Project:

ETAP Page: 1
12.6.0H
Location: Date: 03-26-2019
Contract: SN:
Engineer: Study Case: GRD1 Filename: Pad napona
Revision: Base

Ground Grid Summary Report

Rg GPR Maximum Touch Potential Maximum Step Potential


Ground Ground
Coordinates (m) Coordinates (m)
Resistance Potential Rise Tolerable Calculated Calculated Tolerable Calculated Calculated
ohm Volts Volts Volts % X Y Volts Volts % X Y
1.691 3392.4 730.5 1729.8 236.8 41.6 17.0 2429.7 680.4 28.0 23.40 12.70

Total Fault Current 2.000 kA Reflection Factor (K): -0.923

Maximum Grid Current: 2.006 kA Surface Layer Derating Factor (Cs): 0.921

Decrement Factor (Df): 1.003

Warnings:
The maximum Touch Voltage exceeds the tolerable limits