You are on page 1of 80

HCP 1000 SERIES

Microprocessor Based - Fire Alarm Control Panel

INSTALLATION and OPERATION MANUAL

©2014 by Hochiki America Corporation


Printed March 2014
LT-600HOC Rev.7
Table of Contents

1.0 Introduction 1

1.1 About the HCP 1000 ...................................................................................................... 1

2.0 System Components 2

2.1 Chassis .......................................................................................................................... 2


2.2 Circuit Adder Modules .................................................................................................... 3
2.3 Auxiliary Adder Models .................................................................................................. 3
2.4 Enclosures ..................................................................................................................... 4
2.5 Batteries ......................................................................................................................... 5
2.6 Remote Annunciators‘ .................................................................................................... 5
2.7 HCP-1008EDS Fire Alarm Control Panel Kit ................................................................. 6
2.8 HCP 1000 Accessories .................................................................................................. 6
2.9 Maximum Number of Circuit Adder Modules that may be Installed ............................... 7

3.0 Mechanical Installation and Dimensions 8

3.1 HBBX-1024DS Mechanical Installation .......................................................................... 8


3.2 HBBX-1024XT Mechanical Installation .......................................................................... 9
3.3 Main Chassis Installation ............................................................................................... 10
3.4 Main and Expander Chassis Installation ........................................................................ 11

4.0 Module Mounting Locations 12

4.1 HBBX-1024DS and HBBX-1024XT Main Chassis Mounting Locations ......................... 13


4.2 HBBX-1024XT Expansion Chassis Mounting Locations ................................................ 14
4.3 Circuit Adder Mounting Details ...................................................................................... 15

5.0 Module Settings 16

5.1 Main Fire Alarm Module ................................................................................................. 16


5.2 HMCC-1024-6DS, HMCC-1024-12DS/-12XT Main Display Module ............................. 17
5.3 48 Zone Adder Display Module .................................................................................... 18
5.4 HDM-1008 Detection Adder Module .............................................................................. 19
5.5 HSGM-1004 Signal Adder Module ................................................................................. 20
5.6 HRM-1008HRM-1008 Relay Adder Module ................................................................... 21
5.7 HDACT-9100 Digital Communicator Module ................................................................. 22

6.0 Field Wiring 24

6.1 Main Fire Alarm Module Terminal Connections ............................................................. 24


6.2 Detection Module (HDM-1008) Terminal Connections .................................................. 26

i
6.3 Signal Module (HSGM-1004) Terminal Connections ..................................................... 27
6.4 Relay Module (HRM-1008) Terminal Connections ........................................................ 28
6.7 Power Supply Connections ............................................................................................ 31
6.8 Wiring Tables and Information ....................................................................................... 32

7.0 System Checkout 33

7.1 Before Turning the Power On ........................................................................................ 33


7.2 Power-Up Procedure ...................................................................................................... 33
7.3 Troubleshooting ............................................................................................................. 34

8.0 Indicators, Controls, and Operation 35

8.1 Common Indicators ........................................................................................................ 36


8.2 Common Controls .......................................................................................................... 37
8.3 Circuit Status Indicators ................................................................................................. 38
8.4 Circuit (Zone) Disconnect Switches ............................................................................... 40
8.5 Single Stage Operation .................................................................................................. 40
8.6 Two Stage Operation ..................................................................................................... 41
8.7 Circuit Types .................................................................................................................. 42

9.0 System Configuration 45

9.1 Introduction to Configuration .......................................................................................... 45


9.2 Configuration DIP Switch Functions ............................................................................... 46
9.3 Entering Configuration Mode ......................................................................................... 47
9.4 Exiting Configuration Mode ............................................................................................ 48
9.5 Factory Default Configuration ........................................................................................ 48
9.6 Restore to Default/Resize (Class A or B) ....................................................................... 48
9.7 Resize System (Set Circuit Adder Module Number and Type) ...................................... 49
9.8 Configuration Features ................................................................................................... 50
9.9 Configuring Initiating and Indicating Circuits .................................................................. 52
9.10 Configuring Circuit Correlations ..................................................................................... 53
9.11 Display Configuration ..................................................................................................... 55

10.0 Walk Test Operation 56

11.0 Appendix A: HRA-1000 Remote Annunciator Panels 57

11.1 HRA-1000 Series ........................................................................................................... 57

12.0 Appendix B: Device Compatibility List 58

12.1 HCP 1000 Series UL Listed Two-Wire Smoke Detectors .............................................. 58

ii
12.2 HCP 1000 Series UL Listed Compatible Four-Wire Smoke Detectors .......................... 61
12.3 HCP 1000 Series UL Listed Compatible Signaling Devices .......................................... 62

13.0 Appendix C: Specifications 65

13.1 HMCC-1024-6DS Specifications .................................................................................... 65


13.2 HMCC-1024-12DS Specifications .................................................................................. 67
13.3 HCP 1000 Expander Chassis and System Modules ...................................................... 68

14.0 Appendix D: Power Supply and Battery Calculations 70

15.0 Warranty 71

iii
List of Figures

Figure 1 HBBX-1024DS Installation Instructions and Dimensions ............................................... 8


Figure 2 HBBX-1024XT Flush or Surface Enclosure Installation and Dimensions ...................... 9
Figure 3 Main Chassis Installation ............................................................................................... 10
Figure 4 Expander Chassis Installation ........................................................................................ 11
Figure 5 HBBX-1024DS and HBBX-1024XT Main Chassis Mounting Locations ......................... 13
Figure 6 HBBX-1024XT Expansion Chassis Mounting Locations ................................................ 14
Figure 7 Circuit Adder Mounting Details ...................................................................................... 15
Figure 8 Main Fire Alarm Module ................................................................................................. 16
Figure 9 Main Display Module (HMCC-1024-6DS, HMCC-1024-12DS/-12XT) ........................... 17
Figure 10 48 Zone Adder Module .................................................................................................. 18
Figure 11 Detection Adder Module (Model HDM-1008) ................................................................. 19
Figure 12 Signal Adder Module (Model HSGM-1004) ................................................................... 20
Figure 13 Relay Adder Module (Model HRM-1008) ....................................................................... 21
Figure 14 Digital Communicator Module (Model HDACT-9100) .................................................... 22
Figure 15 Polarity Reversal and City Tie Module (Model HPR-300) .............................................. 23
Figure 16 Main Fire Alarm Module Terminal Connections ............................................................. 24
Figure 17 Main Fire Alarm Module Terminal Connections (continued) .......................................... 25
Figure 18 Detection Module (HDM-1008) Terminal Connections .................................................. 26
Figure 19 Signal Module (HSGM-1004) Terminal Connections ..................................................... 27
Figure 20 Relay Module Terminal Connections ............................................................................. 28
Figure 21 HDACT-9100 Terminal Connections ............................................................................. 29
Figure 22 Polarity Reversal and City Tie Module Terminal Connections ....................................... 30
Figure 23 Power Supply Connections ............................................................................................ 31
Figure 24 Indicators and Control Location ..................................................................................... 35
Figure 25 Evacuation Codes .......................................................................................................... 44
Figure 26 Configuration Indicators and Controls ............................................................................ 45

v
List of Tables

Table 1 Main Fire Alarm Module Circuit Details .......................................................................... 16


Table 2 Cable Connectors and Miscellaneous ........................................................................... 22
Table 3 HDACT-9100 List of LEDs and their Functions ............................................................. 22
Table 4 Jumpers ......................................................................................................................... 23
Table 5 Wiring Table for Input Circuits ........................................................................................ 32
Table 6 Wiring Table for Indicating Circuits ................................................................................ 32
Table 7 Initiating (Detection) Circuit Types ................................................................................. 42
Table 8 Indicating (Signal) Circuit Types .................................................................................... 43
Table 9 Configuration DIP Switch Functions .............................................................................. 46
Table 10 Configuration Features .................................................................................................. 50
Table 11 Configuring Initiating and Indicating Circuits .................................................................. 53
Table 12 HMCC-1024-6DS Specifications .................................................................................... 65
Table 13 HMCC-1024-12DS Specifications .................................................................................. 67
Table 14 HCP 1000 Expander Chassis and System Modules ...................................................... 68

vi
Introduction

1.0 Introduction
1.1 About the HCP 1000
Hochiki’s HCP1000 Fire Alarm Control Units provide a large capacity of supervised Class A or
B (Style D or B) initiating circuits and supervised Class A or B (Style Z or Y) indicating circuits.
All circuits are supervised for opens and ground faults, and indicating circuits are supervised
for shorts. Optional modules include additional initiating and indicating circuits, relay, and
polarity reversal and city tie. Flush or surface mountable enclosures can be used for retrofits
and on new installations.

1.1.1 Overall Features:


• Basic unit has eight Class B (Style B) initiating circuits that may be configured as four
Class A (Style D) circuits. These are configurable as Alarm, Verified Alarm, Waterflow
Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, or Trouble-Only circuits.
There are two LEDs per circuit: one for trouble (amber), and one for status (red/amber)
• Basic unit has four power limited Class A/B (Style Z/Y) indicating circuits with individual
trouble indicators. Each circuit can be configured as Audible (Silenceable) or Visual
(Non-Silenceable). Audibles may be configured as Steady, Temporal Code, California
Code, or March Time
• Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, One-
Man Walk Test
• Subsequent Alarm, Supervisory, and Trouble operation
• Two outputs for four-wire resettable smoke power supply (200 mA each max., 300 mA
total max.)
• Auxiliary relay contacts for Common Alarm and Common Supervisory (disconnectable),
and a Common Trouble relay
• RS-485 interface for HRA-1000 Series Remote Multiplex Annunciators
• Optional modules for additional initiating, indicating, and relay circuits, and city tie and
polarity reversal signalling
• Easy configuration via pushbuttons and switches
• Extensive transient protection
• Surface and flush mountable enclosures

1.1.2 Controls and Indicators


Eight pushbuttons, 16 common indicators, provision for up to 24 points (expansion chassis
adds provision for up to another 48 points).

1
System Components

2.0 System Components


2.1 Chassis

Model Description

Main fire alarm chassis with eight Style B / four


Style D initiating circuits, four Style Y or Z
indicating circuits, and a 6 ampere power supply.
HMCC-1024-6DS, For more information see Appendix C:
HMCC-1024-12DS Specifications on page 65. The HMCC-1024-
12DS is the same as the HMCC-1024-6DS except
it has a 12 ampere power supply. These chassis’
are mounted into the HBBX-1024DS.

Larger main fire alarm chassis with eight Style B /


four Style D initiating circuits, four Style Y or Z
indicating circuits, and a 12 ampere power supply.
For more information see Appendix C:
HMCC-1024-12XT Specifications on page 65. The HMCC-1024-
12XT is expandable up to eight adder modules of
any type and comes with a 48 zone adder
module. This chassis is mounted into the HBBX-
1024XT.

2
System Components

2.2 Circuit Adder Modules

Model Description
HDM-1008 Eight detection circuit modules

HSGM-1004 Four signal circuit modules

HRM-1008 Eight relay circuit modules

2.3 Auxiliary Adder Models

Model Description

HPR-300 Polarity Reversal and City Tie Module

HDACT-9100 Digital Alarm Communicator Module

3
System Components

2.4 Enclosures

Model Description

Universal Enclosure includes the backbox and


HBBX-1024DS
door. Color is all black.

Extended Enclosure includes the backbox and


HBBX-1024XTDS
door. Color is all black.

4
System Components

2.5 Batteries

Model Description

W = 5 15/16"
H = 3 3/4"
D = 4"
BA-110

W = 7 1/8"
H = 6 1/2"
D = 3"

BA-117
12-volt batteries
(2 required for 24 10 to 40AH Batteries.
W = 6 1/2" volts).
H = 5"
D =6 7/8"
BA-124

W = 7 5/8"
H = 6 7/8"
D = 6 3/8"
BA-140
Figures Not Drawn to Scale

2.6 Remote Annunciators‘

Model Description

HRA-1000 Series Remote multiplex annunciator panels

5
System Components

2.7 HCP-1008EDS Fire Alarm Control Panel Kit


For all other combinations, components are ordered separately.

Model Description

Expandable 8 Zone Fire Alarm kit comes complete with


eight Class B (or four Class A) initiating and four (Class A or
HCP-1008EDS B) indicating circuits, expandable to 24 circuits, six amp
power supply. Includes the HMCC-1024-6DS Main Chassis
in a HBB-1024DS enclosure.

2.8 HCP 1000 Accessories

Model Description
MP-300 End-of-line Resistor Plate

MP-300R End-of-line Resistor Plate, red

MP-300S End-of-line Resistor Plate, stainless steel finish

6
System Components

2.9 Maximum Number of Circuit Adder Modules that may be


Installed
The maximum number of adder modules that may be physically installed in a system is
outlined in the table below.

Main Chassis Type Number of Adders


HMCC-1024-6DS or HMCC-1024-12DS Two adder modules of any type.

HMCC-1024-12XT includes a 48 zone adder module Eight adder modules of any type.

The maximum number of each adder module type is outlined in the following table.

Module Description Maximum System Total


Eight detection circuit modules (total of 64 initiating
HDM-1008 7 64
circuits in a system).

Four signal circuit modules (total of 24 initiating


HSGM-1004 3 16
circuits in a system).

Eight relay circuit modules (total of 32 relay circuits


HRM-1008 4 32
in a system).

i Notes: Any HCP 1000 System may have a HPR-300 or HDACT-9100 and up to eight (8)
Remote Multiplex Annunciators externally. As good practice, it is recommended
that circuit adder modules be installed in the order of detection modules, followed
by signal modules, followed by relay modules.

All systems can carry a maximum of eight adder modules in the combinations
permitted above.

7
Mechanical Installation and Dimensions

3.0 Mechanical Installation and


Dimensions
Install the enclosure as shown for the HBBX-1024XT in Figure 1.

3.1 HBBX-1024DS Mechanical Installation


The HBBX-1024DS is suitable for flush or surface mounting, since it has a built-in trim ring.

Dimensions of Enclosure (minus built in trim ring) 26”H x 14 1/2”W x 4 1/4”D


Distance between horizontal mounting screws 12”
Distance between vertical mounting screws 23 1/2”
Complete dimensions of enclosure with door 28”H x 17”W x 5 5/8”D

Figure 1 HBBX-1024DS Installation Instructions and Dimensions


HBBX-1024DS BACKBOX AND DOOR
14 1/2”
5 5/8”
12”

17”

23 1/2” 26 ” 26 ”

28 ”

BACKBOX

4 1/4”
BACKBOX FRONT VIEW 1 3/8”

SIDE VIEW
DOOR
1 3/4”

2”
KNOCKOUT LOCATIONS
6”
1 3/4” 2” 2” 1 3/4” Dimensions of backbox (minus built-in trim ring) 26”H x 14 1/2”W x 4 1/4” D
SIDE VIEW Horizontal distance between mounting screws 12”
1 3/4”
9 1/2”
Vertical distance between mounting screws 23 1/2”

TOP VIEW Complete dimensions of enclosure with door 28”H x 17”W x 5 5/8”D

Size of Knockouts 1”

8
Mechanical Installation and Dimensions

3.2 HBBX-1024XT Mechanical Installation

w

w
w
w

.P
w VOU
J OH
)P
MFT

w
"EIFSF USJN SJOH UP
XBMM TVSGBDF BSPVOE
CBDLCPY
w

.P
VOU w
JOH
 )P
MFT

w

'SPOU%PPS )'"9553#
*OTJEF7JFX
5SJN3JOHGPS #BDLCPY
'MVTI.PVOUJOH

Figure 2 HBBX-1024XT Flush or Surface Enclosure Installation and Dimensions

9
Mechanical Installation and Dimensions

3.3 Main Chassis Installation


To install the main chassis

1. Install the main chassis in the HBBX-1024DS backbox as shown in Figure 3 below, using
the supplied hex-nuts.
2. Group the incoming wires through the top of the enclosure to prepare them for wiring the
modules. Do not run the wires in-between the modules since this could cause a short
circuit.
3. Use a wire tie to group wires for easy identification and neatness.
4. Be sure to connect a solid earth ground (from building system ground / to a cold water
pipe) to the chassis earth ground mounting lug, and to connect the earth ground wire
lugs from the main chassis to the ground screw on the backbox.

Figure 3 Main Chassis Installation

10
Mechanical Installation and Dimensions

3.4 Main and Expander Chassis Installation


To install the expander chassis

1. Install the main and expander chassis into the HBBX-1024XT enclosure, as shown in
Figure 4, using the supplied hex-nuts.
2. Group the incoming wires through the top of the enclosure to prepare them for wiring the
modules. Do not run the wires in-between the modules since this could cause a short
circuit.
3. Use a wire tie to group wires for easy identification and neatness.

Figure 4 Expander Chassis Installation

i Note: Be sure to connect a solid earth ground (from building system ground / to a cold
water pipe) to the chassis earth ground mounting lug, and to connect the earth
ground wire lugs from both the main chassis and the expander chassis to the
ground screw on the backbox.

11
Module Mounting Locations

4.0 Module Mounting Locations


The main chassis in a HBBX-1024DS or HBBX-1024XT enclosure comes pre-assembled with
all power supply, main panel, and display components and boards. The expander chassis is
equipped with a pre-assembled display board. The HPR-300 City Tie Module or the HDACT-
9100 Digital Communicator may be added on the left side, as shown in Figure 7 on page 15.
These modules connect directly to the dedicated P2 connection in the upper-left corner of the
main fire alarm module.

! Attention: There needs to be enough display points for each circuit on an adder
module. These display points are assigned during configuration
(See System Configuration on page 45.) in the order in which the adder
modules are electrically installed (the order in which they have their
cables connected to each other). Both the number of points available
for each display type and the number of points required for each circuit
adder module type are described in Module Settings on page 16.

As good practice, it is recommended that circuit adder modules are


installed in the order of detection modules (HDM-1008) followed by
signal modules (HSGM-1004), followed by relay modules (HRM-1008).

To enable communication from the main fire alarm module to all of the
circuit adder modules, it is necessary to remove the continuity jumper
on JW6 (near P5, the circuit adder module connector) on the main fire
alarm module. This jumper plug must be installed on the continuity
jumper on the last installed circuit adder module. To verify the location
of the continuity jumper on a particular circuit adder module
see Module Settings on page 16.

Note: Only the last circuit adder module should have a jumper plug on
its continuity jumper - all others must be left without a jumper plug.

12
Module Mounting Locations

4.1 HBBX-1024DS and HBBX-1024XT Main Chassis Mounting


Locations

HPR-300 city tie


module (see Note
2 below)

#6-32 x
1 1/4” screw

HDACT-9100 Dialer
Module (see Note 2
below)

Other Circuit Adder Module


Other Circuit Adder

#6-32 x 1 1/2” M/F hex spacer

Figure 5 HBBX-1024DS and HBBX-1024XT Main Chassis Mounting Locations

i Notes: Front plate is not shown. Other circuit adder modules may be:

• HDM-1008 Detection Circuit Module


• HSGM-1004 Signal Circuit Module
• HRM-1008 Relay Circuit Module

To Install Circuit adder modules

1. Install circuit adder modules from right to left using the supplied stand-offs ( Figure 7 on
page 15).
2. Plug the first module with its 26-pin ribbon cable into P5 on the main fire alarm module
using the included MD-579 four-wire power cable (as described in Module Settings on
page 16).
3. You can connect a second circuit adder module by plugging its 26 pin cable into the
matching socket on the module to its right, and by installing the supplied MD-579 four-
wire power cable (as described in Module Settings on page 16).

13
Module Mounting Locations

4.2 HBBX-1024XT Expansion Chassis Mounting Locations


The HBBX-1024XT enclosure with a 48 zone adder module and is equipped with two long
extension cables: one for the 26-pin ribbon cable (MD-575) and one for the four-wire power
cable (MD-580). Circuit adder modules are installed from right to left in two tiers (back then
front). These circuit adder modules are cabled in the same way as the main chassis, except
that the first module on the back tier to the right connects (via the MD-575 and MD-580
extension cables) to the second module in the main chassis. The fourth module on the front
tier to the right connects (via MD-575 and MD-580 extension cables) to the third module on the
first tier to the left. In other words, follow a continuous right to left, bottom to top, and back to
front installation order, see Figure 6 below.

Other circuit adder Other circuit adder


module (see Notes modules (see
below) Notes below)

#6-32 X 1 1/4” #6-32 1 1/2” M/F


screw hex spacer

Figure 6 HBBX-1024XT Expansion Chassis Mounting Locations

i Notes: Front plate is not shown. Other circuit adder modules may be:

• HDM-1008 Detection Circuit Module


• HSGM-1004 Signal Circuit Module
• HRM-1008 Relay Circuit Module

14
Module Mounting Locations

4.3 Circuit Adder Mounting Details

Expander Chassis
Place continuity
Provision for jumper on last
HPR-300 or board
Main Chassis HDACT-9100

7
5

4 6
2
3 MD-580
1 MD-575
MD-575
MD-580
MD-579

MD-575 Long Ribbon Cable


MD-579 Short Power Cable
MD-580 Long Power Cable

Figure 7 Circuit Adder Mounting Details

15
Module Settings

5.0 Module Settings


5.1 Main Fire Alarm Module

P1 RS-485 connection FIELD WIRING TERMINALS


for future expansion

Connector for TPR-300 Module or TUDACT-300A


P2
JW1 JW2 JW3
Remove these jumpers
JW4 to program Class B JW5
Connector for circuit adder P5
modules

MAIN FIRE ALARM BOARD


Power connector for
adder modules
JW6
Factory connection to
Connector for display module
Bridge Rectifier
(TMCC-1024)
Connection to P6
Connector for future 24VDC battery
expansion
F1
P8 P7 P10 P9
P3 P4 -BDG+ -B AT+

Figure 8 Main Fire Alarm Module

5.1.1 Jumpers

JW1 Install jumper for Class A (Style D) operation of initiating circuits 3 and 4.
JW2 Install jumper for Class A (Style D) operation of initiating circuits 5 and 6.
JW3 Install jumper for Class A (Style D) operation of initiating circuits 7 and 8.
JW4 Remove jumper if a HPR-300 Module or HDACT-9100 is installed.
JW5 Install jumper for Class A (Style D) operation of initiating circuits 1 and 2.
JW6 Remove continuity jumper if there are any circuit adder modules installed, and
install it on the last circuit adder module.

i Note: The main display module (part of the main chassis) has four dedicated display
points for the four indicating circuits on the main fire alarm module.

The main fire alarm module contains the following circuits, each requiring a certain number of
display points:

Table 1 Main Fire Alarm Module Circuit Details

Chassis Type Initiating Circuits Indicating circuits Display Points Required

HMCC-1024-6DS 8 Style B / 4 Style D 4 Style Y or Z 8/4 (Style B / D)

HMCC-1024-12DS/-12XT 8 Style B / 4 Style D 4 Style Y or Z 8/4 (Style B / D)

16
Module Settings

5.2 HMCC-1024-6DS, HMCC-1024-12DS/-12XT Main Display


Module

P2

TEST/CONFIG COMMON COMMON ZONE


MODE TROUBLE ALARM 1

REMOTE A.C. COMMON ZONE


FAILURE ON SUPERVISORY 2

BATTERY/
CHARGER ZONE
SYSTEM LAMP 3
RESET TROUBLE
TEST
CPU FAULT ZONE
GROUND FAULT 4
FIRE AUXILIARY
DRILL DISCONNECT SIGNAL 1 ZONE
TROUBLE 5

SIGNAL 2 ZONE
ACKNOW- BUZZER TROUBLE 6
LEDGE SILENCE
SIGNAL 3 ZONE
TROUBLE 7
GENERAL SIGNAL
ALARM SILENCE SIGNAL 4 ZONE
TROUBLE 8

1 8 1 4 1 8 1 8 1 8

P1 CONFIG. SIG. ZONE DET. ZONE ZONE ZONE


DISCONNECT DISCONNECT DISCONNECT DISCONNECT

Figure 9 Main Display Module (HMCC-1024-6DS, HMCC-1024-12DS/-12XT)

5.2.1 Connectors

P1 Cable connects to P3 of main fire alarm module.


P2 Connection to P1 of the 48 zone adder module if used.
SW1 to See System Configuration on page 45 and Indicators, Controls, and
SW5 Operation on page 35.

i Note: The main display module comes with a Label Sheet (NP-2854) including both
English and French slide-in labels. This sheet may be run through a laser printer
for labelling purposes before being installed. The first slide-in section comes in
two versions; one for single-stage systems, and one for two-stage systems.

The main display module provides four dedicated display points for the four indicating circuits
on the main fire alarm module. It also provides the following general-purpose display points:

Chassis Type Display Points

HMCC-1024-6DS 24 The main display has dedicated display


points for the eight initiating circuits and
HMCC-1024-12DS/-12XT 24 four indicating circuits that are located on
the main board.

17
Module Settings

5.3 48 Zone Adder Display Module


P2

Zone 25 Zone 33 Zone 41 Zone 49 Zone 57 Zone 65

Zone 26 Zone 34 Zone 42 Zone 50 Zone 58 Zone 66

Zone 27 Zone 35 Zone 43 Zone 51 Zone 59 Zone 67

Zone 28 Zone 36 Zone 44 Zone 52 Zone 60 Zone 68

Zone 29 Zone 37 Zone 45 Zone 53 Zone 61 Zone 69

Zone 30 Zone 38 Zone 46 Zone 54 Zone 62 Zone 70

Zone 31 Zone 39 Zone 47 Zone 55 Zone 63 Zone 71

Zone 32 Zone 40 Zone 48 Zone 56 Zone 64 Zone 72

1 8 1 8 1 8 1 8 1 8 1 8

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
CIRCUIT CIRCUIT CIRCUIT CIRCUIT CIRCUIT CIRCUIT
DISCONNECT DISCONNECT DISCONNECT DISCONNECT DISCONNECT DISCONNECT

P1

Figure 10 48 Zone Adder Module

5.3.1 Connectors

P1 Cable connects to P2 of main display module.


P2 Not used.
SW1 to See System Configuration on page 45 and Indicators, Controls, and
SW6 Operation on page 35.

The adder display module provides 48 display points:

i Note: The adder display module comes with a label sheet (NP-681) with blank slide-in
labels. This sheet may be run through a laser printer for labelling purposes before
being installed.

18
Module Settings

5.4 HDM-1008 Detection Adder Module

JW4 P2 P4

Data cable to P5 of main Power connector to P6 of


FIELD WIRING TERMINALS

JW3
fire alarm module or to main fire alarm module or
previous adder module. to previous adder module.

JW2
Data connector for Power connector for
next adder module. next adder module.

JW1

P1 P3
JW5

Figure 11 Detection Adder Module (Model HDM-1008)

5.4.1 Jumpers

JW1 Install jumper for Class A (Style D) operation of initiating circuits 1 and 2.
JW2 Install jumper for Class A (Style D) operation of initiating circuits 3 and 4.
JW3 Install jumper for Class A (Style D) operation of initiating circuits 5 and 6.
JW4 Install jumper for Class A (Style D) operation of initiating circuits 7 and 8.
JW5 Remove continuity jumper if there are any more adder modules installed.

i Notes: Jumper JW6 on the main fire alarm module must be removed if there are any
adder modules installed.

The HDM-1008 requires eight display points for Class B (Style B) operation, and four for
Class A (Style D) operation.

19
Module Settings

5.5 HSGM-1004 Signal Adder Module

J11 P2 P4

ZONE 4

1 2 3 Power connector to
FIELD WIRING TERMINALS

JW5 Data cable to P5 of main


fire alarm module or to P6 of main fire alarm
ZONE 3
previous adder module module or to previous
adder module
JW4

ZONE 2
Data connector for next Power connector for
JW3 next adder module
adder module
ZONE 1

JW1
P1 P3
JW2

GREEN SIGNAL LEDs

Figure 12 Signal Adder Module (Model HSGM-1004)

5.5.1 Jumpers

JW1 Remove continuity jumper if there are any more adder modules installed.
JW2 Leave jumper on pins 2 and 3 for Zone 1.
JW3 Leave jumper on pins 2 and 3 for Zone 2.
JW4 Leave jumper on pins 2 and 3 for Zone 3.
JW5 Leave jumper on pins 2 and 3 for Zone 4.
JW11 NOT USED

i Notes: Jumper JW6 on the main fire alarm module must be removed if there are any
adder modules installed.

The HSGM-1004 requires 4 display points.

5.5.2 Components
There are four green LEDs on the board, one for each signal zone. A green LED will illuminate
or flash following the signal rate sent to its zone. It will be off when the system is normal and it
will illuminate when a signal zone is activated. The LED does not reflect what is happening on
the signal zone, just that it is receiving data to activate that signal zone.

i Note: Jumpers JW2, JW3, JW4 and JW5 are positioned on pins 2 and 3 (right two pins
with board orientation as shown above) from factory.

20
Module Settings

5.6 HRM-1008HRM-1008 Relay Adder Module

P2 P4

JP4 JP8
Data cable to P5 of main Power connector to

FIELD WIRING TERMINALS


fire alarm module or to P6 of main fire alarm
JP3 previous adder module module or to previous JP7
adder module

JP2 JP6
Data connector for next Power connector for
JP1 adder module next adder module JP5
JW1
P1 P3

Figure 13 Relay Adder Module (Model HRM-1008)

JW1 Remove continuity jumper if there are any more adder modules installed.

• Jumper JW6 on the main fire alarm module must be removed if there are any adder
modules installed.
• The HRM-1008 requires eight display points.

i Note: To have all relays work independently remove all jumpers off of their pins. To tie
all commons together, have all pins in place on their respective jumpers.

21
Module Settings

5.7 HDACT-9100 Digital Communicator Module

CONNECT RIBBON
CABLE FROM P1
TO SIEMENS FIRE
ALARM CONTROL
PANEL

VR1

Figure 14 Digital Communicator Module (Model HDACT-9100)

Table 2 Cable Connectors and Miscellaneous

P1 Ribbon Cable for connecting to Hochiki Fire Alarm Control Panel (FACP).

P2 RS-232C/RS-485 Connection for computer configuration.

U18 Connector for CFG-300 Configuration Tool.

Lamp Test
Press and hold this button to test all the HDACT-9100 LEDs and LCD display.
button

UR1
This potentiometer is for adjustment of the CFG-300 LCD contrast.
Potentiometer

The following table lists all the LEDs located on the HDACT-9100 board and states the
function of each LED.

Table 3 HDACT-9100 List of LEDs and their Functions

Relay Line 1 Located below Line 1 terminal block. When Line 1 relay is energized, this green LED
will illuminate
Relay Line 2 Located below Line 2 terminal block. When Line 2 relay is energized, this green LED will
illuminate.

RS-485 Status LED for communication, will flash when RS-485 communication is active.

Common Steady amber for any troubles on the Fire Alarm panel or HDACT-9100.
Trouble
CPU Fail Steady amber for any on board CPU trouble.

Telephone Telephone status indicator LED; Red when the line is in use, Amber when there is a line
Line 1 trouble.

Telephone Telephone status indicator LED; Red when the line is in use, Amber when there is a line
Line 2 trouble.

22
Module Settings

Table 3 HDACT-9100 List of LEDs and their Functions (Continued)

Power ON Green LED is ON steady when power is supplied to the board.

Table 4 Jumpers

Jumper Function
JW1 Normally open. Place jumper here and power down the HDACT-9100 by disconnecting
P1 or power down the fire alarm panel (AC and Batteries), then power back to revert to
default passcode. After reset, remove the jumper. Leave normally open.

JW2 Normally open to BLOCK remote configuration via modem, PC with a UIMA converter
module or using the LCD and keypad at the HDACT-9100. Place jumper here to ALLOW
any type of configuration. Remove jumper once configuration is complete.

Jumper JW4 on the main fire alarm panel must be removed if a city module is installed.

Please see the HDACT-9100 Installation and Operation Manual (LT-888HOC) for more
information.

Mounting hole for

+ | -
#6-32 screws

CITY
TIE
P1 P2

REVERSAL REVERSAL
POLARITY POLARITY
+ | -
ALARM
Mounting hole for
#6-32 screws
+ | -
SUPV
JW4

Figure 15 Polarity Reversal and City Tie Module (Model HPR-300)

5.7.1 Jumper and connector

P1 Cable to P2 of main fire alarm module.


JW4 Jumper on the main fire alarm module must be removed if a city tie module is
installed.

The alarm transmit signal to the HPR-300 can be programmed to turn off when signal silence
is active. This allows the city tie box to be manually reset. On subsequent alarms the
silenceable signals will resound and the city tie box will be retriggered (see System
Configuration on page 45).
The trouble transmit signal to the HPR-300 can be programmed to delay AC power fail for
zero, 1, 2, 3 hours if this is the only system trouble (see System Configuration on page 45).

The HPR-300 does not require any display points.

23
Field Wiring

6.0 Field Wiring


6.1 Main Fire Alarm Module Terminal Connections
Wire devices to terminals as shown in Figure 16 and Figure 17. For more information see
Wiring Tables and Information on page 32, Appendix B: Device Compatibility List on page 58,
and Appendix C: Specifications on page 65.

RS-485 INTERFACE TO
P1
ANNUNCIATORS AND
OTHER DEVICES
(POWER LIMITED)
+
RS485 (1) 6
- 5
USE TWISTED SHIELDED
1 4
COM (-) PAIR
22 AWG UP TO 2000 FT.
+ NOT 20 AWG UP TO 4000 FT. 2 3
RS485 (2) USED 18 AWG UP TO 8000 FT.
-
END OF LINE RELAY
NO AUXILIARY COMMON LISTED S3403
COM ALARM CONTACTS MODEL A77-716B
ALARM
28 VDC, 1 AMP MANUFACTURED BY
RESISTIVE LOAD MUST BE SYSTEM SENSOR
NC
CONNECTED TO A
NO LISTED POWER
COMMON TROUBLE
LIMITED SOURCE
CONTACTS
TROUBLE COM OF SUPPLY 4-WIRE
28 VDC, 1 AMP
DETECTION
NC RESISTIVE LOAD
DEVICE

NO TO + + +
AUXILIARY COMMON
ALARM CONTACTS INITIATING
SUPV. COM
28 VDC, 1 AMP CIRCUIT - - -
NC RESISTIVE LOAD
+ +
+
4-WIRE-A POWER
- - -
RESETTABLE 4-WIRE SMOKE DETECTOR
+ POWER SUPPLIES.
4-WIRE-B 22 VDC, 200 mA EACH MAX., 300 mA TOTAL
- MAX., 5 mV RIPPLE.
(POWER LIMITED) LEGEND:
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM

! Attention: Do not exceed 5 amps total current for main chassis HMCC-1024-6DS
indicating circuits, and 10 amps for main chassis HMCC-1024-12DS,-12XT.

i Notes: The terminal blocks are "depluggable" for ease of wiring.

All initiating circuits are Compatibility ID "A".

All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.

Figure 16 Main Fire Alarm Module Terminal Connections

24
Field Wiring

IND1+ (Y/Z)

INDICATION IND1+ (Z)


CIRCUIT 1 SUPERVISED INDICATING CIRCUIT #1 STYLE Y
IND1- (Z) WIRING

IND1- (Y/Z)

IND2+ (Y/Z)
STYLE Z
INDICATION IND2+ (Z) WIRING
CIRCUIT 2 SUPERVISED INDICATING CIRCUIT #2
IND2- (Z)

IND2- (Y/Z)
INDICATION CIRCUITS 3 & 4
ARE NOT SHOWN
INI1+
SUPERVISED INITIATING CIRCUIT #1 STYLE B
INI1- (ALARM ZONE) WIRING
STYLE D
INI1
INI2+
SUPERVISED INITIATING CIRCUIT #2 STYLE B
(SUPERVISORY OR WATERFLOW ZONE) WIRING
INI2-

INI3+
STYLE D
STYLE D INI3- WIRING
SUPERVISED INITIATING CIRCUIT #2
INI2 (ALARM ZONE) SEE STYLE D NOTE
INI4+

INI4-
INITIATING CIRCUITS 5 TO 8 STYLE D NOTE: INITIATING CIRCUITS IN A SERIES 1000
ARE NOT SHOWN MUST BE ALL EITHER STYLE B OR D.
IF STYLE D IS SELECTED, THE
AUX. + NUMBER OF CIRCUITS IS CUT IN HALF.
POWER AUXILIARY POWER
SUPPLY FOR ANNUNCIATORS, ETC.
- 24 VDC UNFILTERED
1.7 AMPS MAXIMUM
TRL
RTI-1 REMOTE TROUBLE INDICATOR
TRB

Legend: (See Appendix A for compatible devices.)

Smoke Detector Supervisory or


Waterflow Switch (no)

Heat Detector Bell, horn, or strobe

Pull Station 3.9K 1/2W ELR listed S5434 model


MP-300 manufactured by Mircom

Figure 17 Main Fire Alarm Module Terminal Connections (continued)

i Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.

Initiating circuits are fully supervised and rated for 22 VDC, 3 mA standby, 5 mV
ripple, 50 mA max alarm. They may be configured as required. the alarm
threshold is 21 mA. Maximum loop resistance is 100 ohms; 50 ohms per side.

Indicating circuits are fully supervised and rated for 24 VDC unfiltered 1.7 amp
max. They must be wired as shown in the wiring tables.

To supervise the 24V FWR Aux Power, use end-of-line relay model A77-716B
(manufactured by System Sensor as shown connected in Figure 17.

25
Field Wiring

6.2 Detection Module (HDM-1008) Terminal Connections


Wire devices to terminals as shown in Figure 18 below. For more information see Wiring
Tables and Information on page 32, Appendix B: Device Compatibility List on page 58 for
compatible devices, and Appendix C: Specifications on page 65.

INI1+
SUPERVISED INITIATING CIRCUIT #1 STYLE B
(ALARM ZONE) (POWER LIMITED) WIRING
INI1-
STYLE B/D
INI1
INI2+
SUPERVISED INITIATING CIRCUIT #2 STYLE B
(SUPERVISORY OR WATERFLOW ZONE) WIRING
INI2-
(POWER LIMITED)

INI3+

INI3-
STYLE B/D SUPERVISED INITIATING CIRCUIT #2
INI2 STYLE D
(ALARM ZONE) SEE STYLE D NOTE (POWER LIMITED) WIRING
INI4+

INI4-

INI5+

INI5-
STYLE B/D
INI3
INI6+
INITIATING CIRCUITS STYLE D NOTE: INITIATING CIRCUITS IN A HCP-1000
INI6-
MUST BE ALL EITHER STYLE B OR D.
5 TO 8 IF STYLE D IS SELECTED, THE
INI7+ NUMBER OF CIRCUITS IS CUT IN HALF.

STYLE B/D INI7-


INI4
INI8+
LEGEND: (SEE APPENDIX A FOR COMPATIBLE DEVICES)
INI8- SUPERVISORY OR
SMOKE DETECTOR
WATERFLOW SWITCH (NO)

3.9K 1/2W ELR LISTED S5434


HEAT DETECTOR MODEL MP-300 MANUFACTURED
BY MIRCOM
PULL STATION

Figure 18 Detection Module (HDM-1008) Terminal Connections

i Notes: Initiating circuits in an HCP 1000 Series Fire Alarm Panel must all be either Class
B (Style B) or Class A (Style D). If Class A (Style D) is selected, the number of
circuits is cut in half.

All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.

Initiating circuits are fully supervised and rated for 22 VDC, 3 mA standby, 5 mV
ripple, 50 mA max alarm. They may be configured as required. The alarm
threshold is 21 mA. Maximum loop resistance is 100 ohms, 50 ohms per side.The
terminal blocks are "depluggable" for ease of wiring.

All initiating circuits are Compatibility ID "A".

26
Field Wiring

6.3 Signal Module (HSGM-1004) Terminal Connections


Wire devices to terminals as shown in Figure 19 below. For more information see Wiring
Tables and Information on page 32, Appendix B: Device Compatibility List on page 58 for
compatible devices, and Appendix C: Specifications on page 65.

IND1+ (Y/Z)
INDICATION
CIRCUIT 1 IND1+ (Z)
SUPERVISED INDICATING CIRCUIT #1 STYLE Y
(POWER WIRING
LIMITED) IND1- (Z)

IND1- (Y/Z)

IND2+ (Y/Z)
INDICATION
CIRCUIT 2 IND2+ (Z)
SUPERVISED INDICATING CIRCUIT #2 STYLE Z
(POWER WIRING
LIMITED) IND2- (Z)

IND2- (Y/Z)

IND3+ (Y/Z)
INDICATION
IND3+ (Z)
CIRCUIT 3 STYLE Y
(POWER SUPERVISED INDICATING CIRCUIT #3
IND3- (Z) WIRING
LIMITED)
IND3- (Y/Z)

IND4+ (Y/Z)
INDICATION
CIRCUIT 4 IND4+ (Z)
SUPERVISED INDICATING CIRCUIT #4 STYLE Z
(POWER
LIMITED) IND4- (Z) WIRING

IND4- (Y/Z)

LEGEND: (SEE APPENDIX B FOR COMPATIBLE DEVICES)

BELL, HORN, OR STROBE

3.9K 1/2W ELR LISTED S5434


MODEL MP-300 MANUFACTURED
BY MIRCOM

Figure 19 Signal Module (HSGM-1004) Terminal Connections

i Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.

HSGM-1004 indicating circuits are fully supervised and rated for 24 VDC
unfiltered, 1.7 amp max. They must be wired as shown in Figure 19

The terminal blocks are "depluggable" for ease of wiring.

27
Field Wiring

6.4 Relay Module (HRM-1008) Terminal Connections


Wire devices to terminals as shown in Figure 20 below. For more information see Wiring
Tables and Information on page 32, Appendix B: Device Compatibility List on page 58 for
compatible devices, and Appendix C: Specifications on page 65.

COM AUX RELAY 5 COM


AUX RELAY 1
RLY 5 NC CONTACTS RLY 1 NC CONTACTS
28 VDC, 1 AMP 28 VDC, 1 AMP
RESISTIVE LOAD RESISTIVE LOAD
NO NO

COM COM
AUX RELAY 6 AUX RELAY 2
RLY 6 NC CONTACTS RLY 2 NC CONTACTS
28 VDC, 1 AMP 28 VDC, 1 AMP
NO RESISTIVE LOAD NO RESISTIVE LOAD

COM COM
AUX RELAY 3
AUX RELAY 7
RLY 7 NC RLY 3 NC CONTACTS
CONTACTS
28 VDC, 1 AMP
28 VDC, 1 AMP
RESISTIVE LOAD
NO RESISTIVE LOAD NO

COM COM
AUX RELAY 8 AUX RELAY 4
RLY 8 NC CONTACTS RLY 4 NC CONTACTS
28 VDC, 1 AMP 28 VDC, 1 AMP
NO RESISTIVE LOAD NO RESISTIVE LOAD

Figure 20 Relay Module Terminal Connections

i Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.

All relay circuits must be connected to a listed power limited source of supply.

The terminal blocks are "depluggable" for ease of wiring.

28
Field Wiring

6.5 HDACT-9100 Main Board Terminal Connections

Wire the two telephone line devices to terminals as shown below in Figure 21 below.

The HDACT-9100 terminals are located on the top left hand corner of the board. If using a
cellular or wireless service, use the Line 2 interface connection only.

1 4 TIP
2 3

RING
7 6
8 5 Public switch
Telephone company
RJ31X wiring
TIP

RING

premise telephone
BROWN

GREEN

IF permitted
GREY

RED

Line 2 is Wired as shown for Line 1

T R T R T R T R
RES C.O. RES C.O.
LINE-1 LINE-2

HDACT-9100

Figure 21 HDACT-9100 Terminal Connections

i Note: Most AHJ's do not allow the connection of premises telephones. See HDACT-
9100 Instruction and Operation Manual (LT-888HOC) for further details.

29
Field Wiring

6.6 HPR-300 Polarity Reversal and City Tie Module Terminal


Connections

Wire as shown below in Figure 22 using proper wire gauges. For more information see
Appendix C: Specifications on page 65.

For use in the U.S.A., the installer must add an Atlantic Scientific (Tel. 407-725-8000) Model
#24544 Protective Device, or similar UL-Listed QVRG Secondary Protector, as shown. For
use in Canada, the protective device is still recommended, but the HPR-300 may be
connected directly to polarity reversal or city tie wiring.

Cable Resistance: Less


than or equal to 300 ohms.

HPR-300 TO

Figure 22 Polarity Reversal and City Tie Module Terminal Connections

i • Plug HPR-300 ribbon cable (P1) into connector (P2) of the main fire alarm module.
• Cut jumper (JW1) on the HPR-300 module in order to transmit a trouble condition to
the monitoring station.
• Remove jumper plug from jumper JW4 on the main fire alarm module.
• The polarity reversal interface is power limited and must use type FPL, FPLR, or
FPLP power limited cable.
• For polarity reversal operation, short tie the city tie connection.
• Either the THPR-300's city tie or polarity reversal interface may be used, but not
both.
• The city tie interface is not power limited.
• The terminal blocks are "depluggable" for ease of wiring.

30
Field Wiring

6.7 Power Supply Connections


The power supply is part of the main chassis. The ratings are outlined in the table below.

Model Electrical Input Ratings Power Supply Battery Fuse on Main


Total Current Module

HMCC-1024-6DS 120 VAC, 60 Hz / 240 VAC, 50Hz 6 amps maximum Replace with 20 amp, 1 ¼"
Main Chassis Fast Acting Fuse
HMCC-1024-12DS, - 120 VAC, 60 Hz / 240 VAC, 50Hz 12 amps maximum Replace with 20 amp, 1 ¼"
12XT Main Chassis Fast Acting Fuse

For more information see Appendix C: Specifications on page 65. Wire as shown in Figure 23
using proper wire gauges.

CONNECT GREEN
EARTH GROUND WIRE
TO MAIN MODULE PCB
P8 P7 P10 P9 MOUNTING SCREW.

- BAT +

TO DEDICATED
BLACK BRANCH CIRCUIT
TO 24 VDC
240V, 50Hz

120V, 60Hz

BATTERY RED
L L N G

GREEN

Figure 23 Power Supply Connections

! Attention: To prevent sparking, connect batteries after the system main A.C. power
turns on.
Do not exceed power supply ratings.

31
Field Wiring

6.8 Wiring Tables and Information


Table 5 Wiring Table for Input Circuits

Wire Gauge Maximum Wiring Run to Last Device (ELR)


(AWG) ft m
22 2990 910
20 4760 1450
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200

i Note: Maximum loop resistance should not exceed 100 Ohms.

Main board HSGM-1004 indicating circuits are rated for 1.7 amps each. The indicating circuits
are rated for 1.7 amps each.
Table 6 Wiring Table for Indicating Circuits

TOTAL MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOP


SIGNAL RESISTANCE
18AWG 16AWG 14AWG 12AWG
LOAD
Amperes ft m ft m ft m ft m Ohms
0.06 2350 716 3750 1143 6000 1829 9500 2895 30
0.12 1180 360 1850 567 3000 915 4720 1438 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 950 289 3
0.90 156 47 250 76 400 122 630 192 2
1.20 118 36 185 56 300 91 470 143 1.5
1.50 94 29 150 46 240 73 380 115 1.2
1.70 78 24 125 38 200 61 315 96 1.0

i Note: Maximum voltage drop should not exceed 1.8 volts.

Auxiliary Power Use Table 6 Wiring Table for Indicating Circuits above to see the wiring
Wiring information for the remote annunciator being used.
RS-485 Wiring See the wiring information for the remote annunciator being used.
4-Wire Smoke The maximum allowable current is 0.2 amperes. The maximum allowed
Wiring voltage drop is 1 volt. Refer to Table 6 Wiring Table for Indicating
Circuits.

32
System Checkout

7.0 System Checkout


7.1 Before Turning the Power On
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering
the system from the main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in
properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe).
8. Make sure to close the front cover plate before powering the system from main AC
supply.

7.2 Power-Up Procedure


1. After completing the above procedures, power-up the panel. The green AC ON LED and
the Common Trouble LED should illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the Battery/
Charger Trouble LED should illuminate, the trouble buzzer should sound intermittently,
and the Common Trouble LED should flash.
3. Connect the batteries while observing correct polarity: the red wire is positive (+) and the
black wire is negative (-). All indicators should extinguish except for the AC ON LED.
4. Configure the fire alarm control panel as described in System Configuration on page 45.

33
System Checkout

7.3 Troubleshooting

Message Description

Circuit Trouble Normally when a circuit trouble occurs, its designated trouble indicator will be
illuminated, as well as the Common Trouble indicator and Trouble buzzer. To
correct the fault, check for open wiring on that particular circuit loop or see if the
circuit disconnect switch is in the ON or CLOSED position. Note: disconnecting a
circuit will cause a system trouble (off-normal position).

Remote Fail The panel will display a Remote Fail for any failure reported by or failure to
communicate with a remote annunciator or other remote device.

Ground Fault The HCP 1000 panel has a Common Ground Fault Detector. To correct the fault,
check for any external wiring touching the chassis or other earth ground connection.

Battery/Charger Check for the presence of batteries and their conditions. Low voltage (below 20.4V)
Trouble will cause a battery trouble. If battery/charger trouble condition persists, replace the
batteries as soon as possible. If the problem still persists, main board may need to
be replaced.
Configuration If the Test/Config Mode LED is illuminated steadily, the system is in either
Mode configuration mode or walk test mode. If the LED is flashing, the configuration has
been corrupted and has been reset to defaults; you must therefore review / re-enter
your configuration.

Common If only a common trouble is indicated on the main panel and none of the above
Trouble confirming trouble indicators are on, then check the following for possible fault:
i) Check for any missing interconnection wiring.
ii) Check for any missing modules that are part of the configuration.
iii) Check jumper positions. Particularly ensure that the continuity jumper is installed
only on the last circuit adder module in the system.
iv) Check for improperly secured cabling.

CPU Fault This LED will only illuminate for a short period upon power up when system is
normal.It will illuminate steadily when there has been a major CPU failure. This
indicates the system is not functioning and main board must be replaced.

34
Indicators, Controls, and Operation

8.0 Indicators, Controls, and Operation


Refer to Figure 24 below for LED indicators, control buttons, and switches locations.

TEST/CONFIG COMMON COMMON ZONE


MODE TROUBLE ALARM 1

REMOTE A.C. COMMON ZONE


FAILURE ON SUPERVISORY 2

BATTERY/
CHARGER ZONE
SYSTEM LAMP 3
RESET TROUBLE
TEST
CPU FAULT ZONE
GROUND FAULT 4
FIRE AUXILIARY
DRILL DISCONNECT SIGNAL 1 ZONE
TROUBLE 5

SIGNAL 2 ZONE
ACKNOW- BUZZER TROUBLE 6
LEDGE SILENCE
SIGNAL 3 ZONE
TROUBLE 7
GENERAL SIGNAL
ALARM SILENCE SIGNAL 4 ZONE
TROUBLE 8

1 8 1 4 1 8 1 8 1 8

CONFIG. SIG. ZONE DET. ZONE ZONE ZONE


DISCONNECT DISCONNECT DISCONNECT DISCONNECT

Figure 24 Indicators and Control Location

The main display panel on the fire alarm control unit consists of:

A) • 8 Common Buttons • 28 circuit / circuit indicators


• Configuration DIP switch • 28 circuit disconnect DIP switches

An adder display module is part of the HMCC-1024-12XT chassis, which adds 48
B)
circuit and circuit indicators and disconnect switches.
LED indicators may be amber, red, or green, and may illuminate continuously (steady),
C)
or at one of two flash fates
• Fast flash: 120 flashes per minute, 50% duty cycle, for
supervisory alarms
• Trouble flash: 20 flashes per minute, 50% duty cycle

Paper labels for buttons and indicators

Each display is supplied with laser printable labels. These labels slide into the plastic label
templates on the panel.The label paper for the main display includes English and French
versions (Hochiki #NP-3038). Two slide-in labels are also included for single-stage and two-
stage operation. For the adder display, the labels are blank (Hochiki #NP-681).

35
Indicators, Controls, and Operation

8.1 Common Indicators


8.1.1 Buzzer
The buzzer is activated by any of the following:

• Fire alarm: steady


• Supervisory alarm: fast flash rate
• Trouble: trouble flash rate
If the buzzer turns on in response to a non-latching trouble or supervisory, it will turn off if the
condition causing it to sound goes away and there is no other reason for it to be on.

8.1.2 AC ON LED
The green AC ON LED illuminates steadily while the main AC power is within acceptable
levels. It turns off when the level falls below the power-fail threshold and the panel switches to
standby (battery) power.

8.1.3 Common Alarm LED


The red Common Alarm LED illuminates steadily whenever the panel is in alarm as a result of
an alarm on any initiating circuit or activation of the manual red General Alarm Button (if the
panel is set for two stage operation). Since all alarms are latched until the panel is reset, the
LED will remain on until then.

8.1.4 Common Supervisory LED


The amber Common Supervisory LED illuminates steadily when there is a supervisory alarm
in the panel resulting from any latching or non-latching supervisory circuit. The LED turns off if
all non-latching supervisory circuits are restored and there are no active latching supervisory
circuits. Latching supervisory alarms remain active until the panel is reset.

8.1.5 Common Trouble LED


The Common Trouble LED flashes amber at the trouble flash rate when the panel detects any
trouble condition. It turns off when all non-latching troubles are cleared.

8.1.6 Remote Failure LED


The Remote Failure LED flashes amber at the trouble flash rate if the panel detects:

• Trouble at the city tie, or


• Trouble at the UDACT, or
• Communication trouble with a remote annunciator, or
• Local trouble with a remote annunciator.
It turns off once these conditions return to normal.

8.1.7 Fire Drill LED


The amber Fire Drill LED illuminates steadily while the fire drill is active.

8.1.8 Acknowledge LED


If the panel is configured as two stage, the Acknowledge LED flashes amber at the fast flash
rate while the Auto General Alarm timer is timing out. It illuminates steadily when the timer is
cancelled by activating the Acknowledge or Signal Silence buttons. If the Auto General Alarm
timer times-out and puts the panel into General Alarm, the LED turns off.

36
Indicators, Controls, and Operation

8.1.9 General Alarm LED


In two stage operation only, the red General Alarm LED illuminates steadily after the General
Alarm button is pressed, a general alarm initiating circuit is activated, or the Auto General
Alarm timer times out. Once the General Alarm LED turns on, it will stay active until the panel
is reset.

8.1.10 Configuration / Test Mode LED


The amber Configuration / Test Mode LED illuminates steadily to indicate that the panel is in
either walk test or configuration mode. If the panel is left in either mode for over an hour with
no operator activity, this LED will flash at the trouble flash rate.

8.1.11 Auxiliary Disconnect LED


The amber Auxiliary Disconnect LED flashes at the trouble flash rate after the Auxiliary
Disconnect button is pressed. It turns off after the button is pressed a second time. When on, it
indicates that common alarm and common supervisory relays are not activated, and
programmable relays (if disconnect is enabled) are not activated. The city tie module, if
installed, is also inactive.

8.1.12 Signal Silence LED


The amber Signal Silence LED flashes at the trouble flash rate when indication circuits are
silenced either by the Signal Silence button or by the Auto Signal Silence timer. It turns off
when the signals are re-sounded by a subsequent alarm.

8.1.13 Battery/Charger Trouble LED


The Battery/Charger Trouble LED flashes amber at the trouble flash rate when the battery is
either low (below 20.4 VDC) or disconnected.

8.1.14 Ground Fault LED


The Ground Fault LED flashes amber at the trouble flash rate when the Ground Fault Detector
detects a ground fault on any field wiring. It turns off when the ground fault is cleared.

8.1.15 CPU Fault LED


The CPU Fault LED Indicator illuminates steadily to indicate a microprocessor failure on the
main board.

8.2 Common Controls


8.2.1 System Reset Button (White)
The System Reset button resets the fire alarm control panel and all circuits:

•Resets all latching trouble conditions •Resets all initiating circuits


•Resets four-wire smoke supply •Turns off all indicating circuits
•Turns off Signal Silence, Acknowledge •Turns off Fire Drill
& General Alarm LEDs
•Stops and resets all timers •Processes inputs as new events
•Reset cannot be activated until the Signal
•Aux Disconnect is not affected
Silence Inhibit timer has expired

37
Indicators, Controls, and Operation

8.2.2 Signal Silence Button (Blue)


Pressing the Signal Silence button after the panel is in alarm turns on the Signal Silence LED
and deactivates any silenceable indicating circuits. Non-Silenceable circuits are unaffected.
Signals will re-sound upon any subsequent Alarm. This button does not function during any
configured Signal Silence Inhibit timer period. It also does not function if indicating circuits are
active as the result of a Fire Drill. In a two stage system, if the Auto General Alarm timer has
timed out, the Signal Silence button also performs the same function as the Acknowledge
button.

8.2.3 Fire Drill Button (Orange)


The Fire Drill button activates all programmed and non-disconnected indicating circuits, but
does not transmit any Alarms via the city tie or common alarm relay. The Fire Drill button may
be programmed to operate specific indicating circuits. The Fire Drill is cancelled by pressing
the button again (toggle switch), or if the panel goes into a real Alarm.

8.2.4 Acknowledge Button (Yellow)


If the Panel is not configured for two stage operation, this button does nothing. If the panel is
configured for two stage operation, pressing the Acknowledge button while the Auto General
Alarm timer is timing (there is an Alarm in the panel, but it is still in the first stage) cancels the
timer and turns the Acknowledge LED on steady amber.

8.2.5 General Alarm Button (Red)


If the panel is not configured for two stage operation, this button does nothing. If the panel is
configured for two stage operation, pressing the General Alarm button immediately sends the
panel into second stage General Alarm. It will also re-activate the signals if they have been
silenced during General Alarm. The General Alarm condition remains active until the panel is
reset.

8.2.6 Auxiliary Disconnect Button (Orange)


Pressing the Auxiliary Disconnect button activates the Auxiliary Disconnect function. Pressing
the button again deactivates the function.

8.2.7 Lamp Test Button (Orange)


Pressing the Lamp Test button causes all front panel indicators to illuminate and sounds the
buzzer steadily. If Lamp Test is active for more than ten seconds, the Common Trouble LED is
activates.

8.2.8 Buzzer Silence Button (Blue)


Activation of the Buzzer Silence button while the buzzer is sounding silences the buzzer. The
buzzer will resound if there is a subsequent event. Pressing the button when the buzzer is not
sounding has no effect.

8.3 Circuit Status Indicators


There is one pair of circuit Status LEDs for each initiating, indicating, and relay circuit. The first
four indicating circuits on the main fire alarm module are part of the common indicators. All
other circuits (including the first eight initiating circuits on the main fire alarm module) are
arranged in columns of eight indicators numbered from one to eight. For each circuit, the
upper circuit Status LED may be red or amber, and will either be steadily illuminated or
flashing at either the fast flash or trouble flash rates, depending on the operation. The amber
Circuit Trouble LED flashes at the trouble flash rate when active. The Status LED is used on
initiating circuits only.

38
Indicators, Controls, and Operation

After the first eight initiating circuits (corresponding to the first column of circuit LED's) the
circuit LEDs are configured in the same order as any adder modules. If there are insufficient
display adders for the number of circuits on the panel, the last circuits will not be displayed. If
there are too many displays for the number of circuits on the panel, the unassigned ones will
be unused.

8.3.1 Alarm Circuit Indicators


The operation of alarm circuit indicators applies to initiating circuits configured as verified
alarm, non-verified alarm, water-flow alarm, sprinkler alarm, or general alarm circuits.

• The Circuit Trouble LED flashes at the trouble flash rate to indicate circuit trouble
(open circuit or Style D / Class A trouble) or a disconnected circuit. It always turns off
when the circuit is in alarm.
• The Circuit Status LED illuminates steady red when the circuit is in alarm. On verified
alarm circuits, sprinkler alarm, and water-flow alarm circuits, the circuit Status LED will
illuminate at the fast flash rate during the pre-alarm condition. This LED will also flash at
the fast flash rate while an active circuit is being un-disconnected.

8.3.2 Supervisory Circuit Indicators


The operation of supervisory circuit indicators applies to initiating circuits configured as
latching or non-latching supervisory circuits.

• The Circuit Trouble LED flashes at the trouble flash rate to indicate circuit trouble (open
circuit or Class A (Style D) trouble) or a disconnected circuit. It always turns off when the
circuit is in alarm.
• The Circuit Status LED turns on steady amber when the corresponding circuit is in
alarm. This LED will also flash at the fast flash rate while an active circuit is being
reconnected.

8.3.3 Monitor Circuit Indicators


The operation of monitor circuit indicators applies to initiating circuits configured as monitor
circuits.

• The Circuit Trouble LED flashes at the trouble flash rate to indicate circuit trouble (open
circuit or Class A (Style D) trouble) or a disconnected circuit. It always turns off when the
circuit is in alarm.
• The Circuit Status LED turns on steady amber when the corresponding circuit is in
alarm. This LED will also flash at the fast flash rate while an active circuit is being
reconnected.

8.3.4 Trouble-Only Circuit Indicators


The operation of trouble-only circuit indicators applies to initiating circuits configured as
trouble-only circuits. The Circuit Trouble LED flashes at the trouble flash rate to indicate circuit
trouble (open circuit or Class A (Style D) trouble) or if the circuit is disconnected. The Circuit
Status LED also flashes amber at the trouble flash rate to indicate a short-circuit trouble.

8.3.5 Signal Circuit Indicators


The operation of signal circuit indicators applies to indicating circuits of any type. The Circuit
Trouble LED flashes amber at the trouble flash rate to indicate short-circuit or open circuit
trouble, or a disconnected circuit.

39
Indicators, Controls, and Operation
8.3.6 Relay Circuit Indicators
Relay circuit trouble indicators flash amber at the trouble flash rate while the corresponding
circuit is disconnected.

8.4 Circuit (Zone) Disconnect Switches


Circuit (zone) disconnect switches are provided for all initiating, indicating, and relay circuits
on the fire alarm control panel. For the first four indicating circuits on the main fire alarm
module, the disconnect switches consist of either a bank of DIP switches. The DIP switches
numbered one to eight correspond to the circuits indicated in the indicator column from top to
bottom

Changing a circuit disconnect switch to the ON position bypasses the associated circuit, turns
on its trouble indicator, and activates common trouble. While a circuit is disconnected, all
changes in status (alarms and troubles) on that circuit are ignored. The panel does not
activate disconnected indicating circuits.

Disconnecting an active latching initiating circuit such as water-flow alarm, sprinkler alarm,
general alarm, and latching supervisory does not affect its status until the panel is reset.
Disconnecting active non-latching initiating circuits including non-latching supervisory and
trouble-only causes them to behave as if conditions returned to normal. Disconnecting an
active indicating circuit immediately deactivates the circuit.

When an initiating circuit disconnect switch is returned to its normal state, the panel checks the
state of the circuit. If the circuit is active, the Status LED flashes for ten seconds at the fast
flash rate without processing the input. If the circuit is not re-disconnected by then, it will be
processed as a new input.

Disconnect switches are also used during Configuration Mode (see page 45) and Walk Test
Mode (see page 56) as described in those sections.

8.5 Single Stage Operation


In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: non-verified alarm, verified alarm, sprinkler alarm, water-flow alarm, and
general alarm circuits. Any of these alarm inputs occurring when the panel is not already in
alarm cause the following:

• The buzzer sounds steadily


• If fire drill is active, it is cancelled
• The Common Alarm LED turns on
• The Common Alarm relay activates if Aux disconnect is not active
• The Auto Signal Silence timer, if configured, starts
• The Signal Silence Inhibit timer, if configured, starts
• All non-disconnected indicating circuits programmed to the input circuits are activated
provided that Aux disconnect is not active
• Non-disconnected strobes associated with the input are activated
• Non-disconnected signals associated with the input are activated at the evacuation rate
Subsequent alarms when the panel is already in alarm cause the following:

• The alert buzzer sounds steadily


• If Signals have been silenced, they are resounded, the Signal Silence LED turns off, and
the Auto Signal Silence timer, if configured, is restarted
• Any additional non-disconnected strobes associated with the input are activated
continuously
• Any additional non-disconnected signals associated with the new input are activated at
the evacuation rate

40
Indicators, Controls, and Operation

8.6 Two Stage Operation


In a two stage system, alarm inputs are either first stage (alert) inputs or second stage
(general alarm) inputs. First stage inputs include inputs from the following types of circuits:
non-verified alarm, verified alarm, sprinkler alarm, and water-flow alarm. Second stage inputs
include alarms on the general alarm circuits, activation of the General Alarm button, or
expiration of the Auto General Alarm timer. Any of these alarm inputs occurring when the
panel is not already in alarm cause the following:
• The buzzer sounds steadily
• If fire drill is active, it is cancelled
• The Common Alarm LED turns on
• The Common Alarm relay activates if Aux disconnect is not active
• The Auto Signal Silence timer, if configured, starts
• The Signal Silence Inhibit timer, if configured, starts
• All Non-disconnected indicating programmed to the input are activated provided that
Aux disconnect is not active
If the alarm is a second stage alarm,
• All non-disconnected strobe circuits are activated continuously
• All non-disconnected signal circuits are activated at the evacuation rate
• The General Alarm LED turns on.
If the alarm is a first stage alarm,
• Non-disconnected strobe circuits programmed to that circuit are activated continuously
• Non-disconnected signal circuits programmed to that circuit are activated with the alert
code ( for more information see Indicating (Signal) Circuit Types on page 43)
• The Auto General Alarm timer, if configured, starts
• The Acknowledge LED starts flashing.
Subsequent First Stage alarms when the panel is already in alarm, cause the following:
• The buzzer sounds steadily
• If signals have been silenced as a result of the silence button or the Auto signal silence
timer, signals are resounded as they were before signal silence, the Signal Silence LED
turns off, and the Auto Signal Silence timer, if configured, is restarted
• If the panel is not already in General Alarm, additional non-disconnected signals
programmed to the new input are activated with the Alert Code ( for more information
see Indicating (Signal) Circuit Types on page 43).
• If the panel is not already in General Alarm and if the Acknowledge LED is on steady
indicating that the Auto General Alarm timer has been Acknowledged the timer is
restarted and the Acknowledge LED is extinguished.
A second stage alarm (general alarm) when the panel is already in alarm causes the following:
• The buzzer sounds steadily
• All non-disconnected signals are activated at the evacuation rate
• If the Signal Silence LED is on, it turns off and the Auto Signal Silence timer, if
configured, is restarted
• The Acknowledge LED if on, turns off
• Alarm inputs are latching: they remain active until system reset.

i Note: If the system is configured for correlations, any second stage / general alarm
condition activates all indicating circuits whether they are correlated or not.

41
Indicators, Controls, and Operation

8.7 Circuit Types


The term circuits refers to an actual electrical interface, either initiating (detection) or
indicating (signal). The term zone is a logical concept for a fire alarm protected area, and will
consist of at least one circuit. Often the terms zone and circuit are used interchangeably, but in
this manual the term circuit is used.

8.7.1 Initiating (Detection) Circuit Types


Table 7 Initiating (Detection) Circuit Types

Circuit Type Description


Non-Verified This is a "normal" type of alarm which may have pull stations, smoke detectors, or heat
Alarm detectors attached. Any activation of these devices will immediately result in an alarm
condition in the fire alarm control panel. An alarm condition causes the associated
circuit Status LED and the Common Alarm LED to illuminate red.

Verified Alarm These alarms are verified by a reset and timing procedure, and may have pull stations,
smoke detectors, or heat detectors attached. Any activation of pull stations or heat
detectors will result in an alarm condition in the fire alarm control panel within four
seconds. Smoke detectors will be verified for a real alarm within 60 seconds
depending upon the startup time of the smoke detectors being used. If four seconds is
too long a response time for pull stations, then they should be wired separately on a
non-verified alarm circuit. An alarm condition causes the associated circuit Status LED
and the Common Alarm LED to illuminate red. Smoke detectors that incorporate a
built-in alarm verification feature must not be connected to a “Verified Alarm” circuit.
For such detectors, use a separately wired non-verified alarm circuit.
Water-Flow An alarm for water-flow sensors. These alarms are identical to normal non-verified
Alarm alarms except that any indicating circuits programmed to these circuits (all are by
default) are non-silenceable. Also, if water-flow retard operation is enabled, then these
circuits are sampled every one second; if ten samples are active within any 15 second
interval, the water-flow alarm is confirmed and processed. An alarm condition causes
the associated circuit Status LED and the Common Alarm LED to illuminate red. Note:
Do not use the retard operation with any external retarding device; maximum
retard may not exceed 120 seconds.

Sprinkler Alarm An alarm for sprinkler flow sensors. These alarms are identical to normal non-verified
alarms unless the water-flow retard operation is enabled. If water-flow retard operation
is enabled, then these circuits are sampled every one second; if ten samples are
active within any 15 second interval, the sprinkler alarm is confirmed and processed.
An alarm condition causes the associated circuit Status LED and the Common Alarm
LED to illuminate red.
Note: Do not use the retard operation with any external retarding device;
maximum retard may not exceed 120 seconds.

General Alarm These alarms provide remote general alarm such as for remote key switches. In a two
stage system, these inputs perform exactly the same function as the front panel or
remote annunciator general alarm button. In a single stage system, these inputs act
the same as non-verified alarms, but if correlations are enabled, general alarm
initiating circuits are correlated to all indicating circuits.
Non-Latching These alarms are for supervisory devices. An activation on these circuits will cause the
Supervisory Circuit Status LED and the Common Supervisory LED to illuminate amber. The buzzer
will sound continuously. If the circuit activation is removed, the supervisory condition
will clear (so long as there are no other supervisory conditions in the system) and the
circuit Status LED will extinguish.

42
Indicators, Controls, and Operation

Table 7 Initiating (Detection) Circuit Types (Continued)

Circuit Type Description


Latching These alarms are for supervisory devices. An activation on these circuits will cause the
Supervisory Circuit Status LED and the Common Supervisory LED to illuminate amber. The buzzer
will sound continuously. If the circuit activation is removed, the Supervisory condition
will not clear.

Monitor This is a supervised general purpose non-latching input used mainly for correlating to
a relay circuit. No other system condition occurs as a result of its activation (short-
circuit), although it is supervised for trouble (open-circuit).

Trouble-Only This circuit is used for monitoring a trouble condition from an external device. Both
open and short circuits generate a non-latching trouble condition.

8.7.2 Indicating (Signal) Circuit Types


Table 8 Indicating (Signal) Circuit Types

Circuit Type Description


Silenceable Signal For audible devices such as bells and piezo mini-horns that may be silenced
either manually or automatically. While sounding, these follow the pattern
appropriate for the condition: the configured evacuation code (default is temporal
code) during single-stage alarm, or two stage general alarm, or the alert code
during a two stage system's alert (first) stage.

Non-Silenceable For audible devices such as bells and piezo mini-horns that may not be silenced
Signal either manually or automatically. While sounding, these follow the pattern
appropriate for the condition: the configured evacuation code (default is temporal
code) during single-stage alarm, or two-stage general alarm, or the alert code
during a two stage system's alert (first) stage.

Strobe For visual devices such as strobes that use no code patterns (they are
continuous).

43
Indicators, Controls, and Operation

8.7.3 Evacuation Codes


Single stage codes

Continuous On 100% of the time


Temporal Code 3 of 0.5 second on, 0.5 second off then, 1.5 second pause
March Code 0.5 second on, 0.5 second off
California Code 5 seconds on, 10 seconds off

Two-stage codes

Alert Code 0.5 second on, 2.75 seconds off


General Alarm Evacuation code as selected from above.

CONTINOUS

0.5s 1.5s TEMPORAL CODE


0.5s

0.5s MARCH CODE


0.5s

5s 10s CALIFORNIA CODE

0.5s ALERT CODE


2.5s

Figure 25 Evacuation Codes

44
System Configuration

9.0 System Configuration


9.1 Introduction to Configuration
Configuration of the HCP 1000 Fire Alarm Control Panel is performed by a combination of
configuration DIP switch settings and button presses. Circuit-related operations are correlated
to their respective disconnect switches.

You can access the configuration DIP switches from the main display module after removing
the protective lexan cover. The DIP switches are labelled as CONFIG. 1 to 8. The circuit (zone)
disconnect switches are re-defined as circuit (zone) select during configuration. Make sure
you have set the circuit disconnect switches to the desired settings before exiting configuration
mode. Normal system operation is suspended while configuration mode is active. You enter
configuration mode whenever any of the configuration DIP switches are set as per the
functions listed in the Table 9 on the following page, and you exit configuration mode by
turning all the DIP switches OFF (put switches in the bottom or OFF positions), then pressing
the System Reset button.

i Note: While in configuration mode the fire alarm control panel is not operating.

9.1.1 Three buttons and LED indicators are used in configuration mode:

Acknowledge This becomes a "Select Setting" button and the LED indicator may
(yellow button) show the current status of a function.
General Alarm This becomes a "Confirmation" button for some functions, used
(red button) together with the Yellow Button.
Buzzer Silence
This button performs its normal function of silencing the buzzer.
(blue button)
California Code All other buttons are non-functional during configuration mode.
Additionally, the Green Power “ON” LED will be “OFF” during
configuration mode. Common trouble LED will flash to test. Config
LED (amber) will be on.

The figure to the left shows the positions of


YELLOW BUTTON
& YELLOW LED
the configuration DIP switch and the yellow
and red buttons. Each has a matching LED
indicator of the same color. Note that the
ACKNOW-
LEDGE
BUZZER labels Acknowledge and General Alarm
SILENCE
will only be shown in an HCP 1000
configured as a two-stage system.
GENERAL SIGNAL
ALARM SILENCE

Configuration functions are selected by the


configuration DIP switches as follows in
1 8 Table 3 on the next page. Note that a
RED BUTTON
& RED LED
switch position of "0" is "OFF" (bottom
CONFIG. position) and "1" is "ON" (top position).

Figure 26 Configuration Indicators and Controls

45
System Configuration

9.2 Configuration DIP Switch Functions


Table 9 Configuration DIP Switch Functions

DIP Switch Function Button Description


Position (1-8) Number Operations

0000 0000 00 None Normal Operation (not in configuration mode)

Features
0000 0001 01 Yellow Select Style D/B (Class A/B) Initiating Circuits

0000 0010 02 Yellow Manual Signal Silence Enable

0000 0011 03 Yellow Fire Drill Enable


0000 0100 04 Yellow Two Stage Operation

0000 0101 05 Yellow Common Alarm Relay Operation

0000 0110 06 Yellow Output Circuit Correlations Enabled


Water Flow Alarm and Sprinkler Alarm Retard
0000 0111 07 Yellow
Operation

0000 1000 08 Yellow Reserved for Future Use

0000 1001 09 Yellow Aux Disconnect disconnects Correlated Relays

0000 1010 0A Yellow Signal Silence Inhibit timer

0000 1011 0B Yellow Auto Signal Silence timer

0000 1100 0C Yellow Auto General Alarm timer

000011 01 0D Yellow Evacuation Code Selection

0000 1110 0E Yellow Number of Remote Annunciators

0000 1111 0F Yellow Alarm Transmit Silence Option


0001 0000 10 Yellow AC Power Fail Delay Time

0001 0001 11 Yellow Common Supervisory Relay Action

0001 0010 12 Yellow Signal Circuit Isolator Option


Initiating Circuits/ Detection Zones

0010 0000 20 Yellow Normal (Non-Verified) Alarm

0010 0001 21 Yellow Verified Alarm

0010 0010 22 Yellow Sprinkler Alarm


0010 0011 23 Yellow Water Flow Alarm

0010 0100 24 Yellow Non-Latching Supervisory

0010 0101 25 Yellow Latching Supervisory

0010 0110 26 Yellow General Alarm

0010 0111 27 Yellow Monitor

46
System Configuration

Table 9 Configuration DIP Switch Functions (Continued)

DIP Switch Function Button Description


Position (1-8) Number Operations
0010 1000 28 Yellow Trouble Only

Indicating Circuits/Signal Zones

0011 0000 30 Yellow Silenceable


0011 0001 31 Yellow Non-Silenceable

0011 0010 32 Yellow Silenceable Strobes

0011 0011 33 Yellow Non-Silenceable Strobes


Relays

0011 1000 38 None Show Relay Circuits

Resize System

0100 0000 40 Yellow and Red Set Circuit Adder Module Number and Type

Correlations

0100 0001 41 Yellow Correlation by Input Circuit

0100 0010 42 Yellow Correlation by Output Circuit

Default

0111 1111 7F Yellow and Red Restore to Default Configuration


Walk Test

1000 0000 80 None Walk Test

9.3 Entering Configuration Mode


The system enters configuration mode whenever any of the configuration DIP switches 2 to 8
(switch 1 is used to enter walk test mode) are set to a "1" or the ON position (top position). The
Test / Config Mode and Common Trouble LEDs will turn on and the buzzer will sound. You can
silence the buzzer at this point.

i Note: The fire alarm control panel is not operating as a fire alarm system while it is in
configuration mode.

If there is no activity (no buttons pressed or switches changed) for one hour, the system will
return to normal operation, but will remain in a trouble condition.

As you change the configuration DIP switches to select different functions, wait for a few
seconds for the appropriate LEDs to change as the system recognizes the change(s). Note

47
System Configuration

that configuration changes take effect immediately as they are made, there is no "undo"
function.

i Note: Write down the configuration changes that you make and store them with the
panel, so that you can refer to them later.

9.4 Exiting Configuration Mode


To exit configuration mode after all desired changes are made, all configuration DIP switches
must be returned to a "0" or OFF position (bottom position). Wait about five seconds before
pressing the System Reset button. The system should now be back in normal operation.

9.5 Factory Default Configuration


The system as shipped from the factory is configured with no adder modules, and with set
defaults as outlined below:

• All initiating circuits are Style B (Class B) non-verified alarms (any alarm on any initiating
circuit activates all indicating circuits)
• Indicating circuits are all common alarm and set as silenceable, temporal code. If shorts
exist on any indicating circuits, then they will not activate on alarms.
• Manual signal silence is enabled
• Fire drill is enabled
• Two stage is disabled (the system will operate single stage)
• If a two stage system is enabled, the common alarm relay operates on both stages
• All indicating and relay correlations are set to common alarm activation
• Water-flow retard operation is disabled
• Aux disconnect will disconnect correlated relays
• The Signal Silence Inhibit timer, Auto Signal Silence timer, and the Auto General Alarm
timer are disabled
• The systems assumes there are no remote annunciators
• Relay adder module(s) activate only on common alarm
• The system assumes that there are no adder modules

9.6 Restore to Default/Resize (Class A or B)


Restore the system to the default configuration whenever you would like to restore the factory
default configuration, and whenever circuit adder modules (detection, signal, or relay) are
added, removed, or re-arranged. Restoring the system to the default configuration is
performed slightly differently depending on whether the system is intended to operate with
Class B (Style B) or Class A (Style D) initiating circuits (detection zones).

i Note: Remember to set the main fire alarm board and detection adder module jumpers
for the appropriate Class (Style) (see Module Settings on page 16.), and that the
Class (Style) setting is global - for all initiating circuits.

48
System Configuration

9.6.1 Class B (Style B) Restore Defaults


1. Set the Config DIP switch to 0111 1111 (restore defaults). Wait five seconds.
2. Press the yellow and red buttons together for five seconds. Wait five seconds.
3. Set the Config DIP switch to 0000 0001 (select Class/Style). Wait five seconds.
4. Press the yellow button until yellow LED turns off.

5. Set the Config DIP switch to 0100 0000 (resize system1). Wait five seconds.
6. Press the yellow and red buttons together for five seconds. Wait ten seconds.

9.6.2 Class A (Style D) Restore Defaults


1. Set the Config DIP switch to 0111 1111 (restore defaults). Wait five seconds.
2. Press the yellow and red buttons together for five seconds. Wait five seconds.
3. Set the Config DIP switch to 0000 0001 (select Style/Class). Wait five seconds.
4. Press the yellow button until yellow LED turns on.

5. Set the Config DIP switch to 0100 0000 (resize system1). Wait five seconds.
6. Press the yellow and red buttons together for five seconds. Wait 10 seconds.
The system is now ready for further configuration, or configuration mode may be exited if the
default settings are acceptable.

9.7 Resize System (Set Circuit Adder Module Number and Type)
You may resize the system without performing a full “restore to defaults” if the only change you
made to the system was adding or removing an adder display module or a circuit module.
Otherwise, perform the “resize system” procedure as a part of a full “restore to defaults”,
failure to do so may cause errors while assigning the circuit-specific configuration.

To resize a system after circuit adder modules were added after existing modules,

1. Set Config DIP switch to 0100 0000 (resize system1). Wait five seconds.
2. Press the yellow and red buttons together for five seconds. Wait ten seconds.
The system is now ready for further configuration, or configuration mode may be exited if the
default settings for the added modules are acceptable.

i Note: The yellow LED indicates how many adder modules (plus the main board) are
found, not how many the system is configured to accept. If the number of adder
modules found is different from the number the system is configured for, the
system will go into a trouble condition.

1. During the resize (set circuit adder module number and type) part of the operation, the yellow LED flashes to
indicate how many adder display modules (in addition to the main display module) and circuit adder modules
(including the main board) are found. The yellow LED indicates the number of adder display modules
followed by the number of circuit adder modules. If no adder modules are found, the LED flashes once; if one
adder module is found it flashes twice, and so on. For example, if the system has one adder display module
and two circuit adder modules, the yellow LED will flash two times (once for the main display module and
once for the adder display module), pause, flash three times (once for the main board and once for each of the
adder modules), then pause again. This sequence is then repeated.

49
System Configuration

9.8 Configuration Features


There are two types of features: those that can be turned on and off, and those with multiple
settings. For on and off features, press the yellow button to toggle the settings on or off. The
yellow LED is illuminated for ON, and not illuminated for OFF. For multiple setting features, the
yellow LED flashes a number of times to indicate the setting, then pauses. Use the yellow
button to change the selected setting. Be sure to pause for about three seconds after changing
the configuration DIP switches or pressing the yellow button to see the results.

Table 10 Configuration Features

DIP Switch
Features Description
Position (1-8)
0000 0001 Style D/B (Class A/B) An illuminated yellow LED indicates that all initiating circuits
Initiating Circuits (detection zones) are Class A (Style D). An LED that is off
(default) indicates that they are all Class B (Style B). This
feature can be checked at any time, but must only be
changed as described in Restore to Default/Resize (Class A
or B) on page 48.

0000 0010 Manual Signal Silence An illuminated yellow LED (default) indicates that manual
Enable silence is enabled.

0000 0011 Fire Drill Enable An illuminated yellow LED (default) indicates that fire drill is
enabled.

0000 0100 Two Stage Operation An illuminated yellow LED indicates that the system is set for
Enabled two stage operation. If the LED is off (default), the panel is
configured for single stage operation.

0000 0101 Common Alarm Relay An illuminated yellow LED indicates that if the system is set
Operation for two stage operation, the common alarm relay will only
operate during the general alarm stage. If the LED is off
(default), the common alarm relay will operate during both
stages.

0000 0110 Output Circuit An illuminated yellow LED indicates that the output circuits
Correlations Enabled (indicating circuits and indicating) operate according to any
set correlations (see Configuring Circuit Correlations on
page 53). If the yellow LED is off (default), all output circuits
are common alarm; all outputs turn on for any alarm input.

0000 0111 Waterflow and An illuminated yellow LED indicates that waterflow retard is
Sprinkler Retard enabled. If the LED is off (default), it indicates that retard is
Operation disabled.

0000 1001 Aux Disc and An illuminated yellow LED (default) indicates that correlated
Programmable Relays relays are disconnected by auxiliary disconnect.
0001 0001 Common Supervisory An illuminated yellow LED indicates that the common
Relay Action supervisory relay will follow the common alarm status. If the
yellow LED is off (default), the common supervisory relay will
follow the common supervisory status. Use this feature to
provide an extra common alarm relay if a common
supervisory relay is not needed.

50
System Configuration

Table 10 Configuration Features (Continued)

DIP Switch
Features Description
Position (1-8)
0001 0010 Signal Circuit Isolator An illuminated yellow LED indicates that if a short circuit
Option exists on any indicating circuit and an alarm condition
follows, then those indicating circuits will be activated
anyway. If the yellow LED is off (default), then under the
same conditions, the indicating circuits will not be activated
to prevent wasting power. This feature is needed when signal
isolator devices are employed so that indicating circuits will
be activated even under shorted conditions.

0011 1000 Show Relay Circuits All display points assigned to relay circuits will be lit.

0000 1010 Signal Silence Inhibit Yellow LED does not flash = Disabled (default)
Timer
Yellow LED flashes 1 time = 1 minute (ULC required)
Yellow LED flashes 2 times = 2 minutes
Yellow LED flashes 3 times = 3 minutes

0000 1011 Auto Signal Silence


Yellow LED does not flash = Disabled (default)
timer
Yellow LED flashes 1 time = 5 minute
(This timer cannot be
set shorter than either Yellow LED flashes 2 times = 10 minutes
the Auto General
Yellow LED flashes 3 times = 15 minutes
Alarm or Signal
Silence Inhibit timers, if Yellow LED flashes 4 times = 20 minutes
those timers are
Yellow LED flashes 5 times = 30 minutes
enabled)
0000 1100 Auto General Alarm Yellow LED does not flash = Disabled (default)
Timer
Yellow LED flashes 1 time = 5 minute
(Leave disabled unless
Yellow LED flashes 2 times = 10 minutes
the system is
configured for Two Yellow LED flashes 3 times = 15 minutes
Stage operation)
Yellow LED flashes 4 times = 20 minutes
Yellow LED flashes 5 times = 30 minutes

0000 1101 Audible Indicating Yellow LED flashes 1 time = Continuous


Circuit Evacuation
Yellow LED flashes 2 times = March Time
Code
Yellow LED flashes 3 times = Temporal Code (default) (UL &
ULC required)
Yellow LED flashes 4 times = California Code

0000 1110 Number of Remote The yellow LED flashes 0 to 8 times to indicate the number of
Annunciators remote annunciators expected by the system. (default 0
flashes)

0000 1111 HPR-300/UDACT An illuminated yellow LED indicates that the alarm transmit
alarm Transmit Silence signal from the HPR-300 or UDACT will be silenceable with
Option the activation of the signal silence button. If the yellow LED is
off (default), it indicates that the alarm transmit signal from
the HPR-300 or UDACT will not be silenceable.

51
System Configuration

Table 10 Configuration Features (Continued)

DIP Switch
Features Description
Position (1-8)
0001 0000 AC Power Fail Delay The AC Power Fail trouble signal from the HPR-300 or the
Time UDACT can be delayed when the only trouble on the fire
alarm panel is AC power fail.
Yellow LED flashes 0 times = No Delay (default)
Yellow LED flashes 1 time = 1 Hour
Yellow LED flashes 2 times = 2 Hours
Yellow LED flashes 3 times = 3 Hours

9.9 Configuring Initiating and Indicating Circuits


Initiating circuits (detection zones) and indicating circuits (signal zones) are configured by
using the configuration DIP switches to select the desired circuit type function, along with the
circuit trouble LEDs and disconnect DIP switches.

To configure initiating and indicating circuits


1. Select a circuit type by raising the specified DIP switch(es) (see the table below). The
yellow trouble LED for each circuit currently configured as that type will illuminate.
2. To configure circuits to be of that selected circuit type, turn on all of the desired circuit
disconnect DIP switches (up position) and press the yellow button for about one second.
After a short pause, the initiating circuit yellow trouble LEDs will be updated to show the
new configuration.
3. Lower all DIP switches to the OFF position and press the System Reset button.

i Notes: Any subsequent selection of a particular circuit as a different circuit type will
supercede the previous selection. Also note that the physical circuit type must be
appropriate for the selected circuit type. For example, only indicating circuits can
be configured as silenceable strobes.

Be sure to reset circuit disconnect switches to OFF (down position) before


attempting to configure any other circuits.

52
System Configuration

Table 11 Configuring Initiating and Indicating Circuits

Config DIP Switch Initiating Circuit (Detection Config DIP Switch Indicating Circuit (Signal
Position (1-8) Zone) Type Position (1-8) Zone) Type
0010 0000 Normal (Non-Verified Alarm) 0011 0000 Silenceable Audible Signal

0010 0001 Verified Alarm 0011 0001 Non-Silenceable Audible Signal

0010 0010 Sprinkler Alarm 0011 0010 Silenceable Strobe

0010 0100 Non-Latching Supervisory

0010 0110 General Alarm

0010 1000 Trouble Only


0010 0101 Latching Supervisory

0010 0111 Monitor

For example, if you wanted Class B operation in a system with eight initiating circuits and four
indicating circuits (main board only), the first six initiating circuits as normal non-verified alarms,
the last two as latching supervisory, and the last indicating circuit as a non-silenceable strobe,
you would use the following sequence:

1. Follow Restore to Default/Resize (Class A or B) on page 48.


2. Set Config DIP switch to 0010 0000. All eight initiating yellow trouble LEDs should
illuminate.
3. Set Config DIP switch to 0010 0101. All eight initiating yellow trouble LEDs should go out.
4. Set the disconnect switches to ON for initiating circuits 7 and 8 only.
5. Press the yellow button for one second. After a pause the yellow trouble LEDs for
initiating circuits 7 and 8 should illuminate.
6. Turn off all disconnect switches.
7. Set Config DIP switch to 0011 0000. All four indicating yellow trouble LEDs should
illuminate.
8. Set Config DIP switch to 0011 0011. All four indicating yellow trouble LEDs should go out.
9. Set the disconnect switch to ON for indicating circuit four only.
10. Press the yellow button for one second. After a pause the yellow trouble LED for initiating
circuit four should illuminate.
11. Turn off all disconnect switches.
12. Exit configuration mode.

9.10 Configuring Circuit Correlations


As a working definition for correlations, circuits can be defined as:

• input circuits = initiating circuits (detection zones)


• output circuits = indicating circuits (signal zones), and relay circuits
With the factory default configuration, all outputs are configured to activate with any inputs
configured as alarms. If output circuit correlations are enabled (see Configuration Features on
page 50), outputs must be configured to one or more inputs to activate at all. This configuration
is referred to as a correlation. There are two configuration options: correlated individual outputs

53
System Configuration

to one or more inputs, or correlated individual inputs to one or more outputs. Output circuits
may be correlated to as many input circuits as desired, and vice-versa.

9.10.1 Correlation by Input Circuit


1. Raise the Config DIP switches 2 and 8. Pause for about three seconds.
2. Turn on (up position) only one input circuit's (initiating circuit / detection zone) disconnect
switch. If you turn on more than one input circuit disconnect switch at one time, the
selected input circuit's yellow trouble LED and the yellow trouble LEDs of any output
circuits (indicating circuit / signal zone, or relay circuit) that are already correlated to that
input will illuminate, and the function will not operate.
If you require only a correlations check, turn off the switch, then repeat step 2 for the next input
circuit that you want to check.

If you would like to set new correlations for the selected input circuit,

3. Turn on (up position) the disconnect switch for desired output circuits.
4. Press the yellow button for one second. After a pause the yellow trouble LEDs for the
newly correlated output circuits will illuminate.
5. Lower all DIP switches to the OFF position and press the System Reset button.

9.10.2 Correlation by Output Circuit


1. Raise the Config DIP switches 2 and 7. Pause for about three seconds.
2. urn on (up position) only one output circuit's (indicating circuit / signal zone or relay
circuit) disconnect switch. If you turn on more than one input circuit disconnect switch at
one time, the selected input circuit's yellow trouble LED and the yellow trouble LEDs of
any output circuits (indicating circuit / signal zone, or relay circuit) that are already
correlated to that input will illuminate, and the function will not operate.
If you require only a correlations check, turn off the switch, then repeat step 2 for next output
circuit that you want to check.

If you would like to set new correlations for the selected output circuit,

3. Turn on (up position) the disconnect switch for desired output circuits.
4. Press the yellow button for one second. After a pause the yellow trouble LEDs for the
newly correlated input circuits will illuminate.
5. Lower all DIP switches to the OFF position and press the System Reset button.
At present, only the following types of circuit correlations are possible:

• Alarm circuits (Verified or Non-Verified, Sprinkler or Water-Flow) to indicating circuits or


relays.
• General Alarm circuits to indicating (they are automatically correlated to all indicating
circuits).
• Supervisory circuits (Latching or not) to relays.
• Monitor circuits to relays.
• Trouble-Only circuits to relays.
• See notes on next page.

54
System Configuration

i Notes: The feature called “Output Circuit Correlations Enabled” must be ON for
indicating circuit correlations to operate (see Configuration Features on page 50),
otherwise all indicating circuits will be common alarm. This means that they will all
activate with any input circuits configured as alarms. Relay circuits are always
enabled for correlations.

If the system is configured as two stage, any second stage / general alarm
(caused by the Auto General Alarm timer, the General Alarm button on the front
panel or remote annunciator, or by a General Alarm initiating circuit) condition
activates all indicating circuits whether or not they are correlated.

9.11 Display Configuration


The main and adder display modules on the front panel are automatically updated to display
all circuits found whenever the function “Resize - Adder Module Number and Type
Configuration” is performed. The main display module has dedicated trouble LEDs for the four
indicating circuits on the main fire alarm module. The eight initiating circuits (four in Class A
mode) also on the main fire alarm module are annunciated on the first column of display points
(from top to bottom). Any adder module circuits are displayed after the base system input
circuits in the same order as the adder modules have been installed (that is from right to left).
For example, if there are two eight-circuit initiating circuit adder modules and one four-circuit
indicating circuit adder module, the main display will annunciate 24 initiating circuits followed
by four indicating circuits. If the fire alarm control panel is configured for Class A (Style D)
initiating circuits, then the number of initiating circuits is cut in half, so that in the example
above, there will only be a total of 12 initiating circuits annunciated, followed by the four adder
indicating circuits. Refer to Figure 24 on page 35 to see how the first 24 circuits are mapped
to display points.

Any configured HRA-1000 Series Remote Annunciators automatically match the main fire
alarm control panel displays, except that there will be no annunciation of Common Alarm,
Common Supervisory, Battery/Charger Trouble, Ground Fault and Four-Signal trouble
indicators.

55
Walk Test Operation

10.0 Walk Test Operation


A walk test allows you to verify the initiating circuit wiring in a system. The walk test is a
special configuration mode function (function 80 on the configuration DIP switches). Circuits to
be tested are identified using the circuit disconnect switches. Activation of any initiating circuit
that has been selected for the walk test will cause the audible indicating circuits (not strobes)
to activate briefly for a number of short bursts corresponding to the selected circuit number. If
the first selected circuit is activated, the indication circuits will sound for one burst. If the
second selected circuit is activated, the indication circuits will sound for two bursts, and so on.
This means that if, for example, circuits 1, 6, 23, and 32 were selected for the walk test, they
would sound with 1, 2, 3, and 4 bursts respectively. The maximum number of circuits that may
be set at any one time for a walk test is 15. The burst interval is half a second on half a second
off. After the sounding pattern has been sent on the indicating circuits, the initiating circuit is
reset and tested again. If it is still active (in alarm) the pattern will be re-sent. Trouble on any
initiating circuit selected for the walk test causes the indicating circuits to be activated
continuously for 5 seconds.

Alarm verification and water-flow alarm retard operations are disabled on circuits being walk
tested. All circuits not selected for the walk test continue to function normally. If a circuit was
disconnected before walk test mode was entered and is not selected for the walk test, it
remains disconnected while the walk test is active. The walk test operation is disabled if the
fire alarm control panel is in alarm or goes into alarm while walk test mode is active.

i Notes: If a UDACT is used with the system, all walk test events will be reported to the
monitoring agency. Instruct the monitoring agency to ignore reported events
during the walk test.

If there is no activity for one hour, the system will return to normal operation, but
will remain in a trouble condition until the DIP switches are reset and the panel is
reset.

56
Appendix A: HRA-1000 Remote Annunciator Panels

11.0 Appendix A: HRA-1000 Remote


Annunciator Panels
11.1 HRA-1000 Series
The HRA-1000 Series of remote annunciators are units with electrical modules and
enclosures matching the configurations of the HCP 1000 Series Fire Alarm Control Panels.
For detailed information see Hochiki Documents HRA-1000 Manual LT-617HOC, HRAM-208
Manual LT-648HOC, HRAM-216 Manual LT-658HOC and HMGD-32 Manual LT-847HOC.

11.1.1 Models
• HRAM-1032TZDS Main Annunciator Chassis with common indicators and controls, and
32-circuit capacity (TZ Version has 32 Trouble LEDs)
• HRAX-1048TZDS Adder Annunciator Chassis with 48 circuit capacity
• HRAM-1016TZDS Non-Expandable Annunciator Chassis with common indicators and
controls, and 16-circuit capacity (TZ Version has 16 Trouble LEDs)
• HRAM-208 Non-Expandable Annunciator Chassis with limited common indicators and
controls, and eight-circuit capacity
• HRAM-216 Non-Expandable Annunciator Chassis with limited common indicators and
controls, and 16-circuit capacity
• HMGD-32 Main Graphic Annunciator Chassis with common indicators and controls, and
32-circuit capacity
• HAGD-048 Adder Graphic Annunciator Chassis with 48-circuit capacity

11.1.2 Enclosures
• HBB-1001 with capacity for one annunciator chassis
• HBB-1002 with capacity for two annunciator chassis
• HBB-1003 with capacity for three annunciator chassis
• HBB-1008 with capacity for eight annunciator chassis
• HBB-1012 with capacity for twelve annunciator chassis

i • Finish: Painted, textured, off-white (standard) (for other paint available colors
and finishes, please contact factory)
• Material:18 G.A. cold roll steel (CRS)

57
Appendix B: Device Compatibility List

12.0 Appendix B: Device Compatibility List


12.1 HCP 1000 Series UL Listed Two-Wire Smoke Detectors

i Notes: Whether mixing different models of compatible smoke detectors or using the
same model on the same circuit, total standby current of all detectors must not
exceed 3 mA.

The below listed smoke detectors are compatible with initiating circuits having
Compatibility Identifier "A".

Smoke Detector Make Model / Base Compatibility Identifier Rated Standby Maximum # of
Head / Base Current devices per circuit
Mircom
MIR-525U FDT-1 0.10 mA 30
MIR-525TU FDT-1 0.10 mA 30
Apollo

55000-225 / 45681-251, -255, -256, -258 225 / 251, 255, 256, 258 0.045 mA 30
55000-325 / 45681-251, -255, -256, -258 325 / 251, 255, 256, 258 0.045 mA 30
Detection Systems Inc.

DS250 B - N/A 0.10 mA 30


DS250TH B - N/A 0.10 mA 30
DS282 B - N/A 0.10 mA 30
DS282TH B - N/A 0.10 mA 30
Edwards

C2M-PD/CM2M-PD

EC-103-3/CSBU

Hochiki
DCD-135/NS6-220 HD-3/HB-72 0.035mA 30
DCD-135/NS4-220 HD-3/HB-3 0.035mA 30
DCD-135/HSC-220R HD-3/HB-3 0.035mA 30
DCD-190/NS6-220 HD-3/HB-3 0.035mA 30
DCD-190/NS4-220 HD-3/HB-3 0.035mA 30
DCD-190/HSC-220R HD-3/HB-3 0.035mA 30
SIJ-24/NS6-220 HD-3/HB-72 0.040mA 30
SIJ-24/NS4-220 HD-3/HB-3 0.040mA 30
SIJ-24/HSC-220R HD-3/HB-3 0.040mA 30
SLR-24/NS6-220 HD-3/HB-72 0.045mA 30

58
Appendix B: Device Compatibility List

Smoke Detector Make Model / Base Compatibility Identifier Rated Standby Maximum # of
Head / Base Current devices per circuit
Hochiki continued
SLR-24/NS4-220 HD-3/HB-3 0.045mA 30
SLR-24/HSC-220R HD-3/HB-3 0.045mA 30
SLR-24H/NS6-220 HD-3/HB-3 0.045mA 30
SLR-24H/NS4-220 HD-3/HB-3 0.045mA 30
SLR-24H/HSC-220R HD-3/HB-72 0.045mA 30
SLR-835/NS6-220 HD-3/HB-3 0.045mA 30
SLR-835/NS4-220 HD-3/HB-3 0.045mA 30
SLR-835/HSC-220R HD-3/HB-72 0.045mA 30
SLR-835B-2 HD-6 55µa @ 24VDC 30
Napco

FW-2 HD-6 55µA @ 24VDC 30


Sentrol - ESL
429C S10A - N/A 0.10 mA 30
429CT S10A - N/A 0.10 mA 30
429CST S11A - N/A 0.10 mA 30
429CRT S11A - N/A 0.10 mA 30
711U / 701E, 701U, 702E, 702U S10A - S00 0.10 mA 30
712U / 701E, 701U, 702E, 702U S10A - S00 0.10 mA 30
713-5U / 701E, 701U, 702E, 702U S10A - S00 0.10 mA 30
713-6U / 701E, 701U, 702E, 702U S10A - S00 0.10 mA 30
721U / 702E, 702U S10A - S00 0.10 mA 30
732U / 702E, 702U, 702RE, 702RU S11A - S00 0.10 mA 30
721UT / 702E, 702U S10A - S00 0.10 mA 30
722U / 702E, 702U S10A - S00 0.10 mA 30
731U / 702E, 702U, 702RE, 702RU S11A - S00 0.10 mA 30
721UT / 702E, 702U S10A - S00 0.10 mA 30
721UT / 702E, 702U S10A - S00 0.10 mA 30
System Sensor

4451HT / B401 A-A 0.12 mA 25


5451 / B401B A-A 0.12 mA 25
5451 / B401 A-A 0.12 mA 25

59
Appendix B: Device Compatibility List

Smoke Detector Make Model / Base Compatibility Identifier Rated Standby Maximum # of
Head / Base Current devices per circuit
System Sensor continued

2451 / B401B A-A 0.12 mA 25


2451 / B406B A-A 0.12 mA 25
2451 / DH400 A - N/A 0.12 mA 25
2451TH / B406B A-A 0.12 mA 25
2451 / B401 A-A 0.12 mA 25
2451TH / B401 A-A 0.12 mA 25
4451HT / B401B A-A 0.12 mA 25
4451HT / B406B A-A 0.12 mA 25
1100 A - N/A 0.12 mA 25
1151 / B110LP A-A 0.12 mA 25
1151 / B116LP A-A 0.12 mA 25
1400 A - N/A 0.10 mA 25
1451 / B401 A-A 0.12 mA 25
1451 / B401B A-A 0.12 mA 25
1451 / B406B A-A 0.12 mA 25
1451DH / DH400 A-A 0.12 mA 25
2100 A - N/A 0.12 mA 25
2100T A - N/A 0.12 mA 25
2151/ B110LP A-A 0.12 mA 25
5451 / B406B A-A 0.12 mA 25
2151 / B116LP A-A 0.12 mA 25
2400 A - N/A 0.12 mA 25
2400TH A - N/A 0.12 mA 25
2400AT A - N/A 0.12 mA 25
2400AIT A - N/A 0.12 mA 25
2451TH / B401B A-A 0.12 mA 25
2WTA-B A - N/A 0.1 mA 1
2WTR-B A - N/A 0.1 mA 1
2W-B, 2WT-B A - N/A 0.1 mA 30

60
Appendix B: Device Compatibility List

12.2 HCP 1000 Series UL Listed Compatible Four-Wire Smoke


Detectors

Smoke Detector Make Model / Base Maximum # of


devices per circuit

Mircom

MIR-545U 30

MIR-545TU 30

Sentrol-ESL

541C N/A

541CXT N/A

709-MV-21 N/A

709-24V-21 N/A

741U WITH 702U or 702E Base N/A

449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE, 449CSRT, N/A


449CSRH, 449CSST, 449CSSTE, 449CTE, 449CSLT

System Sensor

1424 25

6424 30
6424A 30

A77-716B

DH400ACDCI 8

DH400ACDCP 8

DH400ACDCIHT 8

61
Appendix B: Device Compatibility List

12.3 HCP 1000 Series UL Listed Compatible Signaling Devices

System Sensor - SpectrAlert Wheelock continued Wheelock continued


P2415 AS-2430C-FW MT-24-LS-VFR-ULC

P2415W AS-2475C-FW MT-24-WS-VFR-ULC

P241575 AS-24100C-FW AMT-12/24-R-ULC


P241575W AH-24-R AMT-24-LS-VFR-ULC

P2475 AH-24-WP-R MB-G6-24-R

P2475W NS-2415W-FR MB-G10-24-R

P24110 NS-241575W-FR SM-12/24-R

P24110W NS-2430W-FR DSM-12/24-R

S2415 NS-2475W-FR
S2415W NS-24110W-FR

S241575 NS4-2415W-FR

S241575W NS4-241575W-FR
S2475 NS4-2430W-FR

S2475W NS4-2475W-FR

S24110 NS4-24110W-FR

S24110W RS-2415W-FR

H12/24 RSS-241575W-FR

H12/24W RSS-2415W-FR

MDL RSS-241575W-FR

MDLW RSS-2430W-FR

Wheelock RSS-2475W-FR

AS-2415W-24-FR RSS-24110W-FR

AS-241575W-FR RSS-2415C-FW

AS-2430W-FR RSS-2430C-FW

AS-2475W-FR RSS-2475C-FW

AS-24110W-FR RSS-24100C-FW

AS-2415C-FW MT-12/24-ULC

62
Appendix B: Device Compatibility List

12.4 HCP 1000 Series ULC Listed Compatible Hardwire Smoke


Detectors

i Note: Whether mixing different models of compatible smoke detectors or using the
same model on the same circuit, the total standby current of all detectors must
not exceed 3 mA.

Make & Model/Base Maximum # of Make & Model/Base Maximum # of


Devices Devices
Mircom Fenwal continued

MIR-525 30 PSD-7131/70-201000-003 -

MIR-525T 30 PSD-7131/70-201000-005 -

MIR-1400A 30 PSD-7130/70-201000-001 -

MIR-2400A 25 PSD-7130/70-201000-002 -

Apollo PSD-7130/70-201000-003 -

55000-325 30 PSD-7130/70-201000-005 -

55000-325 / 45681-251, -255, 30 PSD-7128/70-201000-001 -


-256, -258

Cerebrus Pyrotronics PSD-7126/70-201000-002 -


D1-2 - PSD-7126/70-201000-003 -

D1-3/DB-3S 30 PSD-7126/70-201000-005 -

Edwards PSD-7129/70-201000-000 -

6249C - PSD-7125/70-201000-001 -

6250C - PSD-7126/70-201000-002 -

6264C - PSD-7125/70-201000-003 -
6266C - PSD-7125/70-201000-005 -

6269C - CPD-7021/70-201000-001 -

6270C - CPD-7021/70-201000-002 -

6269C-003 - CPD-7021/70-201000-003 -

6270C-003 - CPD-7021/70-201000-005 -

Hochiki

DCD-135/NS6-220 30

Fenwal DCD-135/NS4-220 30

PSD-7131/70-201000-001 - DCD-135/HSC-220R 30

PSD-7131/70-201000-002 - DCD-190/NS6-220 30

63
Appendix B: Device Compatibility List

Make & Model/Base Maximum # of Make & Model/Base Maximum # of


Devices Devices

Hochiki continued System Sensor

DCD-190/NS4-220 30 1400-A 30
DCD-190/HSC-220R 30 2400-A 25

SIJ-24/NS6-220 30 1451-A/B401B 25

SIJ-24/NS4-220 30 1451-A/B406B 25

SIJ-24/HSC-220R 30 2451-A/B401B 25

SLR-24/NS6-220 30 2451-A/B406B 25

SLR-24/NS4-220 30 1451DH/DH400A 30
SLR-24/HSC-220R 30 2451-A/DH400A 25

SLR-24H/NS6-220 30 1151A 30

SLR-24H/NS4-220 30 2151A 30

SLR-24H/HSC-220R 30 C2W-BA/C2WT-BA 30

SLR-835/NS6-220 30 C2WTR-B 1

SLR-835/NS4-220 30 C2WTA-BA 1

SLR-835/HSC-220R 30

SLR-835B-2 30

Mirtone

73471 -

73494 -

73575 -
73495/73486 -

73495/73487 -

73595/73486 -

73595/73497 -
73594/73400 -

73405/73400 -

73594/73401 -
73405/73401 -

NAPCO

FW-2 30

Simplex

2098-9110 -

64
Appendix C: Specifications

13.0 Appendix C: Specifications


13.1 HMCC-1024-6DS Specifications
Table 12 HMCC-1024-6DS Specifications

HMCC-1024-6DS Chassis
General Micro-controller based design, fully configurable from front panel, full walk test
function. Up to two circuit adder modules may be added. Displays and
disconnect switches for up to 24 circuits. Optional HPR-300 City Tie Module.

Initiating Circuits Eight supervised Style B (Class B) or 4 Style D (Class A) initiating circuits; fully
configurable. Terminals are labelled INI. initiating circuits are Compatibility ID
"A".
Power Limited: 22 VDC, 3 mA standby, 5 mV ripple, 50 mA max. (alarm)

Indicating Circuits Four Style Y or Z (Class B or A) indicating circuits; configurable as strobes or


audibles. Terminals are labelled IND.

Power Limited: 24 VDC unfiltered, 1.7 amps @ 49 C per circuit 5 A maximum

Aux. Power Supply. Terminals are labelled AUX PWR.

Power limited / 24 VDC Filtered (special application) / 1.7 A @ 49° C

Two Resettable 4-Wire


Terminals are labelled 4-WIRE.
Smoke Supplies
Power Limited: 22 VDC, 200 mA each max., 300 mA total max, 5 mV ripple

RS-485 Connection 1 RS-485 Connection for Remote Annunciators or interface to Audio Systems.
Terminals are labelled RS-485.

Power Limited to 300 mA.


Electrical ratings AC Line Voltage 120V 60Hz / 240V 50 Hz
2A / 1A primary
Power supply ratings 6 Amps. max. (secondary)

For indicating circuits 24VDC unfiltered, 5 Amps. max.

Auxiliary relays Must be connected to a listed power limited source of supply. Terminals are
(resistive loads) labelled "ALARM, TROUBLE, SUPV".

Common alarm Form C, 1 Amp, 28 VDC


Common Supv Form C, 1 Amp, 28 VDC

Common Trouble Form C, 1 Amp, 28 VDC

Type 24VDC, Gel-Cell/Sealed Lead-Acid


Battery Charging capability 10Ah to 24Ah batteries

Current Consumption standby: 200 mA


alarm: 350 mA

65
Appendix C: Specifications

Table 12 HMCC-1024-6DS Specifications (Continued)

HMCC-1024-6DS Chassis
Compliance System Model HCP 1000 Series Fire Alarm Control Panel

System Type Local, auxiliary (using HPR-300), remote protected


premises station (using HPR-300 or HDACT-9100),
central station protected premises (using HDACT-
9100).
Type of Service A, M, WF, SS

Type of Signalling Non-Coded

Applicable Standards NFPA 70 and 72, UL 864 R9, ULC S-524, ULC S-
527

66
Appendix C: Specifications

13.2 HMCC-1024-12DS Specifications


Table 13 HMCC-1024-12DS Specifications

HMCC-1024-12DS Chassis
General Micro-controller based design, fully configurable from front panel, full walk test
function. Up to two circuit adder modules may be added. Displays and
disconnect switches for up to 24 circuits. Optional HPR-300 City Tie Module.

Initiating Circuits Eight supervised Style B (Class B) or 4 Style D (Class A) initiating circuits; fully
configurable. Terminals are labelled INI. initiating circuits are Compatibility ID
"A".

Power Limited: 22 VDC, 3 mA standby, 5 mV ripple, 50 mA max. (alarm)

Indicating Circuits Four Style Y or Z (Class B or A) indicating circuits; configurable as strobes or


audibles. Terminals are labelled IND.
Power Limited: 24 VDC unfiltered, 1.7 amps @ 49 C per circuit 5 A maximum

Aux. Power Supply. Terminals are labelled AUX PWR.

Power limited / 24 VDC Filtered (special application) / 1.7 A @ 49° C

Two Resettable 4-Wire


Terminals are labelled 4-WIRE.
Smoke Supplies

Power Limited: 22 VDC, 200 mA each max., 300 mA total max, 5 mV ripple

RS-485 Connection 1 RS-485 Connection for Remote Annunciators or interface to Audio Systems.
Terminals are labelled RS-485.

Power Limited to 300 mA.

Electrical ratings AC Line Voltage 120V 60Hz / 240V 50 Hz


4A / 2A primary

Power supply ratings 12 Amps. max. (secondary)

For indicating circuits 24VDC unfiltered, 10 Amps. max.

Auxiliary relays Must be connected to a listed power limited source of supply. Terminals are
(resistive loads) labelled "ALARM, TROUBLE, SUPV".

Common alarm Form C, 1 Amp, 28 VDC

Common Supv Form C, 1 Amp, 28 VDC

Common Trouble Form C, 1 Amp, 28 VDC


Type 24VDC, Gel-Cell/Sealed Lead-Acid

Battery Charging capability 17Ah to 40Ah batteries

Current Consumption standby: 200 mA


alarm: 350 mA

67
Appendix C: Specifications

Table 13 HMCC-1024-12DS Specifications (Continued)

HMCC-1024-12DS Chassis
Compliance System Model HCP 1000 Series Fire Alarm Control Panel

System Type Local, auxiliary (using HPR-300), remote protected


premises station (using HPR-300 or HDACT-9100),
central station protected premises (using HDACT-
9100).
Type of Service A, M, WF, SS

Type of Signalling Non-Coded

Applicable Standards NFPA 70 and 72, UL 864 R9, ULC S-524, ULC S-
527

13.3 HCP 1000 Expander Chassis and System Modules


Table 14 HCP 1000 Expander Chassis and System Modules

HCP 1000 System Modules and Annunciators


48 Zone Adder Part of the HMCC-1024-12XT Up to six circuit adder modules may be added.
module
Displays and disconnect switches for up to 48
circuits.

Current Consumption standby: 80 mA / alarm: 100 mA

HSGM-1004 Signal Adder Module Four Class B or A (Style Y or Z) NAC circuits;


configurable as strobes or audibles. Terminals
are labelled "IND".

Power Limited: 24 VDC unfiltered max. 1.7 amps @ 49C per


circuit

Current Consumption standby: 35 mA / alarm: 150 mA


HRM-1008 Relay Adder Module Must be connected to a listed power limited
source of supply. Terminals are labelled "RLY".
(resistive loads)
Eight fully configurable Form C NAC.
Form C, 1 amp., 28 VDC (resistive loads)

Current Consumption standby: 25 mA / alarm: 150 mA

HPR-300 Polarity Reversal and City Tie Module Supervised city tie--not power limited
24VDC unfiltered, 210 mA max., Trip coil: 14
ohms.
Terminals are labelled "City Tie".
Polarity reversal power limited
Terminals are labelled "Polarity Reversal".
24VDC open
12VDC @ 3.5 mA, 8 mA max. (shorted)

Current Consumption standby: 35 mA / alarm: 300 mA

68
Appendix C: Specifications

Table 14 HCP 1000 Expander Chassis and System Modules

HCP 1000 System Modules and Annunciators


HDM-1008 Detection Adder Module Eight supervised Class B (Style B) or four
Class A (Style D) NAC circuits; fully
configurable. Terminals are labelled "INI". NAC
circuits are Compatibility ID "A".

Power Limited 22VDC, 3 mA standby, 5mV ripple, 50 mA


max. (alarm)

Current Consumption standby: 80mA


alarm: 100 mA

HDACT-9100 Digital Communicator Module Transmit alarm, supervisory, and trouble to a


central monitoring station using Ademco
Contact ID and SIA-DCS Protocols.
Current Consumption standby: 45 mA / alarm: 120 mA

69
Appendix D: Power Supply and Battery Calculations

14.0 Appendix D: Power Supply and


Battery Calculations
Use the form below to determine the required main chassis and secondary power supply
(batteries).

IMPORTANT NOTICEIMPORTANT NOTICE


The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous
power without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper
over-current circuit protection that complies with the local codes. Refer toAppendix C: Specifications on
page 65 for specifications.
Power Requirements (All currents are in amperes)
Total Total
Model Number Description Qty Standby Alarm
Standby Alarm
HMCC-1024-6DS Main Chassis (6 amp) X 0.200 = 0.350 =
HMCC-1024-12DS Main Chassis (12 amp) X 0.200 = 0.350 =
Main + Adder module (48
HMCC-1024-12XT X 0.220 = 0.370 =
Circuit Display)
HDM-1008 8 initiating circuit Module X 0.080 = 0.100 =
HRM-1008 4 indicating circuit Module X 0.035 = 0.150 =
HDACT-9100 Digital Communicator Mod. X 0.045 = 0.120 =
HPR-300 City Tie Module X 0.035 = 0.300 =
Two-Wire Smoke Detectors ♦ = * 0.090 = 0.090
0.0001
Four-Wire Smoke Detectors X = =
Signal Load (bells, horns, strobes, and etc.) =
Auxiliary Power Supply for Remote Annunciators Alarm =
Total currents (Add above currents) STANDBY (A) (B)

Total Current Requirement


ALARM (B)______ Amps.

Battery Capacity Requirement


([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [♣Alarm in Hr.] _____) = (C) ______AH

Main Chassis Selection


Select HMCC-1024-6DS if (B) is less than 12 Amps.

Battery Selection
Multiply (C) by 1.20 to derate battery.

Batteries: BA-110 (10AH) and BA-117 (17AH) will fit in the HBBX-1024DS and HBBX-1024XT
boxes. BA-124 (24AH) and BA-140 (40AH) will fit into an external battery cabinet
BC-160(R)

* Assuming three initiating circuits in alarm.


♣ Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.

Using the MIR-525/U 2-wire smoke detector.

70
Warranty

15.0 Warranty
Hochiki America Corp., manufactured equipment is guaranteed to be free of defects in
material and workmanship for a period of one (1) year from the date of original shipment.
Hochiki will repair or replace, at its option, any equipment which it determines to contain
defective material or workmanship. Said equipment must be shipped to Hochiki prepaid.
Return freight will be prepaid by Hochiki. We shall not be responsible to repair or replace
equipment which has been repaired by others, abused, improperly installed, altered or
otherwise misused or damaged in any way. Unless previously contracted by Hochiki, Hochiki
will assume no responsibility for determining the defective or operative status at the point of
installation, and will accept no liability beyond the repair or replacement of the product at our
factory authorized service department.

Hochiki America Corp.


7051 Village Drive, Suite 100
Buena Park, CA
USA 90621
Phone: (714) 522-2246
FAX: (714) 522-2268
Technical Support Phone: 1-899-845-6692
or technical support@hochiki.com

71
Hochiki America Corp.
7051 Village Drive, , Suite 100
Buena Park, CA
USA 90621-2268

You might also like