Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019

Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
127186 Aynor Closed Work Orders not sure what dept to put this under, but there is black mold on the walls outside the 2/9/2015 court yard Painting 8/10/2015
Elementary - building in courtyard. Needs to be cleaned off
0014
128472 Academy for Closed Work Orders iIt seems that a bad order or a mildew smell goes over classrooms 3/2/2015 (507)-(508)- Heating/Ven CHECKED CLASSROOM UNITS. CHECKED MAU. CHCKED DUCTWORK. 3/3/2015
Arts Science at certain times when air condition kick"s on Time Available: anytime (517) tilation /Air CLEANED EVAP COILS ON CLASSROOM UNITS. CLEANED DRAINS. REPLACED
and Tech. - Conditioning FILTERS IN MAU. DID NOT FIND ANYTHING THAT WOULD DEFINITELLY BE
0096 CAUSING A BAD ODOR. SPOKE WITH A.P.

128587 Ocean Bay Closed Work Orders Check Air Quality, check all vents, filters etc and anything else you can think of. 3/4/2015 Heating/Ven CHECKED UNIT OPERATION. FOUND UNIT WAS SLIGHTLY FROZEN OVER. 3/18/2015
Middle - 0061 tilation /Air REPLACED DIRTY AIR FILTER. CLEANED EVAPORATOR COIL. CLEANED INSIDE
Conditioning BLOWER COMPARTMENT.ORDERED NEW DEFROST CONTROL AND DEFROST
SENSOR. CHECKED DEFROST OPERATION. UNIT OPERATING PROPERLY.

128960 Burgess Closed Work Orders The cafeteria is very warm and humid. The thermostats show 72 degrees but it 3/11/2015 cafeteria Climate checked found both stages locked out, reset stage 1 tripped on low pressure switch , 3/13/2015
Elementary - clearly is not. Nearby rooms that show 74 are much cooler than the cafeteria. The Control leak at discharge shredder valve ,repaired added 2 # r-22, stage #2 to reset ,checked
0063 room was the same yesterday and we had a lot of complaints. Time Available: any pressures ok, spoke to Donald, rechecked that next day ok

128996 Waccamaw Closed Work Orders hp 72 it is very hot humid temp is 74.5 3/11/2015 311 Heating/Ven CHECKED UNIT OPERATION. UNIT IS OPERATING PROPERLY. UNIT FAN WAS 3/18/2015
Elementary - tilation /Air SET TO RUN CONTINUOSLY. THIS CAUSES HUMIDITY/COOLING ISSUES WITH
0042 Conditioning THESE UNITS IN THE NEW WING. THE UNIT DOES NOT KEEP UP WITH THE
AMOUNT OF OUTSIDE AIR IT BRINGS IN WITH FAN RUNNING CONTINUOUSLY.
SET FANS BACK TO CYCLE.
129021 Ocean Bay Closed Work Orders Very humid in room compared to other rooms in hall. No air circulation. Please 3/11/2015 Room 716 Heating/Ven checked unit and pressure ok lower fan speed to low. will come back on Tuesday. 3/12/2015
Middle - 0061 check out and see Mike Thanks Time Available: anytime tilation /Air
Conditioning

129094 St. James Closed Work Orders Please inspect room for termite infestation. Also check room for mold issues. Time 3/12/2015 D-Wing Room - Pest Control 8/29/16- Liquid Treatment tentatively scheduled for 2018-19.tjt....3/17 inspected and 8/29/2016
Middle - 0047 Available: Immediate D-7 Indoors documented, Spot Treatment Completed

129141 Waccamaw Closed Work Orders RM 213 - NEW DEHUMIDIFIER IS NOT WORKING 3/13/2015 RM 213 Heating/Ven CHECKED UNIT OPERATION. BUTTONS ON CONTROL PANEL ARE NOT 3/18/2015
Elementary - HOWELL tilation /Air OPERATING. WILL REPLACE UNIT AND TRY TO RETURN MALFUNTIONING UNIT
0042 Conditioning UNDER 1 YEAR WARRANTY.

129257 Seaside Closed Work Orders The dehumidifier is not functioning properly. It does not shut off when full and has 3/16/2015 412 Heating/Ven Went and found night time custodian to help me locate the Dehumidifier that was in 3/20/2015
Elementary - overflowed onto the carpet twice in the last 2 weeks. Time Available: any tilation /Air room 412 when we located it I started checking to see why it was leaking water. There
0050 Conditioning is a drain pan that goes in the unit to catch the water coming out of the unit,but there is
also a plastic float that goes into the drain pan also. The float was not going into the
drain pan like it was suppose to which made the unit continue to run without cutting off
and that is where the water was coming from,I took time to show night time custodian
on how to install drain pan properly so this does not happen again in the future.

129279 Waccamaw Closed Work Orders check humid.paint is peeling off wall smell very bad musty smell 3/16/2015 201 Heating/Ven CHECKED UNIT OPERATION. UNIT IS OPERATING PROPERLY. WILL INSPECT 4/30/2015
Elementary - tilation /Air INSIDE UNIT AND ABOVE CEILING. CLEANED UNIT DRAIN AND DRAIN PAN.
0042 Conditioning UNIT IS OPERATING PROPERLY. CAUSE OF PAINT PEELING APPEAR TO BE
POSSIBLY WATER OR MOISTURE COMING THROUGH OUTSIDE WALL AND/OR
ROOF-WALL JOINT.
129296 Conway Middle - Closed Work Orders Request that air ventilation system be checked for good air quality, concern of mold. 3/17/2015 media center Heating/Ven Checked both units that serve media center. Checked and replaced filters in both units 3/18/2015
0017 Time Available: any tilation /Air also checked supply and return ducts for any signs of excessive moisture. No moisture
Conditioning was found in air ducts. Put unit fans on cycle to cut down on outdoor air entering space.
Space temp was 73-74 degrees and Relative humidity was 40-45%.

Page 1 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
129335 Aynor Closed Work Orders There is black mold on several areas around the exterior of the building that needs 3/17/2015 building Roof We will be using work order 127186 to complete this work. 3/17/2015
Elementary - to be pressure washed. Time Available: 7-6 exterior
0014
129390 Lakewood Closed Work Orders Classroom is hot/humid temp reads 76. 3/18/2015 814 (Lane) Heating/Ven checked found indoor blower motor seized, removed and replaced capacitor ,motor , 3/19/2015
Elementary - tilation /Air checked unit operation , ordered replacement motor, left message for Pauline
0029 Conditioning

129650 Ocean Drive Closed Work Orders The metal panel that is screwed on to the outside bottom of the walk in freezer door 3/23/2015 Cafeteria Heating/Ven 3-25-15 attached diamond plating to door and reseal all around edges to prevent 3/25/2015
Elementary - has lost it's seal and is growing mildew around and behind it. Time Available: any tilation /Air moisture from getting behind plating.
0066 Conditioning

130200 Conway Closed Work Orders the gym is very humid.....the thermostat is reading 73 please check out. thanks! 4/7/2015 gym Heating/Ven Checked space temperature normal maintaining setpoint. Spoke to gym teacher and 5/4/2015
Elementary - Time Available: 7-4 tilation /Air she stated everything has been fine. It was humid earlier when it first got warm outside.
0036 Conditioning

130256 Loris Elementary Closed Work Orders Teacher complains about the temp and quality of air in the room. Could be a 4/8/2015 319 Heating/Ven 4-8 Checked all rooms on 300 hall all rooms 71 to 73 degrees checked mau changed 4/8/2015
- 0032 problem with humidity. She reported seeing mold on a wall before. tilation /Air belts and grease bearings on mau. ran and watched operation everything checked ok
Conditioning per Ross

130380 North Myrtle Closed Work Orders Mold on a tile in the book room in room 402 Time Available: 7:30 4/9/2015 402 Heating/Ven 4-23-15 Markie the head custodian took care this. 4/23/2015
Beach Middle - tilation /Air
0037 Conditioning

130496 Waccamaw Closed Work Orders hp69 their is no number showing on the control panel very hot room 305 , hp 71 very 4/10/2015 room 305/309 Heating/Ven CHECKED UNITS OPERATION. ROOM 309 HAD COMMUNICATIONS ERROR. 4/14/2015
Elementary - hot and humid 77.3 degrees room 309 tilation /Air RESET UNIT AND CONTROLLER. ROOM 305 UNIT HAD BAD DISPLAY ON ROOM
0042 Conditioning SENSOR. REPLACED SENSOR. BOT UNITS OPERATING PROPERLY.

130689 Seaside Closed Work Orders Room 402 the thermostat reads 76 degrees and the override will not come on when 4/14/2015 402, 112 Heating/Ven checked rm 403 checked rm temp 73 , checked unit operation , pressures and temps 4/15/2015
Elementary - pushed, it is very warm and humid in there. Also room 112 there is no air in her tilation /Air ok, Teacher said it did not work yesterday , rm 112 cleaned condensate drain line p-
0050 room and the thermostat doesn't register any temperature on it...it's blank Time Conditioning trap ,emptied EM pan , replaced clogged filter ( Dated NOV 2 2014) checked unit
Available: any operation, spoke to Gary

130697 Myrtle Beach Closed Work Orders Ac unit not putting out like it should teacher says it feels humid and muggy in her 4/14/2015 A207 Heating/Ven no problem found , unit working fine. 4/15/2015
High - 0010 classroom. tilation /Air
Conditioning

130714 Lakewood Closed Work Orders HPO55, check humidity level. 4/14/2015 504 Heating/Ven checked in nite mode , 73.8 turned unit on checked unit operation good, rm humidity 4/15/2015
Elementary - tilation /Air 58% checked other room between 56-60% spoke to rm teacher and Pauline
0029 Conditioning

130732 Loris Elementary Closed Work Orders Room 806, this classroom has a musky, mold and mildew smell. Can someone 4/15/2015 Room 806 Heating/Ven 4-16 Checked found no problem. Mr. Morris checked said no smell present at this time. 4/16/2015
- 0032 please check this. If you have any questions, please call me tilation /Air room temp 72
Conditioning

Page 2 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
130835 Aynor Middle - Closed Work Orders Oak tree at front walkway - Has fungus that needs spraying. This is the tree that we 4/16/2015 Front lawn at Tree 4/21/15. R.E. Sprayed the trees and then some ant hills. 4/21/2015
0057 thought might be dead. However; it is putting out green leaves all over. But a entrance Services This isn't a fungus. This is actually an insect. Please spray with bifen I/t.
couple of people have noticed a black moldy fungus on it. Can we get someone walkway
here to look at it as soon as possible. Wondering if this is also fungus that has
killed so many other trees and shrubs here. Time Available: asap

130982 Carolina Forest Closed Work Orders Back rooms B 111 Thur B 120 Very humid. 4/20/2015 B House Heating/Ven VERIFIED CLASSROOM UNITS ARE WORKING PROPERLY. FOUND ISSUES 4/21/2015
High - 0052 tilation /Air WITH MAU. WILL CREATE SEPARATE W.O. TO REPAIR. MAU.
Conditioning

131029 Loris Elementary Closed Work Orders Teachers says temp says 73 says hot air is blowing out of vent and feels very 4/20/2015 608 Heating/Ven 4-21 Checked found room 71.4 degrees. teacher said room stuffy. Cycled fan to run all 4/21/2015
- 0032 humid. Nothing will stick to walls. tilation /Air the time per Morris fowler
Conditioning

131071 District Office Closed Work Orders Could you have someone check on the air quality in the Budget/Accounts Payable 4/21/2015 Heating/Ven 4-22-15 Check room temp and humidity at 7:00am. Was 72 degrees and 42% humidity. 4/23/2015
Four Mile Road - area? The ladies state that the air is somewhat humid. We currently run a tilation /Air Rechecked at 12:00 and room temp was 73.5 and humidity was 39%. 4-23-15
0401 dehumidifier which must be emptied several times a day. Please have them see Conditioning Checked at 7:00am and room temp was 74.5 and humidity was 41%. 4-24-15
Chrystal. Checked at 7:00am and room temp was 73 degrees and humidity was 42% Checked
accuracy of room temp and humidity sensor. They are correct. Check unit and drain
operation. Tested OK. Checked at 12:00 Temp. is 73.8 and humidity was 40%.Did find
day cooling set point at 74 and day heating set point at 73. Set day cooling to 73 and
day heating to 70 to match the rest of the building. This should help with the problem of
feeling humid in room.

131137 Conway High - Closed Work Orders the inside of my ice machine needs to be cleaned. there is mold on the inside. thank 4/22/2015 kitchen Refrigeration Cleaned and sanitized ice machine. While restarting machine found water curtain 5/2/2015
0004 you in advance magnet assembly was broken. Ordered new replacement will install first thing this
morning. Replaced water curtain and put unit into operation. observing unit to make
sure it is making ice. Left machine with half full ice bin.

131250 Conway High - Closed Work Orders MR. MCCANTS NEEDS TO HAVE 5 CHAIRS, 2 TEACHER CHAIRS, 8 STOOLS, 4/24/2015 CUSTODIAN Pick Up 5/14/2015
0004 2 DESK AND 1 DEHUMIDIFER TO BE PICKED UP FOR DISPOSAL. Time
Available: 7:00 AM
131541 Daisy Closed Work Orders Very strong mildew odor in the hallway of the 3-5 grade wing. 4/29/2015 3-5 Wing Heating/Ven Doing work on wo#131861 per Ross 5/5/2015
Elementary - tilation /Air
0021 Conditioning

131569 Seaside Closed Work Orders The carpet in 413 needs to be replaced; several years ago there was a septic 4/30/2015 413 Space Scheduled for the summer to be replaced 7/23/2015
Elementary - backup and water flooded the carpet. Mold and mildew in the area is a concern. Managemen
0050 Room 413 is needed as a classroom so carpet needs to be removed / replaced. t
Time Available: June
131592 Academy for Closed Work Orders Temps seems ok at 73 but teacher says mornings have been cold & just gets 4/30/2015 B-205 Heating/Ven 4-30-15 Check room temp. 72.5. Set cooling min flow CFM up to help with room 4/30/2015
Tech and stuffy/humid in afternoon. Please check. Time Available: 7:30 - 4:30 tilation /Air humidity. Changed from 20 to 200.
Academics - Conditioning
0098

131861 Daisy Closed Work Orders There is a musty mold smell that starts from the library that leads though out the 800 5/4/2015 Media Heating/Ven 7-6 Checked halls and rooms for smell. checked mau its running. All rooms on this end 7/6/2015
Elementary - hallway. The smell is very malodorous. Time Available: URGENT Center/800 tilation /Air up to correct temps. No smell at this time. Per Ross
0021 hallway Conditioning

Page 3 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
132265 Seaside Closed Work Orders The Library is requesting an extra floor unit air purifier/de-humidifier for one of their 5/11/2015 Media Center Heating/Ven I have ordered an AIR PURIFER from HCS warehouse when it comes in I will deliver. 5/21/2015
Elementary - rooms Time Available: any tilation /Air Delivered Air Purifer to school, installed both new filters.
0050 Conditioning

132274 St. James Closed Work Orders Hot and humid today in room C10. Last week it kicked on every day in the 5/11/2015 C 10 Heating/Ven Greg looked at unit , cleaned condensate pan 5/12/2015
Middle - 0047 afternoon for about an hour. The fan runs but no AC. tilation /Air
Conditioning

132275 Myrtle Beach Closed Work Orders Keep having a recurring problem in this room where its very hot and humid feeling in 5/11/2015 A207 Heating/Ven I don't see any thing wrong with system. 5/12/2015
High - 0010 the morning time. Please check to make sure unit is running and doing what its tilation /Air
supposed to do. Conditioning

132321 St. James Closed Work Orders Can you please put in a work order for them to fix the AC in my room? I am dying of 5/11/2015 Orchestra Heating/Ven checked found burned wiring, compressor contactor seized, swelled compressor 5/22/2015
Middle - 0047 heat in my room and so are the students. Also I am having to spend money to fix Room tilation /Air capacitor, repaired wiring ,replaced contactor, capacitor , hard start kit , also found no
instruments that are cracking due to humidity. Conditioning schedule in programed , called Eric form CMI , he put program in , checked unit op
,spoke to Jeff

132386 Early College - Closed Work Orders Very humid in this room Time Available: 6:30-5:00 5/12/2015 Room 221 Heating/Ven checked today rm temp 73 humidity 56% , I fixed MAU#2 today may have caused 5/13/2015
0074 tilation /Air promlem
Conditioning

132461 Conway Middle - Closed Work Orders Teacher request for a dehumidifier for protection of instruments, very humid in 5/12/2015 B103/Orchestr Heating/Ven Checked room found a dehumidifier already operating in room. HP unit was not 5/13/2015
0017 room although temp gauge reads normal cooling temp. Time Available: Asap a room tilation /Air operating. Checked unit TEC control setting and made several adjustments to help
Conditioning dehumidify room. Left unit operating normally.

132464 Pee Dee Closed Work Orders Room is smoldering HOT..please check air. 5/12/2015 413 Heating/Ven Checked out and found filter dirty, coil dirty, low charge. Changed filter, cleaned coil, 5/15/2015
Elementary - tilation /Air and charged up. (leak on schraeder valve- tighten). Operated unit running normally at
0039 Conditioning this time.

132669 River Oaks Closed Work Orders rOOM 609 has sprung a leak, soaked through ceiling tile. not sure if it is humidity or 5/15/2015 609 Roof CHECKED ABOVED CEILING. FOUND A ROOF NAIL PUNCTURE DRIPPING 5/19/2015
Elementary - leak from a/c. WATER DOWN ON TILES. WILL HAVE NEW W.O. MADE FOR ROOFERS TO
0065 REPAIR.( AWG 5/21/15) checked out seems to be condensation was not raining at
Time Available: any time checked. When quits leaking please change tiles.
132926 Carolina Forest Closed Work Orders B 119 Very Humid , The room is hoter then the rooms around it. 5/20/2015 B House Heating/Ven CHCKED UNIT OPERATION. UNIT OPERATING PROPERLY. TEACHER HAS HAD 5/20/2015
High - 0052 tilation /Air WINDOW OPEN ALL DAY FOR THE PAST TWO WEEKS. UNIT CANNOT
Conditioning OPERATE PROPERLY WITH WINDOW OPEN.

132931 Carolina Forest Closed Work Orders C House Ass Principal Pisaniello's Office and SRO Gasque's office has humid 5/20/2015 C House Heating/Ven CHECKED UNITSOPERATION. UNIT OPERATING PROPERLY. REPAIRED ISSUE 6/10/2015
High - 0052 air/heat and system is loud later in day. tilation /Air WITH MAU.
Conditioning

133311 District Office Closed Work Orders The thermostat in C300 is reading 72.3 but it's really humid in the room. They are 5/27/2015 Switchboard Heating/Ven 5-27-15 Check room. Set units down to compensate for feeling humid. Will set back up 5/27/2015
Four Mile Road - having a meeting right now. tilation /Air after meeting
0401 Conditioning

Page 4 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
133336 Conway Closed Work Orders Please put in a work order for room 109 on the TLC Hallway. There is a smell in 5/27/2015 Room 109 Heating/Ven Checked room for odor and found none. Units operating normally. 6/10/2015
Education there that has been there for a while and Debra and the nurse has tried to find what TLC Hall tilation /Air
Center - 0172 might be causing it but are unable to locate it. I thought maybe you could put it Conditioning
under air quality and see if they can find anything. Time Available: Asap

133359 Myrtle Beach Closed Work Orders room thermometer says correct set temp but training room feels very humid in there. 5/27/2015 PE 114 Heating/Ven drain stopped up .. cleared drain and line. 5/28/2015
High - 0010 Thermometer is located in a office off the training room. Please check to make sure tilation /Air
it is working correctly to get rid of humidity in the training room area. Conditioning

133360 Myrtle Beach Closed Work Orders Very humid and hot feeling in front lobby bathrooms. A/C ducts present in both 5/27/2015 front lobby Heating/Ven there is no a/c in the rest rooms.. the vents are fresh air.. and exhaust.. 5/28/2015
High - 0010 bathrooms but does not feel like any cold air is coming out of them. Please check to gang tilation /Air
see if we have a problem in these bathrooms. bathrooms Conditioning
boys and girls

133387 District Office Closed Work Orders Wayne, RTU11B does not appear to be working on first stage cooling. The room 5/28/2015 C300 Heating/Ven 6-4-15 Check RTU 11b and found free cooling not working properly. Disable free 6/4/2015
Four Mile Road - is reading humid, not sure if completely accurate, but there are complaints. Can tilation /Air cooling. This unit is biggest unit. Recommend letting other two units be set at 73 and
0401 you check 11B out today. I have made some control changes to the other 2 units Conditioning 11B set at 74 to help with humidity control.
12B and 16B to reduce humidity a few minutes ago. Call me about things when
you get there.
133630 Myrtle Beach Closed Work Orders Still very humid feeling in this athletic sports medicine room according to staff in 6/1/2015 PE 114 Heating/Ven temp is 70 degrees in room and 71 degrees. office area. I cleaned out drain line and 6/2/2015
High - 0010 there please check to see if we have a recurring problem in that room. tilation /Air also the pan.. these units are working ..this does not feel humid with door closed.. I will
Conditioning come back and check the humidity ..

133891 Whittemore Closed Work Orders Need science counters removed in the front of the room to improve mildew smell 6/5/2015 116 and 118 Carpentry Checked this and these cabinets do not have any scent coming from them. Met with 8/25/2015
Park Middle - Time Available: any principal and she decided that now was not the time to remove these cabinets. This is
0013 possibly a building modification and will need approval from new construction. Talked
with Joe about this and we don't need to remove cabinets we need to find out what's
causing ordors.
133953 Forestbrook Closed Work Orders The dehumidifier is not working again. This has continued to be an issue all year. 6/5/2015 808 (Bourque) Heating/Ven Dean and helper washed evaporator , pan, drain line blower compartment, I helped 6/15/2015
Middle - 0051 Rooms 808 and 810 are hot, humid and smell like cat urine. The hall custodian can tilation /Air worked on Mau#7 found starter tripped ,#2 heater bad caused by shorted wiring
attest to this; she notices it each day she comes in to clean. Conditioning between starter and motor removed wiring bundle , Gary supplied wiring , replaced
wiring, heater , checked unit operation ,also found main office unit room sensor blank ,
cleaned clogged drain line , removed water from EM pan ,checked unit operation,
spoke to Moses and April

133990 Pee Dee Closed Work Orders Please check this room for dead mice and or dusty mold smells. 6/5/2015 206 Pest Control 6/8 checked all around room and up in ceiling. No mice, pests or mold found 6/9/2015
Elementary - Indoors
0039
134003 Whittemore Closed Work Orders EMERGENCY - Mold/Mildew found growing on classroom wall. Please remove, 6/7/2015 140 Painting The mold and mildew been wiped off wall. Been checked for water source and painted 6/30/2015
Park Middle - check for water source and paint classroom wall. Time Available: any
0013
134078 Conway Closed Work Orders There is a strong odor of mildew in the classroom. This was reported earlier in the 6/8/2015 Rm 110 Climate Checked room and found no signs of visible signs of mold on equipment or duct work. 7/23/2015
Elementary - year, but the problem has gotten worse. Control
0036 The room is on the 3rd grade hall (Mrs. Mileur).
134237 St. James Complete Some of the ceiling tiles need replaced since they have lots of mold 6/9/2015 D3 Custodial complete 9/24/2015
Middle - 0047

134240 St. James Complete Portable needs pressure washed to remove mold, mildew, and bugs that are stuck 6/9/2015 Portable 248 Custodial cleaned areas requested 8/24/2015
Middle - 0047

134268 Loris Middle - Closed Work Orders Please paint over mold on back wall. A leak was repaired last school year, but the 6/9/2015 606 Carpentry Already been done. 9/3/2015
0027 residue is still visible. I am unsure if the mold is actively growing. Time Available:
730-5

Page 5 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
134270 Loris Middle - Closed Work Orders Please check a/c in roon 614. The teacher stated the temp and humidity was high 6/9/2015 614 Heating/Ven 6-11 Checked room 614 found unit 73 degrees. unit was blowing out 59 degree out 6/11/2015
0027 the last few days of school. Time Available: 730-5 tilation /Air vent unit working good per Ross
Conditioning

134335 River Oaks Closed Work Orders Room 401A - HP-05 running 75 degrees and up 6/10/2015 several Heating/Ven CHECKED UNITS OPERATION. REPAIRED LEAKS ADDED FREON. UNITS 6/23/2015
Elementary - 401 work room very hot no circulation, no Thermostat in this room. tilation /Air OPERATING PROPERLY. LOWERED TEMP SETPOINT ON FRONT OFFICE UNIT.
0065 Front Office is very humid through out and workroom (110) does not have Conditioning
circulation either. No thermostat

400 hall(409 and down) Very humid as well, several of the rooms are running
warmer than what thermostats are saying. See Shannon when you come by please.
Time Available: any
134372 River Oaks Closed Work Orders Need Media Center A/C consistently running during the summer at the district- 6/10/2015 101 Heating/Ven MEDIA CENTER UNITS AND MAU NOW RUNNING CONTINOUSLY. 6/25/2015
Elementary - approved temperature. As of 2:30pm today, 6/10/15, HP-43 read 76.2 and HP-44 tilation /Air
0065 read 76.4. Media Center must be kept cooler in order to prevent mold formation on Conditioning
the books that are on the shelves during the summer. Override function did not
work. If questions, contact David Bell Time Available: 7am-4pm

134398 Conway High - Closed Work Orders ASST PRINCIPAL TANIKA MCCKISSICK'S OFFICE DOWNSTAIRS IN C 6/11/2015 C BUILDING Painting work completed on work order 134313 6/24/2015
0004 BUILDING NEEDS TO BE PAINTED. MILDEW FOUND BEHIND THE DRY ASST.
ERASE BOARD WALL NEEDS PAINTING AND HOLE PATCHING. Time PRINCIPALS
Available: 7:00 AM OFFICE
134520 Ocean Bay Closed Work Orders in RM 315 the air conditioner is not coming on the room temp is 79 deg. to humid to 6/15/2015 RM 315 Climate replace motor and moude for blower motor. 6/22/2015
Elementary - finish floors in this room. Time Available: ASAP Control
0060
134656 Myrtle Beach Closed Work Orders HP 32 is two stage, stage 1 cooling does not appear to be working, room humidity is 6/17/2015 Media center Heating/Ven I didn't find anything wrong at this time. 6/22/2015
Primary - 0035 high. tilation /Air
Conditioning

134668 Conway Closed Work Orders Natasha has asked that a work order be submitted to have all of the TLC 6/18/2015 TLC Heating/Ven Cleaned all filters and dumped all water out of dehumidifiers. Also cleaned all return 1/19/2016
Education dehumidifiers and all of the HVAC ducts thoroughly cleaned please. Time Available: tilation /Air registors and changed filters inside of unit.
Center - 0172 Asap Conditioning

134876 River Oaks Closed Work Orders Room 512 PE Office- has a mildew smell in it and wall on stage as well, ceiling tiles 6/23/2015 401a/504/512 Heating/Ven CHECKED UNITS OPERSTION. FOUND UNIT LOW ON FREON. ADDED FREON 6/25/2015
Elementary - look like they may have had water damage possibly condensation from A/C? tilation /Air AND CHECKED FOR LEAK. UNIT OPERATING PROPERLY. MISS SHANNANGELO
0065 Conditioning PLEASE MAKE A NEW WORK ORDER FOR P.E. OFFICE AS ROOF LEAK.
Room 401A- HP-05 running 77.8
Room 504 - HP-61 running 77 degrees Time Available: any

135117 Green Sea Closed Work Orders Ceiling tiles stained. Smell of mildew in the room. 6/29/2015 414 Heating/Ven 7-2 Checked room 414 for bad tile and smell. Didn't find either. Got with Larry Gore and 7/2/2015
Floyds High - tilation /Air he walked and checked with me. room 73 degrees. Per Ross
0006 Conditioning

135160 Forestbrook Closed Work Orders Mold in boys locker room and gym area. Cleaned off by custodians needs to check 6/29/2015 Boys Locker Heating/Ven checked locker ac ok . VAU #9 had no r-22 in system ,pressurized with N2 , searched 7/1/2015
Middle - 0051 air conditioning system in the boys locker room area. See Ronnie Moses for Room side tilation /Air in air handler, condensing unit , found under condenser discharge line ,disassembled
questions. gym Conditioning ,repaired line, pressure tested ,evacuated to 750 microns ,charged 13# r-22 , also
replaced bad room sensor in girls locker room , rplaced air filters in VAU #8,9 7-2
checked unit operation spoke to Moses

135175 River Oaks Closed Work Orders Room 513 (PE Office) has a mildew smell to it, some tiles in back corner look like 6/30/2015 513 Roof If not wet at this time please change tiles. If leaking when raining send in another WO . 7/6/2015
Elementary - they have had water damage in the past. Time Available: any I have a WO for a leak I will check when there.
0065

Page 6 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
136397 Waccamaw Closed Work Orders rm 316 - electrical out (wiring mold) making intermittent buzzing noise. Teacher 7/9/2015 rm 316 behind Electrical The Circuit that goes to this wire is the Pepsi Machine compressor going out is 7/13/2015
Elementary - marked with sticky note. teacher work causing the problem. So I put it on another Circuit that is self problem solved Pepsi
0042 room/lounge needs to be called .

136505 Myrtle Beach Complete Possible mold on walls near ceiling in mini gym. Investigate and clean if needed. 7/13/2015 mini gym Carpentry Needs to go to custodian 7/23/2015
High - 0010

136645 Whittemore Closed Work Orders Leak in corner of orchestra closet. Paint is peeling off the wall due to leak causing 7/15/2015 129 Roof Patched roof with m1 caulk replaced ceiling tiles . Cleaned and reprinted wall . 8/17/2015
Park Middle - mold. Time Available: any
0013
136826 Early College - Closed Work Orders Replace Siemens humidity sensor room 221. This is the new style humidity sensor. 7/20/2015 Room 221 Heating/Ven checked got model # of sensor Siemens QPA2062 cost around 456.00 did not have to 7/27/2015
0074 Please give sensor removed to Dennis. tilation /Air order Dennis corrected problem rm 221 is a 90,000btu unit
Conditioning

136892 Carolina Forest Closed Work Orders Due to the fire marshall's directions to take down all curtains the school must have 7/21/2015 CFHS Carpentry Pee Dee Fire and Safety are going to spray curtains 8/3/2015
High - 0052 blinds installed in the windows. The students are unable to see the computer
screens due to sun's reflection. Air quality is affected due to the sun shining in
windows all day. HVAC units will not be able to keep the rooms cool during the hot
montrhs.
136919 Loris Elementary Closed Work Orders Hot and humid 7/21/2015 319 Heating/Ven 7-28 checked found bad compressor in unit ordered from trane at beach.7-29 Picked 7/29/2015
- 0032 tilation /Air up compressor put new in and took old out put new drier in and pulled vacuum on unit.
Conditioning added 6lbs of R22 to unit. unit cooling at this time per Ross

137197 Seaside Closed Work Orders The insulation that was wet and tore that is attached to the inside of the roof is 7/27/2015 200 Roof Part of the roof insulation had been filling up with water from a roof leak. It finally busted 7/29/2015
Elementary - starting to mold and smells really bad. There may be other insulation pieces that and put water all over the floor and the insulation that was laying on top of the drop
0050 have gotten wet and may need to be replaced as this is a slanted section of the roof ceiling. Removed old wet insulation. Replaced with new instillation. Cut and put back
and the insulation in question is near the bottom, leading me to believe that the new ceiling tile. Went on roof and inspected for a roof leak. Found two holes where
water may have run down and through adjacent pieces which may be getting moldy screws were missing right over the leak area. It was a slow leak that had filled the
as well. Time Available: any insulation over time. Replace screws and caulked around them with green solar seal.

137202 Waccamaw Closed Work Orders RM 201 - MUSKY SMELL - ALSO BLACK MOLD ON WALLS. PAINT IS PEELING 7/27/2015 RM 201 Climate roof leak .. Artie is going to have the roofer to check problem.(AWG)7/29/15 came put 7/29/2015
Elementary - ON THESE WALLS AND THINGS WILL NOT STAY ON THE WALL BECAUSE OF Control dehumidifier in rm. run water on roof at corner found a leak. Caulked with M-1 to seal .
0042 MOISTURE. Time Available: URGENT Didn't have very much water in humidifier. Had HVAC unit turned off . Will leave
humidifier running a few days to completely dry room . Will come back next week run
water again try find if leaking anywhere along wall. Smell still strong in room after
humidifier ran all day.

137358 North Myrtle Closed Work Orders temp reading 77 mold growing Time Available: 7:00 am 7/30/2015 rm 803 Heating/Ven 7-30-15 Check unit. Found out of R-22. Repair leak and gas unit. 6lbs R-22. 7/30/2015
Beach Middle - tilation /Air
0037 Conditioning

137402 North Myrtle Closed Work Orders Gutter leaking at entryway to 7th grade hall, causing mold and mildew on the wall. 7/31/2015 custodial Roof Checked today need to go back and rework gutter joints caulked joints in gutter with 3/2/2016
Beach Middle - Time Available: 7:30 office blue solor seal 900
0037
137565 Conway High - Complete MS. JACOBS SAID THERE IS MOLD ON THE CEILING IN THE CLASSROOM 8/3/2015 AG SCIENCE Custodial 10/11/2015
0004 AREA AND IT IS GETTING WORSE AROUND THE VENTS. Time Available: SHOP
ASAP
137602 Lakewood Closed Work Orders One of the walls in room 404 is covered with mold and it appears it needs to be 8/3/2015 404 Carpentry Cleaned walls, they had hot glue and tape residue all over the entire wall, paint was 8/12/2015
Elementary - painted. Time Available: immediately peeling in some spots as well, painted entire wall.
0029

Page 7 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
137657 North Myrtle Closed Work Orders Large mold spot on carpet in guidance conference room. Needs immediate 8/4/2015 Guidance Heating/Ven 8-19-15 Checked and talked with Markie. No water leak from above. Came to 8/19/2015
Beach Middle - attention. Time Available: 7:30 office tilation /Air conclusion that someone sat something wet on carpet and left it. Markie had already
0037 Conditioning cleaned carpet.

137752 Conway High - Complete There is mold inside of the bookshelves and on the floor tiles. It is behind the 8/5/2015 V1 DRAMA Custodial 10/11/2015
0004 shelves and on the brick walls. Time Available: 7:00 AM ROOM

137800 Forestbrook Closed Work Orders 808 and 810 ongoing issues with air-conditioning not working correctly. The 8/6/2015 808 and 810 Heating/Ven I went and checked the rooms on 8/6/15 I put my gagues on the units the pressure was 8/12/2015
Middle - 0051 teachers complain that it does not work consistently. The items on the walls fall tilation /Air good the condersore was good and the evaporator was good I went back and
because of the humidity changes. See the teacher Stone, Bourque or Mr. Ronnie Conditioning rechecked the units on 8/12/15 everything was still working good
Moses for any questions.

137954 Myrtle Beach Closed Work Orders paint were mold is on wall Time Available: asap 8/10/2015 room 706 Painting 8/11/15, inspected rooms 706 & 708. Walls show small signs of mildew due to rooms 8/11/2015
Middle (old) - being closed up all summer. There was no mold found. Will get some cleaner and
0016x clean walls. Walls in rooms 702, 704, 706, 708. The hvac dept also checked and
cleaned the inside of the a/c units .. vacuumed out inside and cleaned coils with coil
cleaner . no sign of any MOLD .. only DUST..

137998 Lakewood Closed Work Orders This room obviously has had some water damage over the summer. The floor tiles 8/10/2015 717 Carpentry Floor tile will need to be replaced, the cabinet had serious water damage, it will need to 9/4/2015
Elementary - in the back of the room are peeling up and the times in the back cabinet are moldy. be replaced as well. Took measurements to build new cabinet. Purchased plywood and
0029 The items were removed but the cabinets are rotted and have a bad odor. Time laminate for new cabinet. Cut plywood into pieces for cabinet. Built new cabinet and
Available: immediately door along with new drawer fronts. Pulled out old cabinet and counter top. Installed new
cabinet and countertop. Replaced plumbing and cove base. Replaced back splashes
and floor tile.

138071 Kingston Closed Work Orders Unit is draining into wall below unit causing paint to peel. Teacher is allergic to mold. 8/11/2015 102 Heating/Ven Checked out by Dillon Thompkins. Cleaned out drain pain. Per Dillon 8/26/2015
Elementary - It's not mold yet. tilation /Air
0028 Conditioning

138124 Daisy Closed Work Orders Classroom 712 is 76 degrees and is hot. 719 is showing 72 degrees but is warm 8/12/2015 classroom Heating/Ven 8-18 Checked room 712 found unit with blown fuse. found bad crank case heater put 8/18/2015
Elementary - and humid. Time Available: URGENT 712,719 tilation /Air new heater on had spare on truck. unit back cooling now per Ross. Room 719 is
0021 Conditioning cooling good no problem found

138138 Horry Ed. Closed Work Orders Musty smell in room. signs of mildew. Time Available: ASAP-ASAP-ASAP 8/12/2015 RM #14 Heating/Ven Checked unit found Tstat off couple degrees put new Tstat on wall.. Ran unit watched 8/24/2015
Center - 0176 tilation /Air operation unit running good now.. Humidity still high put a dehumidifier in room and a
Conditioning uvair machine told teacher how to use. Per Ross

138227 Ocean Drive Closed Work Orders Mold growing onthe walls in kitchen office. I placed a work order last year for the 8/13/2015 Cafeteria Heating/Ven 8-13-15 Checked for mold in kitchen. None found. Checked in dish room and storage 8/13/2015
Elementary - same type of mold and was told to clean it off. After speaking with a Mr. Sponseller tilation /Air closet. Room temp was 72 and humidity was 57%. Temps and humidity will rise when
0066 at a staff development meeting, he said this was an HVAC issue and that the Conditioning running dishwasher and cooking because of heat and steam generated.
climate could be adjusted to prevent mold from growing in our kitchen areas. We
have also had this problem in a storage closet and in the dishroom. Time
Available: Will be at school each day next week from 7 am until noon.

138268 Forestbrook Complete Black Mold on the wall on the stage.- See Ronnie Moses for questions. 8/14/2015 Gym- Stage Custodial cleaned 8/24/2015
Middle - 0051

138294 Lakewood Closed Work Orders There is mold on the ceiling tiles and wall above the air vent in the classroom. 8/14/2015 103 Painting Cleaned area that had mold, with mold and mildew cleaner. Grid was rusty, so I 8/19/2015
Elementary - When you walk in the door it is on the wall you are facing. The ceiling tiles need to sanded, cleaned, and painted. Also the room had a lot of humidity, looked at filter and it
0029 be replaced, the mold cleaned up on the wall, and the wall repainted. Time had not been changed since March 3, 2015, so I changed the filte, room was feeling
Available: anytime better when I left.

Page 8 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
138308 Aynor High - Closed Work Orders air condition does not work and also we need a dehumidifier in there Time Available: 8/14/2015 senior hallway Climate Unit running normally and was told to close out per Terry Hucks. 8/28/2015
0001 7 to 3 30 b101 Control

138355 St. James Closed Work Orders I need new ceiling tiles, mine are bad. I think the mold spread over the summer. 8/14/2015 D3 Heating/Ven wanted all ceiling tiles replaced in classroom told Mr Green to put in WO for general 8/24/2015
Middle - 0047 Time Available: 100 tilation /Air craftmen
Conditioning

138591 St. James Closed Work Orders Room smells very musty and of mildew. AC is running very loudly. Time Available: 8/18/2015 D1 Heating/Ven this was when I first started I can not remember what ken and I done 8/26/2015
Middle - 0047 100 tilation /Air
Conditioning

138614 Myrtle Beach Closed Work Orders requesting a dehumidifier be put in room V100. 8/18/2015 V100 Heating/Ven Charles Cooke has a new one on order for this area.. ANY QUESTIONS CONTACT 9/23/2015
High - 0010 tilation /Air ARTIE.. or my self LINWOOD.. on Sept.23 2015 in delivered and set up the
Conditioning dehumidifier to the art room.. part number HVA7200.

138621 Aynor High - Closed Work Orders b102 needs to have a dehumidifier installed in the room, very humid and smells 8/18/2015 b102 Climate Unit operating normally. Closed out per Terry Hucks. This room has dehumidifier 8/28/2015
0001 really bad Time Available: 730-430 Control

138660 Pee Dee Closed Work Orders For many years the air has not circulated well in this room. Linwood Dorman was 8/18/2015 202 Heating/Ven Checked out and made adjustment for unit to run longer to dehumidify. Unit working 8/19/2015
Elementary - able to magically get the air circulating good. It is very humid..HOT..temp is reading tilation /Air normally at this time.
0039 73 degrees. Conditioning

138749 South Conway Closed Work Orders Room is not cool enough and is humid. Roomsn on each side are fine. Time 8/19/2015 704 Heating/Ven Checked unit connected to TEC controller and confirmed unit is operating. Made 8/26/2015
Elementary - Available: any tilation /Air adjustment to compressor cycle off percentage parameters. Left unit operating
0045 Conditioning normally.

138786 South Conway Closed Work Orders Hot and humid in rooms 203, 405 & 406 Time Available: any 8/19/2015 203, 405, 406 Heating/Ven Checked Rm 203 and found bad indoor blower motor. Part is on order. Rm 405 was 10/26/2015
Elementary - tilation /Air working, made adjustment to comp off percentage. Rm 406 Found it operating normally
0045 Conditioning maintaining space setpoint. 9/16/15 Update on room 203 repair. Replace failed motor
with new motor, however new motor was faulty from factory. Called and ordered
another replacement motor. The lead time for delivery is about 3-4 days. 9/28 Found
motor was incorrect voltage for unit have replacement on order will be delivered around
10/2. Removed incorrect motor from blower housing and installed new motor. Installed
blower housing in unit and wired. Started unit and checked operation. Left unit
operating normally.

138790 Aynor Closed Work Orders Our thermostat reads 74 degrees. It is very numid and hot in the room. The a/c 8/19/2015 Multi-Purpose Climate Work being done on work order number 139972 8/31/2015
Elementary - was reparired in early June, went out agian during the summer, and appears to be Room Control
0014 working incorrectly at this point. Mr. Gasque requests that someone come as soon
as possible to gauge the issue due to the outside temperatures. The cafeteria
which is being cooled by the same unit is very cool, but the M/P room is so humid
you can feel the difference as you walk in. Time Available: asap

138832 Myrtle Beach Closed Work Orders feels humid in this classroom 8/19/2015 C205 Heating/Ven I checked these rooms both are satisfied at set point which is 73 degrees. I ran units 8/20/2015
High - 0010 tilation /Air to make sure that they were working.. room c205 and c203.
Conditioning

Page 9 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
138880 River Oaks Closed Work Orders Room 504 (HP-61) running 77 degrees and very humid. Need fix quickly please 8/20/2015 504 Heating/Ven CHECKED UNIT OPERATION. FOUND UNIT LOW ON FREON AND LEAKING 8/26/2015
Elementary - Time Available: any tilation /Air FROM HIGH PRESSURE SWITCH. FIXED LEAK AND RECHARGED. UNIT
0065 Conditioning OPERATING PROPERLY.

138913 Aynor Middle - Closed Work Orders The auditorium air is terrible, ask Charles Hucks. The thermostat says 74 degrees 8/20/2015 Auditorium Climate Made some some adjustments on apogee. 8/27/2015
0057 but it is very humid, muggy and stinks. The carpet is probably adding to the smell. Control
Time Available: ASAP
138948 Riverside Closed Work Orders A/c vent in storage closet is dripping water on these humid days. Has done this 8/20/2015 Front office Heating/Ven checked supply register in storage closet and it had no insulation on metal part. 9/2/2015
Elementary - several times before. Maybe duct need to be insulated in ceiling? Time Available: tilation /Air wrapped and taped register with insulation. it was sweating on attic side of register.
0068 Any Conditioning dried and cleaned moisture from supply register.

139039 Waccamaw Closed Work Orders Reese I got an email from Tammy Trulove about the teacher was concerned about 8/21/2015 201 Heating/Ven CHECKED A/C UNIT OPERATION. UNIT OPERATING PROPERLY, PLACED UV 8/25/2015
Elementary - air quality. I think this is the same room as before, We may need to put an air tilation /Air AIR PURIFIER IN ROOM TO HELP WITH AIR QUALITY.
0042 purifier in there. Conditioning

139042 River Oaks Closed Work Orders Room 410 HP-34 temp climbing, at 74.4 now 8/21/2015 410, 414, 415 Heating/Ven CORRECTED ISSUE WITH MAU. ROOMS ARE ALL COOLING PROPERLY. 9/10/2015
Elementary - Room 414 HP-32 Temp climbing 74.2 tilation /Air
0065 Room 415 HP-31 73.9 and climbing Conditioning

The right side of the hall on 400 seems to be hot and very humid. Would like to have
someone come and check please. Time Available: soon please

139082 Palmetto Bays Closed Work Orders Need de-humidifiers in rooms listed. 8/21/2015 200 hall Heating/Ven FOUND AND WORKING TO MAKE REPAIRS TO MAU TO CORRECT HUMIDITY 9/11/2015
Elementary - tilation /Air ISSUE IN THIS WING. WILL GET AIR PURIFIER FOR ROOM 211.
0056 210 Conditioning
211
212
213
215 Time Available: any
139147 Aynor High - Closed Work Orders The humidity and musty smell in these three rooms is bad! Some of them have a 8/21/2015 B101, B102, Climate Units working normally. Closed per Terry Hucks. 8/28/2015
0001 dehumidifier already, and yet, the smell is reminiscent of active and growing mold. B103 Control
Time Available: 8-4
139169 Whittemore Closed Work Orders ASAP - Please check humidity levels in the orchestra room. The instruments have 8/23/2015 129 Climate Ordered a de-humidifier for room 129.Checked room and found unit operating normally. 9/15/2015
Park Middle - mold and mildew and have to be cleaned. We need to know what to do to correct Control maintaining setpoint.
0013 this issue. Time Available: any
139247 Riverside Closed Work Orders Curbing and walks in front of building need some pressure washing to remove 8/24/2015 Parking Lot Road/Street 6/3/16. R.E. Chris completed Friday.6/2/16. R.E. We started yesterday cleaning the 5/17/2016
Elementary - mildew and grime. Time Available: Any walkways.
0068
139313 Whittemore Closed Work Orders ASAP - Both classrooms smell like mildew but we cannot locate the source. Please 8/24/2015 Rooms 118 Climate Met with Tammy Truelove at school and we looked at this while we were there. Waiting 1/29/2016
Park Middle - check and see what we can do to eliminate this issue as teachers and parents are and 116 Control on report. Work was completed on work order 147628.
0013 complaining. Time Available: any
139355 Conway High - Closed Work Orders THE CHORUS ROOM M1 AND DRAMA ROOM V1 ARE HOT AND THE 8/24/2015 M1 & V1 Climate Visited both locations and found room space temps 74deg,73deg respectively. 9/3/2015
0004 HUMIDITY IS HIGH IN THESE ROOMS Time Available: 7:00 AM Control Checked RTU settings and found them to be normal.

139402 Horry Ed. Closed Work Orders Can you please put in another work order for my AC? They changed the schedule, 8/24/2015 A/C #153 =p-6 Heating/Ven 8-25 Checked portable found low on 410a put 1lb in system and checked for leak did 8/26/2015
Center - 0176 but it’s still not working correctly. It is blowing air, but it is humid and muggy. tilation /Air not find. unit back on and operating now per Ross
Thanks!! Conditioning
Time Available: ASAP-ASAP-ASAP

Page 10 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
139453 Whittemore Duplicate Request Nurse request for someone to check if room needs a humidifier. The room may 8/25/2015 129 Heating/Ven
Park Middle - have mold/mildew. tilation /Air
0013 Conditioning

139536 River Oaks Closed Work Orders The office in the gym has issues with water damage. I have had the roofers here, no 8/25/2015 Gym office Plumbing I spoke with Artie about this the other day after we took a look up in the ceiling in her 9/3/2015
Elementary - leak found, the HVAC guys found no condensation or leaks. There is a pipe from office. We found what we think is a leak coming from a 3" fire sprinkler line. We will
0065 the kitchen that runs through this office. need to get VSC to go out and check this situation and repair. Thanks
I have replaced the ceiling tiles 2 times now and now there is mold growing on them.
pleas see pix that i am attaching. Need something done in here due to the smell and
mold/mildew Time Available: soon please
139686 Green Sea Closed Work Orders Please check the all devices involved in the proper air quality produced or removed 8/26/2015 Heating/Ven 8-27 Checked rooms 216 and 218 Both rooms 72 degrees blowing 58 degree air. 8/27/2015
Floyds High - from rooms 216 & 218. There is also an adjoining room in between that should be tilation /Air Checked MAU on roof had 56 degree off coil and 63 degree air going in space. only
0006 included in this inspection. Thanks. Conditioning Calling for 1st and 2nd stage to be running. Air working great in rooms. per Ross

139761 North Myrtle Closed Work Orders High humidity in room. Please see Mr. Furr, teacher has some concerns of where it 8/27/2015 811 Heating/Ven 8-28-15 Check room. Change Temp sensor and set fan to cycle. 8/28/2015
Beach Middle - may be coming from. Time Available: 7:30 tilation /Air
0037 Conditioning

139860 Seaside Closed Work Orders the air conditioner (wall unit) in the gym office is leaking and has molded over. 8/28/2015 Gym office Heating/Ven cleaned clogged condensate drain line, spoke to Liz 9/3/2015
Elementary - please check on this. Time Available: any tilation /Air
0050 Conditioning

139885 South Conway Closed Work Orders Too humid in 704. Room is beginning to have a bad odor. Time Available: any 8/28/2015 room 704 Heating/Ven Was on- site 9/1, there was a issue with the Make-up air unit not operating correctly. 9/2/2015
Elementary - tilation /Air Adjustments were made to remedy the humidity problem.
0045 Conditioning

140052 North Myrtle Closed Work Orders Hot and humid in Curriculum office. Temperature reading 75 this morning. Time 8/31/2015 curriculum Heating/Ven check air in room. supply air is 62. room was full of people. sensor reading 74. 9/3/2015
Beach Middle - Available: 7:30 office tilation /Air condenser unit sweating back on suction. found nothing wrong.
0037 Conditioning

140123 South Conway Closed Work Orders Too humid in room 214 Time Available: any 8/31/2015 room 214 Heating/Ven Checked room and unit. Operating ok and maintaining setpoint. Checked TEC 9/17/2015
Elementary - tilation /Air parameters and found normal.
0045 Conditioning

140126 Daisy Closed Work Orders The theater is 73 degrees and is every humid and wet. Time Available: URGENT 8/31/2015 Theater/104 Heating/Ven 9-1 Checked room found unit 73 degrees cycled fan. unit running fine. per Ross 9/1/2015
Elementary - tilation /Air
0021 Conditioning

140146 Ocean Drive Closed Work Orders Checked & clean A/C's units as necessary and treat with bio -guard disinfectant to 8/31/2015 114,803,804 Heating/Ven purchased MSB-KIT Speedclean Mini Split Bib . Rlane 10-15-15 Take apart all three 10/16/2015
Elementary - eliminate mildew odor and 805 tilation /Air mini split units and clean thoroughly.
0066 Conditioning

140226 Whittemore Closed Work Orders About 150 rolling chairs need to be picked up from the back of the 7th grade hall. 9/1/2015 7grade hall Furniture 9/2/2015
Park Middle - There is also 4 - 32" Zenith tvs that need to be removed as well. A dehumidifyier is
0013 also in this lot to be removed. Time Available: ASAP

Page 11 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
140497 Forestbrook Complete MR cook I NEED A HEAVY DUTY DEHUMIDFIER FOR THE GYM TO HELP WITH 9/3/2015 gym Custodial Closing job. Was advised by Mr Canon this will not fix problem 9/15/2015
Middle - 0051 MOLD,ELE 3716.THANK YOU. Time Available: ANYTIME

140544 Conway Closed Work Orders Per Tammy Trulove-Please put in a work order for maintenance to review. If their 9/3/2015 Adult Ed Heating/Ven We visited classroom and spoke with teacher about his concerns. We found high 9/15/2015
Education recommendation is dehumidifier we will proceed. Staff does not seem to Hall/Room 120 tilation /Air humidity in classroom that caused some mildew spots on walls and door. We placed a
Center - 0172 understand that very often dehumidifiers and air purifiers only contribute to issues Conditioning potable air purifier in room to clean odor. The head custodian has been requested to
we are seeing in the schools. clean all mildew areas. We will check back in a few weeks.

Once maintenance has reviewed we will proceed. Time Available: Anytime

140634 Myrtle Beach Closed Work Orders No digital reading and room is humid 9/4/2015 800S Heating/Ven I replaced the drain pan in unit.. 9/10/2015
Middle (old) - tilation /Air
0016x Conditioning

140885 Myrtle Beach Closed Work Orders A/C off in this training room. Staff also says when a/c is running it still feels humid in 9/8/2015 PE114 Heating/Ven I reset system.. unit was tripped out.. 9/10/2015
High - 0010 that room. tilation /Air
Conditioning

140920 Aynor High - Duplicate Request Please install a dehumidifier in room B101b. The air quality is terrible. Ms. Trulove 9/8/2015 B101b Heating/Ven Work being accomplished on work order 140118.
0001 and Mr. Hucks were at AHS concerning the air quality last week. Time Available: tilation /Air
anytime Conditioning

140924 Seaside Closed Work Orders Teacher is complaining that the room is very hot humid and sticky...I just went in 9/8/2015 102 Heating/Ven I went to checked the unit everything was working good I checked the pressure and 9/8/2015
Elementary - there and the panel reads 72.7 degrees but she said it was very warm in there all tilation /Air temputure I spoke to Mr.Gary
0050 day because she had students in there all day, and only now did it start to get a little Conditioning
cooler. There will be classes in there, for the remainder of map testing, is there a
way to make it stay cool all day? Time Available: any

140953 Loris Middle - Closed Work Orders work order #139810 has become very bad,classroom is leaking with kids inside 9/8/2015 202 Roof Checked room yesterday no leak after all this rain this problem was fixed on another 11/5/2015
0027 class.this could become an mildew issue or worse work order a few weeks ago.

140978 Palmetto Bays Closed Work Orders We have a strong mold/ mildew odor in rm. 211, that needs to be checked ASAP. 9/9/2015 Room 211 Climate CHECKED UNIT OPERATION. FOUND WATER SITTING IN UNIT DRAIN PAN. 9/9/2015
Elementary - HIGH PRIORITY: Time Available: Any Control CLEANED DRAIN. CLEANED DRAIN PAN. ADDED CONDENSATE PAN
0056 TREATMENT. UNIT OPERATING PROPERLY.
141032 Aynor High - Closed Work Orders There is an apparent roof leak above room I 201. The stain on the ceiling tile (which 9/9/2015 I201 Heating/Ven HR . 9/14/15 . I found this to be a drain pan problem . Checked out and found unit 9/16/2015
0001 holds a PA speaker) is becoming larger after each rain storm. It also appears to be tilation /Air sweating, fan sucking for air. Filters totally clogged. Fan pulling water out of drain pan
actively growing mold. Please see the attached picture. Conditioning and throwing down duct work. Insulation got soaked and has to dry. Replaced filters,
Time Available: anytime adjusted temp. unit operating normally at this time.

141115 Myrtle Beach Duplicate Request the art room needs a humidifier put in it. there is one there but due to the size of the 9/10/2015 art room Charles Cooke has a new one on order for this area .. WORK ORDER. #138614..
High - 0010 area the administrator has requested a second one. Tammy Truelove is involved
with this situation.
141147 Palmetto Bays Duplicate Request W,O, 139015 was sent in reguesting de-humidifiers for hall 9/10/2015 200 hallway Heating/Ven THIS IS A DUPLICATE REQUEST. PLEASE SEE W.O. 139082. 9/22/2015
Elementary - way 200. This is a follow-up on the first W.O. SENT. ASAP tilation /Air
0056 HIGH PRIORITY: Time Available: Any Conditioning

141188 Burgess Closed Work Orders The gym has been very humid. The temperature is normal, staying around 74 9/11/2015 gym Heating/Ven we went and checked the units all of them was reading 73 degrees and we checked the 9/15/2015
Elementary - degrees but the P.E. teachers are complaining that it is too hot and humid. Time tilation /Air temperature and pressure everything was working good
0063 Available: any Conditioning

Page 12 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
141425 Aynor Middle - Closed Work Orders humidifier sensor broke off the wall 9/15/2015 305 Heating/Ven Dillon Thompkins replaced broken sensor. 9/16/2015
0057 tilation /Air
Conditioning

141432 Waterway Closed Work Orders We need a teachers desk (with drawers) and dehumidifier if possible. Desk needs 9/15/2015 712 and 503 Furniture 9/18/2015
Elementary - to go to room 503 and dehumidifier to room 712. Thanks, Richie Time Available:
0067 asap
141614 Daisy Closed Work Orders 600 wing has temps in the high 70's and photographers in theater report high 9/17/2015 600 wing and Heating/Ven 9-17 Checked wing 600 found bad drive bypassed drive and got unit going. will order 11/17/2015
Elementary - humidity and temp of 77 Time Available: Asap theater tilation /Air new drive from trane. per Ross11-16 Picked up new drive and installed in unit. ran new
0021 Conditioning communication cable through unit to man panel. Programmed drive and watched
operation everything checked ok at this time per Ross

141668 Pee Dee Closed Work Orders Humid & HOT in this room! 9/17/2015 304, 354 Heating/Ven Checked out and found bad capacitor, replaced and operated unit. Running normally at 9/22/2015
Elementary - tilation /Air this time.
0039 Conditioning

141728 Forestbrook Closed Work Orders Indoor air quality concern. Teacher feels like there may be a mold in the ceiling after 9/18/2015 706 Dunn's Heating/Ven I went and checked the room I did not smell anything I checked the unit everything was 9/24/2015
Middle - 0051 wet ceiling tiles after roof leak. room tilation /Air working properly
Conditioning

141747 Aynor High - Closed Work Orders The ceiling tile, where the AC was leaking needs to be replaced. Black Mold was 9/18/2015 I 201 Carpentry In room I201 where the ceiling tile leaking have been replaced with new tile 9/22/2015
0001 growing on the tile; therefore, the tile was cut to remove the mold. There is now a
hole or partial tile in the ceiling. Time Available: anytime

141914 Palmetto Bays Closed Work Orders An W.O. 140978 was put in because of MOLD,MILDEW odor 9/21/2015 Rm. 211 Heating/Ven WILL GTE DEHUM UNIT. SEE W.O. 141922. 9/23/2015
Elementary - in rm. 211. An a/c technician came out checked the unit, and stated what he tilation /Air
0056 founded. We are still having problems Conditioning
with that same ODOR. ASAP: HIGH PRIORITY: Time Available: Any

141922 Palmetto Bays Closed Work Orders Per Dawn McKinney - Need a dehumidifier in room 211 ASAP Time Available: any 9/21/2015 211 Climate WILL PURCHASE NEW DEHUM UNIT FOR THIS CLASS. PUT AIR PURIFER IN 9/23/2015
Elementary - Control CLASSROOM.
0056
141983 Myrtle Beach Closed Work Orders Mildew on the walls by computers and by flag Time Available: ASAP 9/22/2015 room 702 Painting 9/30/15, all work for this is being documented on wo#142530 9/30/2015
Middle (old) -
0016x
142175 Myrtle Beach Closed Work Orders need to get the mini gym checked out for either poor ventilation and or high humidity 9/24/2015 mini gym Heating/Ven I checked the a/c system and both are running properly .. I had replaced a blower motor 9/25/2015
High - 0010 / AC issues as we are seeing mold forming on the walls in this area way too much. tilation /Air in one of the units earlier this year. the room temp is 68 to 69 degrees and the humidity
Conditioning is at 56%.. I replaced the motor back on 8/6/15 and then we replaced the ceiling tile
after that.. Adam said that wall were cleaned in July we done repairs in August... He
also said that he would have someone to clean the walls again...

142177 Myrtle Beach Closed Work Orders 1. Faucet in Media Center work room continues to leak. Constantly wiping 9/24/2015 media center Plumbing replaced o ring in the hot valve. 9/25/2015
High - 0010 around faucet /sink area and cabinet underneath is wet. Terribly mold/mildew odor office
in this cabinet
142183 Green Sea Closed Work Orders The teacher states that there is a terrible smell in the classroom. She has noticed it 9/24/2015 325 Heating/Ven 10-20 Checked room nobody in classroom room empty. checked for smell. Talk to 10/21/2015
Floyds High - since last year. It has become progressively worse. It smells like urine. It is coming tilation /Air Marcus and larry about smell larry is going to wipe down walls in room and do a real
0006 from the air conditioning vents. She is very concerned that there may be mold up Conditioning good cleaning. I cleaned unit and washed down coil with foaming coil cleaner and
there. washed out drain. Talked to Richard about getting Cayce mechanical to install new
0. I have noticed it since last year. It has become progressively worse. It smells system if they have it ordered per Ross
like urine. It is coming from the air conditioning vents. I'm very concerned that there
may be mold up there. I keep having sinus headaches and I think they are related to
this smell.

Page 13 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
142197 Myrtle Beach Closed Work Orders mildew in room Time Available: ASAP 9/25/2015 rooom 706 Painting 9/25/15, went to MBM this morning. Looked at slight mildew on wall is one small area. 9/30/2015
Middle (old) - Sent job up for when school lets out. Reese and Linwood were meeting me. Work
0016x order has been put on hold waiting on DO personal to inspect. See wo#142530

142214 South Conway Closed Work Orders Room 202 is humid and too hot Time Available: any 9/25/2015 202 Heating/Ven Checked room and found unit operating normally but room very humid due to outside 10/13/2015
Elementary - tilation /Air air being introduced during compressor off cycle. Sealed outside air from entering unit.
0045 Conditioning

142220 Lakewood Closed Work Orders Room 303 (computer lab, front hallway) has MOLD growing on AC outlet. Time 9/25/2015 303 Heating/Ven WENT TO ROOM 303 AND CHECKED ROOM TEMPERATURE AND THE ROOM 9/30/2015
Elementary - Available: asap tilation /Air WAS AT 73 DEGREES AND FOUND THAT THE SUPPLY GRILL HAD BEEN
0029 Conditioning SWEETING. SOMEONE HAD ALREADY CLEANED THE WALL AROUND THE
SUPPLY GRILL AND HAD CLEANED THE STAIN THAT WAS ON THE WALL.

142236 Socastee Annex Closed Work Orders three rooms togather on one thermostat / all fell alittle humid please check Time 9/25/2015 311 Heating/Ven checked classroom temp 73.25 , humidity 56% ok spoke to Harvey 9/29/2015
Available: any tilation /Air
Conditioning

142390 Scholars Closed Work Orders please check temperature in room 118 between 7:30 and 8. 9/28/2015 118 Heating/Ven checked at 730 room temp 74.25 ,se cooling gains back to 30/0/0 it checked unit 9/29/2015
Academy CCU - Teacher stated the room is getting to be 75 degrees and very humid. After 8 it cools tilation /Air operation
0178 down and is ok the rest of the day. Time Available: 7:30-8 Conditioning

142530 Myrtle Beach Closed Work Orders Mildew found in a couple classrooms in 7 th grade hall and in lecture hall. 9/29/2015 Painting 9/29/15, looked at a couple areas today. Took dehumidifier from warehouse and 10/9/2015
Middle (old) - activated in lecture hall. Can't do anything else until we get Tammy Truelove's report.
0016x
142595 Whittemore Closed Work Orders I need three dehumidifiers for some classes... Time Available: asap 9/30/2015 front office Climate Two de-humidifiers were delivered to custodial store room. If another is still required 10/6/2015
Park Middle - Control please let me know. A air purifier was delivered to guidance office in back of
0013 auditorium.
142668 Myrtle Beach Closed Work Orders temp running 76 in this health room and feels humid. 10/1/2015 I3 Heating/Ven I found the unit tripped out.. I reset it and it is running fine now.. the power had went out 10/1/2015
High - 0010 tilation /Air last night.
Conditioning

142712 District Office Closed Work Orders in b building room 307 they are complining of constant sinus infections air quality 10/1/2015 they are Heating/Ven 10-14-15 Cleaned unit and spray Bio gaurd in unit and add pan pills to condsate drain. 10/14/2015
Four Mile Road - Time Available: today if you can complaining of tilation /Air Unit not real dirty but cleaned and treated unit thoughly.
0401 air quality Conditioning

143123 Scholars Closed Work Orders There is a strong mildew smell in the Teachers Offices. It has been ongoing for 10/6/2015 134/Teachers Heating/Ven checked air handler dropped below condensate piping , increased height of air handler 10/7/2015
Academy CCU - over 2 weeks. We did have the A/C pan overflow last month. I just checked filter ok offices tilation /Air 2 inches , releveled , water come from over flow tube, removed water from em pan
0178 and dry but pan is full of water. Not sure if this is the cause of the smell but there Conditioning sanitized pan , spoke to Shawn
shouldn't be water in pan. Need a hose to drain it. I only have 100 ft. hose here.
Time Available: 7:15-4
143198 North Myrtle Closed Work Orders AC out in G115 which also supplies G114. AC supplies air to NJROTC clothing 10/7/2015 G Hall Heating/Ven 10-7-15 Checked and found unit on panel that was tripped. We got this room and 10/7/2015
Beach High - locker so they don't mold. tilation /Air several others back up. Will complete panel repair when burnt up breakers come in
0002 Conditioning tomorrow.

143277 Midland Closed Work Orders I need some filters this size 11-1/2x11-1/2x1 pleat charcoal.they are for humidifiers 10/8/2015 803 801 105 10/20/2015
Elementary - in there rooms.
0033

Page 14 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
143283 Aynor Closed Work Orders Teacher request an air purifier in her room and would like for someone to come and 10/8/2015 rm 207 Heating/Ven Checked out and found no wet spots in room , either in ceiling or on the floor. Installed 10/9/2015
Elementary - check her room. She said it smells like mildew and she has been sick off and on tilation /Air a air purifier in room. Checked other areas and nothing found. Odors subsided from
0014 since school started. Conditioning yesterday. Will keep checking on this regularly.

143387 Forestbrook Closed Work Orders Recommendations (District Responsibility): 10/9/2015 Carpentry 1. Wall surfaces- The majority of the wall surfaces was clean. There were a few areas 12/1/2015
Elementary - 1.Maintenance to review the area and evaluate the wall surfaces, ceiling tiles, air that were dirty and could be cleaned.2. Ceiling Tiles- The ceiling tiles in the new
0046 exchanges and humidity levels in the aforementioned areas. addition were good. The ceiling tiles in the older section of the building were showing
2.A review of the carpet in Room 404 needs completed to determine if it needs signs of dis coloring because of age. ( Not water stained ). It would help the
replaced. (This will require District –Level approval). appearance of the school to have new ceiling tiles and new ceiling grid, especially in
3.Additional custodial assistance to do a thorough clean of the aforementioned the hallways.3. Humidity Levels- Humidity levels seemed okay.4. Carpet Room 404-
areas. There is a lot of difference in the areas cleaned by the 2 custodians. Looked very closely at carpet in room, could not find any spots, carpet looked in good
(Additional training or review may be needed to ensure that these areas of the shape.5. Ceiling Tiles in Rooms 301, 303, and 181- These class rooms were part of the
building are properly maintained). older section of the building. Tiles did appear to be dis colored because of age.6.
4.Ceiling tiles in rooms 301, 303 and 181 need evaluated for possible replacement Honeywell Purifier- Ken went by looked at, everything looked good and working
(This will require District-level approval). properly.
5.Removal of the Honeywell air purifier in Room 181 and replacement with a unit
that is working.
Gary have Ken to work with you on these issues.

143485 Myrtle Beach Closed Work Orders humidity level too high in both boys and girls restrooms in front lobby area. This can 10/12/2015 front lobby Heating/Ven found breaker system to exhaust fans and reset them and then replace the belts on 10/15/2015
High - 0010 lead to unsanitary conditions in the bathroom with the forming of mildew on the walls bathrooms tilation /Air them.
in these bathrooms. Please check and see what can be done in these bathrooms to Conditioning
bring down the humidity levels in those bathrooms.

143679 Carolina Forest Closed Work Orders Miss Johnson needs the HVAC system checked in her room E 103. The room is 10/14/2015 E House Heating/Ven CHECKED CLASSROOM UNITS OPERATION. BOTH UNITS OPERATING 11/30/2015
High - 0052 very humid and has an odor. She says she feels sick every day and thinks it is the tilation /Air PROPERLY. FOUND AND REPLACED WORN BELT ON MAU. CLEANED MAU
room. Time Available: ASAP Conditioning EVAP COIL AND DRAIN PANS. WILL ALSO CLEAN CLASSROOM UNITS COILS
WHEN AVAILABLE. CLEANED COIL AND PAN IN CLASSROOM UNIT.

143690 Myrtle Beach Closed Work Orders Humid and hot in room 813. 10/14/2015 813 Heating/Ven I checked the system . it seem to working correctly. I adjusted the room set point room 10/15/2015
Middle (old) - tilation /Air was at 73 degrees.. I came back by to do a follow up and the teacher said that was
0016x Conditioning fine now.

143761 Carolina Forest Duplicate Request AC not taken humidity out of B 111. Please check back of B House. 10/15/2015 B House Heating/Ven SEE W.O. 143488. ISSUE BEING REPAIRED WITH MAU. 10/27/2015
High - 0052 tilation /Air
Conditioning

143823 Conway Middle - Closed Work Orders Each teacher in the rooms says that its a smell they believe coming from the air 10/16/2015 A214, A206, Heating/Ven Checked classroom A214,A206 and A202 for smells, found no obvious smell. Cut 10/22/2015
0017 vents that's causing sinus issues and bad headaches, concerns of mold issues A202 tilation /Air access in duct borad to check inside duct work for signs of moisture or mold, none
Time Available: asap Conditioning found. Sealed duct work, then checked unit and found blower wheel dirty on A214.
Removed blower wheel and cleaned. Installed in place and left unit operating normally.
Also serviced two Uvair cleaners for classroom. Room A206 sprayed neutralizer to
diminish any residual coil cleaner odor, also flushed coil with clean water. A202 found
unit and duct work normal.

144210 Aynor High - Closed Work Orders we need the trees sprayed at the baseball field for black mold. Time Available: 10/22/2015 baseball field Tree Sprayed all trees with fungicide. Will spray again in couple weeks to try to kill mold 11/23/2015
0001 anytime Services

144474 Homewood Closed Work Orders there is a musty odor to this room the administration wants someone to check this 10/27/2015 610 Heating/Ven Checked out for mold and mildew in duct work and unit due to abnormal smells. 10/28/2015
Elementary - out, to see if there is any water or mold in ducts. Time Available: asap tilation /Air Cleaned out drain pan and inside unit. No evidence of any mold or mildew. Unit
0025 Conditioning operating normally and room smells ok at this time.

Page 15 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
144636 Myrtle Beach Closed Work Orders very humid in the athletic training room please check to see if we have an issue. 10/28/2015 PE115 Heating/Ven I found that the system was a little low on refrigerant ..added to it and checked for 11/4/2015
High - 0010 tilation /Air leaks.. reset system ..unit is now working ok.
Conditioning

144677 Aynor Middle - Closed Work Orders room is very warm moist and sticky very humid Time Available: asap 10/29/2015 501 Heating/Ven Made adjustments to set point, checked operation, running normally at this time, will 11/6/2015
0057 tilation /Air check on Tuesday when I come back to work to see if everything is alright. Unit running
Conditioning normally.

144688 Socastee Annex Closed Work Orders very hot humid at 77 degrees and rising / also room 300 appears to have the 10/29/2015 201 Heating/Ven checked rm 201 found bad connection to reversing valve , rm 300 rm temp 73 found 10/30/2015
same problem. Time Available: any tilation /Air 100% clogged filter , recommended all filters be replaced , spoke to harvey
Conditioning

144776 Myrtle Beach Closed Work Orders Service and change filters in dehumidifiers , Teacher said they are very dirty 10/30/2015 Art Room Heating/Ven I found nothing wrong with the new unit.. 11/4/2015
High - 0010 tilation /Air
Conditioning

144777 Myrtle Beach Closed Work Orders Need the dehumidifier serviced and also make sure it working correctly for that 10/30/2015 V100 Heating/Ven I repaired the drain line on unit and also cleaned the air filter. 11/4/2015
High - 0010 classroom. tilation /Air
Conditioning

144977 Academy for Closed Work Orders Email from teacher:Temp is 73, but it is so humid in the room sweating. Please help 11/2/2015 A-206 Climate 11-3-15 Check room temperature and humidity. Temp 73 and humidity 56%. Found 11/3/2015
Tech and Time Available: 7:00 am to 4:00 pm Control AHU #6 supply air temp at 60 degrees. Turn down to 55 to lower humidity on all VAV
Academics - boxes coming off AHU 6.
0098
145090 Daisy Closed Work Orders teacher in room 719 reports display at 73 degrees but room is very humid and she 11/3/2015 719 Heating/Ven 11-3 Checked found room running when I arrived. cycled fan to run all time. and 11/3/2015
Elementary - smells mold/midew Time Available: asap tilation /Air lowered heating set point to 68.. changed filters and watched unit operation. unit
0021 Conditioning checked ok per Ross supply air temp 57 degrees

145106 Conway Closed Work Orders Although we cannot determine the actual temperature in the small rooms (2 of them) 11/3/2015 Small Rooms Heating/Ven Checked unit that also serves nurses office. Found unit tripped on high pressure safety. 11/6/2015
Education that are adjacent to room 101, the rooms seem rather warm and uncomfortable. Adjacent to tilation /Air Reset and checked operation, found condenser fan not operating. Troubleshoot
Center - 0172 According to the dehumidifier in one of the rooms, the temp is 85. The other room is Room 101 Conditioning controls and found a bad motor capacitor. Replaced capacitor then started unit,
showing 76 but it feels warmer than that. Time Available: After 1:30 checked operation. Left unit operating normally.

145137 St. James Closed Work Orders URGENT Books from media center have beeen found with mold in them from 11/3/2015 media center, Heating/Ven Check units greg , dean cleaned 3 A/C in media , checked unit operation ,11-10 11/12/2015
Elementary - parents that was tooking home from students. Please check media center, cyber cyber lab, tilation /Air conference room/reading room dissembled unit ,blower assembly ,wash and cleaned ,
0030 lab, conf. room and reading room for this issue conf. room Conditioning sanitized all panels ,blower assembly, evaporator,drain pan, reassembled ,checked unit
and reading ro operation, spoke to James

145191 Myrtle Beach Closed Work Orders check air in room 800L. Very humid. 11/4/2015 800L Heating/Ven I adjusted the set point in this room to help with the humidity 11/4/2015
Middle (old) - Thank you, tilation /Air
0016x Conditioning

Page 16 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
145229 Myrtle Beach Closed Work Orders need d-humidifier back in Lecture hall Time Available: ASAP 11/4/2015 lecture hall Painting 11/9/15, delivered dehumidifier to lecture hall today. Will check on this unit daily. 11/28/2015
Middle (old) - 11/10/15, returned this morning to find unit turned off and no water in trash can.
0016x Teacher that was in the lecture hall explained to me that unit was too loud. In my
opinion, the person that was in there last night turned unit off. I got 2 air movers from
Will and set in room. I also explained to Will and Lisa Selph the importance of leaving
the unit running. Dr. Christy was in a meeting at this time. Returned this afternoon to
find both unit and fans still off. I placed fans and started them and the dehu at this
time. 11/11/15, sprayed all fabric on seats with fabreeze today to eliminate the musty
odor. Will check in the morning. 11/12/15, checked lecture hall this morning. Odor is
gone for now. Leaving fans running this weekend and will recheck next week to make
sure odor is gone. 11/24/15, returned dehu to warehouse.

145368 Myrtle Beach Closed Work Orders very humid all the time in both of these rooms. In piano room mildew forms on the 11/6/2015 drama Heating/Ven I have picked up another dehumidifier from warehouse and installed in class room 11/11/2015
High - 0010 wall at times. AUD100 drama room and piano room is within that room. room/piano tilation /Air AUD100 at MBHS.. we now have 2 units in AUD100 and 1 in AUD101..
room Conditioning

145369 Whittemore Closed Work Orders IN THE ORCHESTRA ROOM 129 HAVE SOME INSTRUMENT WITH SOME 11/6/2015 ORCHESTRA Furniture 11/13/2015
Park Middle - MOLD IT THAT NEED TO BE PICK UP.. Time Available: ANY
0013
145398 Aynor High - Duplicate Request Please see request 144186. The teacher reported the tile is growing mold. Please 11/6/2015 J202 Carpentry See w/o 144186 for action taken.
0001 inspect.

2nd Floor
J202 Time Available: 7-430
145515 Myrtle Beach Closed Work Orders requesting dehumidifiers be put in both of these classrooms. 11/9/2015 aud100 aud Heating/Ven I picked up two dehumidifiers from the warehouse and installed in MBH rooms AUD100 11/10/2015
High - 0010 102 tilation /Air and AUD101..
Conditioning

145580 River Oaks Closed Work Orders HP-58 running almost 75 degrees 11/10/2015 512 Heating/Ven CHECKED BOTH UNITS OPERATION. CONTROL BOARDS LOCKED OUT. RESET 11/10/2015
Elementary - HP-59 about 74 tilation /Air UNITS AND CONTROL BOARDS. BOTH UNITS OPERATING PROPERLY.
0065 Multipurpose room is hot and humid,not seeming to cool down. Time Available: any Conditioning

145740 Forestbrook Closed Work Orders Mold on Walls in the Boys Locker Room- See Chad Hawks for questions 11/12/2015 Boys Locker Heating/Ven spoke to Moses he is going to wipe down walls , can see some mildew 11/12/2015
Middle - 0051 Room tilation /Air
Conditioning

145870 Green Sea Closed Work Orders In room 113 the painting is peeling from wall possible some mold present on wall. 11/16/2015 Room 113 Painting Checked room 113,paint was peeling bad,but did not see any mold.Scrapped peeling 11/18/2015
Floyds Time Available: ASAP and surrounding areas.Primed,and applied two coats of paint.
Elementary -
0023
146143 River Oaks Closed Work Orders HP-56 & hp-57 both are above 75 degrees and climbing. Very Hot and humid in the 11/19/2015 cafeteria Heating/Ven CHECKED UNITS OPERATION. FOUND LITERATURE FOR FAULT CODES. BOTH 11/20/2015
Elementary - cafeteria. Time Available: any tilation /Air UNITS LOCKED OUT ON HP FAULT. RESET BOTH UNITS. CHECKED
0065 Conditioning OPERATION. BOTH UNITS OPERATING PROPERLY.

146333 Aynor Closed Work Orders Teacher has concerns about sneezing and watery eyes. Appears to be a black 11/23/2015 215 Heating/Ven Checked out and found that it was dirt in corner of room. Water and ants seeped in and 12/3/2015
Elementary - substance above the cabinet. Concerned it may be mold or mildew. Time Available: tilation /Air the carpet and baseboard needs repaired. Informed Terry Hucks and situation is being
0014 asap Conditioning handled.

Page 17 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
146537 North Myrtle Closed Work Orders Teacher said her room has a mold smell. She thinks there may be mold in the 11/30/2015 607 Heating/Ven 12-1-15 Check unit and also roof above cieling tile. Clean air handler A coil and add 12/1/2015
Beach Middle - ceiling. Time Available: 7:30 tilation /Air drain pills and also added clean air fresh sent 1lb tub. No mold found any where.
0037 Conditioning

146779 Lakewood Closed Work Orders Classroom sink is leaking underneath. They have a handicap child that needs to 12/3/2015 701 Plumbing Got seals from parts store. Faucet was leaking from multiple places. Found stem was 12/29/2015
Elementary - use the sink. He is in a wheelchair. Time Available: asap IMPORTANT** Additional bad, we have to order a new one. 12/29 Picked up and installed faucet stem.
0029 information to WO# 146779 - during cleaning out from under the sink, we noticed
the cabinet is wet from top and bottom and mold is starting to form. Not sure what
part of the sink is leaking. Time Available: asap. please turn this over to General
craft when complete

146784 Lakewood Closed Work Orders **IMPORTANT** Additional information to WO# 146779 - during cleaning out from 12/3/2015 701 Plumbing add this information to work order 146779 12/4/2015
Elementary - under the sink, we noticed the cabinet is wet from top and bottom and mold is
0029 starting to form. Not sure what part of the sink is leaking. Time Available: asap

146866 Aynor High - Closed Work Orders May we have a portable dehumidifier for room B105? This room is located in the 12/4/2015 B105 Heating/Ven Installed a dehumidifier per customers request. 12/11/2015
0001 older section of AHS, where there is an existing moisture issue. Please consider. tilation /Air
Time Available: 7-430 Conditioning

147170 Waccamaw Closed Work Orders look like mold in vault at heat and cooling vent 12/8/2015 vault in office Heating/Ven CHECKED TILES AND UNIT OPERATION. REMOVED STAINED TILE. ORDERED 12/11/2015
Elementary - tilation /Air NEW TILES FROM C.K. SUPPLY. NEW TILES ARE BACK ORDERED AND WILL
0042 Conditioning TAKE 2-3 WEEKS TO COME IN. WILL MAKE NEW WORK ORDER TO PURCHASE
TILES AND REPLACE TILES WHEN TILES COME IN.

147251 Green Sea Closed Work Orders Shower leaks from ceiling and mold . Time Available: now 12/9/2015 high school Roof Fixed roof drain above roof tightin all clamps and bolts and calked all joins in pipe and 2/11/2016
Floyds High - lockedr room fixed Sheetrock with mud and paint
0006
147311 Pee Dee Closed Work Orders It appears there may be something that looks like mold in this classroom. 12/10/2015 419 Custodial Had walls cleaned 6/2/2017
Elementary -
0039
147490 St. James High - Closed Work Orders hot and humid in classroom .... thermostat reads 73 Time Available: high 12/14/2015 D - 126 Heating/Ven checked unit operation , could not find any thing wrong 12/15/2015
0058 tilation /Air
Conditioning

147562 Aynor Closed Work Orders the ramp going in to the OT/PT portable has mold all over it. Mr. Gasque said we 12/15/2015 OT/PT Carpentry checked ramp and it needs to be pressure washed. Talked to Mr. Gsaque and he said 4/17/2016
Elementary - need a new one. Portable his custodial staf would take care of this. After this is done we will go back and coat this
0014 ramp with non skid material. Mr. Gasque will let me know when washing is done. The
handicap ramp in OT/PT portable has been pressure washed and painted

147564 Aynor Duplicate Request ramp at ot/pt portable is very slippery with mold--parent slipped twice. Mr. Gasque 12/15/2015 OT/PT Carpentry Work completed on WO #147562
Elementary - ask that a new one be built. Portable
0014
147689 Daisy Closed Work Orders these rooms are controlled by a thermostats in room 415 and 418 . On humid days 12/17/2015 413,414,416,4 Climate 1-13 Checked rooms these are all offices and tstat are in one room that is satisfied 1/13/2016
Elementary - these rooms are very muggy - to the point of being unbearable. It's not every day 17 & 419 Control while others are hot or cold. unit running good at this time. fans are running all the time
0021 but when it happena the rooms are unbearable. is there anything that can be done to keep air circulating. per Ross
to make them more comfortable Time Available: anytiime Also checked 305 was cool checked found heat on 65 put on 68 for heat per Ross

147699 Aynor Middle - Closed Work Orders I'm not sure, but it appears our AC unit is not working properly again. Very humid 12/17/2015 Auditorium Heating/Ven Made adjustments to set points on units, monitored for several weeks, units maintained 1/8/2016
0057 and muggy and thermostats read 73. tilation /Air set points on temp. and humidity. Systems operating normally at this time.
We must have this working correctly when we return from break with our Conditioning
Play/performances on Jan. 7-10th. Thanks Time Available: ASAP

Page 18 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
147700 Myrtle Beach Closed Work Orders DHEC write-up on refrigerator and freezer. Poor condition, panels coming apart, 12/17/2015 Kitchen Heating/Ven I have contacted Costal Refrigeration to give an estimate on replacing the Freezer and 2/4/2016
Primary - 0035 baseboard coming off, mold and mildew on baseboard in storage room and freezer tilation /Air Cooler. This is hopefully going to be completed this summer in the project.
wall. We clean the mold off as best as possible but it will come back within days. Conditioning
Time Available: Anytime This work order is being closed and has been deferred for consideration as a capital
project.

148091 Ocean Bay Closed Work Orders In the gym on the stage back stairwell near coaches office the roof is leaking and 1/4/2016 GYM BACK Roof This work order is for the wrong school called Richard and gave wo number . Will find 4/22/2016
Elementary - black mold has formed on ceiling tile. from the floor to ceiling tile is about 25ft. Time STAGE out witch school and have to to make new wo. This was placed in as Ocean Drive
0060 Available: ASAP Elem. to begin with.
148102 Palmetto Bays Closed Work Orders We have mildew on carpets in classrooms. HIGH PRIORITY: Time Available: Any 1/4/2016 Rms. 201, 202 Climate 1/6/16, sprayed carpets with mildew killer. Told Mr. Jeffries to dry clean carpet this 1/6/2016
Elementary - Control afternoon.
0056
148287 Loris High - Closed Work Orders 211 air quality is not right Time Available: asap 1/5/2016 211 Climate 1=6 Checked room 211. checked air filters they were ok. Also checked settings. found 1/6/2016
0008 Control in auto on fan and in heat mode. Put fan to run all the time to circulate air in room and
put in auto so if needed heat or cool in would switch back and forth. per Ross

148376 Transportation - Closed Work Orders 2 WORK SHOP TABLES, 3 WHEELING CARTS, TV'S, ICE MACHINE, SILVER 1/6/2016 Furniture Delivered all equipment to Bus Shop 1/8/2016
087 (Bus SHELVE, 2 DEHUMIDIFIERS, PICNIC TABLE
Repair)
148507 Myrtle Beach Closed Work Orders need to find out why mini gym walls continues to get mold and mildew forming on 1/8/2016 mini gym Heating/Ven these a/c units are working. in heat and a/c.. the wall had not been cleaned from the 1/14/2016
High - 0010 the walls on a continued basis. tilation /Air last time..
Conditioning

148513 Lakewood Closed Work Orders The room feels cool - temp. is 70. On the A/C box the paint is falling off and over the 1/8/2016 720 Heating/Ven we went and checked the unit it was just the t-stat was dirty and not connected good 1/8/2016
Elementary - break mold has started. Not sure if it's a leak or moisture. tilation /Air we cleaned it off and reset the unit we left it working good and we told Mr.Gary about
0029 Conditioning the paint peeling we looked and did not see no sign of mold

148528 Forestbrook Closed Work Orders Good afternoon, 1/8/2016 PE/Locker Carpentry Will be there Monday morning 1/11/16 to inspect areas of concern. Wiped off walls in 1/27/2016
Middle - 0051 The PE teachers came to me concerned because over break it was hotter than Room gym (had to use lifts to get all the way to the rafters), wiped off walls in locker rooms,
expected and the AC did not come on in the gym. As a result there was black mold coaches offices and coaches restrooms. Wiped off goal post and supports.
in the locker rooms and in the gym on the walls. There is still some high up in the
gym we might need to have a lift to clean. Mr. Perry cleaned the walls in the girls
and boys locker rooms with bleach as well as in the gym for what our ladders will
reach. We had some kids get into their lockers today for the first time since break
because they were in health and their gym clothes and shoes were covered with
mold. I have asked Perry to also look in the ceiling in the locker rooms to see if we
have mold growing above the ceiling tiles. In addition, one of our PE teachers is
pregnant and is concerned about her health as well. Please advise next steps.

Thanks, April Scott Principal

148540 Green Sea Closed Work Orders The Ceiling has a leak. Mold has grown. Time Available: now 1/10/2016 high school Carpentry Repaired roof drain by putting in new 90 and tightin all clamps and bolts -- ( Kevin need 2/26/2016
Floyds High - lockedr room to touch up plaster and paint in locker room.)
0006
148638 Early College - Closed Work Orders Freezer door is not registering temperature. There is also mold on the door and 1/11/2016 Kitchen Refrigeration checked found blown 1 amp glass fuse replaced ,checked operation recalibrated , 1/13/2016
0074 sweating. Please see Tammy Walker. spoke to Tammy
Time Available: 7:30-4:30
148762 Lakewood Closed Work Orders Ref. to WO# 146779 - still are having problems with the sink & counter. The 1/12/2016 701 Plumbing Caulked backsplash to countertop. Cleaned under sink. Area is good. 1/19/2016
Elementary - counter is pulling away from the wall and the bleach solution we are using to get rid
0029 of the mold is not working.
148878 Ocean Bay Closed Work Orders Please check all sinks for leaks. Know 2 faucets are leaking. Standing water under 1/14/2016 Art Room 303 Plumbing Repaired the back two sinks in this classroom. I had to replace the o-rings inside of the 1/22/2016
Middle - 0061 one cabinet possibly causing mildew. Thanks Time Available: anytime spout.

Page 19 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
148992 Waterway Closed Work Orders need a metal plate behind dishwasher sink in front, keeps getting mold/black and it 1/19/2016 kitchen Painting Measured area behind dishwasher,to see how much FRP I need.3-pieces and 6/28/2016
Elementary - looks gross. they have painted in the past in the summer to make it look better, but Removed all the attachments off the wall,and cleaned area where the panels were
0067 just keeps coming back over the paint(mold) going measured,and glued FRP panels,and slowly worked them in place.Also installed
the trim pieces.
149343 Academy for Closed Work Orders Room 508 _Please check heating and air ventilation for any sign of mold or fungi. 1/22/2016 508 Heating/Ven cleaned indoor coil and checking mau unit found bad fuses replace fuses.mau unit on 2/11/2016
Arts Science The teacher and others have experienced a reaction to something in the room since tilation /Air low charge add r22 looked up in ceiling in class room could not found anything or
and Tech. - the beginning of the school year. May need a dehumidifier. See R Jones or J Conditioning ordors that ceiling go all down the hall to all the classes on that hall.2-1-16 put a ozone
0096 Powers. Time Available: anytime machine in room to run at nights.
put air cleaner in room and took out ozone machine out.
150102 Homewood Closed Work Orders smell of mildew or mold coming from the vents. Time Available: asap 2/3/2016 603 Heating/Ven Checked out system and duct work , no unusual smells or odors. Checked out all areas 2/8/2016
Elementary - tilation /Air of room and found all was fine at this time.
0025 Conditioning

150143 Myrtle Beach Closed Work Orders Move the following from MB Family Learning Center room #23: 2/3/2016 23 Furniture 2/5/2016
Family Learning 1 shredder, 5 shelves, 57 boxes, 1 teacher desk, 6 rolling chairs, 2 wastebaskets, 2
Center - 0173 tables, 7 book cases, 6 filing cabinets, 63 tubs, 2 two door cabinets, 2 dehumidifiers
These items need to be moved to DOA-Transportation room #8.

150243 Myrtle Beach Closed Work Orders Furniture items to be moved from MBFLC to DO - Building C - Room 300 2/4/2016 28 Furniture 2/4/2016
Family Learning 6 files cabinets
Center - 0173 3 desk chairs
3 boxes
1 dehumidifier Time Available: 8 to 4:30
150482 Ocean Bay Closed Work Orders The roof over the stage stairwell at the gym office water is leaking through ceiling 2/8/2016 BACK STAGE Roof Removed tiles an replaced 2/25/2016
Elementary - tile causing black mold on ceiling tile. the height is about 25 to 30 ft. Time Available: OF GYM
0060 ASAP
150554 Palmetto Bays Closed Work Orders Need building power washed due to black mildew that's developed on the 2/9/2016 Outside 5th Road/Street 9/28/16. R.E. Did not get to complete before school started back. You can put back in 9/23/2016
Elementary - building. Meduim Priority: Time Available: After 2:30 pm IS THIS COMPLETE? grade door/ next spring to be done in the summer. I will try to work on it during school
0056 music door shutdowns.3/15/16 looked at the mildew, there will be places we will have to get on the
awings.2/17/16,cb ; checked to see what they were talking about. The mildew is on all
ends of the building and behind gym on back wall. Going to need big blue lift to reach
all areas. Seems to me that the caulking under the flashin where the joints are is dry
rotted and is leaking rain water under flashing causing the outside walls to mildew.

150612 Academy for Closed Work Orders Please check the air quality in rooms 506 & 507. And the temperature is cold (69 2/9/2016 506,507,508 Climate checked units running ok deg was 70deg.put a air cleaner in room got from warehouse 2/11/2016
Arts Science degrees) in 508. Time Available: anytime Control .took ozone machine out and took back to warehouse .
and Tech. -
0096
150722 River Oaks Closed Work Orders Mildew is growing behind caulking in dish room. Located by spray sink and 2/12/2016 kitchen Painting 2/17/16, removed old silicone and cleaned wall. Re caulked. 2/18/2016
Elementary - entrance of dish machine. Time Available: any
0065
151092 Aynor High - Closed Work Orders We need the red maple trees at the baseball field sprayed for black mold and 2/19/2016 baseball field Pest Control 2/25/16 treated red maple trees with Bifenthrin I/T7.9(.25oz/M). Total used .5 oz in 2/25/2016
0001 insects. Time Available: anytime BRIAN, IT IS NOT MOLD. IT IS SCALE INSECT Outdoors 2gallons of H2O. Treated entire tree.
RESIDUE. IF YOU GET TIME SPRAY, OR HAVE SOMEONE SPRAY THE TREE
WITH BIFENTHRIN.
151266 Myrtle Beach Closed Work Orders ceiling above tile ceiling in this rooms storeroom has been leaking and now has 2/23/2016 B110 Roof Investigated area to see where water came from to cause discoloration of Sheetrock 5/19/2016
High - 0010 what appears to be mold growing on that ceiling which looks like is sheetrock. closed door to room please put new tiles in until we can schedule to clean an repair
please investigate the ceiling area. area. 2/26/16 went on slope metal roof on B hall where room has leak had a couple
suspect areas on wall flashing . Caulked with M-1 to seal to brick. 4/13/16 checked
after rain still leaking in a little spot.5/10/16 searched for suspected areas will need lift
to make repairs.5/19/16 caulked again to seal

151277 St. James High - Closed Work Orders Replace outside air humidity sensor for the school. It is reading way off and the 2/23/2016 Climate checked rh sensor ,checked all connections , board has power , and dry , ordered new 3/8/2016
0058 MAU control sequence is not working correctly. Control sensor, replaced humidity sensor checked operation

Page 20 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
151655 South Conway Closed Work Orders Ceiling tile on the stage in the gym needs to be replaced; mold on them. Time 3/1/2016 Gym Carpentry Ceiling tile on the stage in the gym have been replaced with new tile 3/7/2016
Elementary - Available: any
0045
151760 District Office Closed Work Orders Broken dehumidifier needs to be picked up. Time Available: 8 to 4:30 3/3/2016 C-200 Furniture 3/8/16 Items were picked up. 3/8/2016
Four Mile Road -
0401
152057 Aynor Duplicate Request We recently had mold cleaned from the ramp. Mr. Gasque would like the no skid 3/7/2016 ramp to Carpentry will use work order 147562
Elementary - material installed on it. OT/PT potable
0014
152273 District Office Closed Work Orders in building a room 101 learnings services room 101 ice mker have mold or mildew 3/10/2016 learning Refrigeration checked , disassembled all components hand washed , sanitized , reassembled, ran 3/10/2016
Four Mile Road - inside the water line of the ice mker Time Available: today if you can services room cleaner through cleaning cycle (70) minutes. put back in normal ice operation
0401 101
152275 Waccamaw Closed Work Orders Teacher is having complications with allergies with mold and needs to have her 3/10/2016 rm 116/rm 112 Climate CHECKED AC UNITS OPERATION. UNITS WORKING PROPERLY. COULD NOT 3/16/2016
Elementary - room checked. There is an odor in one of the cabinets in her room on the interior Control FIND ANYTHING WITH AC UNITS CAUSING BAD ODOR. ROOMS HAVE
0042 wall on the hallway side. There is a duct near this. Can someone please come CARPETS, CURTAINS, BOOKBAGS, CLOTHING, ETC THAT CAN CAUSE ODORS.
check this out. Also she said that she can't even enter another teachers room for CANNOT DETERMINE EXACT CAUSE OF ODOR WITHOUT REMOVING
same reason rm 112. EVERYTHING FROM CLASSROOMS. WE DID REPLACE ALL AIR FILTERS ON
THIS WING AS THEY WERE ALL VERY DIRTY.
152512 River Oaks Closed Work Orders Cafeteria (HP- 56 & HP-57) are running about 74.8 now and climbing. 3/14/2016 cafeteria/gym Climate CHECKED UNITS OPERATION. FOUND BOTH UNITS NOT RUNNING AND 5/4/2016
Elementary - Control CIRCUIT BOARD SHOWING A HIGH PRESSURE FAULT. RESET BOTH UNITS
0065 Gym (HP-58) 74.6 now both are really warm and humid Time Available: any AND CHECKED OPERATION. BOTH UNITS OPERATED PROPERLY. I COULD
FIND NO ISSUES WITH EITHER UNIT WHICH WOULD LEAD TO A HIGH
PRESSURE FAULT. WILL MONITOR UNITS FOR ANY ISSUES. REPLACED
DEFROST BOARDS. UNITS OPERATING PROPERLY.
152666 Aynor Middle - Closed Work Orders Thermostat reads 72, but it is very humid. This is the band room, and the 3/16/2016 302 Climate Wrong room number and work being performed on 152667. 3/18/2016
0057 temperature is not good for the instruments. Thanks Time Available: ASAP Control

152688 Myrtle Beach Closed Work Orders Feels very humid in this room 3/16/2016 B105 Heating/Ven I reset the unit in this class room , it was tripped out.. seems to be running ok at this 3/16/2016
High - 0010 tilation /Air time.
Conditioning

152722 Myrtle Beach Closed Work Orders the dehumidifier in this room the teacher would like a hose to be connected to it and 3/16/2016 V100 Heating/Ven I found a 36 inch stand to place the dehumidifier. 3/24/2016
High - 0010 ran to her sink for draining. tilation /Air
Conditioning

152756 River Oaks Closed Work Orders Room 415 3/17/2016 415 Heating/Ven I found nothing wrong with the air system in this room .. I found the air filters in there 4/6/2016
Elementary - Per Tammy Trulove, the air quality in this room needs to be tested as soon as tilation /Air needed to be changed.. I replaced both .. air handler and above the ceil tile are clean..
0065 possible. Please see Nurse Mathis for any questions regarding the matter. Conditioning ( JEFF,DENNIS, ARTIE ANS MYSELF DID A FOLLOW-UP ON 4/6/16.

Thank You Time Available: asap please

152957 Whittemore Closed Work Orders 2nd Request - NO A/C - Please check ASAP - This is the room with high humidity 3/21/2016 Orchestra Heating/Ven Checked room and found thermostat was at 72 degrees which is satisfied but actual 3/22/2016
Park Middle - and a roof leak that damaged instruments. It is priority. Time Available: any Room - 129 tilation /Air room temp was 75 degrees. Calibrated t/stat to read actual room temp. Watched unit
0013 Conditioning operate through complete cooling cycle. Configured blower fan to operate constantly
and not cycle with cooling. Left unit operating normally.

153492 Whittemore Closed Work Orders In room 109 we need a dehumidifier Time Available: asap 4/4/2016 109 Climate Arrived at school with dehumidifier for room 109. Found a dehumidifier already 4/7/2016
Park Middle - Control operating in room. Placed second dehumidifier in different location in room and plugged
0013 in. Checked unit operation, also checked room HVAC unit and found t/stat was out of
calibration. Re-calibrated and checked unit operation. Left unit operating normally.

Page 21 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
153525 Myrtle Beach Closed Work Orders need to check the air Quality in office Time Available: High importance 4/5/2016 room Heating/Ven I removed the blower assembly in the indoor unit cleaned it and also the cabinet area of 4/6/2016
Middle (old) - tilation /Air unit.. we placed two air purifiers in both office area. I will be picking one up for the third
0016x Conditioning office.. I reset this fan cycle to run all the time..( JEFF, DENNIS, ARTIE AND MYSELF
DONE A FOLLOW-UP on 4/6/16..

153632 Whittemore Closed Work Orders Walk in cooler has lots of mold. It is getting mold on our boxes of food. Time 4/6/2016 cafeteria Refrigeration Checked out and found sweating in box on ceiling in several places. We will have to 4/14/2016
Park Middle - Available: anytime empty the box and shut down to dry out. Then we will have to caulk all seams where
0013 air can leak in. This must be done during the summer when school is out. Will inform
Principal when back from Columbia. There is no mold evidence at this time. Adjusted
temperature control lower. Left unit operating normally.

154522 District Office Closed Work Orders Please confirm that all three roof top units are working correctly and drains are 4/21/2016 Heating/Ven 4-26-16 Service all three units in C-300 meeting room. Change belts and clean coils. 5/25/2016
Four Mile Road - draining , we have multi-able listing on the calendar for this room to be in use. Also tilation /Air Check drain operation and install pan pills. Set two smaller outside units down one
0401 need to verify the room humidity sensor is reading accurately and check all belts Conditioning degree lower than big center unit to do more dehumidification. Also sent big middle unit
and service as needed. to cycle indoor blower because that unit is the outside air unit. This should also help
with dehumidification. Check room humidity sensor for proper reading and calibration.
Correct reading is being reported to apogee. Making changes lowered humidity in room
from 62% to 55% in one day. Will follow up on the comfort level in this room to see if
changes are making a difference. 4-27-16 Replace blower bearing on
rooftop unit on left side of A building. Check all units and get list to change all belts. 4-
29-16 Check room temperature and humidity Room temp. at 71 and humidity at 54%. 5-
25-16 Replace all belts on all rooftop units. Check operation. Tested OK.

154753 Daisy Closed Work Orders teacher in room 408 is requesting a dehumidifier, see Dale Sumter Time Available: 4/26/2016 408 Heating/Ven 5-9 checked room found that room needed dehumidifier. Got one from shop and put in 5/10/2016
Elementary - asap tilation /Air room showed Dale how to work and keep water dumped. per Ross
0021 Conditioning

154941 Aynor High - Closed Work Orders For the last several days it has been extremely warm and humid in the principal's 4/28/2016 A106 Climate Checked out and room had high humidity. Replaced filters, adjusted set points and 5/4/2016
0001 office. You can tell a distinct difference in temperature and humidity when you walk Control monitored. Unit running normally at this time.
out of the principal's office and into another area. Time Available: ASAP

154945 Aynor High - Duplicate Request please lower the set points on HP-17 to decrease the humidity in the office. jg Time 4/28/2016 A106 Heating/Ven Worked performed on work order #154941.
0001 Available: asap Principals tilation /Air
office Conditioning

154952 Seaside Closed Work Orders The principal is concerned about room 102 feeling like there is no air conditioning in 4/28/2016 102, 201 Climate decreased cool setpoint to 72 in both rooms , spoke to Gary 4/28/2016
Elementary - there. The temperature says 73 degrees in there(102) and in the music room (201) Control
0050 but it feels very stuffy and humid like the moisture is not being taken out of the air.
Time Available: any
155266 Myrtle Beach Closed Work Orders Staff in this room says it feels very humid in this classroom. I have visited and it 5/2/2016 B105 Heating/Ven I placed a dehumidifier in this room to help with the humidity. 5/4/2016
High - 0010 does feel that way. tilation /Air
Conditioning

155405 North Myrtle Closed Work Orders Please change temp. back to 73, too warm in room with hot humid days. Time 5/3/2016 403 Heating/Ven 5-3-16 Set room Temp back down to 73 after raising because teacher was cold. 5/3/2016
Beach Middle - Available: 7:30 tilation /Air
0037 Conditioning

Page 22 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
155448 Conway High - Closed Work Orders NO AIR, IT IS HOT AND MILDEW SMELL, STUFFY NO AIR CIRCULATING! Time 5/4/2016 FRONT Climate Checked space and VAV box, found VAV access cover not on properly and leaking 5/4/2016
0004 Available: ASAP OFFICE Control air. Closed properly and checked and calibrated t/stat. Checked surrounding VAVs and
RTU. Checked main fain, belts and static pressure vanes. Also checked unit operation.
Found unit operating normally and space temp down to 70 deg.

155484 Myrtle Beach Closed Work Orders Mildew issues on the walls in drama room storage. 5/4/2016 drama room Painting 5/5/16, this is in kiln room area of drama room. Exterior vent has been left open for 5/12/2016
High - 0010 long periods of time allowing warm moist air to infiltrate room causing mildew build up
on walls. Will get mildew fogger tomorrow and attempt to clean area. 5/6/16, fogged
room with mildew killer. Will see about cleaning walls next week. 5/10/16, went to
clean walls. Teacher had not cleared room yet. Will do tomorrow. 5/11/16, finished
clearing out room. Cleaned walls and have fan running tonight. Will finish tomorrow.
5/12/16, returned racks to the room.

155554 Aynor Closed Work Orders need filters for humidifier asap- # 207, #202, #205 Time Available: asap 5/5/2016 3rd grade hall Heating/Ven Checked with Charles and found filters lost in transit, will replace when they come in. 6/1/2016
Elementary - tilation /Air Replaced filters in air purifiers.
0014 Conditioning

155760 North Myrtle Closed Work Orders pressure wash sidewalk and mold on walls around the building Time Available: 7:30 5/9/2016 out side Road/Street 8/15/16 I completed the walls out the front entrance and the wall facing hwy. 90. I talked 8/15/2016
Beach Middle - with mr. Cox and let him know what I had completed. He stated that he would work on it
0037 also.8/11/16. R.E. We started cleaning the front today.

155774 Pee Dee Closed Work Orders It appears MOLD is growing on the wall by the window. 5/9/2016 419 Climate Checked out and found this was not mold, Had painter come in and paint wall. Primed 5/18/2016
Elementary - Control and painted wall
0039
155775 Pee Dee Closed Work Orders Room is SMOLDERING HOT! 5/9/2016 413 Heating/Ven Checked out and unit was operating properly at this time. At set point. 5/11/2016
Elementary - tilation /Air
0039 Conditioning

155849 North Myrtle Closed Work Orders A/C is not working in room HP 66 is reading 78+ 5/11 there wont be testing in the 5/10/2016 G108 Heating/Ven 5-11-16 Check unit. 73 degrees in room when arrived. Check belt and motors AMP. 5/11/2016
Beach High - room if you can come tomorrow tilation /Air draw. Checked Freon and could not find any problem. Set down to 70 and watch unit
0002 Conditioning run. Room got down to 71. Set back to 72.
"Emmalee, AC is out again in G108 at 2:00pm the room was 77 with high humidity .
They are doing AP testing in there. I told Beth she should use
the big room which stays at 73 degs. "
155890 North Myrtle Closed Work Orders There is a constant problem of mold growing. We would like the mold cleaned up 5/11/2016 Wrestling Climate 5-11-16 Checked both units and set one unit to run at 74 day and night to remove 6/16/2016
Beach High - and preventative measures taken to stop the mold from continuing. Time Available: Room Control humidity. Other unit has bad compressor and is tripping breaker. Order compressor.
0002 ANY Will return and replace as soon as it comes in. 5-27-16 Called Trane about
compressor. Hopefully will be in in a few days. Coming from factory. Reclaimed Freon
from unit in preparation for compressor replacement.
6-13-16 Pickup compressor from Trane. I am going to try to install this week.
6-16-13 Remove and replace compressor. Evacuate system and went to start up and
found capacitor bad. Pickup and replace. Gas unit and check operation. 12 lbs. R-22
Tested ok.

156057 Forestbrook Closed Work Orders Request for AC to stay on in room over the summer 5/13/2016 Orchestra Climate duplicate wo 156058 5/13/2016
Middle - 0051 See Email Below: Room Control
In regard to the A/C and instruments, if the instruments spend summer months in
hot, humid conditions the wood could warp and the instruments that are housed
here over the summer could be damaged, resulting in a lot of money spent on
repairs.

Page 23 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
156058 Forestbrook Closed Work Orders Request for AC to be on in the summer to prevent black mold which has occurred 5/13/2016 Gym, PE Climate 6/30/2016
Middle - 0051 yearly since 2010 in the summer. In regard to Orchestra Room the instruments, if Locker room, Control
the instruments spend summer months in hot, humid conditions the wood could lecture hall
warp and the instruments that are housed here over the summer could be damaged, and orchestra
resulting in a lot of money spent on repairs. ro
See Ronnie Moses for Questions

156059 Forestbrook Closed Work Orders Request for AC to stay on in the summer in the lecture hall. Mold occurs every 5/13/2016 Lecture hall Climate this is a duplicate of wo 156058 so it will be closed 5/13/2016
Middle - 0051 summer since 2010. See Ronnie Moses custodian for questions. Control

156086 St. James Closed Work Orders Check for mold. Our office has an odor that smells like mold Time Available: 150 5/13/2016 Guidance Heating/Ven teachers said they smelled it on Friday , I checked 6-16,17,18 could not smell any thing 6/6/2016
Middle - 0047 Office on A tilation /Air A/C has been running all 3 days
wing Conditioning

156330 Kingston Closed Work Orders Their is mold growing in the top of the ceiling. Time Available: 7-4 5/17/2016 506 Roof The wall that the mold was on, have been clean 5/24/2016
Elementary -
0028
156331 Kingston Closed Work Orders The top of the ceiling has mold growing from it. Time Available: 7-4 5/17/2016 306 Roof In room the wall mold was on have been clean 5/24/2016
Elementary -
0028
156387 Riverside Closed Work Orders Check dehumidifier and deliver to room 506 per Richard Lane. 5/18/2016 506 Heating/Ven 5-18-16 Get dehumidifier from shop and test run. Cleaned filter and evap. coil. Remove 5/18/2016
Elementary - tilation /Air drain hose and make cap to use with internal bucket. Deliver to room 506 and set up
0068 Conditioning and explain operation to Mr. Ritchie and teacher.

156563 Ocean Bay Closed Work Orders please replace caulking in the refrigerator it is all molded. over the summer please. 5/20/2016 kitchen Flooring 6/8/16, went and looked at this with Mrs. Burrelson. Neither her or myself could find 6/9/2016
Middle - 0061 any problem at all with the refrigerator door.

156735 St. James High - Closed Work Orders We have a hole in the gutter that is right above the door leading into the varsity field 5/24/2016 Varsity field Carpentry Got on roof and found 3 holes in the gutter. Wiped away all the dirt and grime. Sanded 5/24/2016
0058 house. The hole is about the size of a quarter. I tried looking for some flex seal or house area around holes with a sanding block. Cleaned area with Dirtex. Caulked area with M-
something to plug the hole for the time being but i was unsuccessful. Water is 1 roof caulk. Inspected the rest of the gutters on the field house. All other gutters were
draining through the hole onto the brick wall and concrete entrance causing mold ok.
and mildew to grow. Can we plug this hole? Thank you Time Available: med

156934 Riverside Closed Work Orders Wall at dishwasher is full of mold. I would like to get it covered with the white board 5/27/2016 kitchen Carpentry Went to Riverside,cleaned the walls good,and cut silicone seal where dishwasher 8/8/2016
Elementary - please. meets wall.cut panel to fit behind dishwasher,applied glue then put panel on wall.Could
0068 only get one piece up.To get the other panel up,the dishwasher would have to be
disconnected and moved.
157077 Burgess Closed Work Orders Pod #700 Portable classroom restrooms... air is blowing but is blowing 5/31/2016 pod#700 Heating/Ven Checked the temp. on the thermostat in the hall next to the boys and girls restroom. 6/6/2016
Elementary - warm... tried thermostat and checked temp. humidity level seemed high also... portable tilation /Air Thermostat showed that the temperature was 72 degrees. Went outside to check to
0063 unit is running... checked outside at unit also. found nothing other than just classroom Conditioning make sure that compressor and outdoor fan were running. They all were running in a
running warm air. Please see Lynn Time Available: anytime normal order because there was a steady flow of condensation coming out of the unit.
Went ahead and changed all the AC filters in the wall pack units. Used the HI JACKER
to change all the AC filters in the high ceilings.

157081 River Oaks Closed Work Orders Room 606 HP:-72 Room was 74.5 and climbing, room real humid as well, changed 5/31/2016 606 Heating/Ven CHECKED UNIT OPERATION. FOUND UNIT OPERATING PROPERLY. ROOM 6/1/2016
Elementary - filters today in room. Time Available: any tilation /Air WAS 73 DEGREES. SUPPLY AIR TEMP WAS 50 DEGREES.
0065 Conditioning

157083 Riverside Closed Work Orders Pipes in cooler needs to be rewrapped due to tearing and mold. 5/31/2016 kitchen Heating/Ven 5-31-16 Check drain pipe in cooler. took cleaner in and cleaned pipes in cooler to get 11/30/2016
Elementary - tilation /Air stains off insulation
0068 Conditioning

Page 24 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
157315 Burgess Closed Work Orders Room # 117 6/3/2016 ROOM # 117 Climate Please check the hvac system to make sure it is working properly in this area. we went 6/3/2016
Elementary - Mrs.Beers... teacher has observed a recurring issue of mold growth... and a Control and checked the room we looked up in the ceiling to see if anything was wet we found
0063 moisture problem along back right side of room on wall around and behind a bulletin nothing we looked on the computer it was showing cooling good and the room was
board. feeling good room temp was 73degree had arron look at it and cleaned it off we think it
teacher is very concerned with mold issues. sensitive to molds and moisture. was just dust from they drilling screws in the wall to hold the board up
* Not sure of problem catagory... any help or direction is appreciated. Questions
contact Lynn. Thank you. Time Available: anytime

157442 Myrtle Beach Closed Work Orders Temp reads good on the thermostat but it feels humid in this room please check it 6/3/2016 B107 Heating/Ven I turned on the fan cycle to see if the humidity would lower it self.. the temp is fine.. 6/7/2016
High - 0010 out. tilation /Air
Conditioning

157469 Forestbrook Closed Work Orders Good morning, 6/6/2016 805, 808, Roof Fire alarm panel was showing alarm present on duct detector in media center 6/6/2016
Middle - 0051 I am at school the fire alarm is going off again because duct detectors are being set Library conference room. Went and found detector for cleaning. Detector had been unhooked
off by a leaking roof. and was not tied into system. Disabled smoke detector from system. Reset portable fire
The alarm went off in the media center, 808 Stone’s room and 805 Macasek’s alarm panels. Reset main fire system. All alarms were cleared. Enabled smoke
room. There is standing water in the storage room in 805 Macasek’s room. The detector back on. After ten minutes or so. Alarm went back off. Same alarm for same
building is extremely hot and humid. Prinicpal's office is not reading a temperature detector. Disabled detector again. Reset all panels and main panel again. Left smoke
and neither is the media center on temp gauge. According to the fire dept this is the detector in media conference room disabled. Called every electrician at HCS to see
5th time they have reported to a false fire alarm this year at FMS due to the duct who had disconnected smoke detector. No one knew or was aware of problem with this
detector being tripped by the roof leaking and causing steam from hitting the electric detector. Checked 808,805 and media center for water leaking into duct detector.
or lights. Please let me know if there is anything else that needs to be done. I know There is no water present in any of the rooms,on the floor or above the ceiling. The A/C
it is supposed to rain for several days so we may need to put the system in test so in room 805 is condensing pretty bad. I called Greg Gore and he instructed me to turn
that it does not continue to go off. Please advise. the unit off until he could arrive to check the unit out. Phillip stated that Simplex will be
contacted to replace duct detector in 808 and look at media center conference room
Thanks, duct detector. Met with Mr. Weaver from Simplex and showed him all of our findings.
April Scott Principal He said he would be ordering tow duct detectors and replace both. One in media
conference room. And one in 808 storage.

157484 North Myrtle Closed Work Orders Walls need to be repaired in the wrestling room. Serious mold issues with air quality 6/6/2016 Wrestling Carpentry Repaired walls in wrestling room. 9/15/2016
Beach High - issues. Time Available: ANY Room
0002
157768 Aynor High - Closed Work Orders Please inspect the dehumidifier in this classroom to ensure it is operating normally 6/7/2016 C101 Heating/Ven Checked out dehumidifier in this room and one next to it . They were working normally, 6/23/2016
0001 for the upcoming school year. Time Available: anytime tilation /Air cleaned filters, checked operation on both- running normally at this time.
Conditioning

157783 Forestbrook Closed Work Orders Girls and Boys locker room AC not working. We have had ongoing issues with mold 6/7/2016 Boys and Girls Heating/Ven we went and checked the units they both was reading 75 degree at t-stat I checked all 6/8/2016
Middle - 0051 in these areas need help ASAP. Locker room tilation /Air the parts on the air handler and condenser they were working good I looked on the
Conditioning computer and all the mau was off I turn them back on we waited a few minutes and the
See Ronnie Moses for questions rooms started cooling down left room cool

157822 St. James Complete Black/green mold needs removed from steps on both porches. Time Available: 150 6/8/2016 Portable 248 Custodial complete 10/18/2016
Middle - 0047

158104 Myrtle Beach Closed Work Orders conference room #1 on admin hall. Very humid. Thermostat located here. Could 6/14/2016 Custodian hall Heating/Ven found outside unit not running tripped out on low pressure switch low on refrigerant add 6/16/2016
Middle (old) - someone stop by to check. Front admin area-hall- offices very humid. Lisa Selph tilation /Air refrigerant,
0016x Conditioning

Page 25 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
158209 Myrtle Beach Closed Work Orders Temp reads good in room but very humid in this room. 6/16/2016 B105 Heating/Ven I turned the temp back up to 73 degrees.. the unit should cycle off more to get rid of the 6/16/2016
High - 0010 tilation /Air humidity..
Conditioning

158242 Myrtle Beach Closed Work Orders Temp reads okay in this room but it's very humid in there 6/16/2016 PE114 Heating/Ven drain has stopped up .. which had system shut off.. I cleared the drain and also drain 6/20/2016
High - 0010 tilation /Air pan.. system now running.
Conditioning

158523 Myrtle Beach Closed Work Orders Media Center - Mr. Higgins reported today that thermostat is reading 80 at the back 6/23/2016 108 Heating/Ven rooms 108 ,109 and lecture hall has smoke detectors bad .. removed and cleaned them 7/7/2016
Middle (old) - of Library and it is humid in Library. Question - Should temperature stay 72 because tilation /Air but still will not reset.. Ron at Simplex said that Paul would be at school on Thursday for
0016x for book preservation? Conditioning repairs and programing system. we checked supply and return detectors.. simplex
came repaired the problems with the system..

158691 Forestbrook Closed Work Orders The AC unit in the girls locker room is not working. This area molds very quickly. 6/28/2016 Girls Locker Heating/Ven Checked the AC in the girls locker room to make sure it was on and working properly 7/11/2016
Middle - 0051 Please see Ronnie Moses for questions. Time Available: 7:30-5:30 Room tilation /Air and it was. Then checked the MAU in the girls locker room, and found a bad belt in the
Conditioning air handler. Replaced the bad belt and released cooling loop out to the air handler and
checked to make sure air handler came on. Will have to come back with the Hi jacker
because one of the gym AC units drain line is stopped up. I told MR Mosses that we will
be back either on 6-30-16 or the first of next week. 7/6/16 we fixed the line on the girls
locker room MA unit We had Robert's paint to come in and wipe the walls before the
first day of school

158696 Waccamaw Closed Work Orders need a dehumidifier 6/28/2016 116 Heating/Ven DELIVERED DEHUM UNIT. 8/24/2016
Elementary - tilation /Air
0042 Conditioning

159024 Forestbrook Closed Work Orders There is no A/C in the gym, and mold has developed. We will need assistance 7/5/2016 gym/girls Heating/Ven same as wo#158691 7/7/2016
Middle - 0051 wiping down the gym walls. Time Available: 7:30-5:30 locker room tilation /Air
Conditioning

159098 Forestbrook Closed Work Orders moldeling pulling on stall Time Available: any 7/6/2016 5th grade boys Carpentry Metal strips on the bottom of the dividers were warped. Removed metal strips from 7/6/2016
Elementary - restroom dividers.
0046
159099 Forestbrook Closed Work Orders spoke to gray harrleson carpet moldeing 314/313/310/311/210/208/405/202/205 7/6/2016 carpet Carpentry 7/6/16 Vivian called me and told me the transition strips were coming loose from the 8/2/2016
Elementary - Time Available: any moldeing in carpet. I told her to be sure and keep them, so they could be reinstalled.
0046 classroom
159355 River Oaks Duplicate Request Need someone to come and look into the humidity in the nurses office and what it is 7/12/2016 Nurses office Heating/Ven OUTSIDE AIR AND HUMIDITY ISSUE. SEE W.O. 160008 7/25/2016
Elementary - doing to the ceiling tiles. Also the front adult restroom has an issue that I will explain tilation /Air
0065 when you come. Pkease have me paged. Conditioning

Thank You Time Available: asap please


159394 Myrtle Beach Closed Work Orders Basketball tournament in Gym all week. It is in system for air. Double checked this. 7/12/2016 GYM Heating/Ven found 1 unit turned off.. the 2nd unit had a fan motor not running.. it had blown fuses .. I 7/18/2016
Middle (old) - Very humid - can someone come check system? tilation /Air replaced them and gas system back to normal charge . system is now working ok..
0016x Thank you, Lisa Conditioning

159494 Forestbrook Closed Work Orders Lost of AC in the building on 7/6/16 created mold on gym walls. A request for wiping 7/14/2016 gym Custodial walls cleaned on another work order 8/18/2016
Middle - 0051 down the walls was submitted with the AC work order; however, the work order is
listed as closed without the walls being addressed. See Ronnie Moses for
questions. Time Available: 7:30-5:30

Page 26 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
159685 Myrtle Beach Closed Work Orders Extremely humid in room. Will be holding interviews this week. 7/19/2016 Conference Heating/Ven unit on low charge add r22 refrigerant. 7/25/2016
Middle (old) - room 1 tilation /Air
0016x Conditioning

159767 Forestbrook Closed Work Orders moldleing on stall sticking out Time Available: any 7/20/2016 rest by Big Key and repaired molding 7/26/2016
Elementary - Gym Lock
0046
159878 Kingston Closed Work Orders Three vents needs to be painted above front desk. Mold around the vents. Time 7/21/2016 Front desk Painting The vents above the front desk have been cleaned, primed, and painted 7/24/2016
Elementary - Available: 7-4
0028
159919 Waterway Closed Work Orders A/C UNITS FAILED HP 28 RM 415 , HP 28 A , HP 46 , HP 14 Rm. 514 & MAU 01 7/21/2016 Heating/Ven 7/25/ found breaker off for hp28,28a. unit came on and cooling.will check on when I 7/28/2016
Elementary - ROOM CO2 & MAU 01ROOM HUMIDITY tilation /Air go back. also checked computer room in library hp29 was off on head pressure fault.
0067 Conditioning reset unit and found no problem. unit cooling properly.

160008 River Oaks Closed Work Orders Following rooms have wet ceiling tiles, looks like pipes are sweating, not sure : 7/25/2016 several Heating/Ven CHECKED MAU OPERATION. FOUND ENTIRE SUPPLY TRUNK AND DUCTS 7/25/2016
Elementary - 315, 314, 313, 312, 310, 316, 317, 308, 306, 310, 307, 311, 416, 608, 609, 611, tilation /Air ABOVE CEILING ARE SWEATING AND DRIPPING WATER DOWN ONTO TILES. I
0065 612, 613, 501, Conditioning BELIEVE THIS IS BEING CAUSED BY THE ONGOING ISSUES WITH BUILDING
Ceiling tiles have been ordered for replacement on 7-25 sa NEGATIVE PRESSURE CAUSING OUTSIDE AIR AND HUMIDITY TO BE PULLED
Dennis has been emailed as well Time Available: asap please INSIDE BUILDING. I SPOKE SPOKE WITH D. MRCRARY ABOUT IT. HE MADE
ADJUSTMENTS TO MAU SETPOINTS TO TRY TO FIX THE ISSUES.

160126 St. James High - Closed Work Orders Our AC units in our press box needs cleaning please. I have a report that they may 7/26/2016 Press box Heating/Ven we went and checked the thru the wall units they all are working good just the filters are 7/28/2016
0058 have some mold in them. Thank you Time Available: low tilation /Air old and are breaking apart I called the supple company and they have order me new
Conditioning one

160137 Myrtle Beach Closed Work Orders Humid in the room and A/C unit is leaking water down from it. 7/26/2016 PE 114 Heating/Ven I had to add gas to system again.. I cant find the leak.. I also wrapped the bottom with 7/28/2016
High - 0010 tilation /Air insulation .. THIS UNIT NEEDS TO BE REPLACED .. I HAVE HAD NUMEROUS
Conditioning WORK ORDERS ON THIS SAME UNIT..

160498 Forestbrook Closed Work Orders boys girls lockers no air, just finish wiping down walls last THURSDAY FOR 8/1/2016 gym boy Heating/Ven we went and checked the unit. The air handler was working properly. We checked the 8/8/2016
Middle - 0051 MILDEW PLEASE HELP Time Available: anytime /girllockers tilation /Air condenser and the fan was not working. I checked the ohms on it it was reading low I
Conditioning called Charles to order me a new motor. I got the new motor in we replace it and left
unit working properly.

160595 North Myrtle Closed Work Orders Room 404 - closet inside room has a ceiling tile that is coming loose and teacher 8/2/2016 404 Heating/Ven Checked found tile about to fall out. took old tile down and put new in place. 8/3/2016
Beach Middle - said it has left mold on her filing cabinet. Time Available: 7:30 tilation /Air
0037 Conditioning

160682 Green Sea Closed Work Orders Mold on the chairs in this office and on the student computers stored in the office. 8/3/2016 305 Heating/Ven 8/4 checked a/c units in room 305,library, and library office. all cooling properly. 8/9 8/9/2016
Floyds High - tilation /Air placed dehumidifier in room 305 and one in office. changed all filters in library
0006 Conditioning andjoining offices.

160685 Myrtle Beach Closed Work Orders Humid in office 101I - Thank you, 8/3/2016 101 I Heating/Ven system was a little low in gas .. added gas to system.. 8/10/2016
Middle (old) - tilation /Air
0016x Conditioning

Page 27 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
160743 Aynor High - Closed Work Orders Please install a dehumidifier in classroom B103. It is an old science lab in an area 8/3/2016 B103 Heating/Ven Installed dehumidifier in classroom, cleaned the coil on dehumidifier 8/19/2016
0001 of the building that has moisture issues. The new teacher occupying that classroom tilation /Air
has been working to prep her room and has noted a smell and moisture issue. This Conditioning
new teacher is also pregnant. Please install a dehumidifier as soon as possible.
Time Available: ASAP
160776 Burgess Closed Work Orders CAFETERIA... cafeteria is HUMID... 8/4/2016 CAFETERIA Heating/Ven we went and checked the unit they are putting new units in the building. The unit had 8/4/2016
Elementary - does not seem to be cooling tilation /Air tripped out I reset it left unit working properly
0063 you can hear units running but cant feel any cool air. Time Available: anytime Conditioning

160786 River Oaks Duplicate Request Inside gym office, the area above the ceiling tiles need to be treated again from 8/4/2016 512 Gym Heating/Ven AREA WAS RETREATED AND CLEANED BY M. VANDEUSEN ON A SEPARATE 8/23/2016
Elementary - previous leak we had and ceiling tiles replaced. (mildew) Strong oder Time office tilation /Air W.O.
0065 Available: asap please Conditioning

160814 Myrtle Beach Closed Work Orders There is mildew in rooms B-107,108 and 109. Please check the air in this area. 8/4/2016 Heating/Ven the units in these room are working. 71 to 72 degrees.. if they want the temp turned up 8/4/2016
High - 0010 tilation /Air I can do that .. room have been cleaned .. also replaced a capacitor on blower motor for
Conditioning the front office area..

160844 Daisy Closed Work Orders teacher in room 719 reports a humid feel and musty smell in that room. can you 8/4/2016 719 Heating/Ven found no problem with unit. dale said he was going to change filters. they were dirty 8/9/2016
Elementary - check it out for us? Time Available: asap tilation /Air
0021 Conditioning

160861 Forestbrook Closed Work Orders AC not working properly in gym/locker rooms. Mold has developed on the walls. 8/5/2016 gym Heating/Ven CHECKED AC UNITS IN THE GYM AND THEY WERE COOLING CHECK BOTH OF 8/15/2016
Middle - 0051 Space used for professional development on Tuesday, August 9th tilation /Air THE THERMOSTATS IN THE GYM AND THEY WERE READING 74 DEGREES.
Conditioning ALSO CHANGED OUT BAD CONDENSER FAN MOTOR THAT WORKED THE AC
Please see Ronnie Moses Time Available: Anytime UNIT IN THE BOYS LOCKER ROOM.

160870 North Myrtle Closed Work Orders The 8th grade wing has been cleaned multiple times by our custodial staff. The 8/6/2016 812/813 Climate Checked rooms found both units running and keeping rooms at 74 degrees. No 8/10/2016
Beach Middle - walls are covered in mildew once again. We have had the climate control adjusted Control Problem found with A/C units
0037 and it is still not helping. Time Available: immediately

160966 St. James High - Closed Work Orders We do not have any lights in our auditorium. We do not have house lights or stage B-146 F217 Electrical I had to go and reset a few units and I had to cleaned some of the units drain lines out.
0058 lights. We need to have lighting by Thursday morning. Also in room F-217 we do not we have sent Southern Lites to make repairs. Repaired short in dimmer module and
have any lights. I am having issues with the air conditioning as well. This was placed preposition curtain
on a separate work order to the AC department. I did not know if these 2 issues
were connected. Time Available: High
8/8/2016 8/19/2016
160999 Myrtle Beach Closed Work Orders The air in the lecture hall is very damp and musty. There is mold growing on the 8/8/2016 Lecture hall Heating/Ven working on the humidity in the lecture hall.. placed dehumidifiers and o-zone machines 8/14/2016
Middle (old) - chairs and we are currently cleaning them. We are requesting a large dehumidifier tilation /Air .. found bad belts on a air handler on the G -hall. lecture hall room had been cleaned
0016x be brought in like last time. Time Available: any Conditioning before I got there.. I did not see any mildew at this time..

161107 River Oaks Closed Work Orders room 101 HP-78 running 64 degrees, ceiling tiles are soaked thru the room, sweat 8/9/2016 101 Heating/Ven CHECKED UNIT OPERATION. UNIT OPERATING PROPERLY. ROOM TEMP WAS 8/23/2016
Elementary - on door and wall at entrance tilation /Air 73 DEGREES. RH WAT 50%.
0065 Conditioning
restroom next to office is extremely wet on walls, floor and humid, not sure if the 2
are caused by same thing or not Time Available: asap please

161176 Myrtle Beach Closed Work Orders check for airflow /AC related issues for reoccurrence of mildew on walls in those 8/9/2016 B107 &108 Heating/Ven I have not found any thing wrong with the a/c units in these rooms.. I placed 8/10/2016
High - 0010 rooms. tilation /Air dehumidifiers room to see the room are become humid at night when the system is
Conditioning shut off..

Page 28 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
161493 Daisy Closed Work Orders room 412 is registering 81 degrees, the dehumidifier in 706 has to be emptied 2x or 8/12/2016 412 & 706 Heating/Ven Checked room found condenser off on high pressure switch. reset and watched unit 8/15/2016
Elementary - more a day, could we get a bigger one in there? Time Available: anytime tilation /Air operation. unit running good and pressures good at this time.
0021 Conditioning Dehumidifier is working good. don't have one bigger

161520 South Conway Closed Work Orders Room is too hot and very humid. Ceiling tiles replaced with new a/c unit in class 8/12/2016 212 Heating/Ven These problems have been rectified by contractor who has done the work. 8/23/2016
Elementary - was a very sloppy job per teacher. Time Available: any tilation /Air
0045 Conditioning

161545 Conway Closed Work Orders we have a few more items for pick up: 8/12/2016 kitchen/adult Furniture 8/26/16 Picked up fixed assets. 8/26/2016
Education 4 wicker chairs, 3 blue racks, 3 brown chairs, 2 floor lamps, 5 assorted chairs, 2 ed hall
Center - 0172 brown benches, 1 wicker foot stool with cushion, 2 white book shelves, 5 pull down
screens, 1 dehumidifier and 1 box fan. Time Available: Asap

161567 Lakewood Closed Work Orders We need a couple of dehumidifiers in our building. All that we have are being used, 8/12/2016 Old Talking Heating/Ven Delivered dehumidifier to the talking trash room also went on the roof to check the belts 8/31/2016
Elementary - but we have more rooms that need them. The old Talking Trash room (no room Trash Room tilation /Air on the package unit that supplied conditioned air to that room to make sure they were in
0029 number but on main hallway next to computer lab) definitely needs one as soon as Conditioning good working order, checked the fan and the compressor to make sure that they were
possible. Time Available: anytime working properly.

161582 River Oaks Closed Work Orders Coaches office has mildew from roof leak 8/12/2016 Heating/Ven 8-09-16, used mildew dogger in office. Cleared smell. 8/16/2016
Elementary - tilation /Air
0065 Conditioning

161708 St. James High - Closed Work Orders In room D-110 it becomes very warm and humid. The room will not stay cool. Thank 8/15/2016 D-110 Heating/Ven under same work order 160966 8/19/2016
0058 you Time Available: medium tilation /Air
Conditioning

161721 South Conway Closed Work Orders Classroom is very humid and stuffy. Ceiling panel still needs to be fixed correctly. 8/15/2016 208 Heating/Ven These issues have been or will be rectified by contractor who is installing new units. 8/23/2016
Elementary - Time Available: any tilation /Air
0045 Conditioning

161783 Pee Dee Closed Work Orders Room is very hot & humid. Thermostat may be broken! 8/15/2016 202 Heating/Ven Checked out and found no problem with unit, it was running normally- teacher was just 8/18/2016
Elementary - tilation /Air worrying since she had problems in the past.
0039 Conditioning

161802 Homewood Closed Work Orders the teacher in this room is complaining about the room having a musty moldy smell. 8/15/2016 609 Heating/Ven Checked out and found unit putting out smell. Tore apart and cleaned inside cabinet of 8/18/2016
Elementary - Time Available: asap tilation /Air unit and cleaned blower wheel and housing. Put back together and all was fine at this
0025 Conditioning time.

161837 Lakewood Closed Work Orders This room is very hot, humid and muggy. There is no thermostat located in there. 8/15/2016 307 Heating/Ven Delivered dehumidifier to room 307 and talked with the teacher about her room. I also 8/31/2016
Elementary - She may need a dehumidifier to keep in there too. Time Available: anytime tilation /Air told her that I would go on the roof and check that package to make sure that it was
0029 Conditioning running properly. I went up on the roof and check all the high voltage and low voltage
and made sure that the blower motor was running. The blower motor was running I also
checked to make sure that the condenser fan motor and compressor was running and it
was all operating normal.

Page 29 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
161850 Burgess Closed Work Orders ROOM #508... room temperature has risen over past hour. 8/16/2016 ROOM #508... Heating/Ven I went and cleaned the drain pan and the drain line out left unit working properly 8/17/2016
Elementary - seems to be blowing warm. no cool air... humid hot. tilation /Air
0063 ...Thank you for doing what you do~ Time Available: anytime Conditioning

161878 Forestbrook Closed Work Orders No AC in the Gym... Area develops mold/mildew immediately when no air is 8/16/2016 Gym Heating/Ven Had company come clean walls. CHECKED GYM UNITS AND FOUND THAT THE 8/17/2016
Middle - 0051 circulating. tilation /Air UNITS WERE SHUT DOWN BY FIRE ALARM SYSTEM. We have had Gym and
See Ronnie Moses Time Available: anytime Conditioning Locker rooms cleaned and painted

161966 Myrtle Beach Closed Work Orders Room has had a humid feeling in it all day long. Temp was running 75 degrees in 8/16/2016 B107 Heating/Ven I didn't find any thing wring with room 8/18/2016
High - 0010 there all day long. tilation /Air
thanks, Conditioning
Adam

162068 Kingston Closed Work Orders Mold on the studio wall in library. Time Available: 7-4 8/17/2016 306 Painting Cleaned. Wall and air vent and light lens 8/24/2016
Elementary -
0028
162105 Lakewood Closed Work Orders Conference rm./classroom 300 wing very humid 8/17/2016 conferece Heating/Ven Used wet vac. and hoses to cleaned out drain lines and emptied the over flow pan. 8/31/2016
Elementary - 801 gym office - no a/c rm./classroom tilation /Air When new order of ac filters come in I need to come back and change out the old
0029 & 801 office Conditioning filters.

162149 Lakewood Closed Work Orders Temp. is 71 but the room is very humid 8/17/2016 304 Heating/Ven under the same work order 162155 8/19/2016
Elementary - tilation /Air
0029 Conditioning

162210 Conway Closed Work Orders The dehumidifier in the room has stopped working. Time Available: Asap 8/18/2016 TLC Hall - Heating/Ven This work will be completed on W.O.#162083 . 8/21/2016
Education Room 104 tilation /Air
Center - 0172 Conditioning

162241 St. James Closed Work Orders Mold in concession stands. Time Available: 150 8/18/2016 Concession Climate under work order 162582 8/24/2016
Middle - 0047 stand Control

162268 Socastee High - Closed Work Orders Clean mildew off of Senior Balcony 8/18/2016 Senior Carpentry Had Robert's paint to pressure wash senior balcony while he was cleaning front 8/18/2016
0011 Balcony entrance

162384 Green Sea Closed Work Orders The thermostat is reading 74.2 degrees it is very humidity in the room Time 8/19/2016 Room 208 Heating/Ven Checked room found unit satisfied ran unit and watched unit operation unit checked ok 8/22/2016
Floyds Available: ASAP tilation /Air at this time
Elementary - Conditioning
0023

162386 Green Sea Closed Work Orders The thermostat is reading 74.9 Degrees it is very Humidity in the room. Time 8/19/2016 Room 206 Heating/Ven Checked room found unit satisfied. Ran unit and watched operation unit checked ok at 8/22/2016
Floyds Available: ASAP tilation /Air this time
Elementary - Conditioning
0023

162425 St. James Closed Work Orders The air in B-11 comes on and then goes off. several times a day. At times it is very 8/19/2016 B 11 Heating/Ven this is a new unit have to call dennis and let him get contractor out 8/24/2016
Middle - 0047 hot and humid. Time Available: 150 tilation /Air
Conditioning

Page 30 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
162434 Aynor Middle - Closed Work Orders need to make sure this room humidity stays below 60% the reason being this is the 8/19/2016 311 Heating/Ven Checked out and found humidity high. Talked with Richard Lane and made adjustment 8/29/2016
0057 orchestra room high humidity damages the instruments thanks Time Available: asap tilation /Air to fan. System does not have humidity control in building, so we can only do certain
Conditioning things. Room should come down as outside humidity drops.

162436 Daisy Closed Work Orders In reference to a previous WO requesting a de-humidifier that will not have to be 8/19/2016 708 Heating/Ven Took new/used dehumidifier to room and set up for teacher 8/23/2016
Elementary - emptied twice a day the teacher has replied "I know the district said they did not tilation /Air
0021 have any bigger humidifiers, I was wondering if they had any that were quiet. I have Conditioning
to run the one that I have when there are no students so they don’t talk over it."
Time Available: asap

162777 Myrtle Beach Closed Work Orders This is a follow up to work order #157086. The teacher still believes that the air in 8/23/2016 room 205 Heating/Ven I checked this room last year for this teacher. there is not a/c in this area.. sorry. 8/24/2016
Middle (old) - the small rooms is not sufficient enough to keep the instruments from growing mold tilation /Air
0016x or rusting due to higher temps and humidity. These are basically large storage Conditioning
closets with a vent. I explained that the thermostat is in the main room and the room
temp in that room will determine whether the air came on or not. I suggested
keeping the closet doors open so air temperatures would equalize. He still wants to
have a technician look at the system. Time Available: any

162804 North Myrtle Closed Work Orders Classroom has an odor that smells similar to mold 8/23/2016 F106 Climate Checked F106 Found unit not running got bad compressor. Doing work on 8/25/2016
Beach High - Control WO#162639
0002 Teacher planning is 9:45-11:45 Time Available: asap
163123 Myrtle Beach Closed Work Orders We are receiving a large amount of complaints about the air quality and dampness 8/26/2016 throughout the Heating/Ven I have changed the air filters in the make up air units in 6th , 7th , 8th and the gym 9/6/2016
Middle (old) - of the building. The schools administration is concerned about the health of the building tilation /Air halls. and also vacuumed out drain line and pans in all the rooms that I have had work
0016x faculty, staff and students. We are constantly battling mold and mildew in many Conditioning orders on..
different areas of the building and there have been several staff members getting
sick since coming back from summer break. There are on average, 5 classrooms a
day that require the condensate pans to be emptied. We changed the filters 2
weeks ago but that didn't help the air quality. I don't know if there is anything that
can be done to improve the air quality but when the dehumidifiers were brought in
before school started there appeared to be at least some improvement. Dr. Christie
would like to have a conversation about any possible remedies. Time Available: any

163375 Myrtle Beach Closed Work Orders got a email from teacher in room 120 said when a/c came on their was an bad odor 8/29/2016 room 120 Heating/Ven I looked above the ceiling tile and open the air handler to check for MOLD .. I DID NOT 8/30/2016
Primary - 0035 she said smell like mold i did not can you come a check thanks. Time Available: tilation /Air FIND ANY THING BESIDE SOME DUST IN THE UNIT ... NO MOLD.... inside of unit is
anytime Conditioning dry.. I don't know what the smell was that the teacher had smelled..no mildew or mold..

163514 Aynor High - Closed Work Orders Mr. Speer requests: 8/30/2016 Auditorium Heating/Ven Checked out and adjusted temperature. Room was maintaining temp and humidity. 9/2/2016
0001 It has been warm and very humid in the auditorium. Is there a controlled tilation /Air
temperature and humidity level that can be set electronically? Conditioning

Between 40-60% humidity is the ideal for keeping instruments. It’s at least 76% or
above in there. Can we have it set for about 72%?
Time Available: anytime
163587 Aynor Middle - Closed Work Orders humidity sensor is broken off the wall. Time Available: asap 8/31/2016 outside 408 Heating/Ven Checked out and replaced broken humidity sensor. Operating normally at this time. 9/1/2016
0057 tilation /Air
Conditioning

163614 Forestbrook Closed Work Orders Roof is leaking in the gym. We are currently using a trashcan to capture the water. 8/31/2016 gym Roof Walked to a few areas of concern with Mrs. Pilkey. Explained the situation with the rain 9/16/2016
Middle - 0051 and I would get to the roof when the rains are subsidized. 9/16/16- Got all my tools on
Also, the moisture is creating a mold/mildew issue in the locker rooms. Time the roof to do the job. Pressure washed areas that are leaking. Blew area with blower to
Available: anytime remove any extra dirt and water. Applied Gaco to areas. Got tools off roof, cleaned up
and loaded truck.

Page 31 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
163777 Myrtle Beach Closed Work Orders It could be mold or need to be painted. Can not really tell. 9/2/2016 cafeteria Painting 9/8/16, scraped wall and removed mildew. Dried and painted first coat. 9/14/2016
Intermediate -
0053
163838 Scholars Closed Work Orders Mr McQueen had put in an email and was told to put in a work order. Not sure what 9/2/2016 116 Heating/Ven I went and checked the unit. I did not find anything wrong with the unit and the room 9/9/2016
Academy CCU - depth. to select. Teacher said she has allergies and they are acting up bad in her tilation /Air had no bad smell in it. They was think the make-up air unit control the room and it had
0178 classroom she spilt and was cleaning a drink off the carpet and her ARMS Conditioning bad wet filters in it before and that was causing the smell or and other things wrong with
SWELLED UP. SHE STATED that some students have had symptoms as well. her. I explain to Mr.shawn the a/c had nothing to do with her symptoms unit was
used Host machine with host cleaner and resolve carpet cleaner. I'm thinking it working properly and filters was change on correct date
may be mold since her air filters were full of water last year. Time Available: 7-4

164253 St. James High - Closed Work Orders In room C-126 it has been extremely warm and humid for the past 2 days. Can we 9/7/2016 C-126 Heating/Ven I went and checked the unit. The loop out was at 0 I release it and unit came on and 9/12/2016
0058 make sure the AC is working properly in this room . thank you Time Available: tilation /Air start cooling the room. we are having a problem with this room drain backing up
medium Conditioning

164321 Myrtle Beach Closed Work Orders teacher is requesting a dehumidifier be place in her room. 9/7/2016 B102 Heating/Ven found a bad blower motor. I had to order one. replaced the motor on 9-16-16 9/19/2016
High - 0010 tilation /Air
Conditioning

164327 Forestbrook Closed Work Orders Mold/mildew is returning to gym and locker room walls due to AC issues and roof 9/7/2016 gym Custodial We had Custodial staff to clean locker rooms and up to 8 ft in gym. We had Roberts 11/22/2016
Middle - 0051 leaks. Time Available: anytime Paint to clean the rest of high areas of gym.

164453 Aynor Closed Work Orders new gaskets need installed on both milk cooler doors. cannot get mold off . ripping. 9/8/2016 cafeteria Kitchen installed milk cooler gasket 9/13/2016
Elementary - Time Available: asap Equipment
0014
164699 Green Sea Closed Work Orders The AC is not working properly in room 230 and other rooms on the same hall. This 9/12/2016 230 (Other Heating/Ven found bad room sensor in room 230. replaced sensor and roomcooling now. other 9/12/2016
Floyds High - morning the rooms on that hall were very humid and there was an odor in the rooms on the tilation /Air rooms on same hall were reading 73-74 degrees and supply air in 50s. checked room
0006 rooms. same hall) Conditioning 208 and found a/c unit staying off a long time before coming back on. reset points and
unit running and cooling.

164790 Aynor Middle - Closed Work Orders To Mr.Terry Hucks rooms 201,202,711 has musky mildew smells need to be 9/12/2016 201,202,711 Carpentry Checked room 711 and found two ceiling tiles that were wet from HVAC lines and 10/3/2016
0057 checked for mold thanks. Time Available: asap found some dust on walls and vents, spoke with Eric about it. also had carpet cleaned
in 201 and 202, carpet was very dirty. Also clean carpet in Guidance office.

164858 Daisy Closed Work Orders room 306 may need a de-humidifier this is our kid care afterschool room and when 9/13/2016 306 Heating/Ven a/c working fine. put dehumidifier in classroom and showed teacher about drain pan. 9/20/2016
Elementary - they come in at 2 to put the chairs down the chairs, tables, and papers are damp in tilation /Air
0021 there Time Available: asap Conditioning

164891 Forestbrook Closed Work Orders The Equipment room where we keep jerseys, etc.,has a leak again. The spot is 9/13/2016 Gym Roof 9/16/16- Got all my tools on the roof to do the job. Pressure washed areas that are 9/16/2016
Middle - 0051 above a moldy ceiling tile. Time Available: 7am- 4pm Equipment/ leaking. Blew area with blower to remove any extra dirt and water. Applied Gaco to
stroage areas. Got tools off roof, cleaned up and loaded truck.
165019 Lakewood Closed Work Orders Classroom needs a humidifier 9/14/2016 208 Heating/Ven Adjusted room temperature and also found that the teacher had a back door that went 9/19/2016
Elementary - tilation /Air outside to the play ground. I was in the room when the children went outside to play and
0029 Conditioning saw that the door going outside was left open, I ask the teacher if I could close the door
to the outside because with it open and the AC running it would bring in warm air. After
closing the outside door I adjusted the temperature and ask f I could check with her on
Monday to see if she thought that a Dehumidifier was still needed. On 9-19-16 I went
back to room 208 and ask the teacher how did the room fill and she said it felt cool. I
ask her if she still wanted the dehumidifier and she said no.

Page 32 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
165076 Forestbrook Closed Work Orders previous roof leaks have left a horrible odor 9/15/2016 201 Climate On 9-20-16 went to class room 201 and cleaned Evaporator coil with a coil cleaner and 9/21/2016
Middle - 0051 Mr. Cannon has recommended purifiers and dehumidifiers for this room. Control washed down coil good with plenty of hot water using my evaporator coil cleaning
See Mrs. Pilkey Time Available: anytime pressure washer, also placed an odor neutralizer to help cut down on the bad smell. I
will still get the air purifier and dehumidifier. On 9-21-16 went through the dehumidifiers
and check to make sure it was working and also found an air purifier to put in the class
room. Got Dean to drop them both off at the school and set them up in the room.

165090 Green Sea Closed Work Orders AC not working properly in room 231. Very humid. 9/15/2016 Room 231 Heating/Ven checked room and it is cooling 73 degrees in room. 9/20/2016
Floyds High - tilation /Air
0006 Conditioning

165097 Aynor Middle - Duplicate Request band room is warm thermostat reads 72 degrees feels like 85 degrees very humid 9/15/2016 201 Heating/Ven work being done on work order 165556.
0057 Time Available: asap tilation /Air
Conditioning

165134 Aynor High - Duplicate Request this room are very humid in there Time Available: 7 to 4 30 9/15/2016 i103 Climate
0001 Control

165323 Aynor High - Closed Work Orders The teacher reports: 9/19/2016 i103 Heating/Ven Brought up a dehumidifier to custodian to put in room. 9/21/2016
0001 I103 Career Lab is damp and very humid and smells like mildew. It has been humid tilation /Air
in here for about 3 weeks now. Time Available: anytime Conditioning

165441 Daisy Closed Work Orders Tammy Truelove asked me to enter a work order checking the school for humidity 9/20/2016 schoolwide Climate Checked RH% through out school no problems found at this time. all checked around 10/26/2016
Elementary - problems, see attached email Time Available: asap Control 50% rh. checked ok
0021
165477 Green Sea Closed Work Orders The thermostat is reading 72.3 it is very humidity in the class room. Time Available: 9/20/2016 109 Heating/Ven Checked room 109 Found room 72.5 Mr. Dennis MC. changed some points in program. 9/20/2016
Floyds Any Time tilation /Air Room cooling at this time
Elementary - Conditioning
0023

165505 Lakewood Duplicate Request temp. is 77 but very humid 9/20/2016 721 Heating/Ven this is a duplicate work order
Elementary - tilation /Air
0029 Conditioning

165525 Forestbrook Closed Work Orders It is actually the ceiling-We have leakage from some ceiling tiles-some by the air 9/21/2016 307 Flooring Inspected roof and above ceiling. Roof have wear cracks in surface like much of the 10/28/2016
Middle - 0051 vents-some elsewhere in the kitchen and is dripping onto food prep area...Also roof does. Pressure washed 8 areas over kitchen. Blew excess water off with blower.
some tiles need to be replaced from staining and/or looks like molding.... Time Applied M-1 caulk to places with holes. Applied Gaco to areas.
Available: any
165527 Carolina Forest Closed Work Orders The room temperature is fine on the thermostat. The teacher is stating that the 9/21/2016 511 Heating/Ven CHECKED UNIT OPERATION. UNIT IS OPERATING PROPERLY. BLOWER WAS 9/23/2016
Elementary - humidity is very bad in this room. It's been worse in the afternoons. Please take a tilation /Air SET TO OPERATE CONTINUOUSLY WHEN COMPRESSOR CYCLES OFF.
0049 look to see if there's anything that you notice that would cause this. thanks for all Conditioning CHANGED BLOWER TO CYCLE ON/OFF WITH COMPRESSOR TO STOP
you do. Time Available: medium RECIRCULATING MOISTURE BACK INTO ROOM.

165535 Myrtle Beach Closed Work Orders Room 800L is a little warm, 75 degrees, and very humid. The unit is also making a 9/21/2016 800L Heating/Ven had to order a blower wheel . I replaced the blower wheel and motor also the capacitor 9/22/2016
Middle (old) - lot of noise. Time Available: any tilation /Air .. charged system with r22 .
0016x Conditioning

Page 33 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
165539 Lakewood Closed Work Orders Room is damp. Papers and items hanging on wall and desks are curling. Please 9/21/2016 210 Climate Went to room 210 and talked with the teacher about the problem in her class room saw 9/23/2016
Elementary - add humidifier. (D. Morrell's room) Thank you. Control that the AC was working and cooling fine. Then another teacher ask me to check the
0029 book room on the same hallway and I found that warm air was coming out the supply
grill. I then went out side to make sure that the MAU was running and found that it was
not running. Checked the high voltage and checked the fans and fuses inside the panel
and found that everything was in working order. I then checked the MAU on APOGEE
and found that it was turned off I used the computer to turn it back on and after it ran for
an hour I checked back with the teacher in room 210 and she said that it felt better, and
she would wait to see if she still needed the dehumidifier in her room.

165545 Daisy Closed Work Orders Nurse, Principal and Teacher report strong odor in room. Principal requests to have 9/21/2016 408 Heating/Ven teacher back in room today. said it was fine today. thought we had been and fixed 9/22/2016
Elementary - room checked for mold and mildew. Time Available: URGENT tilation /Air problem sometime yesterday. changed filter in unit, found no problem with drain.
0021 Conditioning dehumidifier in room was working. a/c unit cooling properly. found no sign of mold or
mildew or anything else that might be causing odor. spoke with teacher and Brenda and
they will call if it happens again.

165556 Aynor Middle - Closed Work Orders band room is very humid thermostat is reading 72 degrees Time Available: asap 9/21/2016 202 Heating/Ven Checked out and installed dehumidifier. 9/23/2016
0057 tilation /Air
Conditioning

165560 Loris Elementary Closed Work Orders Room 806, the thermostat is reading 73.3, but it is very humid in this classroom. If 9/21/2016 Room 806 Heating/Ven Doing work on WO#165919 9/27/2016
- 0032 you have any questions, please call me tilation /Air
Conditioning

165580 Aynor Middle - Closed Work Orders room is very humid thermostat is reading 72 degrees Time Available: asap 9/21/2016 301 Heating/Ven Checked out and installed dehumidifier. 9/23/2016
0057 tilation /Air
Conditioning

165636 Homewood Closed Work Orders Principal Foye called about the mold & mildew smell in her office. 9/22/2016 Climate Talked with Eric Wilson about this our HVAC tech had already checked everything and 9/29/2016
Elementary - Control everything looked good from our side. Walls were cleaned HVAC was good, ceiling
0025 tiles were good. Tech said one of the teachers had mentioned she had walk in with her
shoes off and notice the carpet was wet. Tech was not able to feel wet carpet but did
note that we had a good amount of water standing outside from all the rain. Called Eric
and talked with him about getting carpet cleaned. Had it cleaned and installed
dehumidifier.

165657 Green Sea Closed Work Orders Inside room 231 there is a moisture problem that is contributing to mildew growth on 9/22/2016 room 231 Heating/Ven checked room for mildew and mold and didn't see any. room did have odor and a uv 9/26/2016
Floyds High - furniture. This needs to be addressed as soon as possible. Thanks! Time Available: tilation /Air air machine was in room. changed filter in machine and left it on high. checked above
0006 any Conditioning ceiling for any sign of water. couldn't see any, room is cooling temperature was 73.3 on
sensor.

165659 Myrtle Beach Closed Work Orders they are requesting a dehumidifier be put in this office. 9/22/2016 guidance Heating/Ven I placed a dehumidifier in this room .. on 9-28-16. 9/29/2016
High - 0010 reception tilation /Air
room Conditioning

165729 Myrtle Beach Closed Work Orders staff is requesting a dehumidifier for this room. 9/23/2016 orchestra Heating/Ven I place a Dehumidifier in this room. on 9-28-16.. 9/29/2016
High - 0010 room tilation /Air
Conditioning

Page 34 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
165757 District Office Closed Work Orders Items need to be moved to storage 9/23/2016 C200 Furniture 9/30/16 Picked up fixed assets. 10/3/2016
Four Mile Road - 1 Dehumidefier
0401 1 HP Office Jet Pro 8500 Printer
1 Wood framed mirrror
1 Large Wood Panel Time Available: 8:00- 4:30
165941 Aynor High - Closed Work Orders THIS room are hot and humid Time Available: 7 to 4 30 9/26/2016 I101 Climate Checked out and found room was okay at this time. Humidity is as low as it can be due 10/24/2016
0001 Control to large make up on roof not working.

165942 Aynor High - Closed Work Orders THIS ROOM ARE HOT AND HUMID Time Available: 7 to 4 30 9/26/2016 I102 Climate Checked out temperature and humidity in room and it was within parameters at this 11/8/2016
0001 Control time.

165980 Carolina Forest Closed Work Orders Teacher wants the panels removed and check for mold under the lab tables in room 9/27/2016 D House Painting 9/26/16, checked room to include removing access door to several labs. No smell 9/28/2016
High - 0052 D 111. She has a smell in there. found at all and cabinets were completely dry.

166062 St. James Closed Work Orders AC has stopped running in D5 again. Room is extremely warm and humid. 9/27/2016 D5 Heating/Ven I went and check the unit. The compressor had tripped out. I reset it left unit working 9/29/2016
Middle - 0047 Old thermostat. Time Available: 150 tilation /Air properly.
Conditioning

166064 Aynor High - Closed Work Orders A very strong stale odor is overtaking the room. Please inspect AC and determine if 9/27/2016 i102 Heating/Ven Checked out and found no unusual odors in the room. Everything appears to be normal 11/8/2016
0001 a dehumidifier is needed. Time Available: ASAP tilation /Air at this time.
Conditioning

166204 Aynor High - Closed Work Orders a very strong stale odor is in this room can we get a dehumidifier place in there 9/29/2016 senior hall Climate Checked out and supplied a dehumidifier. 10/4/2016
0001 Time Available: 7 to 3 30 room c110 Control

166228 Loris Elementary Closed Work Orders Room 806, the thermostat is reading 73 degrees, but very humid and muggy. If you 9/29/2016 Room 806 Heating/Ven Checked a/c in room 806 a/c working good in room Mau tripped that feeds upstairs 800 9/30/2016
- 0032 have any questions, please call me tilation /Air wing. reset and watched operation unit working good at this time
Conditioning

166246 Seaside Closed Work Orders Teacher is concerned that her carpet is still getting wet from water seeping up under 9/29/2016 101a Road/Street A drain needs to be installed to move water from building 11/15/2016
Elementary - the wall. She is concerned that it could become a health hazard with mold and 11/15/16 added new drain line (4") against the wall tied it in with existing (6") drain. Also
0050 mildew. The outside was worked on before but the carpet still seems to be getting added a catch basin. The existing drain had a high spot in it that I smoothed out.
wet Time Available: any
166269 Green Sea Closed Work Orders Air Quality is poor in room 305. It is hot and muggy most of the time. Staff is having 9/30/2016 300/305 Heating/Ven Checked room checked unit unit operating properly at this time checked RH% room 48 10/26/2016
Floyds High - issues with allergies from the presence of mold from the Air. Time Available: Now tilation /Air % no problem found at this time
0006 Conditioning

166284 Forestbrook Closed Work Orders The principal thinks room 107 has mold. Time Available: any 9/30/2016 107 Heating/Ven we went and checked the vents we cleaned it off all it was just dust. 10/19/2016
Elementary - tilation /Air
0046 Conditioning

166329 Aynor High - Closed Work Orders We need a dehumidifier for room A128. Time Available: anytime 10/1/2016 Room A128 Heating/Ven Checked out and found needed a dehumidifier. Added and unit was working fine. 10/4/2016
0001 tilation /Air
Conditioning

166564 Aynor High - Closed Work Orders We have mold crickets on the football field. I saw a lot of them Friday night. Time 10/3/2016 Football Game Turf 10/14/16 spoke with Doug Hinson and we decided not to treat for molecrickets since it's 10/14/2016
0001 Available: anytime Field Maintenance so late in season and fall is coming.

Page 35 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
166641 Myrtle Beach Closed Work Orders The lecture hall is very damp and humid. There are a lot of chairs with mold 10/4/2016 Lecture hall Heating/Ven I have placed the portable Dehumidifier in the Lecture hall. it is operating at this time.70 10/4/2016
Middle (old) - growing. We are in the process of cleaning them off but its only going to happen (107) tilation /Air degrees is the room temp.
0016x again. There is also a multi school safety meeting planned for Thursday Oct, 6th in Conditioning
that room. Time Available: any

167251 North Myrtle Closed Work Orders 708 room is hot. Temperature continues to rise. It is up to 77. 10/14/2016 708, 209 Heating/Ven Checked room 708 found breaker tripped reset and watched operation. unit running at 10/18/2016
Beach Middle - 209- please adjust Temperature to 73. It was set on 74 but the room is having a tilation /Air this time. 209 talked with teacher she said unit working good ran and watched
0037 moldy/ mildew odor. Time Available: 7:30 Conditioning operation unit ok now

167371 Myrtle Beach Closed Work Orders Room 201 is warm and humid. There is a training class for principals in there today. 10/17/2016 room 201 Heating/Ven I lower the room temp for the meeting .. the system seem to fine.. 10/18/2016
Middle (old) - Time Available: any tilation /Air
0016x Conditioning

167505 Forestbrook Closed Work Orders Storm Related Concern- With the power outage and increase moisture/humidity in 10/18/2016 Gym Custodial Delivered product to clean 12/6/2016
Middle - 0051 the building, the mildew issue in the gym has worsened. We need assistance with
the mildew removal. Time Available: anytime

167535 Waccamaw Closed Work Orders room223 hp 12 show 74 degrees it is still muggy and humid /hp 37 room 317 10/18/2016 223/317 Climate CONTROLS ISSUES ARE KEEPING UNITS IN "NIGHT" MODE SINCE STORM. I 10/19/2016
Elementary - show 80 degrees very muggy Control OVERRODE ALL UNITS IN "NIGHT" TO "DAY" MODE UNTIL CONTROL ISSUES
0042 CAN BE RESOLVED.
167628 St. James Closed Work Orders Air is still not working properly in my room. It finally starts cooling down in 3rd block 10/19/2016 C 14 Heating/Ven went and check unit. this is a unit the teacher said it was working good at 12-1 but 10/20/2016
Middle - 0047 but is very humid and muggy until then Time Available: 150 tilation /Air early in the morning not. I told her I would check back next morning to see if it was
Conditioning working properly. 10/20/16 check back unit was working properly

167629 St. James Closed Work Orders air is blowing out but it isn’t cool. Smell of mold. Time Available: 150 10/19/2016 iPad room Heating/Ven I went and check the unit. Their is no smell or sign of mold. We have told them that her 10/19/2016
Middle - 0047 tilation /Air vent is on the very end of the duct and that they are putting in new units and they will
Conditioning give her more air. when the new units are put in.

167707 Aynor High - Closed Work Orders Mr. Mendez reported: 10/20/2016 Band Room Heating/Ven Checked out and found bad low voltage fuse, replaced and operated- running normally 10/24/2016
0001 The air has not worked isince hurricane in band room. I thought it was just hot tilation /Air at this time.
outside. Today I looked at the thermostat and it is not showing any reading and will Conditioning
not activate when I press the override button. Also the 2 dehumidifiers that the
district installed need to be replaced or repaired as they leak and the pump that
they installed is not working. Time Available: ASAP

167781 Ocean Drive Closed Work Orders Room #'s 410,411 and 412 need to have an air quality check performed. Thanks 10/21/2016 410-411-412 Heating/Ven 10/25/16 looked above ceiling in all 3 rooms and no sign of moisture anywhere. the a/c 10/25/2016
Elementary - Jerry Hilburn Time Available: anytime tilation /Air units in these rooms are cooling fine. there was no odor when I was in the rooms
0066 Conditioning andteacher said she didn't smell anything today.11/29 in room 411 found supply duct
had come loose at unit. repaired duct and put hanger under this part of duct. removed
evaporator fan and blower wheel from unit. cleaned drain pan and blower housing also
cleaned evaporator coil. washed blower wheel and reinstalled blower assembly.
teacher was not available to talk with about problem in room. there was a sub in
classroom. unit running at this time.

167937 St. James Closed Work Orders leak in the roof in the library. We mainly see it during torrential rainfall, as in 10/24/2016 Library Roof Found 4 leaks in the media center. Inspected above ceiling tile and on roof. Found 6 11/2/2016
Middle - 0047 Matthew and Hermine. holes in the corners of the roof where the rolled roofing runs under the flashing. Filled
holes with Karnak tar. The other leak is under an A/C unit. After taking with Mr. Green
The leak occurs over two cases of books. In addition to ruining the books, the leak about his experience with the leak and consulting with Greg Gore, we decided the unit
seems to be causing mold in the walls. was leaking when the filter became clogged and the unit was having to work twice as
hard. Making the unit condensate. Changed air filters and 8 ceiling tile in media center.
There is trashcan on top of the book cases to indicate where the leak is.
Time Available: 150

Page 36 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
168024 St. James Closed Work Orders Concession area has mold on floors and cabinets. Teacher has attached pictures. 10/25/2016 Concession Custodial found that there was a little mildew on wall and the custodians are cleaning the affected 12/6/2016
Middle - 0047 Time Available: 150 stand are. also floor will need cleaned by custodial staff

168215 Daisy Closed Work Orders Room need a humidifier to help control moisture in room, teacher and student are 10/28/2016 room 719 Climate Checked with Mr. Dale. Dehumidifier at school for room. Low humidity in room. Told 11/1/2016
Elementary - coughing alot. Time Available: asap Control Dale if she continues to complain put dehumidifier in room
0021
168431 Kingston Closed Work Orders If u can check out the humidity in the room. Many things are not sticking on the wall. 11/1/2016 109 Climate Checked out and found room was within set point of temperature and the humidity was 11/9/2016
Elementary - Time Available: 7-4 Control in tolerance. Unit was operating normally and there was no unusual odors detected at
0028 this time.
168438 Kingston Closed Work Orders The book room across from 503,needs to be check for mold. *Mr. James Time 11/1/2016 503 Roof The walls in 503, the book room have been checked and wipe down 11/16/2016
Elementary - Available: 7-4
0028
168580 Lakewood Closed Work Orders Room feels humid. Temp is normal 11/2/2016 404 Heating/Ven went to the to check the ac unit and found that it was running in a normal cycle and 11/17/2016
Elementary - tilation /Air room temperature was at 73 degrees.
0029 Conditioning

169499 Burgess Closed Work Orders **ROOM 513** Ms.Brown... (not sure of dept. or who to contact) Have an issue of 11/16/2016 ROOM 513. Carpentry Room 513 the back (of two of the cubbies) had a darker stained area. The teacher was 12/17/2016
Elementary - a damp spot coming through the wood on set of cubbies. I am finding no other concerned that this might be a moisture issue. The head custodian (Mr. Lynn) said, he
0063 moisture on walls surrounding. This is a concern with teachers as to MOLD. **In was going to monitor the area to see if it gets worse, if it does he would write another
addition... Room117 Ms.Beers... dampness behind bulletin board, with moisture work order to rework the he cubby. 12/8/16- inspected inside walls where paint is
on bottom of board and some on wall also. ...ALSO... Room 103 Ms.Hotaling peeling. Went on the outside of the walls with a ladder. Caulked holes in mortar joints
strange happenings with paint on exterior wall... not damp though. PLEASE GET and around loudspeaker areas. Also had one wall with electric outlets in it. Sprayed wall
WITH LYNN when you come. Thank you for you attention. Time Available: anytime with brick and mortar sealer. Moved area rug, small dry erase board, and pillows,
scrapped wall where paint was peeling, then primed wall. Came the next day and
painted finish paint on wall.

169505 Daisy Closed Work Orders Teacher in room 720 is requesting a dehumidifier. Teacher in 304 has been to 11/16/2016 304 and 720 Heating/Ven replaced ballast and bulb in uvair machine and replaced bulb in another and placed in 11/28/2016
Elementary - multiple ENT and Allergist appointments and has sinus/allergy/upper respiratory tilation /Air rooms at daisy elementary. Also put dehumidifier in room 720
0021 issues that her doctors believe to be exacerbated by her environment here at Conditioning
school. Is there any procedure to check room 304 for allergens contributing to her
problems or any protocols for supporting staff with allergy problems Time Available:
asap
169809 Green Sea Closed Work Orders Auditorium have mildew in side on seat and floor. Time Available: now 11/22/2016 Auditorium Heating/Ven 11/22 checked for mildew in auditorium. found where possible mold or mildew may 11/23/2016
Floyds High - tilation /Air have been underneath desk tops on seats. wiped off with dry rag. cleaned with mildew
0006 Conditioning cleaner. no moisture anywhere was found. spots in carpet looked like something had
been spilled but cleaned up nicely. checked drain pans in auditorium units and no
standing water.talked with principal and she was satisfied. larry will keep watch and let
us know if problem returns.

170105 Lakewood Closed Work Orders HPO73 - temp. is normal but feels very humid 11/29/2016 719 Heating/Ven i checked the unit on the computer. it showed unit working good. i went to class room 12/2/2016
Elementary - tilation /Air and turned the unit down and let room cool down to 70degree. than i turned it up so it
0029 Conditioning could heat the room to 76degree it worked good in heating and cooling. i checked the
fresh air it was good. i left the unit working properly and teacher was ok with it.

170199 Pee Dee Closed Work Orders This room is VERY HUMID! The thermostat button appears to be stuck at 73 11/30/2016 204 Climate Checked out and made adjustments- kept an eye on room temp and it stayed within 12/2/2016
Elementary - degrees...the room feels like a rain forest! VERY HUMID, MOIST, VERY STALE... Control parameters. Talked with teacher and she said room was much better yesterday and
0039 The children & teachers are sweating.. today was ok but she wasn't in it long. (field trip).
PLEASE WORK ON HUMIDITY IN THIS ROOM!!!

170202 Ocean Drive Closed Work Orders Please service air conditioner units in guidance office, room, and conference room. 11/30/2016 803 Climate removed filters and washed them out. cleaned evaporator coils with coil cleaner and 1/16/2017
Elementary - We also need a dehumidifier for the room in front of the guidance conference room. Control cleaned vents. units are running at this time.
0066 Time Available: anytime

Page 37 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
170215 Lakewood Closed Work Orders 404-unit only blowing warm/humid air 11/30/2016 404, 413 Heating/Ven i checked both unit on the computer. they worked good in the heat and cool. i went to 12/1/2016
Elementary - 413-unit blowing hot air during the day and cold in the evening. Not switching to the tilation /Air the class rooms and they was working good. the teacher said it was too cold so i turned
0029 after hours schedule. Conditioning temp up on the. and i put the override time to 2 hours. both unit was left working good.

170218 River Oaks Closed Work Orders gym HP-58 at 74 and climbing 12/1/2016 cafeteria & Heating/Ven CHECKED UNITS OPERATION. FOUND CONTROLS FOR UNITS AND COMMONS 12/1/2016
Elementary - Cafeteria HP-57 & HP-56 74.5 & 74.6 gym tilation /Air FAN LOCKED OUT. RESET UNITS AND FAN. BOTH OPERATING PROPERLY.
0065 Conditioning
Both rooms are very humid as well Time Available: asap please

170299 Green Sea Closed Work Orders In the cafeteria dry goods storage room, there is an insulated pipe above the ceiling 12/1/2016 Heating/Ven reinsulate refrigeration lines above ceiling and change ceiling tiles that wewr damaged. 12/6/2016
Floyds High - grids along the wall with excess condensation on it. This needs attention ASAP due tilation /Air
0006 to being a contribution to damaged tiles and an environment for mildew or mold Conditioning
growth.

170309 Daisy Closed Work Orders please check indoor air quality in room 719 Time Available: asap 12/1/2016 719 Heating/Ven Checked room 719. Changed filters and ran unit. watched unit operation unit checked 12/8/2016
Elementary - tilation /Air ok. Turned fan on to run all time to keep air circulating. Unit running good at this time.
0021 Conditioning

170378 Daisy Closed Work Orders De-humidifier is not working mr. Dale thinks it may be stopped up. Time Available: 12/2/2016 Media center Heating/Ven 12/5 picked up dehumidifier from library. compressor was not working. 12/8/2016
Elementary - Asap 503 tilation /Air 12-8 Checked found bad compressor. Junked unit and got used from shop. Put in
0021 Conditioning library and plugged in. Unit making water now.

170695 Kingston Closed Work Orders In this room their may be a problem in the ceiling, not sure if its wet are mold above. 12/6/2016 307 Roof 1-2-2016 looked above ceiling and room 307 and 309 share same fire wall 1/2/2017
Elementary - Teacher is having problems with clean air in classroom. Time Available: 7-4 compartment. Saw air filters clean in both 307 and 309. Found fresh air intake half
0028 closed in 307 so I opened all the way.
Found p-trap on HVAC drain capped off so I removed cap to open up.
Treated HVAC cond drain.
Also- repaired classroom entry door so that it will not swing closed by itself and will now
stay open all the way.
171068 River Oaks Closed Work Orders Chaulking in dishroom needs to be replaced along wall and front of machine. 12/12/2016 Dishroom Flooring Transfer to Brian , there is no caulking on front of dishwasher and along the wall is 12/30/2016
Elementary - (MOLD) Time Available: any attached to building so should be a maintenance issue thanks in advance , i will ask
0065 laura farmer to be sure 12/16/16, removed old silicone and cleaned area.m will let dry
over the weekend and recaulk. 12/30/16, re-caulked back splash.

171132 Lakewood Closed Work Orders Unit 079 is making screeching sound (very loud) Shut main unit off. Missing belt on 12/13/2016 712 Heating/Ven Found bad blower motor, replaced with new motor and new run cap. 12/15/2016
Elementary - humidifier unit. See Charlie for details. Time Available: asap tilation /Air
0029 Conditioning

171151 Forestbrook Closed Work Orders I think its mold can someone please come out and this please. Time Available: any 12/13/2016 back office Roof Went by to look at the area they were concerned with. There. Was no mold issue, it 12/17/2016
Elementary - was a stain ceiling tile. The water was dripping from the make up air unit in the ceiling.
0046 Dean was called and he was going to vacuum the unit out and clean it.

171220 Aynor Middle - Closed Work Orders substitute teacher said she is stuffy and mold and mildew smell like band and 12/14/2016 117 Heating/Ven Checked out and found no evidence of any mold or mildew. Checked with custodians 12/19/2016
0057 chorus room did and she gets sick when she sub in those rooms principle want tilation /Air who clean room and she said there is no problems. Checked out unit and it was
room checked for mold Time Available: asap Conditioning running and maintaining set point. No problems at this time.

171726 St. James High - Closed Work Orders E247 is very warm and humid this morning. It says its 70 degrees on the thermostat 1/2/2017 E247 Heating/Ven I check the whole building on the computer everything was working good and at right 1/2/2017
0058 but it is much hotter than that in this room. thank you Time Available: medium tilation /Air temperature. the day was muggy but the building temperature was at 70degree. the
Conditioning heat set point was at 70 and cool at 73. I explained it to Jamie that all the units was
working properly just it was a odd temperature that day.

Page 38 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
171727 St. James High - Closed Work Orders We do not have any AC in the kitchen area of our building. I just placed another 1/2/2017 cafeteria Heating/Ven this is same as work order #171726. I did go and check the kitchen it was good as well. 1/2/2017
0058 work order for E247. Can we make sure the AC is working at SJHS. I notice that it is kitchen tilation /Air
very hot and humid in our building this morning. I do not think the air is running Conditioning
through out our entire building. Thank you Time Available: High

171847 South Conway Closed Work Orders hot and humid Time Available: 6-8 1/3/2017 200 Heating/Ven Was contacted by Terry Hucks regarding issues with humidity in building and was 1/4/2017
Elementary - wing(special tilation /Air informed Dennis McCrary is working on issue.
0045 needs) Conditioning

171894 North Myrtle Closed Work Orders STIIL HAVE RAIN LEAKS IN CANTEEN CAUSING MILDEW PROBLEMS; NEED 1/3/2017 307 custodian Roof went up on top found screws missing and replaced with new ones tightin others up and 1/13/2017
Beach Middle - ATTENTION ASAP Time Available: ANYTIME office calked over heads with solor seal 900 blue.
0037
171962 Loris High - Closed Work Orders Guidance needs air quality checked Time Available: any 1/4/2017 guidance Climate Checked room. everything checked ok. going to put air purifier in room to see if it help 1/5/2017
0008 Control clean the air.

172221 Loris Elementary Closed Work Orders Wants her set point raised. Says the room is too hot and humid and it bothers her 1/9/2017 600 Heating/Ven Checked room made some adjustments to air in room. Talked and told teacher what I 1/9/2017
- 0032 asthma Time Available: 4 tilation /Air done.
Conditioning

173605 Academy for Closed Work Orders RM 424 engineering HP-67 A/C Unit not working and no reading on thermostat. 1/27/2017 RM 424 Heating/Ven unit not running lost low volt found broken wire feeding low volt repair wire. 2/1/2017
Arts Science condensation built up during the night and doors had to be wiped down. the teacher ENGINEERIN tilation /Air
and Tech. - is concerned for mold build up over weekend. Time Available: ASAP G Conditioning
0096

173765 Aynor High - Closed Work Orders Received call from parent stating that child was coming home sick due to mold in 1/30/2017 Climate Went out to school and met with Asst principal and teacher about complaint in room 2/10/2017
0001 teacher's classroom (Ms. Page). Parent indicated that Ms. Page said that she had Control b105. She stated everything was fine at this time damaged ceiling tile had been
written this up and that nothing had been done. Spoke with Asst. Mgrs. for the changed out by school staff. Told her to make sure in the future to get with school staff
region for information on teacher's classroom - B-105. and have them to put in work order if any other problems arise. TH. I went out and
checked per Terry Hucks and found no evidence of any leaks above ceiling- will have
to check back when it rains. The ceiling area was clean and dry

174526 North Myrtle Closed Work Orders Room 802 has an extreme problem with mildew. The mildew is showing on the walls 2/10/2017 802 Climate 2/10 checked class room for mildew and looks like dirt and dust inpores of the blocks 3/20/2017
Beach Middle - and the custodians clean it on a regular basis. This is a problem with the entire wing Control on the wall. took pictures and sent to Richard. custodians did say problem ws worse
0037 of the building. You can see that there is enough moisture in the walls that paint is when school a/c is shut off for extended period of time. no sign of moisture.
even starting to peel. Time Available: jlapier@horrycountyschools.net

175214 South Conway Closed Work Orders please check hvac system in the front office, when it kicks in there is a very, very 2/23/2017 front office Heating/Ven Checked RTU serving area and found odor coming from outdoor air from stagnant 2/23/2017
Elementary - strong odor of mold. thanks Time Available: any tilation /Air water laying on roof. Checked duct work and cleaned duct work and grilles. Closed
0045 Conditioning fresh air intake. Also checked units in media room and found same issue outdoor air
conning in and found no wet areas above cielings. Replaced filters in units. Left all units
operating normally. Odors still there might have to get charcoal filtering system.

175316 Myrtle Beach Closed Work Orders Room 102 is warm. the thermostat shows 71 degrees but the room feels much 2/24/2017 room 102 Heating/Ven found system not running .. gassed system and found the condenser fan motor bad.. 3/1/2017
Middle (old) - warmer than the hall and its humid. Time Available: any tilation /Air went to Trane to pick up and replaced the fan .. system is back up and running..
0016x Conditioning

175672 Waccamaw Closed Work Orders RM 213 HP56 73 degrees - DEHUMIDIFIER IS NOT WORKING PROPERLY. Mrs. 3/1/2017 rm 213 Climate BAD BLOWER MOTOR IN UNIT. REPLACED UNIT. 3/3/2017
Elementary - Murray said, "it feels so moist and hot in here. The book pages are curling because Control
0042 it is so damp in here."

Page 39 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
175731 Palmetto Bays Closed Work Orders pick up 2 broken dehumidifier and send 2 back Time Available: asap 3/3/2017 portable 310 Heating/Ven pick up oz machine and de-hu 3/9/2017
Elementary - tilation /Air got used demidifier from were house and return o-zone machine to warehouse for
0056 Conditioning repair.
had to go back to shop and found plug for dehumidifier.

176008 North Myrtle Closed Work Orders RICHARD, CAN WE LOOK INTO THIS???Trevor - can we tap into the irrigation 3/6/2017 Tennis Plumbing 3/8/17 the well at the tennis courts has a pump start and it also is pumping about 50 3/9/2017
Beach High - that is already there for water? gallons a min. If we put a hose bib at the well it will only put out about 8 gallon a min
0002 Can I throw one more thing on our tennis court improvement list. I might have and that will not work. If they need water they should look at getting a small water
mentioned this before but we need access to water near the courts. Right now we meter. (I have discussed this request and it was decided that at this time we would not
would need a 400 foot hose to get water from either the school building or from the be adding a separate water meter to wash off tennis courts .) RLane
stadium. The courts need to be washed on a regular basis to stop mold and
accumulation of ground in dirt. These things eventually deteriorate the court and
speed up its need to be resurfaced. There are sprinter lines all over the place. Not
sure if we can tap into one of them for a water source.
Time Available: ANY

176327 Myrtle Beach Closed Work Orders MILDEW UNDER CARPET COMING FROM FLOOR Time Available: ALL 3/10/2017 ROOM 123 Flooring 3/10/17, looked at 2 rooms on this wing. There is some moisture below the carpet 3/22/2017
Primary - 0035 squares and the existing vct tile. Will talk with Artie on possible solutions on Monday.
3/13/17, spoke with Dennis McClary about this. He said he would take over this WO.

176672 Aynor Closed Work Orders Please turn the heat down or off. It is smoldering in the office area. The conference 3/15/2017 office area Heating/Ven Checked out and made minor adjustments to set points. Watched units and made sure 3/23/2017
Elementary - room is like an oven tilation /Air running normal. All areas maintained District offices mandatory set points.
0014 Conditioning

177484 Conway High - Closed Work Orders Mr. James, principal said that his front office is hot and humid. The entire front office 3/28/2017 FRONT Climate Checked unit RTU 7 via Apogee and found it to be cooling. Checked room VAVs in 3/29/2017
0004 is hot and humid! Air please! Time Available: ASAP OFFICE Control area and found offices to be cooling.

177496 Aynor Middle - Closed Work Orders The carpet in the media center, auditorium and front office areas is in very bad 3/28/2017 Media Flooring Carpet in Band & Chorus, Guidance has been changed out, now school is asking for 4/7/2017
0057 shape as well as having a musty smell. There have been several staff getting sick Center/Auditor the rest of it to be replaced. Carpet in Main Office has a few puckers and a spot here
working in these areas. We are concerned that the area underneath the carpet is ium/Main and there. Met with Planning committe and it was decided that the funding wasn't
mildewed as the band and chorus rooms were. Please replace ASAP. Time Office available at this time.
Available: Spring Break/Summer

177579 Waccamaw Closed Work Orders this room smell very bad we need two dehumidifer 3/29/2017 112/113 Climate ORDERED TWO DEHUM UNITS FROM WAREHOUSE. BROUGHT TWO UNITS TO 5/2/2017
Elementary - Control SCHOOL.
0042
177684 Daisy Closed Work Orders room very hot and humid, thermostat at 74 % Time Available: ungret 3/31/2017 room 601/ Climate Checked rooms. Found shorted wire in unit. Fixed short and replaced fuse. unit back 4/5/2017
Elementary - 602/ 603 / 608 Control on and running at this time.
0021 /609
178112 Aynor High - Closed Work Orders We have a problem with mold crickets on the football field, baseball field, softball 4/4/2017 Football Turf 4/5/17 treated all fields (7 acres) with Fipronil .0143 (87#/A). Total= 21 30# bags or 4/5/2017
0001 field, and practice football field and practice infield. We need these fields sprayed. field,practice Maintenance 630#. Also walked all fields. Baseball field has some Poa Annua.
Time Available: anytime field,baseball
field and s
178153 Conway High - Closed Work Orders Good afternoon! I was just wondering if we could get the air fixed in B113. We have 4/5/2017 b113 Climate The following work was completed under WO# 178142 Also looked at RTU 1 1st fl B 4/5/2017
0004 the holocaust display up along with student artwork. Students, the news crew, and Control hall and reset power to unit and restarted. Checked operation and found unit to be
news papers will be in and out the next three days as well. It is very humid in here, running normally. Space temp cooled down to setpoint.
unfortunately with how humid it is it can potentially ruin the artwork, especially the
photography prints.

Thank you
Brittany

Page 40 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
178293 Green Sea Closed Work Orders AC not working properly in room 224. Thermostat shows 76. Humid in the room. 4/6/2017 228 Heating/Ven 4/7 unit was satisfied. sensor at 72 4/7/2017
Floyds High - tilation /Air
0006 Conditioning

178535 St. James High - Closed Work Orders Could we check and make sure the override button in the band room B-178 is 4/18/2017 B-178 Heating/Ven Talked with Jamison about room B-178 and he said that the override for the AC was 4/19/2017
0058 working. the temperature was above 74* and with the string instruments the teacher tilation /Air not working, I checked the room on APOGEE and saw that the override time was at
is worried about the humidity in this room. Teacher is requesting that the Conditioning zero set override time at 2 hours.
temperature be set at 74*. thank you Time Available: low

178685 Kingston Closed Work Orders Teacher requests for a dehumidifier for classroom. Time Available: 7-4 4/19/2017 113 Climate Installed dehumidifier per work order. Made sure it was running normally- informed 4/24/2017
Elementary - Control teacher to let custodian know when bucket is full to drain out and get running again.
0028 Will check on in a few days to see how room is maintaining humidity.

178754 South Conway Closed Work Orders For the past week, my room smells musty and feels humid. The temp has stayed 4/20/2017 410 Climate Checked room and connected to TEC operated unit in cooling mode and checked out 4/25/2017
Elementary - around 73.7. The fan runs, but it does not feel like cold air. Control fine. Made adjustment to setpoint.
0045 Time Available: any
178822 South Conway Closed Work Orders Teachers said it was very "muggy, humid" in her room Time Available: any 4/21/2017 403 Climate Checked classroom and found unit running but satisfied. Checked setpoint and 4/25/2017
Elementary - Control adjusted. Ran unit in cooling mode and checked operation. Left unit running normally.
0045
178982 Conway High - Closed Work Orders Inspect and verify that the air conditioning system, including sensors and 4/24/2017 Field House Heating/Ven Checked unit and found condenser fans fuses blown. Checked motors electrically and 2/20/2018
0004 dehumidification, is working properly at the Conway High Field house. tilation /Air found them to be good. However did not have fuses to replace. Asked Dillon to come
Conditioning by with replacement fuses. Ordered new motor and fan blade for unit. (Mike Sowerby).
Coach Shaw has put in a request to have the air conditioning set to an occupied July 12th. Ordered new compressor for first stage cooling. Checked FH for coach
temp 24 hours per day through football season due to the smell and humidity. Shaw. Found compressor 3 and 4 tripped out on blown fuses. Checked compressors
From looking at Apogee with Dennis, the system may not be operating as expected. for any grounds or shorts, all ok. Received fuses from Mike S and went back and
installed check unit operation and found it to be normal. Left unit operating normally.
Discussed with Jeff. Noticed MAU was not cooling visited location and troubleshot unit and found blown
fuses. Checked for shorts and grounds and found compressor 2a was grounded. 11/3
Noticed on Apogee field house heating on MAU not working. Visited unit and
troubleshoot issue was able to confirm ignitor module and electrode probe sparking.
After numerous start attempts I was able to get pilot ignited. Then after several times of
pilot restarts was able to fire stages of main burner. Then commanded on and off
several times with no issues. Returned all controls and Apogee to normal operation.
Purchased new ignitor module to minimize ignition lockouts. Will install tomorrow at
field house MAU. Installed new gas ignition module in MAU. Started up unit and
checked firing of burners. Monitored unit operation and left it running normally.
Checked unit operation next morning and found module operating normally. Replaced
compressor 1A and unit is working normally.

179123 Loris High - Closed Work Orders Room needs to be checked for air Quality. Time Available: asap 4/25/2017 229 Heating/Ven Checked program in room 229 everything checked ok. Also checked unit and operation 4/28/2017
0008 tilation /Air of unit. all Checked good at this time
Conditioning

179252 Burgess Closed Work Orders >>kitchen>as DHEC reported. * 4-101.19 - Nonfood-Contact Surfaces-Material... 4/27/2017 **KITCHEN** Carpentry Kitchen manager has a shelf in the wash room. The piece of wood on the bottom of the 5/1/2017
Elementary - Plate in front of bottom shelf in mop room is bare wood and has begun to absorb shelf was getting wet and starting to rot and turn color. Removed wood and pulled nails
0063 water and mold.<< Your help in corrective measure is greatly appreciated. *See from shelf. Also tightened spud on toilet where it was leaking. I
Ms.Shelley or Lynn. Time Available: anytime

Page 41 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
179330 Lakewood Closed Work Orders My office is very humid and feels sticky. The thermostat reads 73 but it feel like no 4/28/2017 611 Heating/Ven checked unit operation , ok lowered cooling set point , also checked main office unit, 5/1/2017
Elementary - air is circulating. This has been going on for a few days now. I would like it to be tilation /Air spoke to Principal
0029 cooler in here; I have to leave a fan running all day. Thank you for your help. Time Conditioning
Available: anytime

179335 Myrtle Beach Closed Work Orders room 202 temp is reading 77 hot and humid also room 314 hot and humid temp 4/28/2017 202 Heating/Ven replaced the air filter and restarted the system.. may have been tripped out on high 5/1/2017
Intermediate - reading 76 Time Available: 8-5:30 tilation /Air head pressure..
0053 Conditioning

179350 Myrtle Beach Closed Work Orders staff is saying its warm and humid in the athletic training room. 4/28/2017 Pe114 Heating/Ven I reset the system on Apogee and the unit came on and ran fine.. 5/1/2017
High - 0010 tilation /Air
Conditioning

179356 North Myrtle Closed Work Orders Teacher in room 812 says the room is still very warm and humid. Time Available: 4/28/2017 812 Heating/Ven Checked 812 found room 74.5 degrees had 56.7 degree supply air temp unit running 5/1/2017
Beach Middle - 7:30 tilation /Air good at this time
0037 Conditioning

179386 Scholars Closed Work Orders Teacher is stating the room smells like it has mold in it. I didn't see any 4/28/2017 122 Heating/Ven checked rm 122 room temp 73 at 52% humidity, above ceiling clean, spoke to 5/1/2017
Academy CCU - condensation, water leaks or any signs of mold. She said she is having reactions to tilation /Air principal, said do not worry about Teacher, also did find MAU#1 on other side of unit
0178 this. Started last week. Filter was changed 3 weeks ago. Time Available: 7-5 Conditioning not working lockout circuit #1 ,reset all controls, rebooted, checked all motors and
controls ,ok started up checked unit for proper operation

179816 Kingston Closed Work Orders Teacher has a strong smell coming from the closet. Mildew smell. Time Available: 7- 5/1/2017 201 Roof 2MAY2016 investigated for cause- 5/2/2017
Elementary - 4 *replaced three dirty air filters
0028 *sealed AC Condensate drain line where it goes in to the cast iron line close to the wall
*verified minor stain on ceiling tile is no longer a roof leak.
WENT OUT TO SCHOOL FOR A SITE VISIT AND MET WITH MARCUS AND
SHOWED HIM TWO DIFFERENT CLOSETS THAT HAVE TO DIFFERENT SMELLS,
THE SMELLS ARE COMING FROM ALL THE DIFFERENT TYPES OF PRODUCTS
WE ARE PUTTING IN THE CLOSET. THERE WAS NO SIGNS OF MILDEW OR
MOLD ON THE WALLS OR CEILING EVERYTHING WAS CLEAN. CLOSET
DOESN'T HAVE ANY TYPE OF VENTILATION EXCEPT FOR CAP UNDER DOOR.
TERRY HUCKS0

179926 Conway High - Closed Work Orders the HVAC system in field house does not seem to be working-on Monday when 5/2/2017 field house Heating/Ven Checked out unit and found multiple issues. Condenser fan was not operating had 5/17/2017
0004 weather was hotter and more humid very uncomfortable in field house (almost hot) tilation /Air blown fuses. Ohm out motor and found it to be good replaced fuses and test ran.
after practice with everyone in there at one time... Time Available: ASAP Conditioning Operated normally. Then checked out Tandem compressor circuit and found HP switch
grounded. Ordered and replaced with new HP switch started up unit and check
compressor operation and pressures, all normal. Left unit operating normally.

180822 Forestbrook Duplicate Request Gym is in need of painting. Walls have lost their sheen and mildew adheres 5/15/2017 GYM and Painting This a duplicate of another work order
Middle - 0051 constantly during the warm months of the year. Locker rooms

181371 South Conway Closed Work Orders Very Hot and Humid in the main office hall and principal office. Time Available: any 5/22/2017 Front Hall/ Climate Checked unit via Apogee and found it operating normally. Visited school and found 5/24/2017
Elementary - Principal Control hallway area was warm and humid. Made adjustments to TEC setpoints, then checked
0045 Office unit operation. Found unit to be working normally maintaining room setpoint.

Page 42 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
181420 Conway High - Closed Work Orders B215 no air flow...hot! 5/23/2017 b215 Climate Checked RTU 2 which is the unit that serves that area and found both compressors 5/24/2017
0004 B109 77 degrees Control tripped out. Reset compressor and observed them both start up and continue to
Athletic hallway is hot and humid! Time Available: 7:00 AM operate. Checked unit supply air temp and it was dropping. Checked back following day
and unit was running and keeping space cool. Left unit operating normally.

181497 South Conway Closed Work Orders extremely humid this morning,please check. Thanks Time Available: any 5/24/2017 107/Principals Heating/Ven Checked area and finally figured out which unit serves admin hallway and thermostat 5/25/2017
Elementary - office tilation /Air hidden behind cabinet in copier room. Commanded unit cooling on and checked unit
0045 Conditioning operation. Found unit working normally and pulling down room temp. Made slight
adjustment to cooling setpoint. Left unit operating normally.

181529 Green Sea Closed Work Orders Paint peeling off wall in dish room. Caulking molded in dish room needs to be 5/24/2017 cafeteria Painting Started scrapping and removing old silicon that sealed dishwasher to wall.Scrapped off 7/12/2017
Floyds replaced. Cork board strips on wall in dish room need to be removed and painted loose paint cleaned,and repainted.Replaced silicon.
Elementary - behind them. Paint is also peeling off wall around hand sink in kitchen area. Time Removed cork strips from wall,Scrapped and chaulked all holes,primed then painted.
0023 Available: anytime
181563 South Conway Closed Work Orders reports of room being to humid Time Available: any 5/24/2017 401/teacher Heating/Ven Checked room and found unit operating normally and maintaining temperature in room. 5/24/2017
Elementary - resource tilation /Air Left unit operating normally.
0045 Conditioning

181591 Myrtle Beach Closed Work Orders AC feels real hot and humid in this room please check. 5/24/2017 V101 Heating/Ven this room was at 72 degrees when.. I don't know what may have happen to cause the 5/25/2017
High - 0010 tilation /Air room to heat up like that.. I didn't see any problem with the system at this time..
Conditioning

181698 Green Sea Closed Work Orders 76 degrees in room 221 and very humid. 5/25/2017 221 Heating/Ven checked unit and it had tripped out on condensate fault. vacuumed drain and leveled 5/26/2017
Floyds High - tilation /Air drain pipe. unit running at this time.
0006 Conditioning

181898 Aynor Middle - Closed Work Orders teacher complaining of mole mildew odor in room Time Available: asap 5/30/2017 606 Heating/Ven Checked indoor unit and duct work every thing looked clean the room temp was 72 deg 7/12/2017
0057 tilation /Air and the RH was 63% we located the MAU was not operating properly we have to order
Conditioning parts. Installed parts ordered for MUA 1, Went tyo operate and found signal not coming
from Apogee control. Called Dennis McCrary and he is getting hold of CMI to take a
look at. Will open another work order when they find out there problem.

182173 North Myrtle Closed Work Orders The entire 800 wing has a huge issue with mold. This is a reoccurring problem that 6/1/2017 810 Heating/Ven 6-22 Checked Mau's on 8th grade hall got unit back on and running now. it had a 7/17/2017
Beach Middle - seems to be addressed. Our custodians can clean all the walls but that does not fix tilation /Air breaker tripped reset and unit back on and cooling. Hallway should feel and be better at
0037 the existing issue. I am very concerned that we will start the school year with these Conditioning this time
issues not being taken care of. Time Available: jlapier@horrycountyschools.net

182335 South Conway Closed Work Orders Principal came in this morning and opened his office and it is very hot and very 6/2/2017 Principals Climate Checked space temp and RTU operation and found unit to be operating properly. Unit 6/5/2017
Elementary - humid in there. No air flow or air coming on at all. Time Available: any office Control was putting out 56deg supply air temp. Humidity may have been due to weekend night
0045 mode and unit catching up. Left unit operating normally.

182360 Lakewood Closed Work Orders This classroom is very humid and sticky. 6/2/2017 room 410 Climate we went and check the unit. we look on the computer and temp showed 73degree. we 6/6/2017
Elementary - Control check all the parts and pressure all was good. we put the loop-out at 100% to see if it
0029 works. the temp got cooler and we release the loop-out. we left unit working properly.

182896 Seaside Closed Work Orders 1. Cooler-Water on ceiling making mold and water on floor. 6/8/2017 kitchen Kitchen repaired slicer and lubricated , checked cooler adjusted temperature on unit 7/12/2017
Elementary - 2. Slicer-Dial won't move to right settings. Equipment
0050 3. Cold holding box-Will not keep temp cold.
4. Check cooler floor-water is making floor peel again. Time Available: any

Page 43 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
182912 Seaside Closed Work Orders 1. Cooler-Water on ceiling making mold and water on floor. 6/8/2017 kitchen Heating/Ven we went and check the cooler. someone had put caulk down around the bottom of 8/10/2017
Elementary - 2. Check cooler floor-water is making floor peel again. Time Available: any tilation /Air cooler. we will come Monday and seal the ceiling. 7/24/17 I caulk the ceiling. I let phillip
0050 Conditioning know and he can let other guy come and seal the floor. 8/10/17 we start the unit back
up. left it working properly.

182966 St. James Closed Work Orders air quality is poor in room. please check per Mrs. McDavid 6/8/2017 conference Heating/Ven checked a/c it is new free air return , I believe the smell is coming from the old cabinets 6/12/2017
Elementary - room on front tilation /Air and sink ,spoke to Philip
0030 hallway Conditioning

183213 Aynor High - Closed Work Orders Class room I105 Check AC , room has " muggy " feel and "mildew " odor most 6/14/2017 I105 Mildew Heating/Ven Checked out room and found unit is working normally, room was just waxed- no 6/22/2017
0001 morning Time Available: Any time order tilation /Air unusual odors noticed. Humidity is high in building due to outside. Also one of the big
Conditioning make-up units on roof still needs to be repaired, ( Terry Hucks is informed of this
situation.)

183214 Aynor High - Closed Work Orders No visible mold but room should be checked. (Mold has grown over the summer 6/14/2017 Class C101 Heating/Ven Checked room out and made sure systems operating normally, inspected room and 7/13/2017
0001 before in class room) Time Available: Any time check for mold tilation /Air found no evidence of mold or mildew.
Conditioning

183215 Aynor High - Closed Work Orders Class room C112 Humidity in room and constant musky odor Time Available: Any 6/14/2017 Class room Electrical Checked room out and found unit is working fine and there is a dehumidifier in room. 7/13/2017
0001 time C112 musky This is the old section of building and it does have a musky smell. The temp outside is
odor unbearable at this time, will check on in a few days.
183549 Forestbrook Closed Work Orders Please pressure wash the building exterior. We have some areas with lots of 6/21/2017 exterior Custodial This was completed by grounds 9/29/2017
Middle - 0051 mildew. Time Available: anytime

183857 Aynor High - Closed Work Orders Room F111 The walls need to be paint and the cabins need to be sanded before 6/28/2017 Class RM Painting In room F111, the art room, I have took the nails, screws out the wall and corked the 7/25/2017
0001 they are painted. In side the cabins are black ( I am not sure if it is mold or mildew.) F111/Art holes back up. Cleaned and primed under the 3 sinks and painted them. Had
Time Available: Any time contractor to repaint three large walls
183928 Myrtle Beach Closed Work Orders Need the large dehumidifier installed in the small auditorium 6/29/2017 Heating/Ven installed dehumidifier 1/9/2018
Middle (old) - tilation /Air 01/09/2017-Picked up dehumidifier from small auditorium.
0016x Remove and bring back to the shop. Conditioning 01/10/2017-Returned dehumidifier to warehouse.

184722 Carolina Forest Closed Work Orders Air ducks in the ceiling over locker rooms ,ROTC , and Cafateria areas are leaking 7/11/2017 Main Bldg Heating/Ven FOUND BROKEN DUCTWORK ABOVE CEILING. WILL REPAIR DUCTWORK. 8/7/2017
High - 0052 which is causing moisture and mildew on walls and doors hard to open. tilation /Air MADE REPAIRS TO BROKEN DUCTWORK.
Conditioning

184751 Forestbrook Closed Work Orders We have new leaks in the storage room ceiling and in the data quality clerk's office 7/11/2017 storage room Roof 7/12/17 Located the leak in the office and storage room then proceeded to the roof with 7/12/2017
Middle - 0051 in the administration hallway. Time Available: anytime some M-1 sealant. Searched the roof for damage or wear and found a couple of places
that could be the cause along the front wall. I cleaned the area and applied the sealant
there and a few other places in the general area.

184790 Seaside Closed Work Orders Walls are wet with condensation and mildew starting to grow especially on bathroom 7/11/2017 400 hall Heating/Ven we went and check the hall. we found 1 dampier not working properly. we closed it and 7/17/2017
Elementary - walls. Time Available: any tilation /Air see if that will help the with the spots. we talk to dennis to see what else we might can
0050 Conditioning do. 7/13/17 I went back out at 330 to see if wall would have water on them. it had a little
and spots was coming back on wall. will run exhaust fan during the day

Page 44 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
184791 Seaside Closed Work Orders Mildew growing on walls. Especially bathrooms. We will need someone to clean 7/11/2017 400 hall Heating/Ven Expansion joints in the back of the rooms needs repair. (400 hall) started removing 7/20/2017
Elementary - them before school starts. Only head custodian working and he is busy cleaning tilation /Air aluminum hide away plates and scraping old caulking away. Picked up paint from
0050 carpets and waxing floors. Time Available: any Conditioning sherwin Williams and ordered materials from the Wharehouse. Walked 400 hall with
Phillip looking at the rooms to be done. Started caulking expansion joints in rooms
406,408 and 410. They are done with caulk. Need to paint. Also wiped down rooms
411,413,412,404,402,105,111 and 113. Wiped and checked rooms 114,100H,art,girls
bathroom. Cleaned and painted 406,408,410,cafe storage,gym office bathroom,102
and started to paint cafe wall. (3 different paint colors) Finished painting walls and
cleaning up the floors.

184847 Pee Dee Closed Work Orders Mold (BlacK) is grwing a long wall. Located in corner by sink are. please check in 7/12/2017 kitchen Carpentry 17JUL2017 scrubbed area with bleach and investigated. It did not appear to be behind 7/19/2017
Elementary - with Dr. Huggins. Afraid it may be behind the plastic panel. FRP wall board.
0039
184877 Conway High - Complete per Mrs. Spearman mold is all in the main aud. on the wall, seats and carpet. Time 7/13/2017 AUDITORIUM Custodial This have been taken care of. 10/31/2017
0004 Available: ASAP

185199 District Office Closed Work Orders in learning sevices room a101 they ask for a dehumidifier in that room feels damp 7/19/2017 need a Heating/Ven Checked out and found customers wanted an air purifier, Called warehouse and they 8/3/2017
Four Mile Road - Time Available: today if you can dehumifier tilation /Air stated we cant buy anymore. So I informed them that they will have to purchase from
0401 learning Conditioning their own budget.
sevices

185215 Myrtle Beach Closed Work Orders The dehumidifier that is kept in the lecture room (107) has stopped working. There 7/19/2017 room 107 Heating/Ven took old dehumidifler out and rented dehumider from sunbelt renter. 8/10/2017
Middle (old) - is power to the unit but it will not turn on. This room needs a dehumidifier running all tilation /Air repair old dehumidifler and return back to school and return rented dehum.back to
0016x the time. Mold is already beginning to grow on the seats. Time Available: any Conditioning sunbelt renters.

185234 Myrtle Beach Closed Work Orders Six classrooms on B hallway has mildew forming on the walls. We need to make 7/19/2017 B hallway Heating/Ven a/c is running in all rooms on b hall set temperature up because temperature is to cold 7/20/2017
High - 0010 sure these rooms have constant AC temp even when unoccupied to stop the mildew tilation /Air for class room with nobody in room.
from forming on the walls after it is cleaned up. Conditioning will lower temp when school start.

185236 Carolina Forest Closed Work Orders AC needs to be checked in the back of C House. Rooms 115,116,117, and 118 are 7/20/2017 C House Heating/Ven CHECKED MAU OPERATION. FOUND EXHAUST FAN STARTER TRIPPED. 7/20/2017
High - 0052 covered with mildew. This is the second time this summer i have had to get this off tilation /Air CHECKED MOTOR AND RESET STARTER. UNIT OPERATING PROPERLY.
the walls. Conditioning

185272 Forestbrook Closed Work Orders We need immediate assistance with the lecture hall. We have multiple leaks 7/20/2017 Lecture Hall Roof 8/30/17 Removed severely stained ceiling tile from closet. Did not replace tile, right 10/5/2017
Middle - 0051 throughout the area and the mildew smell is very strong. There are several ceiling now, until roof leak is fixed (tile was around a vent).
tiles down. Time Available: as soon as possible 9/15/17 Changed several ceiling tiles in room, two of them had can lights in them.
10/5/17 Finished changing stained ceiling tiles.

185310 Conway Middle - Closed Work Orders There is a strong odor of mildew in both these rooms. It is ongoing and will not go 7/20/2017 B205/B203 Heating/Ven Checked out both rooms and found no evidence of mildew, rooms smelled like rest of 8/9/2017
0017 away. Time Available: anytime tilation /Air building. Both rooms are clean and a/c systems operating and keeping up with set
Conditioning point.

185403 St. James High - Closed Work Orders can we make sure the AC is working properly in room E-207. This room used to be 7/24/2017 E-207 Heating/Ven MAU#3 cools that room , found 2A Compressor shorted to ground, removed from 7/27/2017
0058 a storage closet and now is an assistant principals office. It is very muggy and tilation /Air circuit, also found bad supply fan actuator , ordered, put in bypass mode, cached
humid in this room. thank you Time Available: low Conditioning operation of 3 other compressors ok , a will put actuator, compressor replacement on
new WO#

Page 45 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
185433 St. James High - Closed Work Orders I have what looks like mold or a water stain in the front foyer or our school. you will 7/24/2017 Front foyer Roof 7/25/17 Got a trailer and scissor lift and used lit to reach the ceiling of the front foyer. 7/26/2017
0058 need the lift to reach this area. It looks like the roof is leaking in this spot. Time Cleaned the spot with dirtex and let dry. Then applied some mold and mildew cleaner to
Available: medium insure that it was free of mold or mildew. Then applied some joint compound in a small
line along the joint that had appeared. Also cleaned area in one o the windows in the
foyer and applied some joint compound in that area as well. Cleaned up and loaded lift.
Then I took roofing cement up to the area above and cleared and cleaned area applied
roofing cement. Then I applied a bead of NP1 over the windows in the foyer were water
could be penetrating the exterior. Returned lift and trailer to the warehouse.

185440 Loris Elementary Closed Work Orders Room 204, the thermostat is reading 77.6 degrees. It is very hot in this classroom. 7/24/2017 Room 204 Heating/Ven Checked room 204 found bad blower motor took old motor out and got new from trane. 7/26/2017
- 0032 Also, the ceiling tile has mold on it. If you have any questions, please call me at 843- tilation /Air put new motor in with 10mfd capacitor. unit back on and running now.
390-6860. Conditioning

185558 Lakewood Closed Work Orders Room is very humid. Papers are wet and floor slippery. Mildew has grown on the rug 7/26/2017 311 - Hackett Heating/Ven I went and check the room. the room is a storage room and they want to turn it into a 7/27/2017
Elementary - & fabric chair. tilation /Air class room. the air controlled for this room is in room over. I turn it down to 71degree so
0029 Conditioning more air can get into new class room. I did not see no mildew or wetness on the floor.

185978 Loris Middle - Closed Work Orders Pressure wash all white block on the exterior to LMS. Main purpose is to remove 8/1/2017 Exterior - Road/Street 8/8/17 R.E. 2 x2 Summer help. Put bird spike on the lights at the front door.8/7/17. 8/15/2017
0027 mildew from white block. White Block R.E. 2x 8 hours Summer work. We cleaned the white blocks.8/2/17. R.E. 3 x 7 hours
Summer help. A-1 Painted the letters on the front of the building after it was sand
blasted . Front entrance would not clean up so we had it blasted to bring back to
original color, received estimate and approved and had contractor to do the cleaning
and inspected afterwards . Job turned out great.

185995 Conway High - Closed Work Orders Since coming back to work we are having a MAJOR problem with mold and mildew 8/1/2017 athletic office Heating/Ven This issue is currently being looked at by Dennis McCrary regarding Apogee unit 8/29/2017
0004 in our office and storage room areas. On hot and humid days the paper in my printer area and tilation /Air control during off hours. Unit appears to be operating normally during normal hours.
is so damp when I come in it will not run through the printer...never had this problem JROTC Conditioning Will stop by some time next week. Checked office and spoke to coach Shaw and he is
before in the 2 years I have been in this office. Time Available: ASAP using to personal dehumidifiers to reduce the humidity levels.

186154 Myrtle Beach Complete THERE IS MOLD ON CLOTHING IN NJROTC SUPPLY ROOM AND IN COAH 8/3/2017 NJROTC Custodial 8/22/2017
High - 0010 SEDESKA'S BATHROOM/OFFICE. IT NEEDS TO BE REMOVED BEFORE IT SUPPLY
SPREADS MORE. Time Available: 6am to 5pm ROOM
186354 Forestbrook Closed Work Orders Multiple ceiling tiles building-wide need to be replaced around smoke detectors, 8/7/2017 building wide Roof Went throughout building changing ceiling tiles with exit light, speakers and smoke 9/18/2017
Middle - 0051 speakers, and vents. detectors.
concession stand is badly mildewed Time Available: as soon as possible
186393 St. James Closed Work Orders Purchase supplies to clean mildew off of the furniture 8/7/2017 Carpentry Went to Spectrum Paints and purchased 5 bottles of mildew cleaner and couple boxes 8/7/2017
Elementary - of rags from store room and had Ralph to deliver them to Jamey Couch.
0030
186517 Conway Closed Work Orders We are in need of a dehumidifier on the TLC hall, the old one that we have is 8/8/2017 TLC Heating/Ven Changed out dehumidifier with one from the shop and removed the old one. 8/8/2017
Education freezing up. Time Available: Asap tilation /Air
Center - 0172 Conditioning

186534 Aynor Closed Work Orders In room 502 out in the modular- rain is pouring in the window and the window is 8/8/2017 rm 215 and Carpentry 09AUG2017 Terry will inform contractor of leak at portable because it is still under 8/10/2017
Elementary - closed. 502 (modular) construction.
0014 In room 215 water is coming in and teachers says there is black mold behind her In 215, we treated the soiled area behind the bookcase. We dug up and exposed the
bookcase. entire expansion joint outside the classroom. We then sealed it with fresh caulk and
hydraulic cement. I then sealed that with Through the Roof sealant and covered with
dirt.
186622 Seaside Closed Work Orders please clean off mildew and paint mens and ladies restrooms (400G and 400F) 8/9/2017 Painting Had walls cleaned and painted in 400G and 400F restrooms by Robert's Paint 8/10/2017
Elementary -
0050

Page 46 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
186625 Aynor Middle - Closed Work Orders AUDITORIUM - WARM AND HUMID READING ON THERMOSTAT SAYS 74 8/9/2017 AUDITORIUM Heating/Ven 186600 all work is on this work order. 8/10/2017
0057 DEGREES. WE NEED THIS CHECKED. WE HAVE STAFF DEVELPMENT tilation /Air
SESSIONS HERE ON MONDAY AND TUESDAY NEXT WEEK THAT WILL BE Conditioning
HELD IN AUDITORIUM Time Available: ASAP

186763 Lakewood Closed Work Orders The playgrounds have pine straw, weeds, and debris all over it. We need for it to be 8/10/2017 307 Playground 8/10/17- Emailed requester and asked him to separate each request into its own work 8/10/2017
Elementary - cleaned up. We also need more wood chips in each play area. You can see the order;tjt
0029 matting coming up from underneath. If available, we need equipment to be power
washed. Mildew is growing all over it as well as spider webs. Time Available: asap

186765 Lakewood Closed Work Orders In room 301, the air becomes humid throughout the day. AC is not consistent. Time 8/10/2017 301 Climate I went and check the room. I cycle the fan so it will not bring hot air into the room. this 8/10/2017
Elementary - Available: asap Control room has a package. that supply three rooms. the return air is coming from the ceiling.
0029
186770 Conway Middle - Closed Work Orders Teacher request that the air quality in her room be checked out and feels a bad odor 8/10/2017 A202 Climate Was informed to email to Terry Hucks and he would take care of this. Checked out 8/28/2017
0017 is causing her headaches. Would like to see what options can be done to improve Control room and found no evidence of mold or mildew. Unit was running normally.
the comfort level in classroom Time Available: Any

186813 Facilities Closed Work Orders repair dehumidifier 8/10/2017 Heating/Ven repair 2- dehumidifier one have bad cond pump and the other had low refrigerant had 8/15/2017
Building - 0402 tilation /Air to add service valve pull vaccum and charge unit .
Conditioning

186957 Burgess Closed Work Orders > 100 hall wing... to include rooms number 105, 109, 110, 112. These rooms are 8/14/2017 100 HALL Roof Checked leak areas above drop ceiling. Went on roof and was attempting to locate 9/13/2017
Elementary - affected by leaks... I am concluding as roof issues. WING>> leaks when it started to rain. 9/12/17- Did a bump test on the roof where one man
0063 These are same areas we have had consistent issues with, since storm last year. bumps the roof with a pole and another man stands on the roof and locates the bump.
Leaks are occurring when there is rain. Damaging ceiling tiles and creating a Found location. Cleaned, scraped rock and blew the rock from area for fibered tar
possible mold issue. Your attention is appreciated. Time Available: ANY TIME application. Did this for all the rooms listed. 105, 109, 110, 112 and 118. 9/13/17-
picked up supplies from Lowes. Pulled tools and buckets on the roof. Mixed all the
buckets for the leak areas. Poured tar on the areas. Spread tar with roof brush.
Cleaned up areas. Loaded tools and truck.

187050 Lakewood Closed Work Orders Temp is 76 but the room feels humid 8/15/2017 415 Heating/Ven I went and check the room. the stat read 73degree. I look at unit on computer it was 8/21/2017
Elementary - tilation /Air showing at set point. I cycle the fan so it would turn off when unit was at set point so it
0029 Conditioning will not bring any outside air in. 8/18/17 I went back to check and see if room was still
hot n stuffy. it was not and teacher was ok with it.

187051 Conway Closed Work Orders Good morning Tammy. Yesterday I noticed there was mold on several of my ceiling 8/15/2017 410 Liz Heating/Ven Called school and spoke with Tammy and I ask her to get the nurse to go down and 8/23/2017
Elementary - tiles and ceiling vents. Mr. Willie was great and came and replaced them right away Schafehen's tilation /Air look at the room and see if she seen anything going on in there. I told her we had been
0036 and wiped down the vents. I also had mold on a wooden rocking chair that I room Conditioning seeing this occur in the last few days in several schools due to cleaning of the schools
cleaned and donated to the new 1st grade teacher. My concern is that there is still and humid weather. Terry Hucks Checked unit and found it operating normally.
mold most likely in the ceiling even though the tiles have been replaced. The Maintaining setpoint. Made adjustment to compressor cycle length.
reason I am concerned is that I am VERY allergic to mold. I have terrible allergies.
I had to take Benadryl, a nasal decongestant, and do a Netipot when I got home.
Can you help with finding out if all the mold is gone from the ceiling and my room?
Thank you!
Have a blessed day!

Liz
I have attached the concern from the teacher in this room for you to review. wasn't
sure what problem to put this to Time Available: 7-4

187120 Conway High - Closed Work Orders Please check rooms for high humidity. 8/16/2017 C-100,101 Climate Checked both rooms and found them maintaining temp but was humid in room. 8/16/2017
0004 Control Checked MAU1 and found exhaust tripped. Rest VFD and motor ran waited and
watched unit cooling cycle on. Checked next morning and unit is still running normally.

Page 47 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
187143 Conway Closed Work Orders TLC room 108 There appears to be a possible moldy substance on some of the 8/16/2017 TLC - Room Heating/Ven Checked unit it was operating normally. So I lowered the temp so the compressor can 8/17/2017
Education surfaces in the room accompanied by a very musty odor. We may need the air 108 tilation /Air run longer and dehumidify the area.
Center - 0172 quality checked in this room. Conditioning

187149 Conway High - Closed Work Orders mold on lab table and ceiling in room Time Available: 7:00 AM 8/16/2017 A101 Custodial School called and stated they had took care of this. They found out it was wax. Terry 8/16/2017
0004 Hucks

187209 St. James Closed Work Orders In the dish room, the wall is molded and needs to be painted. 8/16/2017 kitchen Painting 8-21-17 Scraped wall to remove paint that was peeling, cleaned walls, then primed. 8/23/2017
Middle - 0047 8-22-17 Painted walls and caulked along sink.

187285 Lakewood Closed Work Orders Something appears to be growing in and around the in-take vent. It feels very humid 8/17/2017 304 Heating/Ven I check the wall. it was build up dust. I wipe it off the a Clorox wipes. I cycle the fan. the 8/21/2017
Elementary - in the technology lab. tilation /Air unit was pulling outside air in when compressor turn off.
0029 Conditioning

187293 Waccamaw Closed Work Orders hp 04 it show 73 degerees very humid in room 8/17/2017 406 Heating/Ven CHECKED UNIT OPERATION. UNIT WAS OVER COOLING THE UNIT AND NOT 8/18/2017
Elementary - tilation /Air DEHUMIDIFYING. RESET UNIT AND CONTROLLER. UNIT OPERATING
0042 Conditioning PROPERLY.

187295 Lakewood Closed Work Orders Need to request for a air purifier & dehumidifier. 8/17/2017 311 (Hackett) Heating/Ven they had one in room. I empty the water out and left it working. 8/21/2017
Elementary - tilation /Air
0029 Conditioning

187311 Conway Closed Work Orders We have several items in the kitchen area that we need to be picked for disposal: 2 8/17/2017 TLC Hall Furniture 9/1/17 picked up furniture. 9/5/2017
Education tables, 1 shelf, 11 chairs, 3 desks and 1 dehumidifier. Kitchen
Center - 0172
187335 Conway High - Closed Work Orders the weight room has a HUGE moisture problem that has been going on for several 8/17/2017 Weight Room Heating/Ven Checked unit and room and found it was cool but issues with equipment and moisture. 8/29/2017
0004 weeks. Weight equipment is rusting and leather weight lifting belts are totally G4 tilation /Air Looked at unit controller and made changes to control points so unit 1st stage will run
covered in mold. never had this issue in the past same as athletic office never had Conditioning longer with out dropping space temp but dehumidify air. Calibrated thermostat to reflect
this issue in the past and we are dumping 8 to 10 gallons of water a day out out our actual space temp. Also adjusted night cooling setpoint down from 80deg to 76 in an
dehumidifier a day!!! effort to reduce humidity.
Cannot afford for weight equipment to get ruined...... Time Available: ASAP

187355 Forestbrook Closed Work Orders Bad smell, possible MOLD in the room. Teacher had to be relocated. Time 8/17/2017 403 Custodial Went to classroom and found the no smell in the room, the temperature was 72, the 8/30/2017
Elementary - Available: Any room felt comfortable and did not feel any humidity. Ceiling tiles and carpet looks good.
0046 There is a dehumidifier and a air purifier in the room. Ms. Vivian, the head custodian,
stated that the carpet was cleaned this summer. this has now been turned over to
Tammy Trulove.
187420 St. James High - Closed Work Orders Can we check the AC in the field house. coaches are saying it is hot and humid. 8/18/2017 field house Heating/Ven units not scheduled, told Jaminson 8/22/2017
0058 Temp 78* Time Available: low tilation /Air
Conditioning

187431 Horry Ed. Closed Work Orders (Room 6) is not cool. The fan blows but there is no cool air. There is an extreme 8/18/2017 Rm #6 Heating/Ven drain line clogged, cleared unit a little low on charge charged with reclaimed r-22 to get 8/21/2017
Center - 0176 moldy smell and it appears the air filter has not been changed in some time. Time Dusenbury tilation /Air to proper temps
Available: ASAP-ASAP ASAP Conditioning

Page 48 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
187436 Lakewood Closed Work Orders I know that facilities has been out numerous times lately trying to help, but 8/18/2017 older part of Heating/Ven i went and talk with ms.roberts. I explain to her how the units works. I told her I will talk 8/25/2017
Elementary - something is the matter with the air. There is a lot of moisture in many rooms to building tilation /Air with dennis and ask can he turn the units down to 72.50degree and cycle the fans. the
0029 where papers/materials/desks/etc... feel damp and wet, something growing on Conditioning school have only 1 make-up air.
walls, and it is very humid. We can't operate dehumidifiers in every room. Is there
anything that can be done to correct this problem? I am looking for advice and help.
Thank you for your time. Time Available: anytime

187441 Burgess Closed Work Orders **ROOM # 210... Room is humid and hot... Thermostat reads 73* However still 8/18/2017 ROOM # Heating/Ven checked had to reset 200 hall MAU 8/22/2017
Elementary - feels warmer. **I have several rooms on this 200 hall that is humid and warm. 210>> tilation /Air
0063 Thank you for checking out. Time Available: ANY TIME Conditioning

187455 Early College - Closed Work Orders CLASS ROOM AIR UNIT FEELING HUMID, AND STUFFY. HOWEVER, WALL 8/18/2017 PE/121 Heating/Ven checked on computer at home in afternoon room temp 73,73.25 8/18/2017
0074 UNIT READ 74 tilation /Air
Conditioning

187457 Early College - Closed Work Orders CLASS ROOM IS HUMID, STUFFY, HOWEVER, WALL UNIT READ 74 8/18/2017 127 Heating/Ven checked on computer at home in afternoon room temp 73 hud 56% 8/18/2017
0074 tilation /Air
Conditioning

187466 Aynor Middle - Closed Work Orders Thermostat is at 72 but the room is very stuffy and humid feeling. We have Open 8/18/2017 512 Heating/Ven Checked units operation unit is working fine and doing all it can do the room temp is 72 8/22/2017
0057 House Tuesday, Aug. 22nd and school starts Aug. 23rd. Time Available: ASAP tilation /Air degrees
Conditioning

187468 Aynor Middle - Closed Work Orders Thermostat is at 73 but the room is very humid and wet feeling. Time Available: 8/18/2017 610 Heating/Ven Checked room the room temp was 73 degrees and the unit is operating. As far a 8/22/2017
0057 ASAP tilation /Air humidity the unit is doing all it can do.
Conditioning

187469 Aynor Middle - Duplicate Request Thermostat is at 73 but room is very humid and wet feeling! Time Available: ASAP 8/18/2017 703 Heating/Ven All work is on workorder 187330
0057 tilation /Air
Conditioning

187500 Forestbrook Closed Work Orders Please bring dehumidifier for front reception area. There is a strong smell 8/18/2017 front office Climate I put a dehumidifier in the office under desk. 8/25/2017
Middle - 0051 associated with the moisture in the building. Time Available: as soon as possible Control

187516 Midland Closed Work Orders 100% Humidity on Thermostat 8/19/2017 POD #806 Heating/Ven Checked all rooms and all of them were cooling located in the pods. 8/23/2017
Elementary - Blinking Service on Thermostat tilation /Air
0033 Everything is moist. Conditioning
See Debbie Hardwick upon Arrival. Angela Johnson's POD room #806 Time
Available: any
187613 St. James High - Closed Work Orders Can we check the AC in room E-222. Teacher says its very humid and warm. Time 8/21/2017 E-222 Heating/Ven Check the next day off computer Room temperature reading 72.75 to 73.25 8/22/2017
0058 Available: low tilation /Air
Conditioning

187652 Kingston Closed Work Orders Due to mold issues, this class bathroom fan needs to stay on. (This bathroom has 8/21/2017 418 Heating/Ven work completed on w/o# 187202 9/22/2017
Elementary - previously flooded and Maintenance instructed to stay on.) The fan is not working. tilation /Air
0028 Time Available: 7-4 Conditioning

Page 49 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
187671 Pee Dee Closed Work Orders Room has mold in it. 8/21/2017 212 Climate Checked out and found no mold, replaced dirty ceiling tiles around supply grilles. 8/31/2017
Elementary - Control
0039
187771 Conway High - Closed Work Orders Leak in the ceiling in the robe storage closet in the chorus room. She removed the 8/22/2017 chorus room Carpentry 24AUG2017 tried to look but did not want to disturb class in session. 9/25/2017
0004 molded tile leaking from above the tiles. Time Available: 7:00 AM M1 19SEPT2017 located leaking area on the roof
25SEPT2017 applied sealant to repair the leaking area on the roof.
187803 Aynor High - Closed Work Orders The teacher reported: 8/22/2017 J201 Heating/Ven Checked the programming via apogee and seen there was no override time in on the 9/8/2017
0001 My room is continuing to get warmer as the day progresses. The air never turns off. tilation /Air program so I added 3 hours to the overrides time.
It has been running steadily since this morning. The humidity feels very high. I know Conditioning
other teachers are having trouble with the moisture/humidity in there rooms as well.
Time Available: ASAP
187816 Myrtle Beach Closed Work Orders Rooms 706 and 708 are very warm. The thermostats show cooler temps but the 8/22/2017 rooms 706 & Heating/Ven room 706 re-set tec ok now room 708 unit low on refrigerant add refrigerant running ok 8/29/2017
Middle (old) - rooms are very warm and humid. Time Available: any 708 tilation /Air now .
0016x Conditioning

188170 Green Sea Closed Work Orders Requesting a dehumidifier for the Weight Room. The weights are rusting due to the 8/24/2017 Weight Room Heating/Ven Checked room changed points in computer on apogee this should make unit run longer 9/7/2017
Floyds High - humidity in the room. tilation /Air and not have as big as temp swing.
0006 Conditioning

188182 Myrtle Beach Closed Work Orders Rooms 205 and 206 commolds water is backing up will not go down have to fluse 8/24/2017 room 205 & Plumbing toilets will not flush tried to snake and plunged but with no success. after doing that 8/29/2017
Primary - 0035 more than one time before it goes down thanks. Time Available: anytime 206 pulled toilet and ran drill snake down sewer pipe but it seem to be working fine. after
more investigating we found it might be vent pipe. went on roof and the vent pipes look
good. im thinking about running snake down vent pipe to see if that might help. will talk
to more people on the problem. had to get on roof and snake out vent pipe. did that it
seems to be flushing good

188282 North Myrtle Closed Work Orders Room 813 is very damp. Requesting a dehumidifier. Time Available: 7:30 8/25/2017 813 Heating/Ven found outside air opened got 10" damper installed room more comfortable now 9/13/2017
Beach Middle - tilation /Air
0037 Conditioning

188292 Myrtle Beach Closed Work Orders need to have commold check water will not go down in room 204 thanks. Time 8/25/2017 room 204 Plumbing found that the vacuum breaker was leaking. so I turned off the water and replaced the 8/28/2017
Primary - 0035 Available: anytime vacuum breaker with new one and now it works good.

188322 Burgess Closed Work Orders *KITCHEN* ...restroom in back kitchen... Ms.Shelley(kitchen manager) has asked 8/25/2017 KITCHEN> Heating/Ven Check found exhaust fan for that restroom and the hallway restroom connected 8/31/2017
Elementary - if anyway possible to install some sort of exhaust fan in kitchen restroom. Restroom tilation /Air together the fan motor was bad the next day Greg replaced motor explain to kitchen
0063 stays warm and has no air circulation... damp humid air is contributing to growth of Conditioning manager
mold in restroom also. Thank you for your attention. Time Available: ANY TIME

188391 Aynor High - Closed Work Orders For the last three days it is extremely humid in class room F110 and funny sound 8/25/2017 Class RM Heating/Ven Checked this room via apogee. The unit was running properly it was putting out a 20 8/28/2017
0001 coming from the AC in the ceiling. (this is a new sound) The room have a large F110/Chorus tilation /Air degree split and this is all the unit can do. The room temp is 73 degrees and the
dehumidifier in the ceiling. It could be either of the two Time Available: Any time Conditioning compressor points are in the right percentage. This is all the unit can do.

188392 Aynor High - Closed Work Orders Room J103 HP087 temp. 73 but the room is humid. need to be check Time 8/25/2017 J103 Heating/Ven Checked this unit via apogee. The unit is running properly and cooling properly the 8/28/2017
0001 Available: Any time tilation /Air room temp is 73 and the discharge air from the unit was 63 degrees. The compressor
Conditioning on and off points were set at the right values. There is nothing more that can be done
to this unit far a humidity.

188761 Pee Dee Closed Work Orders Room is HOT Heating/Ven Checked out and made set point adjustments, unit working normally at this time.
Elementary - tilation /Air Humidity concerns but should be ok after Make up air handlers are operating normally.
0039 Conditioning Ordered parts.

8/29/2017 305 9/6/2017

Page 50 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
188850 Pee Dee Duplicate Request It is VERY HOT in this room. The thermostat is reading 70 degrees, however, this 8/30/2017 305 Heating/Ven Work being done on work order 188731.
Elementary - room is VERY HOT & HUMID! tilation /Air
0039 Please adjust the humidity in this room! Conditioning

188884 Horry Ed. Closed Work Orders Need: 8/30/2017 Furniture 8-30-17 - Waiting on quotes 10/30/2017
Center - 0176 16 Large round blow mold tables 9-7-17 - Ordered
96 chairs for tables 9- 28-17 - Tables and chairs delivered.
10 Conference Chairs 10-20-17 - Conference Chairs received.
188951 Kingston Closed Work Orders The teacher said that she got mold growing in the studio in the library. Time 8/31/2017 Studio Carpentry work being taking care of on w/o # 191433 10/2/2017
Elementary - Available: 7-4 room306
0028
188954 Kingston Closed Work Orders The closet has mold growing in it,I think its that same wall in the studio. Time 8/31/2017 501 Painting These rooms have been cleaned and disinfected. 11/21/2017
Elementary - Available: 7-4
0028
189191 River Oaks Closed Work Orders rOOM 507 HP-52 Complaints that the room is very humid and thinks thermostat is 9/1/2017 room 507 Heating/Ven CHECKED UNIT OPERATION. FOUND UNIT COOLING SETPOINT HAD BEEN 9/12/2017
Elementary - not correct, is does feel a lot wamer in the room than what it says Time Available: tilation /Air CHANGED TO 74. LOWERED COOLING SETPOINT. UNIT OPERATING
0065 any Conditioning PROPERLY.

189203 South Conway Closed Work Orders Please take down mirrors in the remolded bathrooms and reinstall the all stainless 9/1/2017 Glass\Windo 04OCT2017 all mirrors replaced in areas requested with stainless steel ones. 10/6/2017
Elementary - steel mirrors (located in the warehouse with orange shrink wrap around them). The w Repairs 05OCT2017 old mirrors put on pallet in warehouse at Charles Cooke direction - please
0045 new mirrors are the same size so all previous wall holes should be covered. Please email Charles and let him know to list these on Gov deals.
use stainless screws in plastic anchors to mount the mirrors.

All glass mirror will need to be stored in the warehouse to be sold on GOV Deals.

189222 Forestbrook Closed Work Orders No AC in the gym...water is dropping on the floor 9/1/2017 gym Heating/Ven I went and check water in gym. it look as if they had the outside door open and the cold 9/1/2017
Middle - 0051 This area is prone to mildew Time Available: as soon as possible tilation /Air air was mixing with the hot air. I told them to try and keep doors close. the girls locker
Conditioning room was not cooling good. it has a small unit to try and keep room cool. the make-up
air unit helps keep it cool. it was off. I release it and room started cooling down.

189533 Carolina Forest Closed Work Orders His room has become very hot and humid. Says thermostat is at 77 but feels like 80 9/5/2017 C109 Heating/Ven REPLACED MELTED ROOM SENSOR. CHECKED UNIT OPERATION. UNIT 9/7/2017
High - 0052 in there. Also the teachers planning room in C house is beginning to get warm as tilation /Air OPERATING PROPERLY.
well, please check out Time Available: morning Conditioning

189596 North Myrtle Closed Work Orders Room 813 is very humid, please check. 9/5/2017 See below Heating/Ven closed outside air 9/13/2017
Beach Middle - Room 709 very warm, reading 74 degrees. Time Available: 7:30 tilation /Air
0037 Conditioning

189655 Pee Dee Closed Work Orders Very humid and hot. 9/6/2017 202 Heating/Ven Checked out and found unit operating normally, also went to room 204 and found 9/20/2017
Elementary - tilation /Air defective t-stat. Replaced and operated- running normally at this time.
0039 Conditioning

189661 Loris Elementary Closed Work Orders Room 202 - very Humid and warm. You can feel the moisture in the air. 9/6/2017 809 Heating/Ven Checked room 202 changed points in program to cycle fan and make unit run time 9/7/2017
- 0032 Time Available: mon-fri 8-4 tilation /Air longer to get humidity down in room.
Conditioning

Page 51 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
189708 Aynor Middle - Closed Work Orders auditorium thermostatic reading 72 degrees teachers and students complaining that 9/6/2017 300 Heating/Ven units are at set point there is nothing else they can do. 9/7/2017
0057 it is hot and humid and moldy and mildew smell.l nurse requested for a mold and tilation /Air
mildew test Time Available: asap Conditioning

189717 Forestbrook Closed Work Orders Please check AC unit in this classroom. Teacher also stated the room is humid, 9/6/2017 Room 206 Heating/Ven I went and check the unit. the t-stat read 73degree. they had room door open and told 9/7/2017
Middle - 0051 muggy, and has developed an odor. Time Available: as soon as possible tilation /Air them they was getting hot air from hall and the outside door the was open. I set the loop
Conditioning out to 100% and check the pressure on unit it was 74/235. I asked the teacher to keep
door close and see if it will be better. I did not smell no odor. I talked with ms.pilkey
about it
189889 Kingston Closed Work Orders This reading interventionist classroom is very humid. The teacher has had mold 9/8/2017 205 Heating/Ven fans working 9/15/2017
Elementary - covering her chairs several times that she has cleaned off. Time Available: 7-4 tilation /Air
0028 Conditioning

190162 Conway Middle - Closed Work Orders Classrooms A104 & A105 both are very hot & humid, has a temperature reading of 9/12/2017 A104; A105 Heating/Ven Checked out and found units not cooling, put in portable cooler 9/20/2017
0017 77 degrees & continuing rising Time Available: Any tilation /Air until checked out and found off on head pressure. Reset and operated- units running
Conditioning normally at this time.

190431 Conway Middle - Closed Work Orders Principal request that the air quality of the room be checked out, has a strong odor 9/14/2017 B107 Heating/Ven Checked out and sprayed coil, everything else operating normal. No unusual odors 11/8/2017
0017 inside the room and not sure if its due to the HVAC system Time Available: Any tilation /Air coming from duct work.
Conditioning

190505 Conway High - Closed Work Orders C206 the temperature is 78 degrees also the njrotc classrooms and hallway is very 9/14/2017 c building Climate Visited classroom and found unit not cooling. Troubleshoot unit and found 3phase 10/10/2017
0004 humid Time Available: anytime Control monitor was faulty after checking compressor windings and any phase imbalance.
Temporarily bypassed to provide cooling in classroom. Ordered replacement phase
monitor from warehouse and will replace when part is picked up. Returned Monday and
changed out phase monitor. Checked unit operation and found it operating normally.

190737 Kingston Closed Work Orders Their is mildew all over the tile in the restroom inside the classroom. Time Available: 9/18/2017 203 Roof Changed ceiling tile out and cleaned grids. No sign of mildew.. 10/3/2017
Elementary - 7-4
0028
190781 Aynor High - Closed Work Orders The band room dehumidifiers need repair Time Available: ASAP 9/18/2017 Band room Electrical picked up the dehumidifiers from the warehouse. Installed the dehumidifiers in the band 1/25/2018
0001 room. Ran new drain hoses for the new dehumidifiers. Removed and disposed of the
old dehumidifiers
190792 Aynor High - Closed Work Orders Clean, prime and paint metal work around front of building. Flaking off and mildew 9/18/2017 Painting Had Contractor to clean flaking paint off of all metal at front entrance, prime and 10/4/2017
0001 bad. repaint.

190804 North Myrtle Closed Work Orders The room is very humid and much hotter than the rest of the building the moisture in 9/18/2017 813 Heating/Ven cycled fan checked humidity 58% 10/4/2017
Beach Middle - the air is very noticeable. Time Available: jlapier@horrycountyschools.net tilation /Air
0037 Conditioning

190811 Forestbrook Closed Work Orders Hello...We have several tiles-in the kitchen and vents in the kitchen, dish-room, 9/19/2017 307 Custodial This is a custodial or Food Service request. 5/24/2018
Middle - 0051 storage room that are dirty and appear to have mildew and lighting covers that need
to be cleaned-Was not sure who takes charge of this-Thank you-William

190819 North Myrtle Closed Work Orders Please check air in room 813. Teacher says it is warm and humid in room again. 9/19/2017 813 Heating/Ven work completed on w/o#190804 10/6/2017
Beach Middle - Time Available: 7:30 tilation /Air
0037 Conditioning

Page 52 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
190833 Myrtle Beach Closed Work Orders we are in a urgent need of a humidifier for a room in back of media center where 9/19/2017 media center Heating/Ven purchase dehuuidifler for class room in library. 9/22/2017
Intermediate - teacher has a class tilation /Air
0053 Conditioning

190975 Myrtle Beach Closed Work Orders Mildew on several walls in kitchen area Time Available: asap 9/20/2017 kitchen Painting 9/20/17, removed mildew on several walls. Mildew caused by back door being propped 9/21/2017
High - 0010 open during deliveries. Kitchen manager assured me that she will keep on them about
this.
191044 Loris Elementary Closed Work Orders Room is really muggy. Could you try and adjust the humidity in the room? 9/21/2017 601 Heating/Ven Checked 601 found no problem with unit. room 72.75 putting out 56 supply temp fan is 9/21/2017
- 0032 tilation /Air set to cycle.
Conditioning

191062 South Conway Closed Work Orders Very Hot and Humid in the Cafeteria. Reading 75 but much hotter than that. Floors 9/21/2017 Cafeteria Climate Checked cafeteria dinning room and found all units blower fans running. However no 9/22/2017
Elementary - will not dry because of the humidity and it has become a safety issue. Per Henry Control cooling was operating. Went on roof and checked unit operation found no compressor
0045 Time Available: any control signal from TEC. Checked TEC and found load shed relay holding out all
compressor's for cafeteria. Contacted Dennis McCrary and CMI to look at issue.
Informed Principal of issue. Waiting on update from Dennis. Checked units this
morning on Apogee and they are working normally.

191164 Ocean Drive Closed Work Orders The A/C in room 804 is not working properly can we please get this checked out. 9/22/2017 804 Heating/Ven system low on refrigerant no leak found at this time charged with 410-a cooling now will 10/5/2017
Elementary - Below is an e-mail that I received. Thanks Jerry HilburnGood morning, tilation /Air schedule a time to come in and clean all evaporator 10/05/17 returned today cleaned 3
0066 I hate to be a pain, but I really think there is something wrong in my office. The air Conditioning mini-slit evap coils along with blower wheels
was repaired, yet it is still dripping. (Wet floor and wall streak indicated in photos)
Today there are water droplets and black dots on everything beside my desk. The
stack of notecards are curling from the moisture. (see photos) I am congested and
was this way most of last year. I was on antibiotics five different times. I had tests
ran that revealed I am allergic to nothing. I strongly feel there is something in these
rooms whether it is mold, mildew, or dampness. Ms. Fowler bought a dehumidifier
for me, which is awesome. It fills up 2 times a day and has to be emptied. There is
still an odor and visible spots revealing something out of the ordinary. Can we
please get an air quality check? Please also resubmit work order for repairs.
Thanks!
Jill

Jill Chandler
School Counselor
National Board Certified-Early Childhood Ocean Drive Elementary School
jchandler@horrycountyschools.net
843-390-6908

Time Available: anytime

191312 Conway High - Closed Work Orders 67 degrees, very humid on b hall upstairs 9/25/2017 main office Climate Worked on HP29 nurses office and found a bad blower belt. Went to auto supply and 9/28/2017
0004 It is 78 degrees in the nurses office. HELP. Please place work order. We need it Control picked up replacement belt. Returned and installed belt, adjusted belt to proper tension.
cold in here like it normally is. It was hot Friday but I thought it was a fluke. Started unit up and checked operation. Left unit operating normally. Adjusted RTU 7
which serves admin offices. Also reset tripped unit RTU 5 that serves B hall second
Ginger Peloquin, R.N. floor. It is now cooling properly.
School Nurse
Conway High School
843-488-6103 office
843-488-0686 fax Time Available: 7:00 am

Page 53 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
191395 North Myrtle Closed Work Orders Room 813 continues to be humid and damp. (Teacher has already purchased 9/26/2017 813 Heating/Ven completed on w/o#190804 10/6/2017
Beach Middle - damp rid containers on her own but that has not stopped the problem). Time tilation /Air
0037 Available: 7:30 Conditioning

191433 Kingston Closed Work Orders The indoor air quality is not good in these rooms, per our nurse M. Anderson. Time 9/26/2017 201/502 Heating/Ven addressing humidity issues found all four mau's inoperable for various repairs that need 4/13/2018
Elementary - Available: 7-4 tilation /Air to be completed got list of materials to be ordered
0028 Conditioning 10/3/17 Wipe walls with disinfectant, removed ceiling tiles and wipe walls above ceiling
grid, also (used lift to get to top of walls and above ceiling grid, in music room). Rooms
wiped 607 entire office, the bathroom in 201, the bathroom in 203 (also the ceiling grid
was rusted so we sanded and painted the ceiling grid in this area), 12/4/17 installed
new condenser motor for make up air unit 4 12/5/17 repairing refrigerant leaks in
condenser coil A caused by condenser motor falling on coil 12/20/17 installed new
condenser fan motor and blade for mau 1 charged system with 50lbs of r-22 per rating
plate circuit is working properly 1/15/18 picked up new motor and motor bracket for
mau #3 started assembling

191517 Seaside Closed Work Orders we have a light out in the cafeteria. Also a ceiling tile around a speaker has mildew 9/27/2017 cafeteria Electrical Replaced ballast and bulbs in light fixture in cafeteria. Removed speaker from tile. Cut 9/28/2017
Elementary - on it from when the air conditioners leaked condensation, please change. A tall new tile. Inserted new ceiling tile and mounted speaker back in tile.
0050 ladder or lift will be needed Time Available: any
192342 Forestbrook Closed Work Orders Teacher has reported mildew/mold in her classroom bathroom. Time Available: as 10/5/2017 802 Roof 10/6/17 went to class room and inspected the bathroom and found that there is some 10/6/2017
Middle - 0051 soon as possible wax that probably was spattered on the bottom of the walls when they were stripped.
And some dust along the top of the walls. I took some mildew cleaner and applied to
the walls and scrubbed them then wiped them with a damp cloth. Cleaned up the area.

192343 North Myrtle Closed Work Orders Please check room 209. Reported it smells moldy and stuffy. Time Available: 7:30 10/5/2017 209 Heating/Ven only supply diffuser in room shut not enough air flow in room opened and cycled fan 10/19/2017
Beach Middle - tilation /Air
0037 Conditioning

192614 St. James Closed Work Orders office feels muggy and humid. 10/9/2017 178 Heating/Ven This is the office in the boys locker room ,Adam said the coach was warm and muggy 10/9/2017
Intermediate tilation /Air at 7AM , checked at 330Pm room temp 71.5 ,55% hudmidy, Adam spoke to Contractor
School (New) - Conditioning
0071

192706 St. James High - Closed Work Orders The entrance door to the Media Center is not closing completely……..I’m not sure 10/10/2017 Media center Key and Repaired and serviced exit device 10/17/2017
0058 if it’s from humidity Time Available: low Lock

192710 North Myrtle Closed Work Orders Very humid again in room 811. Time Available: 7:30 10/10/2017 811 Heating/Ven checked system working properly at this time 1/17/2018
Beach Middle - tilation /Air
0037 Conditioning

Page 54 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
192738 Conway High - Closed Work Orders Mrs. Peloquin, 10/10/2017 a208 Carpentry Completed SD,10/17/17 2 glue boards. School personal is going to clean areas of 4/18/2018
0004 concern. Talked with Michael about this 4/20/2018 and he is going to take care of it.
I think I may have mold again all over my classroom's walls. In addition, there are Terry Hucks
mice droppings all over my desk and different parts of my classroom. I have for
traps but none have been placed since the beginning of the year. Thanks.

Enoel Hidalgo
World Languages Teacher
Conway High School
2301 Church Street
Conway, SC 29526
Phone (843) 488-0662 ext 62158
Ehidalgo@horrycountyschools.net Time Available: 7:00 am

192739 Conway High - Closed Work Orders Mrs. Peloquin, 10/10/2017 a208 Roof 10-20-17 wiped/cleaned walls 10/20/2017
0004
I think I may have mold again all over my classroom's walls. In addition, there are
mice droppings all over my desk and different parts of my classroom. I have for
traps but none have been placed since the beginning of the year. Thanks.

Enoel Hidalgo
World Languages Teacher
Conway High School
2301 Church Street
Conway, SC 29526
Phone (843) 488-0662 ext 62158
Ehidalgo@horrycountyschools.net Time Available: 7:00 am

192742 Conway High - Closed Work Orders Tiles in Ms. Closson’s room need to be changed. The tile around the speaker was 10/10/2017 c101 Carpentry Howard replaced tile. See work order 1922821 for action taken. 10/17/2017
0004 never changed (due to difficulty or some reasoning). The vent continues to leak and
mildew has spread to other tiles. The staff continue to have medical issues and this
is a special needs room filled with asthma students. Please place a work order for
tiles to be changed, dehumidifier (or evaluation for one), repair of vent and A/C to be
looked at due to pipe leaking on the floor.

Imperative that this room has what it needs due to the concentrated amount of
students with chronic medical issues. Thank you.

Ginger Peloquin, R.N.


School Nurse
Conway High School
843-488-6103 office
843-488-0686 fax Time Available: 7:00 am

192959 Waccamaw Closed Work Orders need a dehumidifer 10/12/2017 213 Heating/Ven CHECKED UNIT OPERATION. UNIT OPERATING PROPERLY. BOUGHT NEW 10/13/2017
Elementary - tilation /Air DEHUMIDIFIER FOR ROOM.
0042 Conditioning

Page 55 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
192968 Kingston Closed Work Orders Their is a strong mildew older in the classroom. Time Available: 7-4 10/12/2017 115 Heating/Ven Inspected room with Ross. Didn't smell anything out unusual. Teacher in room agreed. 10/13/2017
Elementary - tilation /Air Checked around room above tile and found no issues.
0028 Conditioning

193028 Daisy Closed Work Orders PICK UP BROKEN DE-HUMIDIFIERS Time Available: ANYTIME 10/12/2017 THEATER Heating/Ven picked up dehumidifiers from daisy and dropped off at shop. 10/17/2017
Elementary - STAGE tilation /Air
0021 Conditioning

193146 Myrtle Beach Closed Work Orders Mold in Rm 15. Teacher informs that last year maintenance provided a dehumidifier 10/14/2017 Rm 15 Climate 10/23/2017-purchased a new dehmidifiler and took old one and put in office . 10/23/2017
High - 0010 but it does not eliminate the musty smell, and is too noisy to run during instructional Control set temperature in room up 3 deg it was set at 70deg set to 73deg.
time. Please remove the old dehumidifier and purchase a new one and install per
Jeff, thanks Artie
193285 Conway High - Closed Work Orders N3 in NJROTC the AC unit has a small mold issue. Time Available: 7:00 am 10/16/2017 N3 Climate This classroom and unit was checked by Mike Sowerby on 10/18 and I re-checked it 10/20/2017
0004 Control today and found no signs of mold. There are small indentations in block wall that look
like black spots.
193292 Aynor High - Closed Work Orders 2nd report in a month 10/16/2017 K101 Heating/Ven Checked unit the compressor points had also been changed also so I set the night set 10/25/2017
0001 tilation /Air point a little lower to see if this helps this problem.
Ms. Davenport is reporting- Conditioning
I am sending this up to let you know the humidity in my room has not really stopped
happening. The temperature is hovering around 76 to 78 degrees according to my
wall mount thermostat by my desk. It feels like my compressor is not turning on to
help move the humidity out of my room. Time Available: ASAP

193371 Horry Ed. Closed Work Orders Please put a Dehumidifier or two in RM#14. It has always been very damp in that 10/17/2017 RM # 14 MS Heating/Ven cycled fan so it would shut down when ac is not calling 10/18/2017
Center - 0176 room. The students and staff are affected by the damp conditions. Please help with tilation /Air
this problem ASAP. Thank you! Time Available: ASAP-ASAP ASAP Conditioning

193395 Socastee Annex Closed Work Orders Large area on the walls where mold is coming through the paint. It is located near 10/17/2017 200 hall near Painting Cleaned walls with disinfectant. 10/19/2017
room 210 and goes around to the other side of the hall. Time Available: asap learning zone

193567 Aynor High - Closed Work Orders Please install a dehumidifier in Ms. Johnson's class. She is reportedly having 10/19/2017 i104 Heating/Ven Checked unit the compressor on and off settings have already been changed. so I set 10/25/2017
0001 multiple issues due to humidity in the classroom. Concerns have been emailed to tilation /Air the night set point lower to see if this helps out with humidity problems.
Facilities previously, but some of the concerns are: Conditioning
-classroom doors have been shaved, due to swelling from moisture (door must be
pulled and held to lock)
-classroom items have been damaged or discarded due to reported moisture
problems
Time Available: ASAP
193807 Conway High - Closed Work Orders I was requested by Terry Hucks to check room A/C unit operation and any signs of 10/23/2017 A208 Heating/Ven Checked unit out for proper operation in cooling mode. Found no issues with unit after 10/23/2017
0004 mold. tilation /Air connecting to TEC. Also checked room for any signs of mold and found no signs. Terry
Conditioning stopped by with Mike McCants and they saw no signs of mold in classroom. Also
checked Munters MAU that serves the second floor with conditioned outside air. Found
everything was operating normally.

194350 Kingston Closed Work Orders Their were mildew growing on the wall. Antoine clean the wall real good and 10/30/2017 210 Heating/Ven measured humidity in room was about 70% without air conditioning running cycled fan 10/31/2017
Elementary - removed the mildew. Can u ck to see if the temp is correct in this area. Time tilation /Air so it will not run without the call for heat or cool, after fan shut off humidity dropped to
0028 Available: 7-4 Conditioning 60% will continue to monitor

Page 56 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
194736 Socastee Annex Closed Work Orders Rooms 106,300,306,308 and 312 over flow pan is full of water on the dehumidifier 11/2/2017 Heating/Ven I went and check the units with water in the mau units. I vacuum all the water out of the 11/21/2017
systems. tilation /Air unit. I did not do class room 308, it had a lot of thing in the way. will do it when the
Conditioning remove some of the things. the classroom is not used for teaching but to store things

195719 Ocean Drive Closed Work Orders Need to have HVAC system checked to make sure it is operating properly. Checked 11/14/2017 Room # 716 Heating/Ven checked both bard units both working properly 11/20/2017
Elementary - area and found mildew under carpet. Also please share info with teachers of the and 717 tilation /Air
0066 consequences of propping doors open and the effect it has on The HVAC system. Conditioning
Pictures have been sent to Richard Lane to substantiate this problem. Thanks Jerry
Hilburn Time Available: ASAP``

195919 St. James Closed Work Orders per Mrs. McDavid air quality needs to be checked in P 104 and reading room. There 11/16/2017 reading room/ Heating/Ven Check Room P104 found that that is the Room Gary is working on WO#195266, the 11/17/2017
Elementary - is a musty smell coming from both rooms P104 tilation /Air bathroom walls are dry and there's a dehumidifier to draw the walls are drawing and
0030 Conditioning may be causing the odor I explain to James that wait till after the bathroom is done and
repainted the smell will probly go away. the reading Room , the Room across from the
main office, the rooftop unit is new and clean, there's a series of old very old cabinets
given off a musty smell talk to Mrs McDavid and ask her permission to remove
shelving countertops and repaint Room she said that will be OK she gave us
permission to do , spoke to Philip said he would make a separate work order for that
job 4th

195978 Conway Closed Work Orders We have a dehumidifier in room 105 that is not working. Time Available: Asap 11/17/2017 TLC 105 Heating/Ven Checked unit the reason the compressor is not running on the dehumidifier is because 11/20/2017
Education tilation /Air the humidity is lower than the setting on the unit.
Center - 0172 Conditioning

197199 Socastee Complete My room has been very humid the past few days, feels like very little movement of 12/5/2017 256 Climate Increased minimum airflows. 1/10/2018
Elementary air. Time Available: ASAP Control Requested HCS reduce heating setpoint to 69 degrees.
NEW - 0054
197356 Socastee Complete Room 110 That awful sewer smell is back in my classroom and it is still too warm no 12/7/2017 Room 156, Climate Rm 110 - Have not been able to recreate sewer smell - studor vents were added to the 12/22/2017
Elementary matter what the thermostat says! 140 Control waste stack vents where the Owner felt the smell was coming from. Let us know if the
NEW - 0054 Room 140- Humidity levels are on the rise!! 65% in my room! Time Available: smell comes back along with any information regarding time of day, frequency,
ASAP adjacency to diaper changing stations, etc. We think we have this fixed.
Room 140 - Adjustments were made and are ongoing to this room until such time that
the issue is resolved to the satisfaction of its inhabitants.

197358 Socastee Complete This was emailed to me on 12/6. I know I emailed last week and you put a work 12/7/2017 140 Climate Reduced heating setpoint and increased minimum airflow 12/22/2017
Elementary order in, but no one has been here and it has NOT gotten any better. In fact, today Control
NEW - 0054 was way worse. I was hoping we could possibly put through another work order or
something???? Sorry to be a nuisance, but I was hoping that the work order would
maybe get taken care of soon and maybe they possibly missed it.

We have all been sweating a lot today…. All day! And even right now…very
uncomfortable. We are trying to deal with it and make it through the day, but today
was miserable and I’m already not feeling well again. &#9785;

Also - - I’ve noticed that the humidity in the last week or so has been teetering on
the higher end. I know it should typically be between 40-60% for comfort as well as
mold/mildew growth, so I thought it might be important to pass on what we’ve
noticed. Several teachers and myself have noticed our humidity is always on the
higher end. It is going back and forth between 57%-64
Time Available: ASAP

Page 57 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
197420 Kingston Closed Work Orders Their is mildew around the window inside the classroom. Time Available: 7-4 12/7/2017 115 Painting Did inspections and saw that seals around windows needed replacing. Prices being 5/25/2018
Elementary - submitted.
0028 5-25 glass replaced due to gas vapor escaping. After follow ups seems issue is fixed.

197422 Kingston Closed Work Orders These three rooms has mildew along the outside wall in the classroom. Time 12/7/2017 112,114,116. Painting These windows have had the double glass replaced due to gas vapors escaping. After 5/25/2018
Elementary - Available: 7-4 follow up it looks like issue is under control
0028
197423 Kingston Closed Work Orders The room has mildew along the window seal. Time Available: 7-4 12/7/2017 109 Carpentry Checked around windows and found water condensation due to the argon gas between 4/11/2018
Elementary - the windows has leaked out due to the seal failing. Window glass will need
0028 replacing.Requested estimate from Low Country Glass on replacing 14 windows
throughout building that have the same issue , received estimate and also approval to
start work ,notified Contractor . Work was completed and checked after completion.
RLane Work order on PO # sheet was wrong should be 197423

197753 St. James Closed Work Orders Please set up a dehumidifier in the media center per Pam Dowden. 12/11/2017 Heating/Ven Check out and made sure dehumidifier was operating in a normal order and also took 12/12/2017
Elementary - tilation /Air apart and cleaned the coils to make sure air could flow freely. Delivered the unit to the
0030 Conditioning school and got up with Jamie on where to place it in the Media Center.

197765 St. James Duplicate Request need dehumidifier in media center please 12/11/2017 media center Heating/Ven Work order has already been made wo 197753
Elementary - tilation /Air
0030 Conditioning

197798 Conway Middle - Closed Work Orders As part of the summer work, CMS is requesting that all HVAC systems be checked 12/12/2017 Cafeteria and Heating/Ven I talked with Dennis about this and he said to esimate around 1.5 millon to complete 4/16/2018
0017 and REPLACED if possible. The humidity inside this old building is causing odor Main building tilation /Air this job. There is no funding for this at this time. This type of job would have to be
and bad smell in many of classrooms. The cafeteria (we discovered) a few months Conditioning completed by New Construction
ago is down an entire unit. Terry worked on this and let Ms. Pertell (the principal)
know that facilities would continue to work on this. Ms. Pertell is requesting that this
be a priority since the cafeteria has to work in very heated conditions during this
time. Time Available: Summer Hours

198204 Pee Dee Closed Work Orders There is an awful smell coming from the vents in this room. Please check the area 12/18/2017 405 Filters Checked out and talked with teacher, found odor was no longer since we got back from 1/10/2018
Elementary - for dead rodents..possibly a humidity problem..musky..thick smell. winter break. All is normal at this time.
0039
198205 Pee Dee Closed Work Orders PLease check the air in this room. Even though the temperature may be reading 12/18/2017 202 Heating/Ven Checked out unit and made sure running normally, also checked out humidity in room 12/28/2017
Elementary - OK, the humidity in this room is terrible. A couple years ago we had the same tilation /Air and was in specs. Unit running normally at this time.
0039 issue...humidity is almost unbearable. AC temperature is fine. Conditioning

198261 Ocean Bay Closed Work Orders Mildew on ceiling in bathroom Thanks Time Available: anytime 12/19/2017 Media Center Painting 12/19/17, looked at ceiling. Has mildew all over and also on door jamb. Spoke with 12/22/2017
Middle - 0061 Arnold and discussed potential cause. He said that he just replaced the fan. Possibly
was caused when fan didn't work. Will clean when school is out. 12/20/17, cleaned
ceiling and walls. 12/21/17, checked area to insure that all mildew was gone.

198267 Carolina Forest Closed Work Orders Need to make sure the a/c or heat stay on in this building through xmas break due 12/19/2017 C House Heating/Ven EMAILED DENNIS MCCRARY ABOUT HVAC SCHEDULE. 12/20/2017
High - 0052 to humidity issues going forward Time Available: asap tilation /Air
Conditioning

199125 Conway Closed Work Orders We have several items that we need picked up: 9 student desk, 1 shredder, 1 1/9/2018 TLC Hall Furniture 1/10/18 picked up assets. 1/10/2018
Education dehumidifier, 2 tables, 1 rolling desk a 1 wall organizer. Time Available: Asap Kitchen
Center - 0172

Page 58 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
199130 Loris Elementary Closed Work Orders Teacher says unit runs continuously creating issues for the class. Says numerous 1/9/2018 317 Heating/Ven Checked room cycled fan on indoor unit and dropped heat set point to 68 degrees. ran 1/11/2018
- 0032 students are sick and questions air quality. tilation /Air unit watched operation unit was blowing out 55 degree supply temp in cool.
Conditioning

199355 Academy for Closed Work Orders RM 506 the teacher is stating that a mold type odor coming out vents in her room 1/11/2018 RM 506 Heating/Ven 01 /11/2017-Found no order in room but did find air purifier not working due to UV light 1/12/2018
Arts Science and has to leave window open. i could not smell anything wrong but administration tilation /Air safety switch tripped. Reset switch and air purifier working fine. Checked make up air,
and Tech. - would like the air checked. the air filter gets changed every month and shows Conditioning return air and supply air vents/ducts. All were clean and clear. Checked humidity and it
0096 nothing on filter. teacher name is Rosina Belcher Time Available: asap ranged from 50.2 to 55.6.

199375 North Myrtle Closed Work Orders 812 has no air flow. Very humid in classroom. Time Available: 7:30 1/11/2018 812 Heating/Ven checked temp and and operation system working properly 1/17/2018
Beach Middle - tilation /Air
0037 Conditioning

199433 Palmetto Bays Closed Work Orders Teacher wants the Air Quality check says she cant breathe Time Available: asap 1/11/2018 215 Heating/Ven checked operation of a/c unit running ok relative humidity was 49 per cent and did not 2/19/2018
Elementary - tilation /Air smell anything in air the air filter was stopped up, replace filter.room temperature was
0056 Conditioning 73 deg did not found anything out of the norm.

199455 Aynor High - Closed Work Orders ATT: Terry Hucks MR. Spree would like to know what can be done about the 1/11/2018 POD Heating/Ven Check the RH% in the room the reading was 27% i also set the room humidity to not go 1/17/2018
0001 humidity in the POD. His internment has crached and the strip that whole the panels tilation /Air over 50% on the t stat. The reason the molding was falling off the wall because the
to gather is peeling off Time Available: Any time Conditioning finishing nails that were used looked like they shot threw the molding and was not really
holding anything. Also the thermostat was very loose on the wall. I have attached
pictures to the work order of the wall and the t stat.

199708 Forestbrook Closed Work Orders the teacher thinks it's smells like mold can someone check this out please. Time 1/16/2018 313 Climate I went and check the smell. the unit is new and working properly. I look in the ceiling to 1/19/2018
Elementary - Available: any Control see if any water was getting into class room. everything look good in ceiling. I talk to
0046 ms.vivian and ask if she can spray something on carpet to take smell away. I did not
smell or see anything in room.
200057 Myrtle Beach Complete Room is humid and hot. 1/18/2018 271 Climate Increased minimum airflow to space 2/7/2018
Middle (New) - Control
0016
200371 Myrtle Beach Closed Work Orders room 308 very humid if someone could please come out and check this room 1/23/2018 308 Heating/Ven 01/23/2018-Talked to teacher and tested humidity and temperature in room. Humidity 1/24/2018
Intermediate - usually never has heating or cooling problems tilation /Air running between 52 and 55 RH and temperature good. Checked APOGEE to verify
0053 Conditioning settings. System running properly.

200501 Myrtle Beach Closed Work Orders Do we have any dehumidifier if so can i have two for two of my rooms getting a lot of 1/24/2018 Room 123 Heating/Ven 02/02/2018-Tested dehumidifiers in warehouse over weekend. 2/7/2018
Primary - 0035 moisture in those rooms thanks Time Available: Anytime tilation /Air 02/06/2018- Found good dehumidifier and loaded on van.
Conditioning 02/07/2018-Delivered dehumidifier to room 123.

200783 Pee Dee Closed Work Orders Hot and humid in this room 1/29/2018 202 Heating/Ven Checked out and found room was at set point. Unit was working fine and did not feel 2/1/2018
Elementary - tilation /Air like it was humid in it. The humidity has been low. Will have to check in summer
0039 Conditioning months to see how it reacts.

200970 Ten Oaks Complete We have black mold under our dish machine and sink, we mop the water everyday 1/31/2018 kitchen Flooring 9/19/2018
Middle School - under it. It is the way the floor is pitched, but we need to know how to get rid of the
0070 mold. One of my employees that cleans it everyday is feeling sick. I don't know if it is
from the mold.

Page 59 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
201774 Socastee Complete teacher complaining about humidity room still showing temp at 71 / 72 degrees 2/7/2018 140 Heating/Ven Increased minimum air flow 3/12/2018
Elementary but still appears to be very warm Time Available: asap please tilation /Air Increased maximum air flow
NEW - 0054 Conditioning Decreased heating set point
Cleaned and flushed strainer and coil
Inspected hot water valve operation
201785 Socastee Complete Mrs. Cast- My room is still hot on a daily basis, in waves….I just hate to keep 2/7/2018 140,142,144 Climate Increased minimum air flow 3/12/2018
Elementary complaining but nothing has changed. HOWEVER, today is extremely hot and Control Increased maximum air flow
NEW - 0054 uncomfortable. Decreased heating set point
Cleaned and flushed strainer and coil
Some information that could be helpful: Inspected hot water valve operation

-I know the thermostats are reading 71 or 72 degrees, but I promise you, something
is wrong because this isn’t 71. The open lab thermostat says 71 degrees just like
mine, but when I’m in my room at 71 we are all hot and sweating and when we go
into the hall and open lab area where it also reads 71 we are cold within a minute. In
fact, I had goose bumps after only a minute of being out there.
I say all of this so you can understand that something must be going on if 71 feels
incredibly different from our room to the hall while it also reads the same
temperature.

-Oh, and it isn’t sunny today. And even a few weeks ago when it was rainy and
cloudy and down in the low 40s, it was uncomfortably hot in our rooms. Warm,
stuffy, and definitely not the feel of a 73 degree room.

-Also, I looked around and found that the humidity levels are higher than
normal…maybe that explains the different feeling? Or Part of the reason?
My humidity level is at 58 percent, and I checked a few rooms on this hall, and they
also are at 58 percent. We usually see around 40-46 percent.

-AND the image of a little guy in a box on the display screen, my guy is in his box,
but he is not in the box in room 142 or 144 that I know of since I checked those
rooms. I know that can be a sign that something isn’t working properly. And the
rooms seemed to get warmer and warmer as I walked from my room 140 and up the
hall (142, 144, etc).
Time Available: ASAP

202462 Forestbrook Closed Work Orders she says it feel like the air is not on very humid. Time Available: any 2/16/2018 102 ac Heating/Ven I check the unit on apogee. the temperature was reading 73degree. I check the set 2/19/2018
Elementary - tilation /Air point. the heat was at 70degree and cool 74degree. I put the heat at 68degree and cool
0046 Conditioning at 72.50degree. this came in on a Friday and it was warm out. I did it on a Monday. they
was ok with temperature setting.

202717 North Myrtle Closed Work Orders Please check room 811- Teacher and students complaining about it being 2/20/2018 811 Heating/Ven checked system on apogee cooling properly at this time 3/13/2018
Beach Middle - uncomfortable with humid. Time Available: 7:30 tilation /Air
0037 Conditioning

202728 Academy for Closed Work Orders RM 410 the HVAC is not working and room temp. 75 deg. and humid. Time 2/20/2018 RM 410 Heating/Ven lower room temperature setings and re-set TEC. 2/23/2018
Arts Science Available: asap tilation /Air
and Tech. - Conditioning
0096

Page 60 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
202738 St. James Complete room running 74 to 76 degrees need for them to be lowered to set points. Room 2/20/2018 school wide Heating/Ven Cooling Tower and Chiller were both tripped off. 3/12/2018
Intermediate also feel very humid and hot. Warranty-Construction. tilation /Air Both were reset and restarted.
School (New) - Conditioning
0071

202830 Pee Dee Closed Work Orders The school marquee is VERY dirty with mold & mildew. The lettering on the 2/21/2018 School Carpentry Had Contractor to clean up sign and repaint letters with new color so letters would 7/26/2018
Elementary - marquee is very tarnished and hard to read because the mold & mildew is the same Marquee stand out.
0039 color brown as the lettering. The entire marquee needs to be pressure washed to
make it more visible for our community.
202963 Waccamaw Closed Work Orders Urgent hp 02 75-78 in the noon to afternoon times. Also, very humid. 2/22/2018 principals Heating/Ven 02/22/2018-Found unit not working due to RTU o/d fan not working and bad capacitor. 3/1/2018
Elementary - office tilation /Air Replaced cap and ordered motor.
0042 Conditioning 02/27/2018-Picked up motor from Trane.
got motor and replace and ran unit runingok

203147 St. James High - Closed Work Orders B205 is very humid and warm. the thermostat is not working. B205 is on the first 2/26/2018 B205 Heating/Ven checked found blown fuses, checked for grounds, ohmed compressor, motor, replaced 3/6/2018
0058 floor in Fine Arts Blvd hallway, Time Available: medium tilation /Air fuses, checked found mechanical failure, ordered compressor, coming from Memphis,
Conditioning spoke to Jamison 3-6 Recovered 3.8 oz of refrigerant 20 to check for acid none found
disassembled unit remove compressor installed new compressor and wire and braised
pressure tested triple evacuated charge a with recover refrigerant check unit for proper
operation resembled unit also clean chemically clean evaporator and drain Pan and line

203159 River Oaks Closed Work Orders GYM, HP-58 at 74.4 now, real humid in gym. Time Available: any 2/26/2018 GYM Heating/Ven found outside unit not running and high pressure switch tripped out re-set high pressure 2/26/2018
Elementary - tilation /Air switch and unit came on but pressure not running right.so I cleaned outdoor coil to
0065 Conditioning make sure that's not the problem.pressure running better.
have to have filter change.

203253 North Myrtle Closed Work Orders Paint peeling off wall. Mildew is growing where paint is peeling. Very humid in 2/27/2018 811 Painting Work order has been requested to paint entire school , and was deferred for approval. 11/9/2018
Beach Middle - room. Time Available: 7:30
0037
203332 Aynor Middle - Closed Work Orders room is very humid and stuffy thermostat is reading 71 degrees Time Available: 2/28/2018 506-A Heating/Ven Checked unit via apogee. The set points were correct i just had to adjust the 3/1/2018
0057 asap tilation /Air compressor on and off settings.
Conditioning

203369 South Conway Closed Work Orders Something is growing out of wall..Looks to be mold. There are a couple other places 2/28/2018 Main Hazmat/Wa Visited school after admin staff had left for the day and found no visible signs of any 3/6/2018
Elementary - that have the same things growing out of the walls in other rooms. Time Available: Office/Office ste growth in front lobby area, admin office hallway or copier room. took pictures of walls in
0045 any Hall and office all areas and were sent to manager. Will stop by when staff is in to get location of
on main hall growth.
3-1-18 contacted staff and inspected areas , no mold or growth was found Not mold ,
burrs and blemishes about 1/4" on the walls that the paint popped off , avg 3 or 4 per
room in about 3 offices,
203659 District Office Closed Work Orders Air Quality; Tammy spoke with Jeff Carland; smell in hallway Time Available: when 3/2/2018 A Bldg hallway Heating/Ven Checked with Terry Huck and odor was not present, will check out on Monday morning. 3/5/2018
Four Mile Road - you are available to health tilation /Air Came back Monday morning and checked around for any unusual odors , none
0401 Conditioning detected at this time. Checked with employees in areas and they don't smell it either.
Plant near doorway was checked also.

204200 River Oaks Closed Work Orders In Media center HP-44 is blank, not sure if it is running or not, warm and Humid. 3/8/2018 LIBRARY Heating/Ven found thermostat blank checked unit and have voltage so I replace thermostat and unit 3/12/2018
Elementary - tilation /Air started running ok.
0065 Having several issues in library with the books and humidity, please see Shannon Conditioning library teacher said having issues in working.
when you come by Time Available: any so I purchase a dehumidifier and ran hose to sink for drain.
checked in and out.

Page 61 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
204289 Seaside Closed Work Orders Dehumidifiers in media center do not function properly. Please check Time 3/9/2018 media center Climate I went and check the dehumidifiers. they was working but one was making some noise. 3/16/2018
Elementary - Available: any Control I talk to teacher. she said it was use because it be very damp and books be messed
0050 up. I told her I will turn them off and see how it work without them. they had just got new
units last year and do not really need them. I will come back when it get warmer and
see how it doing. we do not have any dehumidifier to give her.

204292 Aynor High - Closed Work Orders Please inspect the HVAC vents and filters for dust, mold, humidity, etc. The teacher 3/9/2018 F11/Art Heating/Ven Checked unit the return has no duct work it is an open air return. So i checked inside of 3/12/2018
0001 states she is suffering from respiratory issues and her doctor suggests her tilation /Air the unit did not see anything out of the ordinary. I took some evaporator cleaner and
classroom be inspected. See Terry Hucks for details. Time Available: anytime Conditioning cleaned the indoor coil and washed it off with warm water. I also changed the filters that
are located on the roof. I also took a humidity reading the it was at 48%.

204907 Socastee High - Closed Work Orders Door to the freezer and ref ridge is rusted at the top where the door opens 3/19/2018 122C Heating/Ven checked out ,found this to be walk in coolers and freezer. 3/27/18 I check the cooler 5/11/2018
0011 It needs cleaned , Also the strips down the coolers and outside needs to be re tilation /Air and freezer. The gasket is in the wall and will have to put new caulk on it to cover the
calked due to mold Conditioning stain on it. I can not remove the gasket. The door bracket is rusted. I will order new
Time Available: asap bracket. The door gasket is old. I order new door gasket. I will put the new items on
when they come in. I will see if cleaning the gasket work for them. i
the gasket and door closer was order wrong. 5/9/18 i got the right gasket and door
closer. we put them on. we had to drill new holes in the stainless door cover. manager
was ok with what we done

205002 North Myrtle Closed Work Orders Room 1023 is humid and warm. Please check. Time Available: 7:30 3/20/2018 1023 Heating/Ven cycled fan and lowered set point system cooling properly 3/21/2018
Beach Middle - tilation /Air
0037 Conditioning

205029 St. James Complete please check cooling tower and chiller as rooms and the gym felt warm and humid 3/21/2018 school wide Heating/Ven Checked cooling tower and chiller 9/19/2018
Intermediate yesterday. tilation /Air
School (New) - warranty- Construction Conditioning
0071

205177 Palmetto Bays Closed Work Orders Please check air quality. The room has an unpleasant odor. Time Available: any 3/22/2018 412 Heating/Ven checked insde air-handler and cleaned coil and checked blower motor could not smell 4/9/2018
Elementary - tilation /Air anything looked inside duct and change filter,
0056 Conditioning came back and still cant found anything.

205178 Palmetto Bays Duplicate Request Air quality needs to be checked in this room. There is an odor. 3/22/2018 412 Heating/Ven
Elementary - Time Available: any tilation /Air
0056 Conditioning

205254 Myrtle Beach Closed Work Orders It was reported that a sewer smell was in the front office can you come and check 3/23/2018 Front Office Plumbing Went out to inspect we didn't detect any smell we checked around clean outs in the 3/26/2018
Primary - 0035 the air quality thanks. Time Available: Anytime office area no smell we talked with the front office they stated that the smell lasted
about two hours and smelled like broccoli we talked with custodian he said the same
thing also they had broccoli for lunch I'm thinking because we didn't find anything that
when the front doors at the office are opened it's creating a draft pulling the smell from
the kitchen down the hall to office area.

205596 North Myrtle Closed Work Orders Teacher reporting again from room 1023: Room is very humid...system is the same. 3/29/2018 1023 Heating/Ven completed on work order 206276 4/13/2018
Beach Middle - Time Available: 7:30 tilation /Air
0037 Conditioning

206194 District Office Closed Work Orders Please clean and service dehumidifier in H R Dept. 4/10/2018 H R Dept Climate Pulled dehumidifier per Terry Hucks and checked out and started PM. Checked out and 4/11/2018
Four Mile Road - Control replaced bulb and filter, operated unit and found running normally at this time.
0401

Page 62 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
206241 St. James Complete staff member in this room says the classroom feels humid and muggy on a daily 4/11/2018 134 Heating/Ven 9/19/2018
Intermediate basis in this room. Please check to see if we have a problem. tilation /Air
School (New) - Conditioning
0071

206376 Conway High - Closed Work Orders the weight room has been humid the last few days and very "stuffy." Time Available: 4/12/2018 weight room Heating/Ven Checked unit on apogee and found it failed. Visited classroom and found room sensor 4/18/2018
0004 ASAP tilation /Air blank. Checked main circuit breaker for unit and found it closed. Went on roof and
Conditioning checked RTU and found transformer circuit breaker tripped. Reset and then checked
unit operation. Found unit was now operating normally. Returned next morning and
found RTU for weight room failed again. Checked unit and found transformer had
tripped again but could not reset. Replaced transformer with same and restarted unit.
Contacted Ross to look at unit programing due to unit being in night mode during
daytime. He found a problem in unit program and rectified it. Will check unit in morning.
Checked unit in morning and found it in normal operation.

206766 Pee Dee Closed Work Orders Think there is mold in this classroom around vents, flag, and back wall. 4/18/2018 212 Climate Checked out and informed Terry Hucks , He will check out in morning after meeting to 5/2/2018
Elementary - Control see how to handle this. CALLED SCHOOL AND TALKED WITH SHERRY RABON
0039 ABOUT THIS AND SHE WAS GOING TO LOOK AT THIS, TOLD HER IF SHE SEEN
ANYTHING ON WALLS OR VENTS SHE WOULD NEED TO GET TONY TO CLEAN
EVERYTHING. I WILL HAVE TECH TO CHECK THIS UNIT OUT AND SEE WHY
VENTS ARE SWEATING IN THIS ROOM AND NONE OF THE OTHERS ROOMS
LOCATE AROUND THIS ROOM IS HAVING THIS PROBLEM. TERRY HUCKS. Made
changes to make up unit to ensure everything was working correctly. Teacher was
satisfied at this time.

206812 Academy for Closed Work Orders RM 410 HVAC HP 80 TEMP IS 73DEG. the teacher states there is no circulation of 4/19/2018 RM 410 Heating/Ven found temperature setings on 74 lower to 73 deg should me better. 4/19/2018
Arts Science air and room feels hot and humid. Time Available: asap tilation /Air
and Tech. - Conditioning
0096

207077 Waccamaw Closed Work Orders Please check the air quality in room 104, humidity level, co2 level, look and clean 4/23/2018 104 Heating/Ven cleaned indoor coil 2- times and cleaned out main drain and checked inside duct work 5/15/2018
Elementary - inside unit, coil etc. check all duct above ceiling. Also replace filter, label the old one tilation /Air looks ok just little dust from over the years of running. replace filters in room.
0042 and put in my office. Please take pictures of before and after. Conditioning came back next day and checked temperature in room was 72 temperature coming out
of ceiling regrister was 54 and humidity in room was 61 percent.and looked up in ceiling
with flash light and could not found anything out of the normal.0n Tuesday went back
with artie and paul and air -quality control to take measurements.
.

207096 Whittemore Closed Work Orders The things I have in walk in cooler are mildewing really fast. Time Available: anytime 4/24/2018 cafeteria Refrigeration Checked out and found cooler was operating normally, no mold or mildew was noticed, 4/25/2018
Park Middle - will schedule cooler to be cleaned in summer. Checked out with Terry Hucks and will
0013 have to do a couple of repairs to box in summer, also need some heater door strip
cover for both sides of door. Foam filled line set to outside of building. Ordered door
strip covers. Began cleaning out cooler to make repairs to box. Cleaned out box,
caulked every seam. Washed the walls and coil on evaporator. Letting box dry over the
weekend and will put racks back in and start unit. Also repaired heater strip on door
frame. Finished up caulking of cooler box, will come back Tuesday and turn unit back
on. Visited cooler to check cooling performance and box temp range. After watching
digital thermometer the temp swing in box is 30.7 deg to 35 deg (with box door closed).
Left walk-in cooler operating normally.

Page 63 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
207218 Palmetto Bays Closed Work Orders Principal wants air quality check in room Time Available: asap 4/25/2018 room 418 Heating/Ven checked operational of unit pressure good air flow was good look up in ceiling and did 5/29/2018
Elementary - tilation /Air not see or smell anything out of the normal the in roo at 72.5 deg and humidity level
0056 Conditioning was at 52 percent and filters was cleaned or just been change.

207287 Conway High - Closed Work Orders We need a humidifier in the front office ASAP its stuffy! Time Available: 7:00 am 4/25/2018 front office Heating/Ven Checked and cleaned dehumidifier and then dropped off at CHS office for Vickie 4/26/2018
0004 tilation /Air Hickman however she was not in. So I left it unplugged near her desk and informed
Conditioning receptionist.

207372 Green Sea Closed Work Orders In room 316 the teacher constantly complains about an unknown source of odor. 4/26/2018 316 Heating/Ven Did not smell anything in class room, checked with custodian, said they did not smell 4/27/2018
Floyds Smells like a damp odor. Please check hvac system or humidifier. Rug in room has tilation /Air anything either. Blower was not cycling, so I changed blower to cycle with system, will
Elementary - been replaced smell still remains. Time Available: Any Time Conditioning see if this makes any changes in damp smell reported by teacher.
0023

207444 Aynor High - Closed Work Orders Nurse Johnson tells me I should report indoor air quality issues to you. 4/27/2018 L102 Heating/Ven Checked above the ceiling I could not find any vent pipes above the ceiling. I took all 5/1/2018
0001 tilation /Air the covers off the indoor unit and cleaned and deodorized the indoor coil. I also
There is some kind of putrid smell that has invaded my classroom via the air system Conditioning checked the the indooor filters and the custodian had already changed them. I also
for the last two days while we are away at lunch. Yesterday, it was almost checked the emergency drain pan and it was dry also. This should fix the problem.
unbearable when we returned for 3B.

Today, I kept a check on the smell of the room in between classes. The custodial
staff did an extra cleaning yesterday just to be sure. There was no noticeable smell
all morning. I had an outside student walk in and smell the room after 3A before
leaving for lunch and she noticed NO bad smell. I then locked the room. When we
returned for 3B after lunch, I unlocked the door and the smell was back; not quite as
strong as yesterday, but bad none the less. The air system was on and should have
been the only way a smell could have entered the room.

Whatever we need to do to check this problem out would be much appreciated by


me and our students.
Time Available: ASAP

207520 Forestbrook Closed Work Orders Mrs.Brown said Tammy from the district said to put work order for air control 4/30/2018 403 Heating/Ven i went and check the room and unit. there was no mold on walls. the unit is new and 5/3/2018
Elementary - because they its mold in the room. Time Available: any tilation /Air there was no mold on it. the teacher said she was ok and did not smell or see and sign
0046 Conditioning of mold. i told ms vivain i will keep check on room

208105 South Conway Closed Work Orders Per Mr Hayes- Air smells really moldy or mildew Time Available: any 5/4/2018 front office Climate Spoke with principal and receptionist and smell is only present when unit cycles on. 5/4/2018
Elementary - Control Called for cooling on unit and shortly after I began to smell afoul odor. Went on roof
0045 and checked around then inside unit for any signs of possible cause. Found no direct
issue. Cleaned coil with coil cleaner. Then checked space for odors and none was
present. Reset all controls back to normal. Explained to receptionist what we did and
hopefully this will solve issue.

208362 River Oaks Closed Work Orders up on stage, very humid and screen is blank HP-60 Time Available: any 5/7/2018 gym/stage Heating/Ven checked unit and unit lost low voltage have to come back with 16ft. ladder 10/1/2018
Elementary - tilation /Air have to come back went the furniture on stage is gone.got 16foot ladder and paul
0065 Conditioning helped me , I found bad blower motor got motor from warehouse and replace motor.

208365 River Oaks Closed Work Orders **NEED CHECKED SOON PLEAse** 5/7/2018 gym Heating/Ven re-set TEC in unit ok. 8/15/2018
Elementary - Gym HP-59 at 75 this morning. It is very humid and warm in here... Time Available: tilation /Air
0065 soon please Conditioning

Page 64 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
208366 St. James High - Closed Work Orders Can we check the AC in the field house. It is being reported that it is hot and humid 5/7/2018 field house Heating/Ven varsity a/c ,found iced up ,ecm module burned, pick up replacement , removed blower 5/8/2018
0058 and the AC units are not cooling down like they should. Time available for service is tilation /Air assembly, removed and replaced motor, added capacitor , replaced filter, checked unit
anytime. Time Available: low Conditioning for proper operation, 5-8 JV a/c found low on gas found discharge Schrader valve cap
loose, added 3.5 #recovered refrigerant, replaced filter checked for proper operation

208371 Aynor Middle - Closed Work Orders a few area in the school a/c is not working thermostat is reading 76 degrees and is 5/7/2018 front lobby Heating/Ven There was a problem with apogee. Ross got the problem fixed and all units and hot 5/7/2018
0057 very humid Time Available: asap tilation /Air water heaters came on and worked properly.
Conditioning

208397 South Conway Closed Work Orders Teacher said room is very humid and hot air is not coming on. reading 74 but feels 5/7/2018 215 Climate Checked unit and room temp via Apogee and found room temp at 72 degrees with a 5/8/2018
Elementary - much warmer. Thank you! Time Available: any Control cooling setpoint of 73 degrees. Classroom appears to be cooled down to normal range.
0045
208751 Conway Middle - Closed Work Orders we are getting mold on the walls behind the paper goods and in the small room that 5/11/2018 stock room Climate Checked out and found several areas with mold/mildew build up. Contacted Terry 5/11/2018
0017 the pots and pans are in. Time Available: any Control Hucks and he got me some cleaner to clean up. Informed Manager and she will keep
an eye on. She plans on cleaning and rearranging storage area in summer. Also
noticed the pots and pan room is not conditioned and if they put wet pans in there it
might be a problem.
208785 Aynor High - Closed Work Orders MR. Davenport reported - The AC unit in my room (K101) is having trouble cooling 5/11/2018 Class K101 Heating/Ven I adjusted the compressor on and off percentage so the compressor will stay on longer 5/15/2018
0001 consistently during the day. Each morning I have to open my window and vent out tilation /Air to dehumidify the space this should also help the smell problem also.
the odor ( musty locker room smell ). I am not sure if the humidity is causing the Conditioning
smell or what it may be. After lunch each day for my 3b class, the smell gets
stronger. By 4th block the AC will kick in a bit Time Available: ASAP

208803 Seaside Duplicate Request Please lower the temperature in the cafeteria. The front thermostat reads 76.1 5/11/2018 Cafeteria Heating/Ven
Elementary - degrees and the rear one says 77.1 degrees and it is extremely humid in there Time tilation /Air
0050 Available: any Conditioning

208918 Conway High - Closed Work Orders roof is leaking down bookcase and causing mold 5/14/2018 A210 Roof 5-17-18 identified leak 7/5/2018
0004 7-2-18 cleaned and sealed roof
7-3-18 repaired roof and cleaned areas
208967 Pee Dee Closed Work Orders This room is HOT HOT HOT---the humidity in this room is making it almost 5/14/2018 213 Heating/Ven Checked out and found unit leaked out all its freon. Also noticed teacher has lamp 5/15/2018
Elementary - unbearable. Its thick & HOT in this room. Previous problems with the humidity in tilation /Air directed on t-stat keeping unit from ever shutting down. Checked for leak and found
0039 this room. Conditioning and repaired. Charged up unit- running normally at this time.

209067 Aynor High - Closed Work Orders CHORUS WILL BE HAVING THEIR CONCERT THIS WEEK 5.15 - 5.17.18 AND 5/15/2018 AUDITORIUM Heating/Ven Checked both units and units are operating. The compressor on and off percentages 5/16/2018
0001 THEY NEED THE AIR CONDITIONING ON ALL DAY IN THE AUDITORIUM. IT IS tilation /Air are good and they are holding the commanded temperature.
VERY HUMID IN THERE...... Time Available: ASAP Conditioning

209074 South Conway Closed Work Orders Therm. moves from 77 to 70ish very humid in classroom Time Available: any 5/15/2018 602 Climate Have checked unit and space temp over several days and found no issues with room 5/18/2018
Elementary - Control temp. Unit appears to be working normally and maintaining room temp.
0045
209176 St. James Closed Work Orders all rooms in this area are humid and sticky feeling tstat in nurse office reading 73.5 5/16/2018 nurse area Heating/Ven checked at stjhs, found cool p-gain factory default causing cooling not coming on until 5/17/2018
Elementary - but its warm A111 A110 tilation /Air 74 degrees ,and over cooling , causing higher humidity, reset to 30,0,0 checked unit for
0030 A105 vault Conditioning proper cycling
A107

Page 65 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
209218 Seaside Closed Work Orders There is a roof leak in the kitchen in the bathroom to the right. The cafeteria 5/17/2018 kitchen Heating/Ven 5/21/18. Went in the rest room and located a line set above the area that was frozen 5/23/2018
Elementary - manager just pointed it out to me yesterday, but it looks like it was leaking for some bathroom on tilation /Air and it leaks on to the ceiling tiles when it goes into defrost cycle. Traced it to the
0050 time, since there is black mildew on the ceiling tile Time Available: any the right Conditioning outside and found the big unit on the loading dock area is the one causing it . Talked to
Mr. Gary about it and that it wil be taken care of. On 5-22-18 looked above the ceiling to
find that the suction line going back to the condensing unit was freezing and melting
due to not having enough insulation wrap around the service line and in some places
the insulation was worn and very thin. I then went to the supply house and got some
new and thicker armor flex to wrap around the service line. After removing all the old
armor flex from the outside storage room wall to the new armor flex coming from the
freezer, I made sure that all the lines were covered and insulated. Also used foam tape
to join each armor flex to the next to make sure it was sealed good. Used a 1 inch thick
armor flex which should give it very good insulation, and keep the heat from making it
sweat and freezing up and causing moisture problems in the future.

209236 Conway High - Closed Work Orders B113, B114 nad B hallway VERY humid and hot 5/17/2018 B Hallway Climate Checked area and RTU 1 which supply's that area. Also checked other RTUs and reset 5/17/2018
0004 Control compressors. Made adjustments to set points on RTU1, 4, and 5. Monitored unit
operation and space temps. Unit and areas operating properly.

209248 Aynor High - Closed Work Orders If possible, please adjust the settings on the AC unit in K101 to match the unit in 5/17/2018 K101 Heating/Ven Adjusted the set point via apogee. I made the set point and the comp on and off 5/18/2018
0001 I110. K101 has a strong odor and feels very humid. Time Available: anytime tilation /Air percentage the same as I110.
Conditioning

209317 Green Sea Closed Work Orders Replace plug,Humidifier Time Available: Now 5/18/2018 325 Electrical 5/18/18 9:12 am changed the plug pulled out the blade job complete. 5/18/2018
Floyds High - 5/18/18 8:15 am The blade of the plug broke off in the receptacle
0006
209351 Loris Middle - Closed Work Orders very humid 5/18/2018 514/ 712/ Heating/Ven Found bad blower relay in server room, will return with new relay asap. 5/25/2018
0027 sever room in tilation /Air Replaced blower relay in sever room, system operating normally.
library Conditioning Rooms 514 and 712 out on emergency pan switch, cleared condensate lines and
removed water from emergency pans. Systems operating normally.

209446 North Myrtle Closed Work Orders Rm. 813 is hot and humid. The humidity is extremely high and there is an odor 5/21/2018 813 Climate work will be completed on work order 209950 6/7/2018
Beach Middle - coming from the room. Time Available: asap Control
0037
209459 Lakewood Closed Work Orders mold on back room wall in 415/See Mrs. Cook Time Available: asap 5/21/2018 415 Heating/Ven i went and check the room. there was no mold on the wall. it was only dust that was left 5/25/2018
Elementary - tilation /Air from having paper and other things tape on the wall. mr charlie and me clean it off with
0029 Conditioning some spray. the paint was coming off the wall as well. this is the room the teacher say
its cold some days than very hot.

209460 Early College - Closed Work Orders Several rooms on the second floor are claiming hot and humid and their rooms. 5/21/2018 222, 230 Climate problem caused by MAU #2 using WO# 209747 for repair 5/29/2018
0074 They keep hearing noises in the ceiling Time Available: 7:30-4:30 Control

209529 Aynor High - Closed Work Orders Kimberly Mendez - The room smells moldy / mildewed....I notice a wet spot on one 5/22/2018 Class Rm. Heating/Ven Checked unit i cleaned out the drain pan and also cleaned the indoor coil with evap- 5/29/2018
0001 of the ceiling tiles. 1st. floor in the new building class room I102 I102 tilation /Air Gard plus. This cleans and disinfects the coil this should fix the smell if the unit is
( Special need room need your attention ) Time Available: ASAP Conditioning producing the smell.

209628 Early College - Closed Work Orders The humidity in these rooms are unbearable. Time Available: 7:30-4:30 5/23/2018 Room 222 and Climate problem caused by MAU #2 using WO# 209747 for repair 5/29/2018
0074 223 Control

Page 66 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
209722 Socastee Annex Closed Work Orders Teacher says the room is hot and muggy. The room is humid and the T-stat is 5/24/2018 room 202 Heating/Ven i went and check the room. i found the air handler working. i check the condenser unit it 5/25/2018
reading 77 degrees. Please check. Time Available: asap tilation /Air had no high voltage to it. i check the fuss and 2 of them was bad. i replace it with new
Conditioning one. i still did not have high voltage. i found a breaker tripped. i reset the breaker and
turn the unit on. the fuss blew again. i ohm the compressor. it was short to ground. i talk
to ms sowerby and let her know to move teacher. they are about to be out of school
and will not be using build next year. did not want to spend money on building

209780 Lakewood Closed Work Orders The whole front office is very humid and hot. My office is especially hot. The desk 5/25/2018 611 Heating/Ven i check unit on apogee the unit was showing it was at set point. i went on roof and 5/25/2018
Elementary - and table tops feel damp. I am concerned about the air quality in this building. Time tilation /Air check unit. everything was working properly. front office said it got cool.
0029 Available: anytime Conditioning

209798 Aynor Middle - Closed Work Orders room is very humid and warm thermostat is reading 74 degrees Time Available: 5/25/2018 301 Heating/Ven Checked out and found room has high humidity. Changed set point to get to cool room 5/29/2018
0057 asap tilation /Air to a lower set point which removed some of the humidity. It felt a lot better, will check
Conditioning next week after tropical storm passes and the humidity lowers in the area.

Checked room and room was cool and the humidity was lower.

209800 Conway Closed Work Orders Dehumidifier is not working correctly because it is not pulling moisture from the air, 5/25/2018 TLC Front Climate Checked dehumidifier and found the humidity level was to low for the unit to run. I 6/7/2018
Education bin does not fill with water. It would be appreciated if it could be checked. Thank Office Control lowered the RH% and the unit came on and operated properly. I adjusted set point and
Center - 0172 you. Time Available: anytime cleaned the washable filter. After doing this the unit operated normally.

I also changed the in line water filter on the ice machine in the kitchen.

209819 Seaside Closed Work Orders teacher is complaining of a musty smell in her room and that it is too warm and 5/25/2018 411 Heating/Ven i check the rooms on apogee. i set the cool set point to 72 degree. i went int the class 6/1/2018
Elementary - humid in her room and the other kindergarten rooms as well. Time Available: any tilation /Air room and i did not smell and bad odder. i check the unit to see if air handler might had
0050 Conditioning something in it. everything in unit was good and working properly. i will ask mr gary to
spray something on carpet to see if it take smell away for teacher.

209950 North Myrtle Closed Work Orders Room 813 has so much humidity that everything, including brand new atlases, are 5/29/2018 813 Heating/Ven took and put dehumidifier in room 8/23/2018
Beach Middle - damp. Time Available: 7:30 tilation /Air
0037 Conditioning

210030 Socastee Complete The school is extremely hot and it is not even 7:00 am. The exterior rooms are 5/30/2018 Entire School Climate 8/22/2018
Elementary above 75 degrees already today. It is also humid and damp in the rooms. Time Control
NEW - 0054 Available: ASAP
210058 Conway Closed Work Orders please check get humid in classroom HP50 77" 5/30/2018 room 207 Heating/Ven Checked classroom and found room did feel humid. Checked cooling system in 8/14/2018
Elementary - tilation /Air classroom and found it operating normal. However I did check MAU that serves the 200
0036 Thanks Conditioning hall and found it not operating normally. Was unable to get on roof and check MAU out
do to a walk-in freezer problem at PDES. Checked out MAU2 for 200 hall. Found
several issues but got called off to check freezer at CHS. Plan on returning next week
to complete checkout and begin making necessary repairs. Returned and checked
several unit MAUs and found supply and exhaust motors tripped reset and checked
operation. MAU 1 was working but later in day it stopped working on lack of call from
Apogee Contacted ross and he was looking in to it. MAU 1 operates normally stand
alone. MAU 2 fond supply fan belts loose and worn. Picked up 2 new belts from
warehouse and installed and adjusted. Also greased all bearings in unit. Checked unit
operation and found 1st stage compressor not running. After trouble shooting found
unit was low on gas after leak checking found leak and repaired.Then charged up unit
with gas and checked unit operation. Cleaned up tools from area and left unit operating
normally.

Page 67 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
210081 Scholars Closed Work Orders Teachers say it feels like air is stale and not moving. Both said rooms are usually 5/30/2018 132,133 Heating/Ven checked on computer rooms ok humidity 59% 5/30/2018
Academy CCU - cold but today they've had to open door to get it to circulate a bit. I told them it may tilation /Air
0178 be due to rain and sun keep coming out making it extremely humid outside. Just Conditioning
need it checked. One room 73.1 other 73.3

210137 Lakewood Closed Work Orders **Maybe Mold** Back wall, didn't see until teacher moved bookcases. See 5/31/2018 402 Carpentry Checked wall in the room. Found mildew on the wall where a bookcase had been. 5/31/2018
Elementary - attached pictures. Mildew was grey in color and cleaned off very easy with moldex concentrated cleaner.
0029 Teacher has lamp by the thermostat that makes the unit run all the time. Room was
very cold. Had Dean come look at the room and the A/C was operating normally. With
the bookcase up against the wall and the room being cold it cold have caused
condensation on the wall, causing dirt and dust to adhere to the wall. Pictures attached.

210181 Waccamaw Closed Work Orders URGENT - Media center is extremely humid (abnormally) and feels like part of it has 5/31/2018 Media Center Heating/Ven Checked Media center, wet bulb is 60 degrees, humidity not high. 6/14/2018
Elementary - no air. It has multiple t-stats. tilation /Air
0042 Time Available: ASAP Conditioning

210738 District Office Closed Work Orders in learning servic room 101 building A the temp is really hot and no moving of air in 6/5/2018 in A 101 the Heating/Ven Checked out on Apogee and made adjustments to several inputs to get unit operating 6/6/2018
Four Mile Road - the room we would like to have dehumidifire we have 4 women 2 men in this room it temp is really tilation /Air to satisfy workers. Checked in on after a couple days and they were satisfied. Unit was
0401 get stuffay in here Time Available: today if you can hot Conditioning maintaining temp and humidity as much as it can.

210762 Academy for Closed Work Orders RM 111 the HVAC unit is not keeping the office cool. the air is damp and humid in 3 6/5/2018 RM 111 Heating/Ven checked unit and running ok but did found room next to her room was not working and 6/7/2018
Arts Science offices in administration area. cold air is not coming through the vents. Time tilation /Air thermostat was blank found fuses tripped from a short in the low voltage wire ,found
and Tech. - Available: asap Conditioning bad wire and repair wire unit running ok.
0096

210805 Socastee High - Closed Work Orders Our Milk box seal needs replaced molded , cant clean Time Available: asap 6/6/2018 122C Kitchen cleaned gaskets 6/20/2018
0011 Equipment

210865 Facilities Complete Need a spare key for the Parts Warehouse. Please give key to Sandy Barfield. 6/6/2018 Key and Cut key and gave to Sandy. 6/6/2018
Building - 0402 Need key by Thursday. Lock
Dennis McCrary needs to test the de-humidification system. in the furniture
warehouse.
210917 Lakewood Closed Work Orders Maybe mold not sure. Could not attach pictures will forward the email with the work 6/7/2018 416 Carpentry Wiped dirty areas...it isn’t mold...side wall where paint is peeling is scheduled for the 6/7/2018
Elementary - order #. outside wall to be sealed and the inside to be primed and painted during the summer.
0029 See work order -208068 for that information.
211333 Burgess Closed Work Orders ROOM #507> inside, Left side of outer wall, head high... > found block wall to be 6/11/2018 ROOM #507 Carpentry 6/13/18-Used pump sprayer to seal outside of classroom wall with Thompson’s water 6/20/2018
Elementary - damp/wet. paint has deformed in this area also. Teacher found this when arranging seal. Pre cleaned sprayer with water then done a thro clean with mineral spirits.
0063 for summer cleaning. She stated had a similar problem before on same wall several 6/20/18-Removed things that were stacked in the way of the wall. Scraped block on
years back... Which had been a mold issue for her as well. the inside, cleaned and applied 2 coats of paint. Put things back on the shelves. Swept
Your attention is greatly appreciated. Time Available: at your convenience floors and loaded truck.

211515 Ocean Bay Closed Work Orders The white brick over our front doors needs cleaning. There is mold. It was pressure 6/14/2018 outside Painting 8/30/18, washed white block at front entrance. There is some more black that needs 8/31/2018
Middle - 0061 washed a few years ago. Time Available: anytime removed across the front of school. Will open new WO for that.

211678 Daisy Closed Work Orders Media center needs new humidifier 6/18/2018 305 Climate stand alone dehumidifier, bucket full, dumped bucket, operating correctly. 6/20/2018
Elementary - 711- check temp. thermostat reads 73/74 degrees Time Available: Any Control
0021
211777 Kingston Closed Work Orders Check out and deliver dehumidifier from ware house . 6/19/2018 Heating/Ven delivered dehumidifier to Kingston and instructed custodians how to operate got more 6/25/2018
Elementary - tilation /Air drain hose for better placement of unit. (Keep work order open so we can go back and
0028 Conditioning pick up after floors have been cleaned.)RLane

Page 68 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
211798 Aynor High - Closed Work Orders Senior hall class room I104 wrote - Check humidity level Time Available: Any time 6/20/2018 Class Rm. Climate Checked room the humidity is a little high due to the set back on the units. I checked 6/25/2018
0001 I104 Control units operation and the unit operated normally and i also checked the unit compressor
on and off percentage and the were in range.
211799 Aynor High - Closed Work Orders Senior hall class room C112 Lourel hall wrote - Check humidity level Time 6/20/2018 Class Rm. Climate Checked unit and the room temp was 75 this is in range of the set point. I checked 6/25/2018
0001 Available: Any time C112 Control compressor percentage and they looked okay to. I put the unit in 100 percent cooling
and the unit came on and operated normally so i released the cooling loop out.

211849 River Oaks Closed Work Orders The gym office has started again with the humidity and condensation, ceiling tiles 6/21/2018 Gym office Heating/Ven its because the unit on stage is not working and it runs the office to. 9/27/2018
Elementary - are getting wet and smells bad in office and gym area. Time Available: any tilation /Air replace blower motor on stage.
0065 Conditioning

212079 Green Sea Duplicate Request rooms are not drying fast correctly because we don't have enough air in the room 6/26/2018 mini gym Heating/Ven Same as WO# 211784
Floyds High - they are hot and humid Time Available: now tilation /Air
0006 Conditioning

212131 Waccamaw Closed Work Orders it the small room with the single door need to be sprayed down has mildew 6/27/2018 storage room Painting 7/10/18, looked at this with Janice. She will empty room then I will treat it. 10/17/18, 10/17/2018
Elementary - behind room due to hurricane, room has not been emptied. When this is complete, please submit a
0042 101 work order.
212636 River Oaks Closed Work Orders Room 507 HP-52 room is always humid, Time Available: any 7/2/2018 room 507 Heating/Ven re-set on aopgree running ok. 7/2/2018
Elementary - tilation /Air
0065 Conditioning

212736 Aynor High - Closed Work Orders Can the dehumidifier in C112 be updated or replaced with a newer model? This unit 7/4/2018 C112 Heating/Ven I checked with Terry on this and he said as long as the dehumidifier was operating we 7/17/2018
0001 is very old and loud. The teacher dumps two buckets of water each day. Time tilation /Air could not do anything. The school can replace if needed due to noise. If they are
Available: anytime Conditioning dumping it out twice a day that means it's working good. Terry Hucks

212874 Waccamaw Complete storage room behind room 101 has mildew 7/9/2018 storage room Custodial will spray 10/20/2018
Elementary -
0042
213427 North Myrtle Closed Work Orders since the new construction there is a tremendous amount of humidity in the air. 7/18/2018 front office Heating/Ven cycled fans for equipment in office area so will not run until a call for heat or cool 7/23/2018
Beach High - Paper feels damp, new envelopes are sealed before we can even us them. tilation /Air humidity went down
0002 Conditioning

Page 69 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
213937 Conway High - Closed Work Orders Check room A/C units and MAU for proper operation due to high humidity. 7/25/2018 A104-A108, Heating/Ven Checked room cooling units and was requested by Terry to adjust room setpoint so 7/25/2018
0004 B104-B107 tilation /Air room is not over cooled. Raised cooling setpoint up to 75deg and set indoor fans to
Conditioning constant run during day mode. Also checked both MAUs 3-4 serving affected
classrooms. Found units were tripped out on false failed sensor. Reset unit control and
unit began cooling and dehumidifying. Also replaced filters in both MAUs. Returned
next morning due to principal calling about hallways being humid again. Found MAU
units not running so I checked control circuits and found apogee was not calling.
Contacted Ross control specialist and he stopped by with CMI. They went over control
system and found units were in enable off. CMI tech rectified control signal command
to run units in day night mode. Also worked with them on installing access to units on
school graphics. Also replaced filters and belts on both units. Checked unit operation
and had to add some gas in circuit D on MAU 4. Also helped move desks in
classrooms for cleanup of walls. Also ordered to failed sensors on units. Returned 7/31
due to unit failed and rooms building moisture. Checked both MAUs and found both off.
MAU 3 off due to failed sensor which is on order and will arrive on Wednesday.
Monitoring MAU 3 operation thru out the day. MAU 4 after troubleshooting found
problem with fire system and duct detector. Simplex has to come in and repair fire
system before MAU can operate. Visited school in morning and checked all classrooms
and found no moisture on walls. Also monitored MAU several times during the day. Re-
visited school at end of day and checked classrooms for moisture on walls. Set MAU
for 1st fl De-Hum on Will re-check in morning. Also will install failed sensors if they
were received today. Received parts and visited school and replaced both OA
Temp/RH sensors and MAU3 DX BD coil sensor.

213939 Conway High - Closed Work Orders Nine classrooms and two sections of hallways have mildew all over the walls due to 7/25/2018 Painting HAD WALLS CLEANED DOWN TO REMOVE MILDEW IN A AND B HALLWAYS ON 8/22/2018
0004 hvac system going down. NEW WING NEXT TO OLD MAINTENANCE SHOP. HALLWAY AND CLASSROOMS.
WE ALSO HAD TO GO BACK AND CLEAN ALL FURNITURE IN THE
CLASSROOMS EXCEPT FOR SPECIAL NEEDS FURNITURE THERE WAS STUFF
IN THE ROOM THAT NEEDED TO BE GOTTEN RID OF SO YOU COULD GET TO
OTHER STUFF. WE NEED TO GET WITH SCHOOL ON THIS FURNITURE. SEE
PHOTO'S
8-17-18 cleaned areas in classrooms
214188 Lakewood Closed Work Orders A/C unit is not cooling the room. Very humid. 7/30/2018 208 Heating/Ven i went and check the unit. everything was working properly. the room temperature was 8/2/2018
Elementary - tilation /Air 73 degree. i check all the parts to make sure no loose wire. the night before was a bad
0029 Conditioning storm and i feel it had just tripped the unit out and did not come on as it normal do. i will
keep an eye out on unit.

214297 Forestbrook Closed Work Orders During the summer of 2017, Forestbrook Middle had gym area cleaned and 7/30/2018 Stage area in Climate we clean the walls in gym and locker rooms. 8/2/2018
Middle - 0051 repainted due to Mildew forming on walls of gym, locker room, and stage areas. Gym and walls Control
The mildew has return.
Please advise on concern that has been addressin summer of 2017... Time
Available: 7:30am until 5:30pm

214540 Conway Closed Work Orders Please adjust temperature in room 104. In the afternoon teacher reports it becomes 8/1/2018 TLC-Room Climate I adjusted the temp via apogee and after doing this. The unit operated normally. 8/1/2018
Education very hot/humid in the room. The system shuts off early and it is very humid and hot 104 Control
Center - 0172 in the room. Ms. Howard was told by facilities at the end of last year that this school Ms.Howard's
year the temp. could be adjusted so that it will remain cooler in her room for longer
than 1:30. The students leave at 1:30 but she is still here working in the room until 3-
3:30 at least. Thank you Time Available: Any

Page 70 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
214957 District Office Closed Work Orders Please check rooftop unit RTU -3D prior to tonight's Board meeting. The unit is 8/6/2018 Heating/Ven Checked both RTU3D and RTU1D. Checked pressures and temps on both system and 8/8/2018
Four Mile Road - running, but has poor temperature drop and room humidity is up. tilation /Air found both units were working at full capacity. The only adjustment I made were to the
0401 This unit does the board members seating area of the large board room. Conditioning outside dampers to get them fully closed which helped bring down supply air temps on
unit and brought down space temp over a degree close to setpoint. Spoke with Ross
Dennis about units and he agreed with my determination. Left unit operating normally

215005 Aynor Middle - Closed Work Orders cabinet/desk that is attached to walls need to be removed and 1 moved to data 8/6/2018 #418 & 414 Furniture 8/15/18 disassembled desk move to another room and reassembled. 8/15/2018
0057 quality clerks office and the other to room#412 as soon as possible. will probably
need some touch up painting done when moved Time Available: 7-5

215085 North Myrtle Closed Work Orders 4 large stained ceiling tiles in Chorus room and 4 in the closet. The closet has one 8/7/2018 Chorus room Carpentry Switched tiles out for new ones. Addressed drain on roof 8/27/2018
Beach Middle - with a lot of mildew on it! This room continues to have ceiling tile issues. Time 402
0037 Available: 7:30
215316 Conway Duplicate Request Teachers in these two rooms have reported a problem with mold starting to grow all 8/9/2018 Room 207 and Heating/Ven This work order is a duplicate to existing work order 210058. Work was completed
Elementary - over the bulletin boards, office chair, and small group chairs. May need a Room 108 tilation /Air under that work order.
0036 dehumidifier in the classrooms. Time Available: ASAP Conditioning

215439 Conway High - Closed Work Orders Mr. Hucks reported that Mr. McCants call and asked him to turn on the A.C. In the 8/12/2018 Heating/Ven 08/12/2018- ADJUSTED TEMPS IN MINI GYM AND GYM. 8/14/2018
0004 mini gym ,because the humidity was high and the finish on the gym floor was not tilation /Air
drying. Conditioning

215553 Myrtle Beach Closed Work Orders masssive humidity mold build up... started ac please check !!! help Time Available: 8/13/2018 800 port b Heating/Ven 08/16/2018- CHECKED UNIT AND IT IS RUNNING AND REMOVING HUMIDITY BUT 9/6/2018
High - 0010 any tilation /Air ROOM HAS TOO HIGH OF HUMIDITY. ROOM IS 68-70 F AND AT 70-71% RH.
Conditioning SYSTEM WILL NEED TO BE CHECKED, PORTABLE UNDER LEASE. TSTAT RH%
IS NOT ACCURATE, READING 88-94%.
08/17/2018- RETURNED TO DOUBLE CHECK UNIT AND READINGS AND SAME
RESULTS. SYSTEM WILL NEED TO BE CHECKED, PORTABLE UNDER LEASE.
TSTAT RH% IS NOT ACCURATE, READING 88-94%
09/05/2018- GOT EMAIL THAT TECH FOUND ISSUE AND FIXED TSTAT, FROM
MOBILE MODULAR ON 9/5/18
215569 Midland Closed Work Orders Water leak under sink. Mold has developed. Pipes visible under sink aren't leaking. 8/13/2018 403 Plumbing This is a warranty issue. There is something causing the cabinet underneath the sink to 8/28/2018
Elementary - Leak appears to be coming from somewhere in the wall. Time Available: any get a substance on the wall of cabinet
0033
215618 River Oaks Closed Work Orders Room 504 HP-61 8/13/2018 504 Heating/Ven found thermostat not lite up ,replace stat and and found compressor not coming on lost 8/17/2018
Elementary - Room warm and humid, can[t read screen Time Available: any tilation /Air low voltage from defrost board replace board unit started running.
0065 Conditioning

215703 Carolina Forest Closed Work Orders There is no air moving in the bathroom of the Athletic Directors office. 8/14/2018 Athletic Climate 8/21/18 checked system bathroom/shower rm not conditioned room is cooling talked 9/10/2018
High - 0052 Condensation is consistent and mildew continues to form on the walls. Time Director Office Control with teacher no issues found at this time.
Available: anytime
215718 District Office Closed Work Orders Air Quality of the suite needs to be checked; dehumidifier running constantly; see 8/14/2018 B307 Heating/Ven This work order was completed by Terry Hucks and Ross Brazier. They had carpets 10/25/2018
Four Mile Road - Chrystal Frye when you come to assess Time Available: As soon as you can tilation /Air professionally cleaned and made other repairs to units.
0401 Conditioning

215850 Forestbrook Closed Work Orders Hello...There is mold where the tile meets the walk-in cooler-freezer all the way 8/15/2018 307 Flooring Cut out old silicone and cleaned with Spray nine and then sprayed mold stain remover 8/16/2018
Middle - 0051 across them-Needs to be cleaned and re-caulked-Thank you-William. on area and wiped it down. Once it was dry I applied a new bead of silicone at top of
quarry tile base where it meets walk in box and freezer.

215851 Forestbrook Closed Work Orders Hello...There is mold where the back splashes meet the wall in the dish room- 8/15/2018 307 Painting Cut out old silicone, washed area with Spray 9 and mold killer and caulked with clear 8/16/2018
Middle - 0051 Cleaned and re-caulked-Thanks you-William. silicone.

Page 71 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
215853 Forestbrook Closed Work Orders Hello....It is warm in the kitchen and serving areas-can you please adjust the temp- 8/15/2018 307 Heating/Ven i check the unit for kitchen. it was working properly. we ask kitchen manger to keep 8/24/2018
Middle - 0051 somethings were showing mold so they had to be wiped down...Also there is tilation /Air back door close so no hot air can mix with cold air. we did not see any mold
moisture coming from where the ceiling tiles meet the wall by the ice machine-you Conditioning
will be able to see streaks down the wall-Thanks-William.

215956 Conway Closed Work Orders Room is extremely muggy. Teacher reports dehumidifier has to be emptied 8/16/2018 TLC-Room Heating/Ven Adjusted compressor settings to try to help with humidity. 8/16/2018
Education continually and currently the temperature is 73.3. Time Available: Any 104 tilation /Air
Center - 0172 Conditioning

216073 North Myrtle Deferred We are in desperate need of repainting of the original building of NMBM. We have 8/17/2018 Entire School Painting
Beach Middle - hallways and classrooms where paint is falling off the walls. The paint is very dull
0037 and it is probably causing the mildew that is throughout the classrooms in the
building. We work very hard to to clean and maintain but the building still looks
terrible. Time Available: asap
216165 Academy for Closed Work Orders Call came in about portable out back had no a/c in it this summer and the walls had 8/17/2018 Heating/Ven 08/17/2018- WHEN ARRIVED UNIT RUNNING. TESTED TEMPS AND RH%. 69-71 F 9/6/2018
Arts Science mildew on them, school staff had cleaned walls today and they didn’t want this to tilation /Air AND 60% RH. CONDITIONS ARE GOOD BUT RH (RELATIVE HUMIDITY) SENSOR
and Tech. - happen again so they wanted someone to check a/c out Kelly Wilson made the call Conditioning ON TSTAT NOT READING CORRECTLY (88-90% RH) AND WILL NEED TO BE
0096 CHECKED AND POSSIBLY REPLACED. THIS UNIT IS ON A PORTABLE WHICH IS
LEASED, THEY WILL NEED TO BE CONTACTED FOR REPAIR.
09/05/2018- GOT EMAIL THAT TECH FOUND ISSUE AND FIXED TSTAT, FROM
MOBILE MODULAR ON 9/5/18

216267 Seaside Closed Work Orders The library thermostats read 73 degrees but the humidity in there is unbelievable. It 8/20/2018 library Climate Checked library at seaside. Found room temps at 72.5-73 degrees and 51%RH in 8/29/2018
Elementary - almost feels like being outside. Time Available: any Control space. No problem found at this time.
0050
216344 Early College - Closed Work Orders HP27 78 degrees and very humid Time Available: 7:30 8/20/2018 Rm 127 Climate we found the fan motor bad. we order a new one. we put new motor in and left unit 8/24/2018
0074 Control working properly.

216370 Conway High - Closed Work Orders HVAC was not working in the field house when we went down for practice this 8/20/2018 field house Heating/Ven Checked MAU and found the main disconnect was turned off. Restarted unit and 8/22/2018
0004 afternoon around 5pm. Hours for football have been entered on FS Direct facility tilation /Air checked operation. Found unit to be operating normally cooling down space. Left unit
use. with the new wet bulb calculations we need air on if we have to stop practice Conditioning operating normally
due to temp. and humidity. Time Available: ASAP

216418 North Myrtle Duplicate Request The majority of the 800 wing is extremely humid. The custodial staff has cleaned the 8/21/2018 813 Heating/Ven
Beach Middle - walls many times and the mold/mildew will reappear over night. Time Available: tilation /Air
0037 asap Conditioning

216694 Conway Closed Work Orders Dehumidifier is broken in room 107. Very humid Time Available: Any 8/22/2018 TLC-Room Heating/Ven Checked dehumidifier and found that it needed to be reset. i rest it and lowered the 8/24/2018
Education 107 tilation /Air humidity setpoint and the compressor and fan came on after doing this. The unit
Center - 0172 Conditioning seemed to work properly after this.

216763 Carolina Forest Closed Work Orders A house, A110 is very HOT they cannot have class in there due to the humidity in 8/23/2018 A110 Heating/Ven 10/1/18 signed in/out system not cooling. after diagnosing found system iced per low 10/2/2018
High - 0052 the room. Please send some one soon Time Available: ASAP tilation /Air charge. shut condenser off to protect compressor. will allow system to de ice over night
Conditioning will return in the morning to charge system.
10/2/18 Added 2 lbs R22 to system. system cooling at this time.

216903 Conway Closed Work Orders We have several items that we need to be picked up: 8/24/2018 kitchen Furniture 8/29/18 picked up assets. 8/30/2018
Education 1 bookshelf, 3 file cabinets, 1 dehumidifier, 1 easel, 6 tables, 10 desks, 9 chairs and
Center - 0172 1 lamp. Time Available: Asap

Page 72 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
216996 North Myrtle Closed Work Orders Rent two dehumidifiers from FSA during the summer to help remove additional 8/24/2018 Heating/Ven After visiting NMBM and seen the amount of water that was associated with stripping 8/31/2018
Beach Middle - water that will be associated with stripping the floors. tilation /Air the floors at the beginning of the summer, I requested that Building Services rent
0037 Conditioning dehumidifiers to remove the excess moisture that was associated with the floor
stripping after a month of running the dehumidifiers I determined that it was in our best
interest to rent them an additional month and since Building services paid for the first
month Maintenance would pay the second. Since HCS rented the dehumidifiers over
the summer it has definitely decreased the indoor quality complaints from years in the
past especially with mildew being discovered the first week of school, this does not
mean that this was a fix all but definitely an improvement.In large I think that schools
that are not equipped with dedicated MAU units that not only condition the entering air
into the facility but also has the means to dehumidify should have at least one to two
large machines at there disposal all the time.

217386 Aynor Middle - Closed Work Orders room is hot and humid thermostat is reading 76 Time Available: asap 8/28/2018 709 Heating/Ven Checked unit via apogee. The discharge air temp was 63 degrees. This unit seems to 8/28/2018
0057 tilation /Air be operating properly.
Conditioning

217468 Myrtle Beach Closed Work Orders room gets warm and humid feeling in the afternoon hours with temp going up to 8/29/2018 room 420 Heating/Ven 09/10/2018- ADJUSTED TEMPS AND TOOK READINGS. 10/1/2018
Elementary - 75,76 degrees on the thermostat in that room. Please check to see if we might have tilation /Air 10/01/2018- CHECKED TEMPS/RH %. READINGS WERE GOOD.
0034 a thermostat problem in that room. Conditioning

217585 Seaside Closed Work Orders Library is getting mildew on and probably inside the vents in the center of the main 8/30/2018 library Heating/Ven i clean the wall and vents. i think it was because units was off from fire guys. i will keep 9/7/2018
Elementary - area. It's not the vents along the side that are lower, it's the vents in the middle that tilation /Air and eye on vents to see if it happen again
0050 are higher and sideways. The most obvious one is straight up to the left as you walk Conditioning
in the library, just about over the main desk Time Available: any

217604 Waccamaw Duplicate Request The AC was broken for several weeks and the TRANE people corrected it last 8/30/2018 Large Office Climate 9/11/18 duplicate request see w/o 215112 work in progress.
Elementary - week. Since it was fixed it is not extremely humid in the room off and on. Please Conference Control
0042 check humidity and assist. Papers and other work materials are almost wet during Room (PLC)
the day because of the humidity. Time Available: ASAP

217651 Forestbrook Closed Work Orders Room 619 is hot - teacher reports heat throughout day, but after 3:30pm room 8/30/2018 619 Heating/Ven Ms. Rutenberg, i will have the HVAC System checked to see why it is warm in the 8/31/2018
Middle - 0051 becomes very chilly. There is a strong odor in the room as a result. It smells musty tilation /Air morning and cool in the evening. As for the carpet you may need to get with Pamela
and mildewed and source of smell is the carpet. Time Available: any Conditioning Dowden about having carpet professionally cleaned to help with the smell. look at work
order 216011

217720 River Oaks Closed Work Orders Room 508 HP-51 warm and humid Time Available: any 8/31/2018 508 Heating/Ven checked unit in room and room temp was 73 deg and temp coming out of vents was 59 9/6/2018
Elementary - tilation /Air deg r/h was 56% unit running ok.
0065 Conditioning

217739 Socastee High - Closed Work Orders Check A/C in the auditorium warm/humid in the auditorium. Time Available: 7am- 8/31/2018 auditorium Heating/Ven I check the unit. It was working properly. Will set temperature lower. 9/5/2018
0011 4pm tilation /Air
Conditioning

217785 Early College - Closed Work Orders classroom humid and muggy. Time Available: 7:30-5:30 8/31/2018 rm 202 Heating/Ven i check the unit. it was working properly. i put the cool loop out to 100% and see if unit 9/9/2018
0074 tilation /Air would come on and cool room. unit cool room to 71 degree. i put the cool set point to
Conditioning 72 degree and see how it would be for the day. it work good for teacher.

Page 73 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
218163 North Myrtle Duplicate Request Room 813 is extremely hot and humid. The dehumidifier is not working as well as 9/4/2018 813 Climate
Beach Middle - we would have anticipated. Time Available: asap Control
0037
218305 Carolina Forest Complete We have a high volume of students that are sick with upper respiratory and sinus 9/5/2018 Kindergarten Filters I inspected the filters and did not find that they were restricting airflow that would 9/21/2018
Elementary - infections. Also we have rooms with students that have asthma that are complaining and 1st grade require early change out. I will be back onsite Tuesday, 9/25 and plan to touch base
0049 of the air quality. Can you please check the filters and or change them to help hallway with Mr. Zilbermann
alleviate some of this. Thanks for all you do. Time Available: high priority

218327 Myrtle Beach Closed Work Orders need all wood supports attached to block wall and shelving removed from this room 9/5/2018 outside Carpentry Went by and inspected took pictures and talked with Artie Teasley about issues 10/9/2018
Elementary - and thrown away. Had a mold/mildew issue in this room and we are trying to get it storeroom 321 shelving doesn't need to be removed and trashed in our opinion they only need to be
0034 back right so it can be used for storage again. See Adam about it. cleaned and put back up to be used thanks for all you do.

218351 Conway High - Closed Work Orders Said the walls are wet need a dehumidifier it's a area we had problems with this 9/5/2018 a 106 Climate Checked MAU and found it had an alarm keeping compressors off. Reset and 9/18/2018
0004 summer Time Available: anytime Control compressors began running with no alarms. Monitored operation including next
morning. Will continue to monitor for next few days. Working normally..

218353 Lakewood Closed Work Orders HP072 - room feels very humid - temp. reads 76 9/5/2018 717 Heating/Ven i check the unit. the unit was at set point. i put the cool set point to 72.50 degree. left 9/9/2018
Elementary - tilation /Air unit cooling room
0029 Conditioning

218354 Lakewood Closed Work Orders The 2 units read 77 but feels very humid and warm. 9/5/2018 Media Center Heating/Ven i check the units. one of the units was frozen up at the compressor. i defrost it and 9/9/2018
Elementary - tilation /Air check pressure. it was 45/170. i put 2lb of r-22 in unit. left unit with pressure 70/220.
0029 Conditioning other unit was at set point. i put the cool set point to 73 degree. left both units working
properly

218429 St. James Closed Work Orders THE HUMIDITY IS VERY BAD AND PAPERS ARE SO DAMP THEY ARE HAVING 9/6/2018 E-100 AND Heating/Ven Went on the roof to the roof top to check the AC unit And found that the damper was 9/10/2018
Elementary - AN ISSUES GETTING THEM TO RUN THROUGH THE COPIERS. E-100 HAS A THE WHOLE tilation /Air open at 100% letting outside air mix with the AC air. Also found that wall packs on the
0030 DEHUMIDIFIER AND IS HAVING TO DUMP IT VERY OFTEN BUT IS SO LOUD RIGHT SIDE Conditioning right-hand side of the hall also had there dampers open letting hot outside air into the
MUST TURN IT OFF WHEN TEACHING. TEACHER IS SAYING IT IS HOT IN OF HALL classrooms, using the Apogee system close to all the dampers so it would not let the
THE ROOM. Time Available: 7:00AM - 4:00PM hot outside air in.
218498 Myrtle Beach Duplicate Request room running warm and feels humid. please check system. 9/6/2018 room 311 Heating/Ven SEE W/O 217148
Elementary - tilation /Air
0034 Conditioning

219356 River Oaks Closed Work Orders In front office area, rooms 110, 112, 113 are extremely hot, the only thermostat is 9/18/2018 Front office Heating/Ven found 2 blowed fuses and replace thermostat.turn unit on and found the bloer motor not 10/31/2018
Elementary - HP-04 in room 113 tilation /Air working and moulde on motor bad have to order new moyor from lennox.replace motor
0065 Conditioning checked unit running ok.
Room 111 HP-03 is very humid Time Available: any

219357 River Oaks Closed Work Orders Room 201 - no thermostat- extremely warm, no ventilation working in this room 9/18/2018 Media/Tech Heating/Ven re-set TEC unit running ok. 10/15/2018
Elementary - lab tilation /Air
0065 Room 206 HP-42 is warm and humid thermostat reads 71.7 though, p;lease check Conditioning
feels 80 Time Available: any

219358 River Oaks Closed Work Orders Rm 414 - blank screen 9/18/2018 400 hall Heating/Ven found thermostat blank replace thermostat and unit running ok.replace blower motor in 10/15/2018
Elementary - tilation /Air room408
0065 Rm 408 HP-35 Blank screen warm/humid in room Conditioning

Rm 402 -HP-39 Blank screen Hot/humid

Rm 406 HP-36 Room is very humid Time Available: any

Page 74 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
219360 River Oaks Closed Work Orders Room 108 - Carolina room HP-79 blank screen and warm and humid in room Time 9/18/2018 108 Carolina Heating/Ven found thermostat blank replace stat unit running ok. 10/15/2018
Elementary - Available: any room tilation /Air
0065 Conditioning

219362 River Oaks Closed Work Orders Following room are warm and Very humid: 9/18/2018 500 hall Heating/Ven checked temp in room was 73 deg and the hum% was 60 percent. 10/24/2018
Elementary - 504A - HP-62 says 73.1 but feels warmer in here tilation /Air
0065 505 HP-50 Conditioning
504 - HP-61
506 - HP-49
507 HP-52
508 - HP-51 Time Available: any
219995 Loris Elementary Closed Work Orders Room muggy. No leak but mildew in room Time Available: 10/1/2018 508 Heating/Ven Found no issues, holding at set point, 73, AUX temp 54.5. Operating normally. 10/18/2018
- 0032 qevans@horrycountyschools.net tilation /Air
Conditioning

219998 Academy for Closed Work Orders The HVAC in portable is not keeping the room cooled. the humidity is high causing 10/1/2018 MODULAR Heating/Ven found copreressor not running tripped out on high pressure because of bad cond motor 10/4/2018
Arts Science mold build up. Time Available: asap tilation /Air I slingged cond fan motor blade and got motor running have to replace motor.
and Tech. - Conditioning order motor from warehouse and replace motor unit running ok.
0096

220013 St. James Closed Work Orders their is mildew present in classroom on chairs and desks. was asked to put work 10/1/2018 E104 Heating/Ven i went and check the rooms. by the time i got into room they had done had the room 10/3/2018
Elementary - order in so someone could come and check to make sure their is nothing to worry tilation /Air wipe down. teacher showed me picture of things that had spots on the. teacher say the
0030 about when children come in tomorrow. Conditioning room is muggy at one time than cold next time. also say when they cut the grass they
could smell it in the room. i check the units and the fresh air was pulling either hot
muggy air or cold air into the room. when the unit turn off at set point the fresh air was
still running. i set it where it would not run and pull any air from outside. i stayed around
for a few to see how the room feel afterwards. teacher say it feel much better the way i
put it.

220056 Daisy Closed Work Orders ceiling leak there is mold in the ceiling tile Time Available: urgent 10/1/2018 room 814 Roof Tile has been changed. Roof has been addressed by sealing bolt heads and caulking 10/12/2018
Elementary - expansion joints. Rained 2 days prior and no leaks showing
0021
220122 Riverside Closed Work Orders The bulletin board in classroom 411 has started bleeding through a sticky substance 10/1/2018 Classroom Carpentry Went to school and talked with teacher and got a time to check board. Checked boards 12/18/2018
Elementary - since the storm caused the school closure. The teacher is wanting to make sure this 411 and ordered new boards for classroom. Got new boards and installed in classroom.
0068 is not a mold issue. Please check out as soon as possible. Time Available: ASAP

220124 Riverside Closed Work Orders The bulletin board in classroom 415 has a sticky substance bleeding through the 10/1/2018 Classroom Carpentry Went to school and talked with teacher. Got a time to come back and check board. 12/18/2018
Elementary - board This teacher would also like to make sure this isn't a mold issue. 415 Checked boards and ordered new boards for classroom. Got new boards and took
0068 We have had to replace two other boards for this problem here at RES. Time down old boards and installed new boards in classroom.
Available: ASAP

220352 Horry Ed. Closed Work Orders WO # 220121 the leak in the roof is causing mold to grow in portable 5A. 10/2/2018 A/C#113=P- Roof Duplicate w.o. I created another when I couldn't find this one. Materials and details on 10/12/2018
Center - 0176 Staff member has a breathing problem so if something could be done ASAP to fix 5A other w.o
roof it would be appreciated. Thank you!! Time Available: ASAP-ASAP ASAP

220387 Early College - Closed Work Orders HP-07 - Very humid in this room - very uncomfortable Time Available: 7:30-4:30 10/3/2018 Room 152 Climate 10/17/2018
0074 Control

220457 Aynor Middle - Closed Work Orders nurse station is very humid Time Available: asap 10/3/2018 408 Heating/Ven Checked system via apogee and i adjusted the compressor on and off percentage to 10/4/2018
0057 tilation /Air make the compressor run longer. This should pull moisture out of the air.
Conditioning

Page 75 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
220584 Lakewood Closed Work Orders Can I get the air set at a lower temperature? It stays hot and muggy in my office 10/5/2018 611 Heating/Ven i lower the room temperature to 71 degree. her unit feeds all the main lobby and her 10/8/2018
Elementary - even though the thermostat reads 73. I have been running a dehumidifier. The tilation /Air office. i also put the fan to turn off when unit turn off
0029 entire drawer fills at least 3 times a day. Time Available: anytime Conditioning

220587 Lakewood Closed Work Orders When the teacher went to use her chart paper, it was covered with mold/mildew. 10/5/2018 414 Heating/Ven i went and check the unit. the unit was working properly. their was some brown spots 10/8/2018
Elementary - The wall in her classroom has paint peeling off and moisture causing some type of tilation /Air on the wall. the paint is coming off the wall in some spots near the window. there was
0029 substance to come through the walls. Please see the attached pictures. Time Conditioning no sign of mold around the unit supply and return vent. i will tell phillip to get the gc to
Available: anytime look at paint on wall.

220804 St. James High - Closed Work Orders Call came in Friday evening that a area in the media center was at 77 degrees and 10/8/2018 Heating/Ven Checked the high voltage and the low voltage, and the pressures on the unit. Found 11/6/2018
0058 mildew was on some on the book shelves. tilation /Air that the control board was not letting the compressor 3 phase contact pull in to work in
Conditioning a normal manner. Got the information off the old board and Ordered a new control
board from Trane parts and it should be in 10-9-18 when the part comes in will be back
to install. Ken installed new board on Monday and got the unit running. Checked on
APOGEE on Tuesday and it was cooling media center to 72 degrees.

220828 St. James Closed Work Orders Room B11 is very hot and humid. The AC is not blowing. Please check, thanks! 10/8/2018 B11 Climate Check unit operation clean clogged drain line check unit Operation Room temperature 10/9/2018
Middle - 0047 Control 73

220836 River Oaks Closed Work Orders ****AIR QUALITY TEST NEEDED*** 10/8/2018 GYM Heating/Ven 10/9/2018- TOOK TEMP AND RH 5 READINGS IN GYM, STAGE AND OFFICE. 1/2/2019
Elementary - GYM AND OFFICE AREA, DAMAGED CEILING TILES IN OFFICE DUE TO tilation /Air TEMPS WERE GOOD THROUGHOUT ALL AREAS RANGING FROM 72*F - 75*F.
0065 CONDENSATION DRIPPING, STRONG ODOR IN ENTIRE GYM CAUSING Conditioning RH % IN GYM WAS 59 - 61 %, STAGE WAS 59 - 61 % AND OFFICE WAS 65 - 69%.
SINUS PROBLEMS IN TEACHERS Time Available: ANY THERE WAS NO MOISTURE/CONDENSATION ON CEILING AT ROOF AT THIS
TIME. CHECKED A/C UNIT OVER STAGE WHICH WAS REPAIRED LAST WEEK
AND IT IS WORKING PROPERLY.
220837 River Oaks Closed Work Orders *****AIR QUALITY TEST NEEDED**** 10/8/2018 400 HALL Heating/Ven in rooms 416 to 420 I did not smell any ordors and checked RH and it reading 59-61 % 10/12/2018
Elementary - ROOM 416 THROUGH 420, REAL MUSTY SMELL IN THE AIR, PLEASE NOTE (END) tilation /Air rh and room temp was at 72 to 73 deg.could not found anything out of the normal.
0065 WHEN YOU DO REPORT OF ALL AND ANY AIR PLUG INS THAT TEACHERS Conditioning I took one plug inn out of rec,
HAVE, THEY HAVE BEEN ASKED NOT TO HAVE THEM Time Available: ANY

220950 North Myrtle Closed Work Orders Check room for mold/mildew issue. Time Available: 7:30 10/9/2018 209 Heating/Ven bought and installed new dehumidifier checked room much better 10/25/2018
Beach Middle - tilation /Air
0037 Conditioning

220997 Aynor Middle - Closed Work Orders room is very hot and humid and muggy Time Available: asap 10/9/2018 709 Heating/Ven I checked system via apogee and the room temp was 73.5 degrees. I turned the unit on 10/15/2018
0057 tilation /Air via apogee and the discharge air temp was 58 degrees. The unit seems to operate
Conditioning properly.

221108 Conway Closed Work Orders This morning, the AC in the cafeteria was reading 80 degrees. We have also had 10/10/2018 cafeteria Heating/Ven I walked in the cafe area and looked at both t-stats and they were both reading 73 10/12/2018
Education ongoing issues with high humidity levels in that area. Anything you can do to help tilation /Air degrees. I turned both units on via apogee just to make sure they were operating
Center - 0172 with the heat and humidity would be greatly appreciated. Thank you for your help. Conditioning properly. Both units seemed to be operating properly.
Time Available: ASAP

221159 St. James High - Closed Work Orders I was hit with the strong odor of mildew. Teacher moved a box away from the wall 10/10/2018 C 121 Carpentry Checked conference room for odor and water that may be in the room. Pulled on 10/12/2018
0058 and mildew and water had stained the box. Not sure where the water is coming carpets and made sure they were secured. Inspected outside wall area and found no
from. Strong mildew odor. Time Available: high evidence of water entry. There is currently no oder of any kind. There are some stained
ceiling tiles in the room, look to be old stains. Please have custodial staff change ceiling
tile.
221251 Conway Closed Work Orders We are in need of some dehumidifiers for the childcare rooms, the air quality is 10/12/2018 Child care Heating/Ven Called school and spoke with Woodrow about this and told him to get with Nurse and if 10/23/2018
Education really bad in these rooms. Time Available: Asap rooms tilation /Air she seem to think that this was still needed she would need to contact Tammy
Center - 0172 Conditioning Truelove. Terry Hucks

Page 76 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
221358 Forestbrook Closed Work Orders Please pick up and remove the blue upholstered couches and chairs from the 10/12/2018 multiple rooms Furniture 10/19/18 picked up assets. 10/19/2018
Middle - 0051 following rooms (furniture is old and holding odors and mildew): (see list)
Mail Room 4 Chairs
101h – 1 Couch
205 - 1 chair
802- 1 chair
100 – 2 chairs
104- ISS 1 Chair
700A – 1 Couch
700L – 1 Couch – 2 Chairs
600H – 2 chairs
600G – 2 Chairs
600- 2 chairs – 1 couch
615 – 2 Couches
Time Available: any

221482 Lakewood Closed Work Orders Need a dehumidifier for the Guidance Counselor Office / Classroom. 10/15/2018 307 Heating/Ven i check the room to see why they needed a dehumidifier. teacher say unit do not turn on 10/17/2018
Elementary - tilation /Air and have a smell in room. i went to check the unit. the unit t-stat for the room is across
0029 Conditioning the hall in another room. they are ok with their smell and temperature. both rooms have
air purifier. i tried check the unit on apogee but its not showing up and i can not get a
reading. i let ross know and he will check it out.

221499 Lakewood Closed Work Orders All area's that have the mulch are highly infested with fire ants due to the rain and 10/15/2018 All Pest Control Landscape crew was on site today and treated playground area. DMS 10-15-18. 10/15/2018
Elementary - humidity. Playgrounds Outdoors
0029
221553 Carolina Forest Closed Work Orders The air conditioning in the field house is still not working. It is incredibly warm in the 10/15/2018 Field House Climate 10/16/18 system low on charge also running high head pressures. cleaned coils and 11/6/2018
High - 0052 locker rooms and offices. This causes a problem with mildew on the athletic Control added R410a freon to system. system has tandom compressors one not operating at
equipment and uniforms. Time Available: anytime all. After checking second compressor found tripping out on high head pressure per
condenser fan motor runs short time them shuts off. condenser motor is failing
internally. trying to find manufacture who carries motor. mini split for laundry area not
working. found high pressure switch tripped reset switch also cleaning coils on all 3
mine splits and changing capacitor on #2 for laundry room. all 3 running at this
time.parts on order thru manufacturer shipping to office est. arrival 10/25/18.
10/30/18 installed new condenser motor for 2nd stage compressor. system is running
on both stsges at this time may need to adjust charge at later time.

221815 St. James Closed Work Orders Teacher has expressed concerns about poor air circulation and high humidity. Time 10/18/2018 Room C-3 Heating/Ven Put fan from cycle to on in day mode to keep circulation in classroom check unit 10/18/2018
Middle - 0047 Available: Immediate tilation /Air operation Room temp 73.2
Conditioning

221893 Conway High - Closed Work Orders The tile around the water sprinkler in this classroom has green mold all over the tile. 10/19/2018 c106 Carpentry 30OCT2018 replaced tile. 11/1/2018
0004 Abston's classroom

Time Available: 7:00 am


222214 Pee Dee Closed Work Orders Please check the air in this room. The tstat is 73.2 degrees. The room is HOT, 10/23/2018 202 Heating/Ven Checked out and found unit was satisfied but controls needed some changes. Lowered 10/24/2018
Elementary - STICKY, and VERY HUMID. In order to breathe, a fan has to fun ALL DAY LONG. tilation /Air set point and put fan on continuous so air circulation in room. It was stated air was
0039 The children are sweating. Step into the hall and is it cool & crisp. This room is Conditioning stagnate. Checked on after changes and all was fine at this time.
VERY HUMID.

222265 Aynor High - Closed Work Orders Received email regarding air quality and bat droppings 10/24/2018 Pest Control 10/24/2018
0001 Indoors

Page 77 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
222282 Lakewood Closed Work Orders HP 77 10/24/2018 716 Climate i check the unit on apogee. it was at set point. i put cool temperature to 72.50. i went 10/29/2018
Elementary - temp 74 Control and check the room teacher was ok with temperature.
0029 Saying that it is very humid in the classroom
222472 Conway Middle - Closed Work Orders Principal request that the air unit be checked out for cleanliness and air quality, 10/26/2018 A103 Heating/Ven Checked out and found unit was working normally and maintaining temps. No odors 11/7/2018
0017 starting to have an odor inside room Time Available: Any tilation /Air being produced by unit but probably is spread. E-mailed Terry Hucks to get filter crew
Conditioning to steam clean unit.

223042 Green Sea Closed Work Orders In room 218 we have a Musky Mildew order & it is really strong. Time Available: 11/1/2018 218 Heating/Ven Did not smell any offensive odors but the window was open and door to hall was open 11/5/2018
Floyds ASAP tilation /Air flushing room with fresh air. Paint is peeling off wall on Ext. wall (inside) there may be
Elementary - Conditioning an issue with water being trapped in wall causing smell. Checked AC system found no
0023 issues, pan dry, condensate line clear. System operating normally. Further diagnoses
need on water infiltration of wall.

223047 Green Sea Closed Work Orders In room 109 we have mildew odor smell. Time Available: Anytime 11/1/2018 109 Heating/Ven Smelled no offensive odor, checked system performance, holding at set point, 73, AUX 11/5/2018
Floyds tilation /Air temp 57. Pan dry and condensate flowing correctly. Filter clean and evap coil clean.
Elementary - Conditioning System operating normally.
0023

223133 Aynor High - Closed Work Orders Class room I101 - The vent in the ceiling will not come on in the bathroom.The 11/2/2018 Class Room Heating/Ven I checked this room and the humidity was high. The exhaust fan is tied to the mau units 11/6/2018
0001 humidity in the room are awful and the bathroom floor are wet. Ms. Mendez using a I101 tilation /Air that are on the roof that we are waiting to get fixed. I lowered the night cooling set point
fan to circulate the air but that is not working Time Available: ASAP Conditioning so it will not get so warm and the humidity will not be so high. I also adjusted the
compressor on and off set point to remove humidity out of this room.

223387 Seaside Closed Work Orders The gym is very humid even though the temp says 72.8 and 73 degrees on the 4 11/5/2018 gym Heating/Ven i check the area. someone had a back door open and was bringing warm air into 11/18/2018
Elementary - sensors. There is a huge difference when walking in from the cafeteria to the gym, tilation /Air building.
0050 it's like a wall of humidity Time Available: any Conditioning

223403 Pee Dee Closed Work Orders Please check the air in this room ASAP! Its really hot in this room. we have parent 11/5/2018 211 Heating/Ven Checked out and unit was at set point, but had to change a few of the settings on the 11/6/2018
Elementary - teacher conferences tonight..tstat is reading 72.3 degrees. tilation /Air control system. Unit running normally and teacher satisfied.
0039 IT IS REALLY HOT & HUMID IN THIS ROOM! Conditioning

223438 Myrtle Beach Closed Work Orders teacher in this room says her room feels very humid all the time. 11/5/2018 room 604 Heating/Ven 11/8/2018- CHECKED RH% AND TEMPS. ALL READINGS WERE GOOD. 12/19/2018
Elementary - tilation /Air
0034 Conditioning

223450 South Conway Closed Work Orders Very hot and humid in Mr. Hayes office and conference room. Thanks Time 11/5/2018 principal office Climate Checked unit via Apogee this morning and found unit was supplying a 55 deg air temp 11/6/2018
Elementary - Available: ecribb@horrycountyschools.net and Control with a room temp of 72deg. Will visit office tomorrow morning. Visited school and office
0045 conference and found room at setpoint. However I did make a slight calibration to thermostat. Left
room unit operating normally.
223462 Kingston Closed Work Orders Teacher has stated that there is mildew in room. Has had a student complain of 11/5/2018 501 Heating/Ven make up air unit turned off due to bad fuses for condenser replaced working properly 11/12/2018
Elementary - getting dizzy. tilation /Air checked system for room also working properly checked room humidity at 57%
0028 Conditioning

223491 Seaside Closed Work Orders Is there a way to lower the temp in the cafeteria where the voting is taking place? It 11/6/2018 Cafeteria Heating/Ven i close the doors at other parts in building 11/18/2018
Elementary - is really warm and humid in there from the amount of people we have and the door tilation /Air
0050 constantly opening and closing. All the sensors are functioning but it is 73.5 and Conditioning
climbing. Time Available: high!

Page 78 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
223520 St. James High - Closed Work Orders Ceiling leaking from AC unit when we removed the pregnant tile, it revealed mildew 11/6/2018 A122 Carpentry Dean and Greg repaired the A/C unit this morning 11/7/18. I got a ladder and went 11/7/2018
0058 in the area where leak has been for a while. Time Available: about the drop ceiling searching for any kind of moldew or mold. Checked multiple
pdowden@horrycountyschools.net places in the room above the drop ceiling. Did not find anything, everything is like it
should be.
223580 Aynor High - Closed Work Orders The AP's office is hot and humid. The t-stat reads within a normal range; however, 11/7/2018 J204 Heating/Ven I checked unit via apogee and found the room temp was in over ride of 72 degrees, i 11/8/2018
0001 it is always muggy and warm. Students and teachers make remarks about the tilation /Air released the the point so the t-stat could control the unit. If i did not the unit was not run
temperature each time they enter the office. Please lower the set point or Conditioning due to it thing the room temp was 72.
investigate. Time Available: anytime

223592 Conway Closed Work Orders The air quality needs to be assessed in the cafeteria. The humidity is so high it 11/7/2018 Cafeteria Heating/Ven I checked bot units in the cafe and the both came on and operated normally. I adjusted 11/12/2018
Education produces moisture on the floor. This produces a safety hazard for trips and falls of tilation /Air the cooling set point and the compressor run time this should make the unit pull the
Center - 0172 both staff and students. A dehumidifier would be helpful to remove the excess Conditioning humidity out while the unit is running. I think the humidity is caused by the unit not
moisture from the air. This is a large area and may need 2 dehumidifiers. Thank running due to the temp but the humidity outside is high. i lowered the temp to make the
you. Time Available: Any unit run so it would pull humidity out of the room.

Installed a new wall mounted fan to move air in the area. Installed a new receptacle for
the power of the fan.

223593 North Myrtle Closed Work Orders Report from teacher in room 208: "There is an issue with the ac system in my room. 11/7/2018 208 Heating/Ven checked system working properly measured humidity in room at 51 witch is good 11/12/2018
Beach Middle - The posters in the room are sagging due to high humidity and the room is very tilation /Air
0037 warm. Students are "fanning" with paper to cool down - me included. Time Conditioning
Available: 7:30

223614 Daisy Closed Work Orders there is a file order, teacher said that it smell mildew Time Available: urgent 11/7/2018 room 716 Climate Slight odor when entering room, after a few minutes no odor detected. Filters very dirty, 11/19/2018
Elementary - Control contractor for filters changing was on site and said he would change those filters next.
0021 Will return and check for odors after filters are changed. Checked system performance,
holding at set point, 73. 15 degree split, system operating normally.
Returned after filter change, still had slight smell, cleaned coil, will return and check
after system has time to run.
Returned next day, still slight odor, checked hallway leading to room and various areas
inside room could not locate source of odor. Believe odor is not coming from HP unit.

223672 Conway Closed Work Orders The copier keeps jamming in the copy room and the paper is curling which adds to 11/8/2018 TLC Hallway Heating/Ven I checked room and i think the same thing is going on in there as the cafe. The room 11/12/2018
Education the jamming. I noticed that the paper in the mailboxes is wavy. There was a Room 108 last tilation /Air temp is not bringing on the unit due to the temp in the room is at set point so it is not
Center - 0172 dehumidifier in the room previously that was removed to give to a teacher that his room on the Conditioning pulling humidity out of the room. I went to shop and found a dehumidifier that works and
had broken and now we are having an issue with the copier jamming and paper right i added to this classroom. This should help with the humidity in this room.
being too damp and curling up. Thank you Time Available: Any

223731 Aynor High - Closed Work Orders Appears to be the same issue as J204. Warm, humid, and unit doesn't seem to run 11/8/2018 J203/Luksa Heating/Ven I checked system via apogee and the room temp was in range of the set points. I 11/12/2018
0001 often enough. T-stat says 73-74, but the rooms is very warm. Time Available: asap tilation /Air adjusted the compressor on and off settings. This should help remove some of the
Conditioning humidity out of the room.

223999 Conway High - Work In Progress During summer break this room has humidity issues. 11/12/2018 band uniform Heating/Ven Surveyed room and connected duct system to make assessment. Found that this room
0004 closet tilation /Air is totally sealed and has only a supply duct and know return. Will plan to add a return to
Conditioning this room when summer break begins.
26NOV2018 began running return ductwork.
28NOV2018 tied in returns at registers above ceilings in both closets replaced modified
ceiling tiles.
06DEC2018 created penetration through drama classroom closet wall above drop
ceiling and ran 12” duct through it. Then Tied in 12” duct in to tee in closet. Cleaned up.

Page 79 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
224050 Carolina Forest Closed Work Orders Need to have a Dehumidifier put in the costume room in the main building/Drama 11/13/2018 Costume Heating/Ven 11/14/18 checked room. thermostat in room reading 70 degrees, rm temp on meter 11/14/2018
High - 0052 side hall. they are cleaning it out and want to prevent mold and moisture build up. room/terry cox tilation /Air was 66 degrees w/ 52% RH. not further actions needed at this time.
Time Available: ASAP Conditioning

224519 Lakewood Closed Work Orders General Facility Inspection: 11/20/2018 400 wing Carpentry Looked at exterior and took pictures to show PC. The whole area needs pressure 11/28/2018
Elementary - Exterior wall-peeling paint / water damage, mold/mildew appearance. washed,sealed and painted. My opinion would be to paint a color similar to the brick
0029 that won't show dirt as bad as the white does. Will wait for a decision from PC.
Spoke with PC and this job will be completed when the weather allows during spring or
summer. For now this work order will be closed and a new one will be opened once
work begins on this project. Pictures are attached of damaged areas.

224525 Lakewood Closed Work Orders General Facility Inspection: Exterior walls - paint peeling, water damage from a/c 11/20/2018 100 wing Carpentry Any exterior will- a work order will need to be created to clean and paint during the 11/20/2018
Elementary - units - mildew appearance. summer during in the spring.
0029
224533 Lakewood Closed Work Orders General Facility Inspection: Need HIPA air purifier for rm. 410 to replace 11/20/2018 410 Heating/Ven i went and check room. everything was good. i talk to ms. pauline about room. teacher 11/21/2018
Elementary - dehumidifier tilation /Air say she was either hot or cold all the time. the unit was in the on mode for fan. it was
0029 Conditioning pulling air from outside in room. i set fan to auto and teacher was ok with it.

224557 Loris Elementary Closed Work Orders very warm in room... air isn't circulating. Has a moldy smell in room 11/20/2018 714 Heating/Ven Found system out on low pressure lock-out. Reset at condenser control board, system 11/21/2018
- 0032 tilation /Air operating normally.
Conditioning

224558 Loris Elementary Closed Work Orders 74.8 Room has no air - it smells like mold and mildew. 11/20/2018 713 Heating/Ven Found blown fuse at condenser disconnect, replaced fuse, system operating normally. 11/21/2018
- 0032 no air circulation tilation /Air
Conditioning

224565 St. James High - Closed Work Orders Clean wall units in field house. Mold and mildew on units. Time Available: 7:30 AM- 11/20/2018 field house Heating/Ven Cleaned 4 Mini split evaporators clean filters wiped down unit clean filter rack also 11/20/2018
0058 5:30 PM tilation /Air clean all supply
Conditioning Grills and exhaust grills for 2 wallpack's and 2 ER units changed filters in wall packs

224598 Conway Middle - Closed Work Orders Teacher request that her room be checked for Air Quality Control do to moisture 11/21/2018 A108 Heating/Ven 11/21/18 Went by and took pictures of paint peeling, glue coming up through floor tile 12/5/2018
0017 issues Time Available: Any tilation /Air seems and landscaping for drainage. Checked out room temps and humidity and wet
Conditioning bulb, still a little high humidity and wet bulb even after temps outside got colder and
outside humidity is low. Still will keep an eye on since temps are going down to the mid
to upper twenties. Installed a air purifier and dehumidifier. Cleaned them up before I
installed them. Let teacher know how to empty dehumidifier. Checked room out and
found everything was working normal and room was feeling okay.

224600 Conway Middle - Closed Work Orders Request that these classroom room be checked for Air Quality Control do to a 11/21/2018 A102,A103,A1 Climate Checked on classroom unit to make sure working - adjusted temps and unit was 12/5/2018
0017 concern of smell from moisture inside the rooms Time Available: Any 04,A105,A106, Control running normally at this time. Recorded temp-humidity-wet bulb. Will check on next
A107,A108 week, also consulted Dennis McCrary on this issue. Checked out a few of these rooms
after the weekend and felt no major changes, will check again tomorrow when temps
outside is really low. Also found room A104 needs a new compressor the sound is very
noticeable and affecting the teaching of the children. Need to get info for a new
compressor. Went ahead and ordered compressor and will do work for room 104 A on
another work order. Went through and checked all rooms for temp, humidity and wet
bulb. All looked good. Talked with Wendell about moving dehumidifiers around where
needed.

Page 80 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
224634 Kingston Closed Work Orders Fan is working good inside the classroom,but their is mildew growing all over the top 11/21/2018 309 Heating/Ven cleaned door frame and bathroom wall 11/29/2018
Elementary - of the frame inside the restroom.Also its on the wall near the tile as well. Time tilation /Air
0028 Available: 7-4 Conditioning

224754 Palmetto Bays Closed Work Orders Mold smell in classroom Time Available: any 11/26/2018 room 211 Heating/Ven checked in morning smelled musty , possible dry p-trap told teacher that I wound be 11/26/2018
Elementary - tilation /Air back after school to clean A/C ,did not smell anything this afternoon, removed panels
0056 Conditioning unit not that dirty , had been cleaned before, chemically cleaned evaporator, blower
compartment condensate pan,reassembled left Cleanair hvac order block in return
duct, checked unit operation

225601 Aynor High - Closed Work Orders It has been very warm in my office for the last several weeks. Students and visitors 12/3/2018 J204 Heating/Ven I re initialized the tec and the unit reset and went into cool mode. The discharge air 12/4/2018
0001 comment upon entering. A previous work order stated t" tilation /Air temp was 52 degrees and it pulled the room temp down. I will go by and check room
The AP's office is hot and humid. The t-stat reads within a normal range; however, it Conditioning tomorrow and make sure it is cool.
is always muggy and warm. Students and teachers make remarks about the
temperature each time they enter the office. Please lower the set point or
investigate. Time Available: anytimeI checked unit via apogee and found the room
temp was in over ride of 72 degrees, i released the the point so the t-stat could
control the unit. If i did not the unit was not run due to it thing the room temp was
72."

Nevertheless, it is 76.5 degrees currently and was warmer first thing this morning. I
have a fan going and am leaving the door open to help. Time Available: anytime

225612 Aynor High - Closed Work Orders In classroom I101 1st. floor in new building (special) the floors are damp and they 12/3/2018 Classroom Electrical Checked out and found room had high humidity, put fans to dry floor also had Dennis 12/4/2018
0001 are slipper. Humidity in this classroom and it is a slip hazard Time Available: ASAP I101 make changes to unit. Make up is being replaced in the summer so this is all we can do
for now. Looked over make up to make sure dampers closed and unit cleaned out.

225622 Kingston Closed Work Orders The Teacher wanted some one to check her room for mildew.She left papers on the 12/3/2018 115 Heating/Ven turned fan on to circulate air also turned make up air fans on 1/7/2019
Elementary - ground and all the work got wet. Not sure how but if AC man can check. Time tilation /Air
0028 Available: 7-4 Conditioning

225704 St. James New Request The back door leading to the hallway in the back of the media center becomes stuck 12/4/2018 Media Center Key and Exit device is installed too close to the latch so there is no clearance this issue has
Intermediate at times. I do not know if this is do to swelling on humid days or if it has to do with Lock been reported several times on many doors at all 5 schools this needs to be
School (New) - the door mechanisms. Time available is anytime. Time Available: low addressed.
0071
226237 North Myrtle Closed Work Orders Teacher reported: A/C unit has not kicked on once in two weeks and it is usually 12/10/2018 413 Heating/Ven checked system working properly 12/10/2018
Beach Middle - like the Arctic in here. I think the unit/humidifier or pan/tray needs emptying and/or tilation /Air
0037 the thermostat is broken. Time Available: 7:30 Conditioning

226395 Daisy Closed Work Orders Humidifier bad want turn on. Time Available: urgent 12/11/2018 library Climate Small stand alone dehumidifier, not operating because unit not calling (low humidity). 12/13/2018
Elementary - Control This is a small disposable unit, if issues arise, it should be replaced not repaired.
0021

Page 81 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
226401 Aynor Middle - Closed Work Orders Per Ms. Truelove this area needs to be checked see attachment 12/11/2018 media Heating/Ven Per Tammy Truelove we are closing this work order. 1/7/2019
0057 Put in a work order to check the area. tilation /Air
Conditioning
Tammy J. Trulove, RN, MSN, NCSN
Director of Health and Safety Services
Horry County School District
(843) 488-6805 (Office)
(843) 488-7794 (FAX)

From: Kimberly Martin


Date: Tuesday, December 11, 2018 at 12:55 PM
To: Tammy Trulove
Subject: Employee Allergic Reaction??

Tammy,

We have a new employee in our Media Center. After cleaning some bookshelves
she had a bad reaction with welts and swelling of her face and lips. She states it
happened about 2am in the morning after she was cleaning the previous day. She is
seeing an allergist tomorrow. Her dermatologist seems to think it is environmental.
She said she is on 3 different kinds of medication at this time.

When I went and surveyed the area, the bookshelves have not been dusted in
forever. There was mice droppings on shelves in the storage area. The ladies in the
media center state they have never known the carpet to be cleaned. (Mr. Willie is
not here, so I do not know if this is true).

I tried to call Mr. Eric Wilson, but I received his voicemail. The employee did not
have a reaction here at work. I did not see any welts today. She is supposed to be
sending me the pictures of what happened so I can show you. The welts in the
pictures certainly were an allergic reaction to something......

Please let me know if you think we need to put in an air quality control order to
check out that avenue as well.

Thank you Mrs. Tammy,


226796 North Myrtle Closed Work Orders check the air quality control in ventilation in the locker rooms the painting on the 12/17/2018 custodian Climate turned on fan in both locker rooms to circulate air 12/20/2018
Beach Middle - ceiling is peeling from the more stir in the locker rooms restrooms boys in girls office Control
0037 Time Available: 7am
227233 St. James Complete there is a mildew smell in classroom and conference room Time Available: 1/2/2019 E101, Heating/Ven Check portable could not smell anything unusual other than the carpet but we will clean 12/27/2018
Elementary - jcouch001@horrycountyschools.net reading/confer tilation /Air and wash and replace filters end of air conditioners when it's not raining 12-27
0030 ence room Conditioning Chemically clean all evaporators and 6 air conditioners clean Blower
parkcompartments replaced air filters with Merv 8 Electro static filters reprogram and
checked all thermostats set heat at 70 and cool at 73 scheduled Monday through
Friday 6:00 a.m. to 5:00 p.m.
227248 Waccamaw Closed Work Orders hp 76 teacher room get cold then it get very humid 1/2/2019 312 Heating/Ven 1/2/19 adjusted rm temp in apogee. went to rm checked tstat temp. monitored system 1/2/2019
Elementary - tilation /Air temp was maintaining at set points.
0042 Conditioning

227273 Aynor High - Closed Work Orders Had air quality in I110 checked and it was recommend by Tammy Truelove to install 1/2/2019 Climate Ordered Air Purifier thru Tony Jordan in ware house 1/2/2019. Received Air Purifier 1/16/2019
0001 air scrubber machine for one week. Control and checked operation prior to installing in class room.

Installed air scrubber in classroom and cleaned all vents with cleaner that was given
me to clean with. I will remove air scrubber Monday morning which will be 5 days from
when installed in classroom.

Page 82 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
227344 St. James Closed Work Orders The chorus room, E6, is very warm and humid. When trying to read the temperature 1/2/2019 Gym Heating/Ven checked all rooms 73-73.3 degrees 1/2/2019
Middle - 0047 on the thermostat, it reads, "No sensor." tilation /Air
Conditioning

227363 Aynor High - Duplicate Request Kimberly Mendez class room I101 - Her floor is once again wet due to the humidity, 1/2/2019 Classroom Heating/Ven all work is on 227428
0001 and her door been close today Time Available: ASAP I101 tilation /Air
Conditioning

227428 Aynor High - Closed Work Orders Class room I101 - due to the humidity - A request is being made for a dehumidifier 1/3/2019 Class Room Heating/Ven We have Energy Management checking in to this to see if we can keep room at a 1/15/2019
0001 because the floor once again wet. This is an on going problem ( this is special need I101 tilation /Air certain temp all through the night and not let temps rise.
class and the floor will be to slippery for them) Time Available: Anytime Conditioning

227927 Aynor High - Closed Work Orders Please hang HCS Sportsmanship banners (2) in the main gym. Screws will be 1/7/2019 Main Gym Carpentry Met with Coach to see locations, etc. 1/11/2019
0001 needed. Humidity level is too high for adhesives. Banners are 4 foot x 4 foot. See 11JAN2019 banners installed where requested. Used screws, anchors, and washers.
athletic director for exact location to be mounted. Time Available: As soon as Cleaned up.
possible
227951 Conway Closed Work Orders Dehumidifier is leaking that is in the front office. Water doesn't collect in the drip pan 1/8/2019 FRONT Heating/Ven I checked dehumidifier and the drain plug on the back of the of it was loose. I fixed the 1/29/2019
Education and it leaks out. Can it be replaced please? Very humid in the building. Thank you OFFICE TLC tilation /Air leak.
Center - 0172 Time Available: Any Conditioning

228208 Loris Elementary Duplicate Request Room - 713 Very warm and humid. 1/10/2019 713 Heating/Ven Same job as WO# 228207
- 0032 Per teacher - warmer than any other room..students uncomfortable Time Available: tilation /Air
mon- friday Conditioning

228453 Carolina Forest Closed Work Orders The dehumidifier in these classrooms need repair or replace. I have replaced the 1/14/2019 C house/ Heating/Ven 1/25/19 signed in/out checked dehumidifiers for rms 115/109 bulbs are burning filters 1/31/2019
High - 0052 filters on them and also replaced the bulbs. the units continue to beep and will not C115, C109 tilation /Air need replacing but not the source of issue. no instructions or manual found on how to
reset. Tried looking for instructions on how to reset but cannot come across any. Conditioning reset tried several different orientations units still beeping and showing bulb needs
please check out Time Available: ASAP replacing. will try to find manual online if no luck will replace both units.
1/31/19 found instruction manual online was able to reset indicator to green for bulb
replacement. beeping has stopped both systems operating properly.

228590 Conway Closed Work Orders Mr. Conary has requested that the air quality at CEC be tested. Time Available: 1/15/2019 Entire Building Heating/Ven Duplicate WO 228940 1/28/2019
Education Asap tilation /Air Terry Walked Building with Brian.
Center - 0172 Conditioning 21JAN2019 replaced 6 panels under windows in Gym/Cafeteria; treated with bleach,
removed bad, replaced insulation, installed paperless gypsum board, FRP, and
aluminum top trim. Caulked in and cleaned up.
228813 Green Sea Closed Work Orders In room 113 the paint is peeling off the wall due to moisture and possibly mold. Time 1/18/2019 113 Painting 2/20/19 R.E. The area did not need to be painted.Went to school and talked with 2/20/2019
Floyds Available: ASAP custodian and teacher. Cleaned around windows and base board. Sprayed telex
Elementary - around windows and base board.
0023
228940 Conway Duplicate Request Could you please replace the mildew stained gypsum board under the windows in 1/21/2019 Carpentry
Education the Activity Room?
Center - 0172

Page 83 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
229295 Forestbrook Closed Work Orders Please dispose of all moldy instruments in storage room. Teacher, Dr. Horsley will 1/25/2019 orchestra Furniture 1-31-19 - Scott Scrivner will provide paperwork for disposal. 2/19/2019
Middle - 0051 advise on all materials. Time Available: after school from 3:30pm on storage room 2-14-19 - Received paperwork to dispose of instruments
2/19/19. Arrived at the school signed in and started coordinating with the staff and
getting things ready. Took a large rolling container along with some large trash bags
into the storage room and bagged up the instruments and cases that Mr. Horsley had
identified as the things to be disposed of. Once bagged we took them out and loaded
them on the dump truck. Made sure with Mr. Horsley that all materials that he needed
gone was out. Then spoke with Mr. Perry about the cleaning of the room and that he
stated that he would wipe down the walls and the instrument holders that are on the
walls.
2-20-19 unloaded material out of dump truck from school and disposed of properly

229386 Seaside Closed Work Orders The wall behind the dishwasher in the kitchen is growing black mold on the wall and 1/28/2019 kitchen Heating/Ven Checked the roof top exhaust fans for the dishwasher and hood exhaust fans and 2/5/2019
Elementary - is all behind the machine as well. Not sure if this is a ventilation issue with the tilation /Air found that the belts needed to be replaced after changing the the belts on all the
0050 machine, or the kitchen itself. There is a lot of mold growing on this wall, so it could Conditioning exhaust systems for the kitchen we went into the dish washer area. Found were water
possibly be a health issue Time Available: any from the dish washer was setting on the wall, saw that it was causing the wall to turn
dark. We spoke to the kitchen manager and she told us that she keeps some cleaner
for the dish washer to spray on the wall to stop it from turning dark. Explained to her
what we had found on the roof exhaust, and told her that we went ahead and replaced
all the belts on the kitchen exhaust systems.

229465 Myrtle Beach Closed Work Orders Please run an Indoor Air Quality test per Tammy Trulove. Time Available: 1/28/2019 Room 320 Heating/Ven 01/30/2019- SIGNED IN AT FRONT DESK. CHECKED DUCTWORK, VENTS, RTU, 2/18/2019
Primary - 0035 stonner@horrycountyschools.net tilation /Air CO, RH% AND TEMP. DUCTWORK AND VENTS WERE GOOD. RH%=50%, TEMP
Conditioning 68-70* F AND ALL CO READINGS AT 0 PPM. FOUND BELT ON RTU FOR BLOWER
WAS WORN. REPLACED BELT.

SEE ATTACHED PICTURES BELOW

229518 Seaside Closed Work Orders please install a backsplash behind the dishwasher to alleviate mold growth Time 1/29/2019 kitchen Carpentry Stopped to get measurements for AS. Piece is 41-3/4 wide and 45-3/4 tall. You will 1/31/2019
Elementary - Available: any need an inside corner piece on right side and j trim on top and left side where it butts
0050 against rolling door. Sink bracket will need removed and refastened. Also need two
tubes of white silicone as old caulk needs replaced and new FRP will need caulked.
Picture attached.
1/30/19-purchased FRP board and trim for edges. Took to shop and cut to fit area.
Scheduled with cafe to install.
1/31/19-scrapped wall, cleaned, dried with rags and fan. Cut old caulking out of all the
grooves. Cleaned area. Dry fitted FRP board. Applied power grab to the wall and
installed FRP board. Attached top cap and side cap to FRP board. Finished caulking on
top,side and bottom where the FRP comes in contact with the sink. Cleaned area and
loaded truck.
Also, while we were there the cafe manager showed us 4 places where the pint was
peeling off the wall. We scrapped the areas, found paint,wipes walls and applied a thick
coat of paint to the areas.

229643 Loris Elementary Closed Work Orders very strong mildew/mold odor . If you stay in the room for any amount of time your 1/30/2019 305 Heating/Ven Checked system, found no issues. I did not smell any musky or moldy odors in room, 1/31/2019
- 0032 clothes begin to smell like it. tilation /Air walked room with Ms. Mincey, who did not smell any odors at this time. Will monitor for
Conditioning further issues.

229941 Carolina Forest New Request please change the filters in room 209. The teacher stated that she has a student 2/1/2019 room 209 Filters
Elementary - with asthma that is having issues with the air quality. Time Available: high
0049

Page 84 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
230373 St. James Complete The following was a text from Daryl - From a board member. At SJE can we check 2/5/2019 Ms. Gaskins Heating/Ven Checked the return and found a small amount of dust in the return grill, I took a 2/6/2019
Elementary - the air duct in 1st grade class Gaskins? Apparently its full of mold. Parents have 1st Grade tilation /Air cleaning rag and cleaned the dust out of the return grill. After cleaning the return grill
0030 put samples in plastic zip lock bags. They are also going around and lifting up the Class Conditioning looked inside the return duct to check it for any dust or trash, also took pictures of the
ceiling tiles and checking them." inside the return duct and the return side of the evaporator to make sure it was free
I want someone to check this out today. from dust. Also checked the supply ducts and registers all through the class room,
checked the inside of the blower compartment for any dust or trash. Took pictures of all
the things I checked, and emailed to Phillip Cannon.

230448 Forestbrook Work In Progress Indoor air quality test request. 2/6/2019 building wide Climate Ms. Rutenberg,
Middle - 0051 After a survey of staff members we have six employees reporting illness due to the Control In order to have a test done on these areas, you or the nurse will need to contact
exposure of a contaminant within the building. The symptoms include, watery/itchy Tammy Trulove from Health Services. We can use this work order to start the process
eyes, respiratory issues like coughing and wheezing, sore throat and sinus of removal if needed.
infections. Thanks,
10 rooms have reported visible mold on walls, around window casings or on Phillip Cannon
furniture. Those rooms include 800L, 812, 803, 811, 800R, 813, 806, 203 orchestra,
the gym. These rooms also report odors that resemble cat urine or sewage that HCS Asst. Manager
come and go. In addition the "new" wing at the end of the 6th grade hall has a very South Region
strong odor that seems to come from the carpet in those rooms. It goes away after 2/25/19 PC asked me to check 800 rooms to see what the problem is with windowsills.
powder deodorizer is used, but comes back soon after that wears off. The library Mrs Rutenberg wound up walking me through all the problems listed in the work order
needs review as well. The carpet in that area has been soaked with storm water a and I relayed info to PC by phone.
number of times and holds a strong musty odor. Mrs. Rutenberg has confirmed the
issues in all of these spaces through walk throughs, previous work orders and
collected data through a staff survey. Lastly, there are 4 rooms in the front office
suite that have very old carpet which holds a musty/moldy odor and need to be
reviewed. Thank you. Time Available: any

230490 Conway Work In Progress Please check we need a Dehumidifier help pull extra moisture in the air. 2/7/2019 Room 114 Heating/Ven This work order is on hold while dehumidifier is being located. Visited location but was
Elementary - tilation /Air unable to access classroom due to testing. However checked MAU serves 100 hall.
0036 Conditioning Activated cooling to lower R.H. levels. Checked operation of unit and it appears to be
Thanks working fine with 45% average humidity.

230628 Socastee Complete There is a leak in the fire sprinkler system causing wetness and black mold by the 2/8/2019 258 Fire Alarm Item was reviewed in the field. There were no signs of an active leak. 2/19/2019
Elementary vent in the ceiling. The custodian was checking for wetness and his finger went System After waiting a week still no signs of an active leak.
NEW - 0054 through the moldy area. Time Available: cstreater001@horrycountyschools.net Hole was patched.
Note: The building is out of warranty, Metcon/FFEP was not required to close this
issue out but did so nonetheless.
230633 Lakewood Closed Work Orders HPO73 - temp is 75. Classroom feels very humid 2/8/2019 719 Heating/Ven i went and check the room. everything was working properly. 2/18/2019
Elementary - tilation /Air
0029 Conditioning

231285 Myrtle Beach Work In Progress Can you come and check these rooms for mold a teacher started talking about her 2/18/2019 Room 118/121 Painting Went by with in the hour that this work order came in stopped by and inspected with
Primary - 0035 room with some people so you know how that work. Time Available: anytime and more Mr.Hanna Alan Graham and myself we found no sign of any mold any were but in
room 123 there Is moisture between the carpet and existing vct tiles that the teacher
stated had been on going since 3/9/17 I've talked with Artie and emailed him several
pictures from the teacher in 2017 . Also attached a picture that was taken while I
inspected.

2/27/19 went by and removed carpet out of room 122 removed trash

Page 85 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date
231290 St. James Closed Work Orders teacher telling me its to humid and hot in classroom. T-stat is reading 72.8 2/18/2019 P113,P111,P1 Heating/Ven On 2-18-19 checked each class room on the APOGEE program and saw that they all 2/19/2019
Elementary - 08 tilation /Air were below day cooling set point and above the day heating set point,but did find that
0030 Conditioning the blower fans were not cycling on and off in rooms P-113, P-111, and P-118, turned
fans to cycle mode with the APOGEE system. On 2-19-19 went by the school to check
with James Couch and told him what I had found and ask if the teachers could tell the
difference and he replied that they had not complained so I told him with the drop in the
outside temperature we will try this to see if it fixed the problem in the class rooms.

231410 Forestbrook New Request a previous request for outside power washing was submitted. This was put off until 2/19/2019 all external Custodial
Middle - 0051 the new roof was installed. The roof has been completed for a number of months surfaces
now, therefore another request is being submitted for pressure washing of all
external brick and surfaces. Some areas are badly stained with black mildew from
rain and moisture. Time Available: any

231419 River Oaks Closed Work Orders Teacher has stated she has been sick, principal stated a few stained ceiling tiles in 2/19/2019 Room 414 Carpentry 2/19/19 4:00pm after receiving a text from Artie Teasley about room 414 we arrived 2/21/2019
Elementary - the classroom. Please investigate, look for water intrusions, dirt, mildew etc. with in minutes of receiving text we inspected room found two stained (dry)ceiling tiles
0065 Replace ceiling tiles. with spots about as big as a softball after inspection of attic area we believe it was
caused by condensation as is the case in several locations throughout the school no
signs of a roof problem after further inspection we noticed several stained spots in the
carpet other than that the room appeared to be clean and dry no moisture found on any
surfaces I’ve emailed Artie pictures of everything also a few on work order (we did
notice a smell as we entered the room it was determined to be coming from decorative
items made out of burlap material)

2/20/19 stopped by and inspected to see if we could find a roof leak after it’s been
raining for most of the night and all day we found everything dry the teacher stated that
the two small stains on the tiles we changed out had been like that for a very long time
and she has never noticed a leak in her room.

231482 St. James Complete per McDavid, the humidity is high in classroom t-stat reading 73-74 today. warm and 2/20/2019 P107 Heating/Ven Checked room P-107 and found that the blower fan was continuous running which 2/21/2019
Elementary - humid in there today other classroom beside her are around 71 degrees tilation /Air would circulate the warm air around in the class room making it seem warm. Also
0030 Conditioning checked the rooms temperature and it was below the 73 degrees set point I will get with
Ross to see it there is anything else we can do. On 2-21-19 when I got to work checked
room P-107 and room temperature was at 70 degrees.

Page 86 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date

Page 87 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date

Page 88 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date

Page 89 of 90 3/13/2019
Horry County Schools Work Orders Feb 1, 2015 through Feb 20, 2019
Request Description containing: "mold", "mildew", "humid", "air qual"

Work Submittal Actual Completion


Order ID Location Status Request Description Date Area Number Craft Action Taken Date

Page 90 of 90 3/13/2019