. PRINCIPLE OF THE PROPOSED CONTROL STRATEGY For convenience, the following discussions are firstly
carried out under unbalanced grid voltages (without higher
Figure 2 shows the block scheme of the proposed strategy
harmonics). Then, the derived equations are generalized for
for distributed sources connected to the power grid, where
more general fault conditions.
L and R represent the inductance and resistance of the
interconnected reactor, SCEs and SVEs are short for sequence When the grid voltage is unbalanced, the VF vector can be
component extractions and state variable estimations expressed as [17], [18]
(including grid frequency, grid voltage and power estimations),  
respectively. \ \  \ \  e j ( Z t  M )  \  e j (  Z t M )
(4)
where \  and \  are the magnitude of positive and negative f
qc qq q  Z ¦ n (\ n i n  \  n i  n )
sequence VF , and M  , M  are their initial phase angles, n 1

respectively. f f (11)

Combining (1) and (4) gets


Z ¦ [sign(m)m\ ¦ i
m f
m
A
s f
s
]
szm

d d ª  j (Z t M  )
 \  e j (  Z t M ) º

f
v \ \ e
p  Z ¦ n(\ nA i n  \ A i  n )
n

dt dt ¬ ¼ pc p p
  n 1
jZ\  e j (Zt M )  jZ\  e j ( Zt M )
(5) f f (12)
ª \ E  \ E º
  Z ¦ [m\ ¦ i m s
]
Z«   »
m f s f
szm
¬ \D  \D ¼
where the subscript “ A ” indicates lagging by 90$ with
that is
respect to the original vector.
ª vˆD º ª \ E  \ E º When taking the positive sequence current operation as
«vˆ » Z«  »
. (6)
¬ E¼

¬ \D  \D ¼ control target, the negative sequence and higher harmonics of
FXUUHQWV VKRXOG EH HOLPLQDWHG ,Q WKLV VHQVH WKH ÀXFWXDWLQJ
Literature [19] points out that when the grid voltage is power generated by these current components will be null.
distorted, the instantaneous power can be expressed as Whereas, WKH UHVW ÀXFWXDWLQJ FRPSRQHQWV JHQHUDWHd by
positive sequence current are inevitable, and will be added to
ª pº ª p  p º the power references.
«q» « q  q » (7)
¬ ¼ ¬ ¼ f

where p and q denote the average parts of p and q ,


pc (vˆ  vˆ + )i  Z ¦ [sign(m)m\
m f
m
A ] i (13)
m z1
whereas p and q are their oscillating parts. Under
unbalanced grid voltages, they can be represented as f
qc (vˆA  vˆA )i  Z ¦ [m\ m
] i (14)
ª pº ª \ E

\E 
\D 
\D º ªiD º
  m f
m z1
« » «  »« »
« p» \ \ E \D \D » «iD »
Z « E . (8) IV. SIMULATION RESULTS
«q » « \D \D \ E \ E » «iE »
« » «  »« » The behavior of the proposed control strategy was
¬ q ¼ «¬ \D \D \ E \ E »¼ «¬iE »¼ simulated using MATLAB/Simulink and the toolbox
From [6], [8] we know that any combinations of the SimPowerSystems. The parameters of the circuit used for
requirements (involving FRQVWDQW DFWLYH SRZHU ÀRZ FRQVWDQW simulation are L 19.7 mH, R 0.67 : , Ts 333 P s and
UHDFWLYHSRZHUÀRZDQG positive sequence current operations) vDC 180 V. The pre-fault grid voltage is set to vL-L(RMS) 85
cannot be met at the same time. That is, a constant power Àow V, f 50 Hz.
will induce distorted line currents, meanwhile, the constant
active pRZHU ÀRZ DFFRPSDQLHV reactive power oscillations, Figure 3 gives the simulation results for VF estimations
and vice versa. based on SOGI-based and LPF-based observers when the grid
Therefore, to obtain the FRQVWDQW DFWLYH SRZHU ÀRZ i.e., frequency steps from 50 to 40 Hz (the grid voltage is
p 0 , the oscillating component q have to exist in the sinusoidal and balanced in this case). Where the LPF based
observer is the one proposed in [12], which realizes the phase
reactive power Àow. In other words, the oscillating component and amplitude compensations for WKH ¿UVW-order LPF [11] at
should serve as a compensation for the reactive power the fundamental frequency. As the Fig. 3 (b) reÀected, when
reference. the grid frequency is the rated value, i.e., 50 Hz, both of them
qc qq can realize accurate estimation. Nevertheless, after the step
. (9) occurrence, the LPF-based scheme introduces phase and
Z \D iD  \ E iE  \D iD  \D iD amplitude errors while the SOGI-based results are not
deteriorated.
Similarly,
To check the correctness of generalized compensation
pc p p principles descried by (11), (12), (13) and (14), the grid
. (10) voltage is simultaneously affected by the positive sequence
Z \ E iD  \D iE  \ E iD  \D iE
fault voltage v  0.747‘  14q pu, the negative sequence
Following the above compensation principles, the fault voltage v  0.163‘8.63q pu and the 5th order
generalized expressions of power compensations can be harmonic v 5 0.07‘  60q , which are set with respect to the
given as pre-fault voltage. In order to better reflect the compensation
effect, instantaneous active power and reactive power The simulation results of positive sequence current
waveforms showing in the simulation results are calculated operation are shown in Fig. 4. As observed in Fig. 4, the grid
based on the measured grid voltages rather than on the voltage is seriously distorted, while the line current is
estimated VF used in control strategy realization, which are sinusoidal, symmetrical and in inverse phase with the positive
marked by pv and qv . sequence voltage. Meanwhile, the instantaneous power flows
are fluctuated. Figure 5 (a) indicates that, when the
instantaneous active power reference is compensated by the
fluctuating component (12), the target of constant reactive
power flow operation is achieved successfully. Although the
line currents are unbalanced and distorted, it is still in inverse
phase with the positive sequence voltage. In contrast, in Fig. 5
(b), there are only ripples in reactive power flow, while the
active power flow is constant and smooth. The waveforms of
line currents are similar with those in Fig. 5 (a).

Figure 3. Comparative results between the SOGI-EDVHG DQG WKH ¿OWHU-based


VF observers against the grid frequency disturbance.

Figure 5. Simulation results under seriously distorted grid voltages for (a)
constant reactive power operation and (b) constant active power operation
with p 475 W and q 0 Var.

As Fig. 6 shown, a grid fault occurs at 0.5 s, which


consists of v  0.747‘  14q pu and v  0.163‘8.63q pu. At
the same instant, the grid frequency jumps from 50 to 40 Hz.
As reflected by Fig. 6 (a), with the active power compensation
activated, the target of constant reactivHSRZHUÀRZRSHUDWLRQ
is realized. The line currents are sinusoidal, asymmetrical and
in inverse phase with the positive sequence voltage. On the
contrary, in Fig. 6 (b), only the waveform of reactive power
Àow is fluctuating, whereas the active power curve is flat. The
Figure 4. Response of the proposed strategy for positive sequence current
operation in presence of higher harmonic and unbalanced voltage dip with
line currents are still sinusoidal, asymmetrical and in inverse
phase with the positive sequence voltage. Furthermore, in both
p 475 W and q 0 Var.
of the cases, the transient processes are short and smooth.
[1] F. Blaabjerg, Z. Chen, S. B. Kjaer, "Power electronics as efficient
interface in dispersed power generation systems," IEEE Trans. Power
Electron., vol. 19, pp. 1184-1194, Sep. 2004.
[2] The Grid Code, National Grid Electricity Transmission Std. London,
U.K., 2008. Available: http://www.nationalgrid.com/uk
[3] Standard for interconnecting distributed resources with electric power
systems, IEEE Std. 1547-2003, Sep. 2010.
[4] P. Rodríguez, A. V. Timbus, R. Teodorescu, M. Liserre, and F.
Blaabjerg, "Flexible active power control of distributed power
generation systems during grid faults," IEEE Transactions Ind.
Electron., vol. 54, pp. 2583-2592, Oct. 2007.
[5] F. Wang, J. L. Duarte,M. A. M. Hendrix, "Pliant active and reactive
power control for grid-interactive converters under unbalanced voltage
dips," IEEE Trans. Power Electron., vol. 26, pp. 1511-1521, May 2011.
[6] J. A. Suul, A. Luna, and P. Rodriguez, "Virtual-flux-based voltage-
sensor-less power control for unbalanced grid conditions," IEEE Trans.
power Electron., vol. 27, pp. 4071-4087, Sep. 2012.
[7] J. Hu, Z. Q. Zhu, "Investigation on switching patterns of direct power
control strategies for grid-connected DC–AC converters based on
power variation rates," IEEE Trans. Power Electron., vol. 26, pp. 3582-
3598, Dec. 2011.
[8] L. Shang, J. Hu, "Sliding-mode-based direct power control of grid-
connected wind-turbine-driven doubly fed induction generators under
unbalanced grid voltage conditions," IEEE Trans. Energy Convers.,
vol. 27, pp. 362-373, Jun.. 2012.
[9] J. A. Suul, and T. Undeland, " Impact of Virtual Flux reference frame
orientation on voltage source inverters in weak grids," in Proc. 2010
International Power Electronics Conf., pp. 368 - 375.
[10] M. Malinowski, M. P. Kazmierkowski, S. Hansen, F. Blaabjerg, and G.
D. Marques, "Virtual-Àux-based direct power control of three-phase
3:0 UHFWL¿HUV," IEEE Trans. Ind. Appt., vol. 37, pp. 1019–1026,
Jul./Aug. 2001.
Figure 6. Transient process under unbalanced grid voltages and frequency [11] M. Malinowski, M. JasiĔski, and M. P. Kazmierkowski, "Simple direct
step condition for (a) constant reactive power operation and (b) constant power control of three-phase PWM rectifier using space-vector
active power operation with p 475 W and q 0 Var. modulation (DPC-SVM)," IEEE Transactions Ind. Electron., vol. 51,
pp. 447-454, Apr. 2004.
[12] N. R. N. Idris, and A. H. M. Yatim, "An improved stator flux
V. CONCLUSION estimation in steady-state operation for direct torque control of
induction machines," IEEE Trans. Ind. Appl., vol. 38, pp. 110-116,
This paper has proposed a voltage sensorless PDPC for Jan./Feb. 2002.
DC/AC converters interfacing the DG systems with the utility [13] J. A. Suul, A. Luna, P.Rodríguez, and Tore Undeland, "Voltage-sensor-
network. In order to verify the feasibility of the proposed less synchronization to unbalanced grids by frequency-adaptive virtual
control scheme, simulation verifications have been carried out flux estimation," IEEE Trans. Ind. Electron., vol. 59, pp. 2910-2923,
Jul. 2012.
in MATLAB/Simulink under the following grid conditions: [14] A. Kulka, "Sensorless digital control of grid connected three phase
unbalance voltage dip, grid frequency deviation and higher converters for renewable sources," Ph.D. dissertation, Dept. of Electric
harmonic distortion. The simulation results indicate that the Power Eng., Norwegian Univ. Sci. Technol., Trondheim, Norway,
SOGI-based VF observer can estimate the VF accurately 2009.
independent of the grid frequency deviation; With power [15] Y. K. Tao, Q. H. Wu, L. Wang, and W. H. Tang, "voltage sensorless
predictive direct power control of three-phase PWM converters,"
references compensated by corresponding fluctuating power unpublished, accepted by IET Power Electron.
components, the DC/AC converter can realize positive [16] P. Rodríguez, A. Luna, R. S., et al., "A stationary reference frame grid
sequence current, constant active and reactive power synchronization system for three-phase grid-connected power
operations. In other words, the correctness of the derived converters under adverse grid conditions," IEEE Trans. Power
generalized compensation equations is demonstrated. Electron., vol. 27, pp. 99-112, Jan. 2012.
[17] V. Ignatova, P. Granjon, and S. Bacha, "Space vector method for
Moreover, the transient simulation results reflect that the voltage dips and swells analysis," IEEE Trans. Power Delivery, vol. 24,
proposed control strategy offers a short and smooth transient pp. 2054-2061, Oct. 2009.
process when the grid voltage is affected by unbalance voltage [18] M. Cichowlas, M. Malinowski, et al., "Active filtering function of
dip and grid frequency jump simultaneously. three-phase PWM boost rectifier under different line voltage
conditions," IEEE Trans. Ind. Electron., vol. 52, pp. 410-419, Apr.
2005.
REFERENCES [19] H. Akagi, E.H. Watanabe, and M. Aredes, Instantaneous power theory
and applications to power conditioning, Vol. 31. New York: John
Wiley & Sons, 2007, pp. 34-89.

You might also like