You are on page 1of 21

Design Simulation Using PVsyst

Sun Paths Diagram

Tawi Tawi
03/17
9
03/17/19
Site Monthly Values

The figure shows the generation of synthetic hourly meteo values based on the PVSyst that applies the
synthetic generation and used the monthly diffuse to re-normalize the hourly output values of diffuse.

Input Data
Protective Device Coordination (PDC)

It is compulsory to properly select and set the power system protective devices to accomplish this goal line.
This proficient by performing a time current evaluation between the protective devices. Coordination is
generally a concession between the mutually desirable but somewhat unreliable goals of maximum
protection and maximun service continuity. With the use of precast circuit breakers it is usually dreadful to
synchronize the system in the instantaneous region due to the overlap of curves unless a zone interlock is
utilized. For this and other details, such as established system design, many combinations of device
situations may be classified as acceptble.

Figure 6-2. Protective Device Coordination of the Final Design

The figure 6-2. Shows the final protective device coordination (PDC) simulation using the software EDSA
Paladin Design base.
Arc Flash Calculation

IEEE 1584
IEEE 1584 takes into interpretation the heat of an arc, and not the secondary properties such as molten
metal spatter and pressure-wave effects. The guides for determining arc flash incident energy levels and
protection boundaries. It contains an empirical calculation method based upon extensive test results using
a Design-of-Experiments (DOE) method, resulting in a 95% confidence level that the arcing fault current will
be higher than calculated. In situations where the empirical method does not apply, the “Lee” method is
recommended, and is described in IEEE 1584.

This method is valid for the following systems with following characteristics;
 Voltage range of 208V – 15kV
 Frequencies of 50hz or 60hz
 Voltage current range of 700A – 106kA
 Grounding of all types and ungrounded
 Gaps between conductor of 13mm-152mm
 Faults involving three phases – in applying the empirical method it is assumed that a phase-to-
ground fault will escalate into a phase-to-phase fault

Formula
Ia =k+0.662(Ibf )+0.0966(V)+(0.000526(G)+0.5588(Ibf )-0.00304(G)(Ibf )

Where:
Ia = Arc Fault Current in kA IEEE 1584 Guide to
K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV
3 phase short circuit fault current
ZF =0if Bolted Fault
3 phase Fault @ Generator 1
1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 1

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 2


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 2

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 3


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 3


Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 4


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 4

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 5


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 5


Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 6


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 6

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA


IEEE 1584 Guide to
K = -0.153 for open air- arcs and -0.097 for enclosed arcs
Ibf = 3-phase bolted fault current in kA performing Arc Flash
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 7


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.
Arc Flash Calculation @ Generator 7

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA


IEEE 1584 Guide to
K = -0.153 for open air- arcs and -0.097 for enclosed arcs
Ibf = 3-phase bolted fault current in kA performing Arc Flash
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 8


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 8

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 9


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.
Arc Flash Calculation @ Generator 9

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 10


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 10

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 11


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 Sbase
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(𝑉𝑏𝑎𝑠𝑒)
I3phase = 1837.1412A
Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 11

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 12


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 12

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 13


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A
Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 13

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 14


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 14

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA


IEEE 1584 Guide to
K = -0.153 for open air- arcs and -0.097 for enclosed arcs
Ibf = 3-phase bolted fault current in kA performing Arc Flash
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 15


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 15

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 16


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 16

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 17


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 17

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 18


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 18

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 19


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 19

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 20


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 20

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV
3 phase Fault @ Generator 21
1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 21

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV

3 phase Fault @ Generator 22


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 22

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA


K = -0.153 for open air- arcs and -0.097 for enclosed arcs IEEE 1584 Guide to
Ibf = 3-phase bolted fault current in kA performing Arc Flash
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV
3 phase Fault @ Generator 23
1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 23

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV
3 phase Fault @ Generator 24
1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25MVA
I3phase = 𝑥
j0.0496 + j0.0496 + j0.0496 √3(13.2𝑘𝑣)
I3phase = 1837.1412A

Since IEEE 1584 Arc Flash Calculation states that bolted fault currents should be determined for each of
equipment likely to require maintenance or inspection while energized. The only parameter that has been
considered is the motors and generator.

Arc Flash Calculation @ Generator 24

Ia = -0.097+0.662(1837.1412A)+0.0966(230)+(0.000526(0.5)+0.5588(1837.1412A)-0.00304(0.5)(1837.1412A)
Ia =2.2621 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV
Arc Flash Calculation @ Primary side of the transformer from 1-24

3 phase Fault @ Generator 24


1 Sbase
I3phase = 𝑥
Z1 + Z2 + Z0 √3(𝑉𝑏𝑎𝑠𝑒)
1 6.25 MVA
I3phase = 𝑥
j0.01583 + j0.01583 + j0.01583 √3(480)
I3phase = 158.2952kA

Arc Flash Calculation @ Generator 1-24

Ia = -0.097+0.662(158.2952A)+0.0966(230)+(0.000526(0.5)+0.5588(158.2952A)-0.00304(0.5)(158.2952A)
Ia = 0.2151 kA

Where Ia = Arc Fault Current in kA IEEE 1584 Guide to


K = -0.153 for open air- arcs and -0.097 for enclosed arcs
performing Arc Flash
Ibf = 3-phase bolted fault current in kA
V = Voltage Calculation. Arc Flash
G = conductor gap in mm. Calculation Formula for
system 0.208kV – 1kV
Arc Flash

According to the arc flash by the help of the software paladin design base. It shows that in every generator
given there must be a Globe Glass which is in level 2, the Insulated tools should be used, the proper suit
should be use as well as for the eye protection and finally it is internment to Non melting FR hair/beard nets
for safety purposes. It has a given 13.8kv and max short circuit of 3.7 Ka.

You might also like