The document provides calculations to determine the required capacity and head of a hot water circulation pump (CP-1) for a 300 meter insulated pipe loop. It calculates a heat loss of 9000 Watts and a required pump flow of 0.217 liters per second. Adding a 10% safety factor increases the required flow to 0.3 liters per second. It then calculates a total friction head loss of 60 kilopascals and selects a pump with a capacity of 0.3 liters per second at a head of 60 kilopascals (6 meters).
The document provides calculations to determine the required capacity and head of a hot water circulation pump (CP-1) for a 300 meter insulated pipe loop. It calculates a heat loss of 9000 Watts and a required pump flow of 0.217 liters per second. Adding a 10% safety factor increases the required flow to 0.3 liters per second. It then calculates a total friction head loss of 60 kilopascals and selects a pump with a capacity of 0.3 liters per second at a head of 60 kilopascals (6 meters).
The document provides calculations to determine the required capacity and head of a hot water circulation pump (CP-1) for a 300 meter insulated pipe loop. It calculates a heat loss of 9000 Watts and a required pump flow of 0.217 liters per second. Adding a 10% safety factor increases the required flow to 0.3 liters per second. It then calculates a total friction head loss of 60 kilopascals and selects a pump with a capacity of 0.3 liters per second at a head of 60 kilopascals (6 meters).