Professional Documents
Culture Documents
• Introduction
• IEC Technical Specification 60076-20
• Analysis approach and methodology
• Findings from surveys and analysis
• Conclusions and Recommendations
Introduction
• Project title: Reducing Losses in Power
Distribution through Improved Efficiency of
Distribution Transformers
• Objective:
– To build awareness and capacity of policy makers on
impacts of adopting IEC TS 60076-20 (Energy
Efficiency Technical Specification) in terms of energy
loss and GHG emission reductions
– To come up with key recommendations (in
consultation with key stakeholders) on the next steps
• Timeline: November 2016 – January 2018
IEC Technical Specification 60076-20
• Published in January 2017
– Power Transformers – Part 20: Energy Efficiency
• Provides methods for efficiency and efficiency index
calculation
• Provides two levels of recommendations
– Level 1 is for basic energy performance
– Level 2 is for high energy performance
• Energy performance MAY be specified in one of the
following ways:
– Minimum PEI (Peak Efficiency Index)
– Maximum load losses and maximum no-load losses
– Minimum Efficiency Index at a load factor of 50%
IEC 60076-20 Recommendations -
Observations
Energy Performance Indicator 50Hz DT 60Hz DT
Minimum PEI (Method A)
Maximum load losses & no-load losses
Minimum Efficiency Index at a load factor of 50% (Method B)
99.50% 99.50%
Efficiency at 50% Load Factor (Method A)
Tier 1 Tier 1
97.50%
97.50%
0.8
loading factor loading factor
0.6
0.4
50% 50%
0.2
0
00:00:00 02:00:00 04:00:00 06:00:00 08:00:00 10:00:00 12:00:00 14:00:00 16:00:00 18:00:00 20:00:00 22:00:00 00:00:00
Worst Case
1
0.8
0.6
50% 71%
0.4
0.2
0
00:00:00 02:00:00 04:00:00 06:00:00 08:00:00 10:00:00 12:00:00 14:00:00 16:00:00 18:00:00 20:00:00 22:00:00 00:00:00
Realistic Case
1
0.8
0.6
50% 57%
0.4
0.2
0
00:00:00 02:00:00 04:00:00 06:00:00 08:00:00 10:00:00 12:00:00 14:00:00 16:00:00 18:00:00 20:00:00 22:00:00 00:00:00
Different DT Designs for the same Efficiency
Index
Design No-Load Losses (W) Load Losses (W)
Design A 30 408
Design B 66 264
Design C 96 144
99.30%
99.10%
98.90%
98.70%
Efficiency (%)
98.50%
Design A
98.30%
Design B
98.10%
Design C
97.90%
97.70%
97.50%
Diversity of Daily Load Profiles
0 0 0
00:00:00 02:00:00 04:00:00 06:00:00 08:00:00 10:00:00 12:00:00 14:00:00 16:00:00 18:00:00 20:00:00 22:00:00 00:00:00 00:00:00 02:00:00 04:00:00 06:00:00 08:00:00 10:00:00 12:00:00 14:00:00 16:00:00 18:00:00 20:00:00 22:00:00 00:00:00 00:00:00 02:00:00 04:00:00 06:00:00 08:00:00 10:00:00 12:00:00 14:00:00 16:00:00 18:00:00 20:00:00 22:00:00 00:00:00
6,000
26%-74% Higher
Daily Energy Losses (Wh)
5,000
4,000
9%-24% Higher
3,000
2,000
1,000
-
Ideal Case Worst Case Realistic Case
Design A (NL=30W, LL=408W) 3,102 5,397 3,854
Design B (NL=66W, LL=264W) 3,102 4,587 3,588
Design C (NL=96W, LL=144W) 3,102 3,912 3,367
Source: Estimation by ICA
Diversity of Loading Factors
3,500
35% Average loading factor
6,000
50% Average loading factor -
Ideal Case Worst Case Realistic Case
Design A (NL=30W, LL=408W) 1,880 3,004 2,248
Daily Energy Losses (Wh)
3,000
2,000
1,000
-
Ideal Case Worst Case Realistic Case
Design A (NL=30W, LL=408W) 3,102 5,397 3,854
9,000
75% Average loading factor
Design B (NL=66W, LL=264W) 3,102 4,587 3,588
8,000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Energy Losses - Savings
Annual Load Factor
Energy Demand of PEA
GWh
12,000
11,500
2016
11,000
10,500 2015
10,000 2014
9,500 2013
9,000
8,500
IEC 60076-20 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
IEC 60076-20
Scenario Scenario
DT designs to meet Key Variables:
- Load losses/no Per Unit Annual
efficiency Electricity Tariff
load losses requirements Energy Losses
(current/
- Efficiency at 50%
projection),
load
Emission Factor,
- Peak efficiency
discount rate,
index
service life
Comprehensive Data Required
• Stock of installed DTs classified by kV and kVA
– Popular kVA rating, Expected lifetime of DTs
• Typical load profiles of different end-use sectors, seasonal
variation and load factors
• Average loading factor or average RMS loading
• Current energy performance standards
– National Standards and Utility Procurement Specifications
• Electricity tariff, electricity emission factor
• Data collection activities include:
– Review of secondary resources
– Questionnaire distribution
– Direct interview with utilities
Key Parameters and Assumptions (1)
• Baseline (business-as-usual) scenario
– Energy performance levels based on either the national
MEPS or the utilities’ procurement documents.
• IEC 60076-20 scenario
– Level 1 recommendations are not used due to their less
stringentcies.
– For 50Hz DTs - level 2 energy performance
recommendations on no-load and load losses and EIB50
– For 60 Hz DTs - level 2 energy performance
recommendations on EIB50
– The PEI recommendations referenced as indicators not as
EE options
Key Parameters and Assumptions (2)
• Per unit analysis - characteristics of the most common
kVA rating represent the whole DT population (Utility-
owned, liquid-immersed)
• Focus on three major end-use sectors:
– Residential, Commercial and Industrial (Three sets of daily
load profile)
– Annual average loading factors based either on feedback
from APEC/ASEAN economies or historical energy
consumption statistics
• Maximum loading factor for DTs is 100% (at any time of
the day) – no overloaded!
– Two analysis points – annual average loading factors (per
data collection) & 50% loading factor
Baseline Scenario
Baseline Scenario
Liquid-Immersed DT (50Hz, ≤24 kV, ≤3,150 kVA) Liquid-Immersed DT (60Hz, ≤2,500 kVA)
Not implemented in
selected economies Flat/Constant Residential Sector Commercial Sector Industrial Sector
Daily Load Profile Daily Load Profile Daily Load Profile Daily Load Profile
(no peak demand) (evening peak (afternoon & evening (multiple peak
demand) peak demand) demand)
PEI (%) of each model – for comparison & reporting Annual energy loss analysis
99.500%
• Baseline: based on existing
99.000% losses requirements
98.500%
Efficiency
96.500%
99.500%
– Design B - low no-load
99.000% losses and high load losses
98.500%
– Design C – High no-load
Efficiency
97.500%
Design A
Design B
losses and low load losses
97.000% Design C
96.500%
96.000%
Loading Factor
Four DTs Designs – 60Hz
Baseline: 1-Phase, 50kVA DT, Philippines
100.000% • Baseline: based on DOE
99.500% 2010 requirements, NEMA
99.000%
TP-1 compliant
Efficiency
Baseline Model
98.500% Design A
97.500%
level 2 EIB50 for 60Hz (or
Loading Factor
DOE 2016)
– Design A – Medium no-load
Baseline: 1-Phase, 25 kVA DT, PG&E, USA
99.500%
losses and high load losses
99.300%
99.100%
– Design B - low no-load
98.900% losses and high load losses
98.700%
– Design C – High no-load
Efficiency
98.300%
98.100%
Design A
Design B
losses and low load losses
Design C
97.900%
97.700%
97.500%
Loading Factor
Per Unit Analysis – Philippines (1)
Utility Owned DT Population
50,000 2,500
1-Phase, 50 kVA DT selected
40,000
for per unit analysis 2,000
Unit Installed
MVA Installed
30,000 1,500
- -
≥ - - - - - ≥ - - - - -
200 100
0
Flat 0 Flat
Design A Design B Design C
-200 Design A Design B Design C
Residential Residential
-100
Commercial Commercial
-400
Industrial -200 Industrial
-600
-300
-800
-1,000 -400
Provincial Electricity Authority (PEA) PEI gained = 0.35%-0.52% EIB50 gained = 0.31%
2,000 400
1,000
Flat 200 Flat
0 Residential Residential
Design A Design B Design C 0
-1,000 Commercial Commercial
Design A Design B Design C
Industrial -200 Industrial
-2,000
-3,000 -400
-4,000 -600
2,500
Per Unit Annual Savings (kWh)
0 1,900
Design A Design B Design C Design A Design B Design C
1-Phase, 25 kVA DT
selected for per unit
analysis
60
100
Per Unit Annual Savings (kWh)
-500 -20
10.00%
8.00%
6.00%
4.00%
2.00%
0.00%
Others
kVA Rating
Source: Market Study for Utility Distribution Transformer - Vietnam, ICA, 2015
PEI gained = 0.115%-0.247% EIB50 gained = 0.1%
7,000 1,200
6,000
Flat 1,000 Flat
5,000
Residential 800 Residential
4,000
Commercial 600 Commercial
3,000
Industrial 400 Industrial
2,000
1,000 200
0 0
-1,000 Design A Design B Design C Design A Design B Design C
35%
30%
25%
20%
15% Design A
10% Design B
5% Design C
0%
-5% Philippines Thailand Thailand USA Vietnam
(MEA) (PEA)
-10%
-15%
PEI vs Annual Energy Losses @ 50% Loading
Factor
1-Phase, 50 kVA DT, 60Hz, Philippines 3-Phase, 160 kVA DT, 50Hz, Thailand (PEA)
4,000 99.500% 14,000 99.500%
3,500 99.400%
99.400% 12,000
99.300%
3,000
99.300% 10,000
Flat 99.200% Flat
2,500
99.200% Residential 8,000 99.100% Residential
2,000
99.100% Commercial 6,000 99.000% Commercial
1,500
Industrial 98.900% Industrial
99.000% 4,000
1,000 98.800% PEI (%)
PEI (%)
500 98.900% 2,000
EIB50 (%) 98.700% EIB50 (%)
0 98.800% 0 98.600%
Baseline Model Design A Design B Design C Baseline Model Design A Design B Design C
1-Phase, 25 kVA DT, 60Hz, USA (PG&E) 3-Phase, 250 kVA DT, 50Hz, Vietnam (SPC & HCMC)
1,320 99.300% 9,000 99.550%
1,300 99.500%
99.200%
60,000
50,000
New Installation
40,000
Replacement
30,000
Baseline Model Stock
20,000
10,000
0