You are on page 1of 8

ARYADUTA HOTEL - MEDAN

Prepared By Bagus Perkoso


February 2017

SELECTION UNIT

Project : ARYADUTA HOTEL - MEDAN Report By : Bagus Perkoso


Date : 4th February 2017 No Doc : 001/DOC/AD/IV/2017

1 Description :
Quantity Room : 376 room

2 Standard Hot Water


Shower + Bathtube : 148 liter / person / peak
Kitchen :5 liter / person
Westafel :3 liter / person

3 Assumption Consumption
Standard per room :2 person
Peak per Period :2 hour
Temp. Hot Water : 60 °C
Temp. Cold Water : 28 °C
Temp. Mixing Water : 40 °C
ΔT : 32 °C
Occupancy Percentage : 100 %

4 Calcullation Hot Water for Hotel

a Shower + Bathtube = 376 room x 148 liter x


= 44,518 liter / peak

Total Peak per days = 44,518 liter / peak x 2 times/peak


= 89,037 liter

b Kitchen = 376 room x 5 liter x


= 3,760 liter / peak

Peak Period / 3 hour = 3,760 liter / peak : 3 hour


= 1,253 liter / peak

Total Peak per days = 1,253 liter / peak x 9 times/peak


= 11,280 liter

c Westafel = 376 room x 3 liter x


= 2,256 liter / peak

Total Peak per days = 2,256 liter / peak x 1 times/peak


= 2,256 liter

Total Consumption per days = Shower + Bathtube + Kitchen +


= 102,573 liter

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

SELECTION UNIT

Project : ARYADUTA HOTEL - MEDAN Report By : Bagus Perkoso


Date : 4th February 2017 No Doc : 001/DOC/AD/IV/2017

5 Energy Hot Water per days

Total Consumption per days = 102,573 liter/hour


= 0.028 m³/s
Delta Temp. = 32 °C

Energy Hot Water per days = 3,829 kW

Heatloss per hour = 38 kW


Heatloss per days = 919 kW

Total Energy Hot Water per days


include Heat Loss = 4,748 kW

6 Selection Heat Pump Alternatif 1

Total Energy Hot Water per days = 4,748 kW/days


include Heat Loss

Total Energy Hot Water @ 2 hour per peak = 1,187.11 kW/hour


Total Hot Water Consumption = 31,798 liter / hour
Demand 70% = 22,258 liter / hour

Hot Water Storage = 10,000 liter


Quantity = 2 unit
Total Hot Water Storage = 20,000 liter
Water Back Up HW Storage = 1.11 cycle/hour

Heat Pump Trane (Heating Mode)


Heat Capacity = 205.98 kW/h
Delta Temp. = 5 °C
Quantity = 1 unit
Hot Production = 35.3 m³/h
35,311 liter / hour
Total Heat Capacity = 206.0 kW

Heatloss per hour = 38.29 kW

Total Heat Capacity include Heat Loss = 168 kW

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

SELECTION UNIT

Project : ARYADUTA HOTEL - MEDAN Report By : Bagus Perkoso


Date : 4th February 2017 No Doc : 001/DOC/AD/IV/2017

Total Hot Water Production = 28,746 liter/hour

Conclusion
Total Hot Water Storage = 20,000 liter/hour
Total Hot Water Production = 28,746 liter/hour

Back Up Period = 0.70 hour


= 42 minute

7 Selection Heat Pump Alternatif 2

Shower + Bathtube = 44,518 liter / peak


Kitchen = 3,760 liter / peak

Total Hot Water / peak = 48,278 liter / peak


Demand 80% = 38,623 liter / peak

Hot Water Storage = 12,874 liter


Quantity = 3 unit
Total Hot Water Storage = 38,623 liter

Heat Pump Air To Water


Capacity = 105 kW
Delta Temp. = 32 °C
Quantity = 3 unit
Hot Production = 2.8 m³/h
= 2,813 liter/hour
Total Heat Capacity = 315 kW

Heatloss per hour = 38.29 kW

Total Heat Capacity include Heatloss = 276.71 kW


Total Hot Water Production = 7,412 liter/hour

Conclusion
Total Hot Water Storage = 38,623 liter/hour
Total Hot Water Production = 7,412 liter/hour

Back Up Period = 5.21 hour


= 313 minute

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

SELECTION UNIT

Project : ARYADUTA HOTEL - MEDAN Report By : Bagus Perkoso


Date : 4th February 2017 No Doc : 001/DOC/AD/IV/2017

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

/2017

80 %

2 person

2 person

Westafel

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

/2017

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

/2017

Return Of Investment Cooled And Hot Water System


ARYADUTA HOTEL - MEDAN
Prepared By Bagus Perkoso
February 2017

/2017

Return Of Investment Cooled And Hot Water System

You might also like