Application Note

Measurement of Bushing CTs with the CT Analyzer

Author
Yvo Langnaese | yvo.langnaese@omicron.at

Date
Sep 01, 2010

Related OMICRON Product


CT Analyzer

Application Area
CT Testing

Version
v1.0

Document ID
ANP_10046_ENU

© OMICRON Page 1 of 17
Content

1 Introduction........................................................................................................................................... 4
2 Recommended Connection Methods ................................................................................................. 4
2.1 For CTs in Windings; Ratio Error 0.062 %............................................................................... 4
2.2 For CTs in the Feeding Line of a Winding; Ratio Error 0.037 % ............................................. 5
2.3 For CTs in a Winding; Ratio Error 0.077 % ............................................................................. 6
3 Less Optimal Connection Methods and Corresponding Errors ...................................................... 7
3.1 Connection Methods for CTs in Windings................................................................................ 7
3.1.1 Measurement in Winding; Ratio Error 0.064 %........................................................................... 7
3.1.2 Measurement in Winding; Ratio Error 0.075 %........................................................................... 7
3.1.3 Measurement in Winding; Ratio Error 0.095 %........................................................................... 8
3.1.4 Measurement in Winding; Ratio Error 0.098 %........................................................................... 8
3.1.5 Measurement in Winding; Ratio Error 0.106 %........................................................................... 9
3.1.6 Measurement in Winding; Ratio Error 0.13 %............................................................................. 9
3.1.7 Measurement in Winding; Ratio Error 0.24 %........................................................................... 10
3.1.8 Measurement in Winding; Ratio Error 2 %................................................................................ 10
3.1.9 Measurement in Winding; Ratio Error 4.035 %......................................................................... 11
3.2 Connection Methods for CTs in the Feeding Line of a Winding............................................ 12
3.2.1 Measurement in the Feeding Line of a Winding; Ratio Error 0.035 %...................................... 12
3.2.2 Measurement in the Feeding Line of a Winding; Ratio Error 0.037 %...................................... 12
3.2.3 Measurement in the Feeding Line of a Winding; Ratio Error 0.037 %...................................... 13
3.2.4 Measurement in the Feeding Line of a Winding; Ratio Error 0.042 %...................................... 13
3.2.5 Measurement in the Feeding Line of a Winding; Ratio Error 0.052 %...................................... 14
3.2.6 Measurement in the Feeding Line of a Winding; Ratio Error 0.062 %...................................... 14
3.2.7 Measurement in the Feeding Line of a Winding; Ratio Error 1.35 %........................................ 15
3.2.8 Measurement in the Feeding Line of a Winding; Ratio Error 1.35 %........................................ 15
3.3 Connection Methods for CTs in a Winding............................................................................ 16
3.3.1 Measurement in a Winding; Ratio Error 4.080 % ..................................................................... 16

© OMICRON 2010 Page 2 of 17


Please use this note only in combination with the related product manual which contains several
important safety instructions. The user is responsible for every application that makes use of an
OMICRON product.

OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON.

© OMICRON 2010. All rights reserved. This application note is a publication of OMICRON.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical
character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON.
Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this application note represent the technical
status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and entirely
reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present.
OMICRON translates this application note from the source language English into a number of other languages. Any
translation of this document is done for local requirements, and in the event of a dispute between the English and a non-
English version, the English version of this note shall govern.

© OMICRON 2010 Page 3 of 17


1 Introduction
This application note describes how to connect the CT Analyzer to a bushing CT inside a ( )
transformer and points out the influences of the respective connection method to the measurement
results.

To determine the typical ratio error for each connection method, various measurements have been
performed on a ( ) transformer containing a measurement CT in a bushing.

2 Recommended Connection Methods

2.1 For CTs in Windings; Ratio Error 0.062 %


Here, only one transformer winding is connected in series to the CT. This connection method
provides least possible influence to the measurement result for Rct. The delta winding and the
remaining windings of the transformer's star winding are short-circuited to avoid influence of the core
flux to the measurement.

© OMICRON 2010 Page 4 of 17


2.2 For CTs in the Feeding Line of a Winding; Ratio Error 0.037 %
Here, only two parallel transformer windings are connected in series to the CT. This connection
method provides least possible influence to the measurement result for Rct. The star winding and the
remaining windings of the transformer's delta winding are short-circuited to avoid influence of the
core flux to the measurement.

© OMICRON 2010 Page 5 of 17


2.3 For CTs in a Winding; Ratio Error 0.077 %
For this measurement, it is essential to select a delta compensation of Ratio 2/3 in the CT-Object
card of the CT Analyzer.

One transformer winding is connected in series to the CT. This connection method provides least
possible influence to the measurement result for Rct. The star winding and the remaining windings of
the transformer's delta winding are short-circuited to avoid influence of the core flux to the
measurement.

© OMICRON 2010 Page 6 of 17


3 Less Optimal Connection Methods and Corresponding Errors

3.1 Connection Methods for CTs in Windings

3.1.1 Measurement in Winding; Ratio Error 0.064 %

3.1.2 Measurement in Winding; Ratio Error 0.075 %

© OMICRON 2010 Page 7 of 17


3.1.3 Measurement in Winding; Ratio Error 0.095 %

3.1.4 Measurement in Winding; Ratio Error 0.098 %

© OMICRON 2010 Page 8 of 17


3.1.5 Measurement in Winding; Ratio Error 0.106 %

3.1.6 Measurement in Winding; Ratio Error 0.13 %

© OMICRON 2010 Page 9 of 17


3.1.7 Measurement in Winding; Ratio Error 0.24 %

3.1.8 Measurement in Winding; Ratio Error 2 %

© OMICRON 2010 Page 10 of 17


3.1.9 Measurement in Winding; Ratio Error 4.035 %

© OMICRON 2010 Page 11 of 17


3.2 Connection Methods for CTs in the Feeding Line of a Winding

3.2.1 Measurement in the Feeding Line of a Winding; Ratio Error 0.035 %

3.2.2 Measurement in the Feeding Line of a Winding; Ratio Error 0.037 %

© OMICRON 2010 Page 12 of 17


3.2.3 Measurement in the Feeding Line of a Winding; Ratio Error 0.037 %

3.2.4 Measurement in the Feeding Line of a Winding; Ratio Error 0.042 %

© OMICRON 2010 Page 13 of 17


3.2.5 Measurement in the Feeding Line of a Winding; Ratio Error 0.052 %

3.2.6 Measurement in the Feeding Line of a Winding; Ratio Error 0.062 %

© OMICRON 2010 Page 14 of 17


3.2.7 Measurement in the Feeding Line of a Winding; Ratio Error 1.35 %

3.2.8 Measurement in the Feeding Line of a Winding; Ratio Error 1.35 %

© OMICRON 2010 Page 15 of 17


3.3 Connection Methods for CTs in a Winding

3.3.1 Measurement in a Winding; Ratio Error 4.080 %


Select a delta compensation of Ratio 2/3 in the CT-Object card of the CT Analyzer for this
measurement.

© OMICRON 2010 Page 16 of 17


OMICRON is an international company serving the electrical power
industry with innovative testing and diagnostic solutions. The application of
OMICRON products provides users with the highest level of confidence in
the condition assessment of primary and secondary equipment on their
systems. Services offered in the area of consulting, commissioning,
testing, diagnosis, and training make the product range complete.
Customers in more than 130 countries rely on the company's ability to
supply leading edge technology of excellent quality. Broad application
knowledge and extraordinary customer support provided by offices in
North America, Europe, South and East Asia, and the Middle East,
together with a worldwide network of distributors and representatives,
make the company a market leader in its sector.

Americas Asia-Pacific Europe, Middle East, Africa


OMICRON electronics Corp. USA OMICRON electronics Asia Limited OMICRON electronics GmbH
12 Greenway Plaza, Suite 1510 Suite 2006, 20/F, Tower 2 Oberes Ried 1
Houston, TX 77046, USA The Gateway, Harbour City 6833 Klaus, Austria
Phone: +1 713 830-4660 Kowloon, Hong Kong S.A.R. Phone: +43 5523 507-0
+1 800-OMICRON Phone: +852 2634 0377 Fax: +43 5523 507-999
Fax: +1 713 830-4661 Fax: +852 2634 0390 info@omicron.at
info@omicronusa.com info@asia.omicron.at

For addresses of OMICRON offices with customer service


centers, regional sales offices or offices for training,
consulting and commissioning please visit our web site. www.omicron.at  www.omicronusa.com

You might also like