Integrated
Variable Refrigerant Flow
AHU/PAU
(R410A)
CONTENTS
Dimensions 13
Notes 14
Features of VRF AHU/PAU
Designing of air conditioning system is simple, no water pump, no cooling tower and no
cooling / chilled water piping
Simple control system, built-in controls for VRF outdoor unit plus field installed LMCP for
AHU/PAU
Integrated package with VRF system
Easy installation and maintenance
Simple cable and refrigerant piping connection
Max 224kW (80HP) cooling capacity
Built-in backup, interlock and heat pump operation
Long pipe run available for greater design flexibility
Excellent full load COP for VRF outdoor unit (10HP) is 3.6, 50% COP is 4.3
Custom design of AHU/PAU arrangement to improve IAQ
Flexible Design
VRF AHU/PAU
OA
EEV Control Unit RA
SA
Filter
Humidifier
(Optional) Variable
Refrigerant
Flow Outdoor
Re-heat DX Coil
Unit
(Optional)
A pair of
Refrigerant Tube
DX Cooling Coil
one
eZ Variable
Se rvic Refrigerant
Sup Flow Outdoor
ply Unit
Air
Retu
rn Ai
r
2
Simple Installation
Compare Custom made VRF PAU to VRF Conventional Fresh Air Pre-treated Unit
VRF PAU system Traditional VRF System for Fresh Air
Up to 6,000 l/s or even more Small air flow rate (Max. 1800l/s)
Large cooling capacity (up to 80HP) Small cooling capacity (Max. 20HP)
Large external static pressure provided (up to 1,800Pa) Limited external static pressure (Max. 150Pa)
Lots of IAQ options No space to install IAQ components
(Eg. dehumidifier, UV light, PCO, Heat pipe or heat wheel)
3
Excellent Energy Saving
gy
NE E
5.0
Ener in
NE
E
SAVING ●
RG
g Y SAVING ● E
VRF Outdoor (10HP)
Sav
RGY
4.0
NE
Outdoor with 2 scroll
N
ER E
GY
SAVING ●
compressor (10HP)
3.0 with "ON/OFF" control
Custeosmign
2.0 D
1.0
0 on &
100% Part Load (50%) Load % a s y I n stallati ce
E nan
Mainte
Temp.
Temp.
Supply air temperature is closer to setpoint Supply air temperature will be colder than
Zone Zone temperature is kept tightly near setpoint at needed due to excess capacity
Temperature all times by continuous load-matching operation. Zone Zone setpoint is maintained by on-off cycling
Temperature
Setpoint Setpoint
Time Time
With VRF compressor With Scroll compressor
Post-cooling unit
NEW
DX Cooling Coil
OLD
12°C 16°C
Duct AHU
r
Post-Cooling Section
or
Heat mode is standard
provision for heating or Chiller
dehumidifying ller system with
in g ch i
Ex i s t ooling capacity
JJ JJ JJ JJ JJ
f fic ient c
JJ JJ JJ JJ JJ insu
4
Control System
Alarm occured
(Duty Unit) Unit "ON"
AHU "ON" PAU "ON" Duty & Standby Mode (Standby unit)
Automatic Mode
NEW
System Controller
Individual control is possible for Max. 32 AHUs.
Control of 32 AHUs / PAUs individually into 4 zones. (One zone can have up to 8 units)
Control is possible for ON/OFF, operation mode, operation monitoring, alarm monitoring,
remote controller local operation prohibition, etc…
5
Simple Wiring Requirement
LonWorks Interface
LON
Center Control Device
LonWorks (Field Supply)
Communication Line
System Controller
(Max. 64nos. AHU/PAU)
System Overview
B K
A A
AIR HANDLING UNIT KIT TO CONNECT
A : AHU kit controller box (with control PCB)
www.eggeassociats.net
B : AHU unit
GHP
AHU CONNECTION KIT
J
Remote control can be easily installed
PCB, Power trans, Terminal block on the AHU Kit box. Remote control Optional parts: Following functions
must be purchase separately.
are Technical Zoom
available by using different type
of · Maximum capacity: 60 HP (168
control accessories: kW)
· Maximum piping length: 180 m
CZ-RTC2 Wired remote controller · Maximum total piping: 210 m
G
the suction air at AHU Kit: Cool:
H
states output
CZ-CAPBC2 Mini seri-para I/O · Drain pump control (Drain-pump
unit and the float switch to be supplied
PRO Club · Temperature setting by 0-10 V · External target temperature setting in local)
or 0-140 Ω via Indoor/Outdoor signal interface
CZ-CAPBC2. (Ex. 0 – 10 V) is available with
warning in order to improve the product. The total or partial reproduction of this catalogue is prohibited
I
www.panasonicproclub.com · Room (inlet air) temp outlet by · Connectable with P-LINK system
4-20 mA
Or connect simply with your · Mode select or/and ON/OFF control · Fan control signal from the PCB
Smartphone to the PRO Club using
· Fan operation control can be used for control the air volume
this QR. for Th-off) (High/Mid/Low and LL
E
CZ-560MAH1 x3 155.0 50 25,000 / 17,500 0.9 (recommended) 10 / 100 10 - 30 DB
168.0 420 x 280 x 160 3/4 (19.05) 1 1/2 (38.15)
189.0 60 30,000 / 21,000 0.9 (recommended) 10 / 100 10
420 x 280 x 160 3/4 (19.05) 1 1/2 (38.15)
10 / 100 10
D
3/4 (19.05) 1 1/2 (38.15)
AHU Connection Kit / System
Combination
PACi Capacity (HP) Outdoor unit combination
2-PIPE ECOi 6N SERIES All capacities Common use for all outdoor units AHU kit combination
6
Optional - EC Plug Fan
Transformation of Power
Comparison
level for ηe(s)
Po
7
Other Features
The total run-time of compressors are Compressors with histories showing shorter
monitored by a built-in microcomputer, run times are selected first, ensuring equal
which ensures that operation times of all wear and tear across all units and extended
compressors within the same refrigerant circuit the working life of the system.
are balanced.
System example
A,C : DC inverter compressor
B,D : Constant speed compressor
Load Load Load
A B C D increase
A B C D increase
A B C D increase
A B C D
* Depending on accumulated operation time of each compressor
* Compressor priority has possibility to be changed
(e.g) Case1: AACABAD, Case2: CAAADAB, Case3: AACADAB, Case 4: CAAABAD
* Also other cases available
C. Automatic backup operation in the case of compressor failure or outdoor unit malfuction
(Except for single unit installation) Even if fan motor or Even if a whole Even if a compressor in
sensor fail outdoor unit fails a single system fails
Backup operation allows uninterrupted
X
X
cooling or heating to continue whist waiting
for service. X
Users should contact their authorized
service centre as soon as fault occurs. X
NEW function The other outdoor unit The other compressor
can keep running can keep running
8
Innovative
CONCEPT
Green & Technolog
y Solution
Internal lining
EC plug fan
DX cooling coil
Chilled
water
coil
Slim Type VRF Dual Coil (CHW+DX) Package Air Handling Unit (Slim VDC AHU)
F
AHU
V DC EC Plug Fan DX Coil C/W
m
Y
Sli
(Multi-fans for Water Coil variable flow
Filter section standby/duty C/W 2-way electrical
(Optional) function) valve expansion valve
Height in mm
=650
- mini shop
- Server room
Length in mm = 1450(+250)
Width in mm = 900
9
VRF Outdoor Unit Performance Data (Standard Series)
HP 10 20 30 40 50 60 70 80
Power Supply 380 / 400 / 415V-3-phase / 50Hz ; 380 / 400V / 3-phase / 60Hz
COP-Cooling W/W 5.03 3.76 4.31 3.74 4.09 3.76 3.90 3.76
Dimension Width mm 770 1,540 2,420 3,140 4,020 4,740 5,570 6,340
Net Weight kg 210 375 630 750 1,005 1,125 1,335 1,500
Power Input kW 5.57 14.90 19.70 30.20 34.20 44.70 50.30 59.6
Starting Current A 1 2 4 4 6 6 7 8
Airflow Rate m3/h 13,440 24,300 27,840 48,600 52,140 72,900 86,340 97,200
Refrigerant Amount at
shipping
kg 5.6 9.5 16.6 19.0 26.1 28.5 34.1 38.0
10
VRF Outdoor Unit Performance Data (High Efficiency Series)
10 20 30 40 50 60
HP U-10ME2H7 U-20ME2H7HE U-30ME2H7 U-40ME2H7HE U-50ME2H7HE U-60ME2H7HE
Starting Current A 1 2 4 4 5 7
11
Drawings
H
W
Performance Data
AHU Performance Data
Standard Unit Dimensions On Coil Off Coil System
AHU Air flow
VRF Outdoor Cooling
AHU Model No. rate Height Width Length DB/RH DB
Model No. Capacity
m /s
3
mm mm mm °C/% °C kW
A1-1170H-1050W U-10ME2H7 1.49 1,210 1,050 1,595 25/55 12.5 28
A1-1450H-1350W U-20ME2H7 2.90 1,550 1,350 1,595 25/55 12.5 56
U-16ME2H7
A1-1770H-1650W 4.47 1,870 1,500 1,595 25/55 12.5 85
U-14ME2H7
U-20ME2H7
A1-1770H-1950W 5.92 1,870 1,950 1,900 25/55 12.5 113
U-20ME2H7
U-20ME2H7
A1-1930H-2250W U-16ME2H7 7.45 2,030 2,250 2,205 25/55 12.5 140
U-14ME2H7
U-20ME2H7
A1-2250H-2250W U-20ME2H7 8.94 2,250 2,250 2,205 25/55 12.5 168
U-20ME2H7
12
Dimensions (Standard Series)
10 HP
U-10ME2H7 According to the installation site, you may
Air Outlet choose the setting positionin the depth
Installation anchor hole direction of the anchor bolt from A, B or C.
8-15x21 elongated holes
A: (Installation hole pitch)
Air intake
For removing tube forward
B: (Installation hole pitch)
For removing tube downward
C: (Installation hole pitch)
1842
A:964
1000
Air intake
Air intake
953
B: 730
18
C:730
15 740
770
953
18
15 1150
B: 730
1180
20 HP
According to the installation site, you may
U-20ME2H7
choose the setting position in the depth
Air Outlet
direction of the anchor bolt from A, B or C.
Installation anchor hole
8-15x21 elongated holes A: (Installation hole pitch)
Air intake Air intake 740
For removing tube forward
B: (Installation hole pitch)
For removing tube downward
1842
953
15 1510
B:730
18
1540
Unit in mm
13
Dimensions (High Efficiency Series)
10 HP
U-10ME2H7
According to the installation site, you may choose the setting position in the depth direction of the
anchor bolt from A, B or C.
B:730
1000 A:964
C:730
Air Intake
Air Intake
15 740 18 1842
770
953
12/14/16 HP
U-12ME2H7
U-14ME2H7
U-16ME2H7
According to the installation site, you may choose the setting position in the depth direction of the
anchor bolt from A, B or C.
A (Installation hole pitch) For removing tube forward
B (Installation hole pitch) For removing the downward Air outlet
C (Installation hole pitch)
Air Intake
B:730
1000 A:964
C:730
953
15 1150 18
1180
Unit in mm
14