Can We Go Wireless in Hazardous Areas?


Readers help a reader solve this problem. Next: Screw or IDC--Which works better?
Sep 03, 2003

A Reader Writes:
We've been providing wireless communications solutions as alternatives where additional device-level nodes
are needed in difficult-to-wire locations. We've not been involved with hazardous locations until now. Can we
use wireless in Class I, Div. 1 and Class I, Div. 2 areas?

-From May 2003 Control Design

Answers
Use Spread-Spectrum Monitoring
New technology is enabling greater use of spread-spectrum radio for monitoring and control in industrial
environments. Today, spread-spectrum can securely move small amounts of sensor and control information
from a transmitter measuring flow, level, pressure, temperature, etc., even transmitting mission-critical
information through heavy interference. The most efficient interference-tolerating technology for such
applications is frequency hopping, a part of spread-spectrum.

...The maximum allowable transmit power according to the FCC is 1 W for a frequency-hopping spread-
spectrum device. The devices can be connected directly to a transmitter located in a Class I, Div. 2 hazardous
location and can send the signal 600-1,000 ft. in a plant in harsh industrial conditions, eliminating the need for
wire, conduit, trenching, and all associated labor. No setup, configuration, or software is required. Simply plug
in, power, wire the transmitter or signals to it, and get it out on the other end.

...However, the 1 W maximum transmit power and the circuitry around it is used to achieve the distances and to
tolerate interference levels, which pose a problem in a Class I, Div. 1 area. For applications in a Div. 1 area, the
device can be mounted in a supplied explosion-proof housing with a clear window. The propagated radio signal
penetrates through the clear window, while maintaining an explosion-proof rating. The receiver is placed in the
safe area or Div. 2 area by the controller. This method eliminates the need for additional explosion-proof conduit
systems, seals, glands, and associated labor.
Davis Mathews, Instrumentation Product Manager
https://www.controldesign.com/articles/2003/143/ 1/7
3/18/2019 Can We Go Wireless in Hazardous Areas?

Phoenix Contact, Harrisburg, Pa.


It's All About the Label

In addition to the UL ordinary locations/general purpose standards that may apply and the installation
requirements per the local Authority Having Jurisdiction (such as ANSI/NFPA 70, "National Electrical Code"
Article 500), the node(s) should be evaluated in accordance with the following UL hazardous locations
standards and their protection method philosophies briefly described below. Readers first may wish to refer to
www.ul.com/hazloc to familiarize themselves with the different protection methods, standards. and area
classifications noted in this article.

...It may be difficult to place the node, antenna and all, inside an explosion-proof enclosure and have it perform
as desired with other nodes. But it could be possible to evaluate the node's enclosure as explosion-proof, or
obtain an appropriate UL-certified explosion-proof enclosure suitable for the location, so the node could be
placed inside. This enclosure most likely would be evaluated to ANSI/UL 1203, "Explosion-Proof and Dust
Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations." In this scenario, any
atmospheric ignition caused by the node would be contained within the enclosure and not propagate into the
surroundings. (The same argument would apply to Class I, Zone 1 Flameproof protection in accordance with
ANSI/UL 2279, "Electrical Equipment for Use in Class I, Zone 0, 1 and 2 Hazardous (Classified) Locations."

...A more viable choice for Class I, Div. 1 hazardous locations may be to have the node evaluated as
intrinsically safe per standard ANSI/UL 913, "Intrinsically Safe Apparatus and Associated Apparatus for Use in
Class I, II, and III, Div. 1 Hazardous (Classified) Locations." The intrinsically safe method achieves its protection
by evaluating, and more importantly limiting, the potential energy of the node under electrical fault conditions so
that the specific atmosphere or group of atmospheres the node is located in are not capable of being ignited by
a possible spark from the node. An evaluation per UL 913 also would allow the node to sit openly and transmit
without the interference of being in a thick-walled enclosure. (The same argument would apply to the
consideration of using the Class I, Zone 0 or 1 Intrinsically Safe protection methods in accordance with
ANSI/UL 2279, "Electrical Equipment for Use in Class I, Zone 0, 1, and 2 Hazardous (Classified) Locations.")

...In addition, the possibility of the node being used only in Class I, Div. 2 hazardous locations should be
addressed. In this case, the protection method used for evaluating the node would be Non-Incendive per UL
1604, "Electrical Equipment for Use in Class I and II, Div. 2, and Class III Hazardous (Classified) Locations."
Though this method of evaluation would also evaluate the potential energy in the node as in the above
intrinsically safe method, it does not limit the energy nor does it consider the potential energy under the
electrical faults introduced during the intrinsically safe evaluation. Instead, this method evaluates the normally
sparking parts as well as the possibility of shorting or grounding exposed electrical circuits (such as the
antenna), and their ability to keep the ignitable atmosphere out of the electrical contact area, or by the parts not
having enough energy under normal conditions of use to ignite the hazardous atmosphere.

...This type of evaluation would most likely also require an evaluation of the combination of the node and the
device it is installed with, not just the node itself. The same argument would apply to the consideration of using
the Class I, Zone 2 Non-Incendive protection method in accordance with ANSI/UL 2279, "Electrical Equipment
for Use in Class I, Zone 0, 1, and 2 Hazardous (Classified) Locations."

...There are currently many radio/modem devices that are UL-certified under the intrinsically safe and non-
incendive protection methods. Many of these devices involve process control applications located near
pipelines, furnaces, etc., gathering temperature and pressure information and relaying it back to a central
computer via antennas.
Jason Frieders, UL HazLoc Project Engineer

Underwriters Laboratories, www.ul.com/hazloc


Built Our Own Antenna

https://www.controldesign.com/articles/2003/143/ 2/7
3/18/2019 Can We Go Wireless in Hazardous Areas?

We have run into this problem frequently and decided to develop an antenna that would pass the rigorous
certification tests.

...We chose the 2.4 GHz Mobile Mark body-mount antenna because of its rugged construction for vehicular
applications. This antenna can be manufactured with a solid two-piece aluminum mounting base and radome
containing the radiating element.

...The antenna was redesigned to reroute a coaxial cable through the mounting base and was internally sealed
using fibrous packing and approved conduit-sealing compound. The bottom side of the base has a plug that
further seals and secures the coaxial cable. This is an accepted method of preventing gases from leaking inside
the housing through the antenna-mounting base.

...A radome containing the radiating element of the 2.4 GHz or 900 MHz antenna is threaded and securely
screwed onto the aluminum base section with a proprietary sealant cement securing the two pieces. The base
of the antenna has a 3/4-in. NPT fitting, containing the feedthrough, for assembly into a hub on the top of the
housing. The figure shows the prototype explosion-proof antenna attached to an Adalet explosion-proof
enclosure.
Ed Rasmussen, President

Analynk, Houston
Certifications Are Invaluable

Industrial wireless modems typically carry some form of UL certification. Our line of wireless industrial
communication solutions carry multiple hazardous certifications, including UL1604, Class I, Div. 2, Groups A, B,
C, and D for the U.S. This certification is also regarded as an acceptable certification for much of the rest of the
world. The products are cUL (Canadian Standard CSA) Class I, Div. 2, Groups A, B, C, and D for use in
Canada. For Europe, we are completing the testing process for ATEX certification.

...UL1604, Class I, Div. 2, Groups A, B, C, and D, is the most common certification, permitting wireless modem
operation in locations where flammable or explosive gases, fluids, or vapors are possible, but are not
necessarily part of the normally operating environment. Class I, Div. 1 is essentially for industrial locations
where there is an ongoing risk of explosion due to the presence of combustible gases, liquids, and vapors. A
key requirement here is that enclosures must be explosion-proof. For a work-around for using Industrial
wireless products in a Class I Div I area, the devices can often be placed in containers that meet Class I
Division I standards."

...Getting these certifications can be expensive and time consuming for the manufacturer, however, the benefit
to the customer of having this certification is that a company can standardize wireless networks on a single type
of device, and use it for many applications, regardless of the environment."
Wally Gastreich, Wireless Application Engineer

Kevin Zamzow, RadioLinx Specialist

ProSoft Technology, Bakersfield, Calif.

November's Problem:

Screw or IDC--Which Works Better?


Until recently, for better or worse, we used screw-clamp terminal blocks for connections. Now, we have customers that
prefer and sometimes specify insulation-displacement connectivity. They argue that IDC means lower installation costs
and reduced cabinet space as a result. That's fine, but I'd like to hear what real users know about increased likelihood of
having to run down loose connections in the field later on. We sell into global environments with varying degrees of
vibration, repetitive motion, etc.

https://www.controldesign.com/articles/2003/143/ 3/7
3/18/2019 Can We Go Wireless in Hazardous Areas?

Send us your comments, suggestions, or solutions for the problem. We'll include them in the November 2003
issue. Send visuals, too,a sketch is fine. E-mail us at CDTheAnswer@putman.net or mail to The Answer to Your
Problems, CONTROL DESIGN, 555 W. Pierce Rd., Suite 301, Itasca, IL 60143. You can also fax to 630/467-1124.
Please include your company, location, and title in the response. Have a problem you'd like to pose to the readers?
Send it along.

Free Subscriptions
E-Newsletters Digital Editions

controldesign.com E-Newsletters
Biweekly updates delivering feature articles, headlines with direct links to the top news stories that are critical to
staying up to date on the industry — company news, product announcements, technical issues and more. Subscribe
Today.

Most Popular
Past 7 Days Past 30 Days Past 6 Months All Time

01 Siemens and Litmus Automation partner on IoT edge computing


Litmus' LoopEdge will be Integrated with Siemens' MindSphere to collect…

02 Newark releases insights from global Raspberry Pi survey


According to the development distributor, price and ease of use are the…

03 Beckhoff Automation president on what's driving the company forward


Kevin Barker shares the keys to growth that are guiding the company in…

04 Reusable software is ever-developing


Software development platforms and the controllers that run the software…

05 How to ensure your pneumatic system is robust


When it comes to the use of compressed air in automated machines, there…

https://www.controldesign.com/articles/2003/143/ 4/7
3/18/2019 Can We Go Wireless in Hazardous Areas?

About
Contact Us
Advertise
Media Kit
Rates & Spec
Privacy Policy
Legal / T&C

Content
Voices

https://www.controldesign.com/articles/2003/143/ 5/7
3/18/2019 Can We Go Wireless in Hazardous Areas?

White Paper Library


News
Webinars
White Papers
Multimedia
Special Reports
Events
Products
Technology Roundups
E-lits
Vendor Notes

Magazine
Subscribe
Digital Edition
Issue Archive
Reprints

Site Tools
Knowledge Center
Company Profiles
Site Map

Stay Connected
My Account
Newsletters
RSS
Twitter
Facebook
LinkedIn
YouTube

Contact Us | Advertise | Privacy Policy | Legal Disclaimers, Terms & Conditions


Copyright © 2004 - 2019 Control Design. All rights reserved.
P: 630-467-1300 | 1501 E. Woodfield Road, Suite 400N, Schaumburg, IL 60173

Chemical Processing | Control | Control Design | Food Processing | Pharmaceutical Manufacturing | Plant Services | Smart
Industry

https://www.controldesign.com/articles/2003/143/ 6/7
3/18/2019 Can We Go Wireless in Hazardous Areas?

https://www.controldesign.com/articles/2003/143/ 7/7

You might also like