YOUR PROBLEMS & OUR SOLUTIONS Index

Problems related to Cooling Water Treatment

Why should cooling towers be cleaned ?

What are cooling water treatment chemicals ?

What type of water treatment do you recommend for a closed-loop cooling system?

Why is water quality in closed systems important?

What type of water treatment do you recommend for an open-loop cooling system?

Why are bacteria a problem in closed water systems?

Do I need to treat the water in my closed-loop cooling system?

What type of filtration do you recommend for cooling tower water?

What is the difference between a "forced draft" and "induced-draft" cooling tower?

What is the difference between a "counterflow" and a "crossflow" cooling tower?

How does cooling actually take place inside a cooling tower?

What is the entering wet-bulb temperature?

Why is blowdown important?

What is cooling tower drift?

Why is minimizing drift important?

How can drift be minimized?

What is Legionnaires' Disease?

How can the transmission of Legionnaires' Disease be eliminated?

1 of 6 10/29/2012 2:23 PM
http://www.ieiknowledgepark.com/yourproblem and our solution/Coolingwatertreatment.htm

When acid cleaning a cooling tower or evaporative condenser, how do I know when the system is clean?

Why should cooling towers be cleaned?

Physical debris which resides within cooling towers can cause operational problems by blocking strainers etc but the major
cause for concern is that the debris creates areas where bacteria can replicate. These bacteria may include Legionella which
can be a health hazard.

What are cooling water treatment chemicals?

Cooling water treatment chemicals are used to protect systems from the four problems encountered by such systems namely,
scale, corrosion, suspended solids and bio-fouling. These chemicals help improve system efficiency and maintain safe working
conditions within the cooling system itself.

Following are the cooling water treatment chemicals manufactured by IEI

Biodispersants and antifoulants

Corrosion Inhibitor and Scale Inhibitors

Iron Specific dispersants

Non-oxidising Biocides

Oxidising Biocides

Silica Dispersants - Indion 5000

What type of water treatment do you recommend for a closed-loop cooling system? Go to Top

2 of 6 10/29/2012 2:23 PM
http://www.ieiknowledgepark.com/yourproblem and our solution/Coolingwatertreatment.htm

Most closed-loop water systems use a sodium nitrite based inhibitor and a biocide to prevent biological contamination. These
inhibitors will protect both the ferrous and non-ferrous materials in your piping system. Vendors can supply the inhibitor with a
colorant, which allows the treatment to be visually monitored.

Why is water quality in closed systems important?

Closed water systems are carefully designed to create precise and adaptable environmental conditions within buildings or
process plant. The design necessitates the use of small bore control and regulating valves. If corrosion debris, installation
debris or microbes are present these orifices may become blocked or restricted and the system will not operate to design
parameters. Ultimately if systems are not cared for the pipe work and fittings may fail prematurely due to corrosion and other
contributory factors. Water quality and water treatment are therefore very important.

What type of water treatment do you recommend for an open-loop cooling system? Go to Top

Because evaporative towers scrub the air that passes through them, they are prone to collecting debris from the air. This debris
can accumulate and cause flow restrictions; as well as aggravate corrosion. Also, after the water evaporates, dissolved minerals
are left behind and accumulate rapidly. For these reasons, a properly engineered and administered water treatment program
must be employed continuously with the cooling tower.

In an open tower cooling system, the water quality must be regularly monitored and treated to control the following conditions:

1) Lime scale and other water mineral deposits


2) Corrosion of all types
3) Micro-biological growth, such as algae, bacteria, fungus and molds
4) Suspended solids accumulations, such as airborne dirt and debris that is washed into the cooling tower water

Dry Coolers recommends consulting a local water treatment supplier that is familiar with your local water quality to monitor
your treatment program.

Why are bacteria a problem in closed water systems?

There are many different types of bacteria many of which are harmless. Some bacteria can however cause problems if they get
into the wrong place. In closed systems bacteria which cause biofilm are problematic since this biofilm can reduce the efficacy
of flushing (leaving debris within pipe work), affect thermal transfer, create conditions for under deposit corrosion and in
association with other debris, cause blockages or restrictions in control and regulating valves as well as strainers. Other
undesirable bacteria are associated with microbial corrosion or loss of corrosion inhibitor (in the case of nitrite based
inhibitors).

Do I need to treat the water in my closed-loop cooling system? Go to Top

Closed-loop systems are less susceptible to scaling because pretreated water (RO/ DM/ Softened Water ) is used in these
systems. For this reason they are often left untreated for scales. However, closed-loop systems must have corrosion protection.
An untreated closed-loop water system can cause serious corrosion in your equipment.

3 of 6 10/29/2012 2:23 PM
http://www.ieiknowledgepark.com/yourproblem and our solution/Coolingwatertreatment.htm

What type of filtration do you recommend for cooling tower water?

The fan on a cooling tower draws in thousands of cubic feet per minute of outside air that contains sand, dust, insects, and
fibers from vegetation. These airborne contaminants mix with the process cooling water and eventually these suspended
particles find their way into heat transfer surfaces. After a period of time these surfaces become fouled and insulated causing
equipment to run hotter and replacement or repair is necessary.

By removing 98% of these suspended solids mechanically (PSF/SSF), fouling is greatly reduced and chemical water treatment
and bleed from the system can be reduced significantly.

Full stream filtration protects the system from dirt deposits such as winds blowing over newly plowed fields, chunks of scale
eroding from steel pipe or foreign deposits encountered by adding new piping to an existing system.

What is the difference between a "forced draft" and "induced-draft" cooling tower? Go to Top

As the terms suggest, forced-draft cooling tower employ an air distribution system that forces air into the tower, while an
induced draft tower operates by pulling air through the tower. Forced draft towers are characterized by fans positioned on the
side of the cooling tower. Induced draft cooling towers utilize fans located on top of the cooling tower.

What is the difference between a "counterflow" and a "crossflow" cooling tower?

The crossflow or counterflow designation characterizes the orientation of the airflow within the heat transfer media (fill) in the
tower with respect to the direction of water flow. In counterflow towers air travels vertically upwards through the fill and makes
intimate contact with water droplets falling down through the fill media. Hence the air and water travel in opposite directions.
In crossflow cooling towers the air passes through the fill media in a horizontal direction, thus crossing the downward water
flow. Counterflow towers are inherently more efficient than crossflow towers.

How does cooling actually take place inside a cooling tower? Go to Top

There are two primary mechanisms by which water is cooled inside a cooling tower. Sensible heat transfer takes place when the
incoming air temperature is lower than the temperature of the incoming water, thus heat from the water is absorbed by the
colder air. If that were the only cooling that took place inside a cooling tower, the cold-water temperature would be limited by
the ambient temperature. However, the bulk of the cooling that takes place inside the cooling tower (>80%) is driven by
evaporation of the water itself. Evaporation requires energy (heat), so when water is evaporated within the fill media in a
cooling tower, heat is removed with the water vapor and leaves in the exiting air stream from the top of the tower. The result is
that the remaining water is cooled significantly, even to temperatures below the actual ambient temperature.

What is the entering wet-bulb temperature?

Simply stated the entering wet-bulb temperature (EWBT or WBT) is a measure of the level of humidity in the ambient air
entering the cooling tower. In general, the higher the wet-bulb temperature, the more moisture that exists in the air. The
wet-bulb temperature is a key parameter in the designing/sizing of a cooling tower, since it determines the degree to which
more water can be evaporated. Cooling towers operating in high wet-bulb temperatures require a larger tower than those

4 of 6 10/29/2012 2:23 PM
http://www.ieiknowledgepark.com/yourproblem and our solution/Coolingwatertreatment.htm

found in lower wet-bulb regions of the country.

Why is blowdown important? Go to


Top

Blowdown is the term given to water discharged from the cooling tower system to control the buildup of dissolved solids, such
as salts or other impurities that occur in water as well as suspended solids that are "washed-out" of the entering air. As a pot of
tea gets concentrated if it continues to boil, so the water in a cooling tower becomes concentrated with salts and other
impurities as water evaporates. In addition to blowdown, the predominant loss of water from a cooling tower system is through
the planned and desirable evaporation that takes place. When water is evaporated to pure water vapor, it leaves behind many
impurities which redissolve in circulating water or even deposit on cooling tower internals. Make-up water is introduced to the
system to compensate for water losses, but the circulating flow continues to become increasingly concentrated with these
impurities as more water evaporates. If the dissolved solids level becomes too high, accelerated scaling can occur inside the
cooling tower and reduce the efficiency and or capacity of cooling in the tower. Blowdown of the circulating flow is implemented
to keep this dissolved solids level below that saturation level.

What is cooling tower drift?

In every cooling tower, there is a loss of water to the environment in the form of pure water, which results from the
evaporative cooling process. This evaporated water leaves the tower in a pure vapor state, and thus presents no threat to the
environment. Drift, however, is the undesirable loss of liquid water to the environment, via small unevaporated droplets that
become entrained in the exhaust air stream of a cooling tower. These water droplets carry with them minerals, debris and
microorganisms and water treatment chemicals from the circulating water, thus potentially impacting the environment. High
drift losses are typically caused by fouled, inefficient or damaged drift eliminators, excessive exit velocities or imbalances in
water chemistry.

Why is minimizing drift important? Go to


Top

Minimizing drift losses in a cooling tower reduces the risk of impacting the environment with potentially corrosive water
treatment chemicals. Drift is usually responsible for damage to property near the cooling tower yard, i.e. buildings, cars, etc.
Water use and chemical consumption are also reduced since more remains in the circulating flow, thus generating savings in
operating costs. Last but not least, excessive drift losses pose serious health risks, not only because of the chemicals released,
but because of microorganisms that can be transmitted through drift, most notably L. pneumophila, the bacterium that causes
Legionnaires' disease.

How can drift be minimized?

Certainly, the most effective means of reducing drift is to install high-efficiency drift eliminators in your tower. The drift
eliminators are your last, but most critical line of defense for mitigating drift. Maintaining a balanced water chemistry is also
very important. Certain chemicals used specifically for cooling water treatment can reduce the water’s surface tension, thus
interfering with the normal agglomeration of water droplets that occurs in the drift eliminators. The result is that water
droplets are smaller and more easily entrained in the exiting air stream. There is no substitute for a well maintained water

5 of 6 10/29/2012 2:23 PM
http://www.ieiknowledgepark.com/yourproblem and our solution/Coolingwatertreatment.htm

treatment program. Finally, periodic inspection of spray distribution systems and drift eliminators is recommended. A clogged
spray nozzle, fouled drift eliminator or even an improperly installed drift eliminator can cause excessive drift in a cooling tower.

What is Legionnaires' Disease? Go to


Top

Legionnaires' Disease is a potentially serious illness that affects the human respiratory system. It is contracted through the
inhalation of air-born water droplets or mist containing viable Legionella pneumophila bacterium that occur naturally in most
US water sources. Cooling towers provide a hot, humid environment that is an ideal breeding ground for the bacterium. Once a
tower is infected, the bacteria are easily transmitted in the drift leaving the cooling tower. About 1,000 cases are reported each
year in the US, though the CDC estimates that 10 – 15 times that number of cases may actually occur each year.

How can the transmission of Legionnaires' Disease be eliminated?

While there is no doubt that Legionnaires' Disease is a real and potentially serious health issue for cooling tower operation, the
implementation of sensible equipment designs and the execution of appropriate operations, maintenance and housekeeping
procedures can virtually eliminate the risk to human health. Tower designs that feature low drift losses, readily
accessible/cleanable internals, and basins that promote the accumulation and removal of sedimentation are key to lowering the
associated health risk. Periodic cleaning of the cooling tower internals is strongly recommended.

When acid cleaning a cooling tower or evaporative condenser, how do I know when the system is clean?

Both Liquid Scale Dissolver and Imperial Scale Remover (Season Start) contain a "pH color indicator" that will guide you
through the process. When the acid/water cleaning solution is at proper strength, it will be green-to-light blue in color. When it
is neutralized and unable to dissolve scale, it will be purple. When it turns purple, another dose of acid equal to the first must
be added. The system is usually clean when you can maintain the green color for 20-30 minutes.

6 of 6 10/29/2012 2:23 PM