Professional Documents
Culture Documents
Ensure the volume of the receiver is not filled up with water by reducing number of starts per hour for
the compressor. For better operation number of starts per hour (N) should not be greater than 15.
b) Use the correct load ratio for pneumatic actuators.
c) Use only the amount of pressure required for the force needed to do the work.
Pressure Drop f = (.0042 𝐿𝑄 2 )/{𝑃/𝑃𝐴 X 5.31d}
d) Use regulators with performance characteristics that meet the requirements of the application.
e) A regulator is an on-demand valve that shuts off at the set point.
f) Use standard regulators on the supply side of a directional control valve unless
otherwise noted.
g) Size regulators in conjunction with filters by sizing the filter first.
h) Downstream regulators should be self-exhaustive with vent.
i) Always calculate peak flow demand for each end effector in a machine.
j) For multiple end effectors operating at the same time, peak flow demands can be
summed.
k) Size all pneumatic components based upon their flow capacity for the peak flow
demand required.
l) For tubing and piping size successively from small at point of use, to medium at
transmission, to large at point of compression, sum the simultaneous peak flow
demands common to each line.
m) The longer the tubing or pipe, the less the flow capacity. Each 4-fold increase in length
reduces the flow capacity by 1/2.
n) For pneumatic logic, avoid long signal transmission lines if possible.
o) Before switching on a compressed air supply unit, one should thoroughly inspect the whole
circuit to see if there are any loose parts, abnormal pressure or damaged pipes.