Troubleshooting
Not getting a Run signal
12/9/2011 Step by step guide
Step-1 : IN EMS PROGRAM
Confirm EMS Module for “Run Input” is communicating (IOM, 8IM, MINIO).
a) MINIO: Will need to check Module Directory if no loads to see if communicating.
b) 8IM: Will need to check Module Directory to see if communicating.
c) See examples above.
Step-2 : INSIDE EMS PANEL
a) Locate EMS Gen Run wires on ice cube relay inside Generator.
b) Wires must be connected to relay’s C & N/O spades.
Touch the EMS wires together.
(Common & N/O spades)
EMS wires on Gen run relay should have 24 vdc across the pair.
Touch the EMS wires together.
a) If 24vdc across wires: EMS should see a “Close”.
b) If no 24vdc present: possibly a break in wires or the wrong wires.
24 vdc wires from EMS panel
Coil wires
1. In EMS program:
Confirm EMS Module for “Run Input” is communicating (IOM, 8IM, MINIO).
a) MINIO: Will need to check Module Directory if no loads to see if communicating
b) 8IM: Will need to check Module Directory to see if communicating.
3. At the Generator:
a) Locate this pair of wires inside Generator.
b) Wires must be connected to Gen run ice cube relay on C & N/O spades.
4. At the Generator:
EMS wires on Gen run relay typically have 24 vdc across the pair.
Touch the EMS wires together.
a) If 24vdc across wires: EMS should see a “Close”.
b) If no 24vdc present: possibly a break in wires or the wrong wires.