SECTION 207C – Buildings MWFRS (Envelope Procedure)

Part 2: Enclosed Simple Low-Rise Buildings


#4. Determine the design wind loads for the concrete three story house below.
Location: Bulacan
Exposure C in all directions
Roof slope: 30°

9m

25m
12m
SECTION 207C – Buildings MWFRS (Envelope Procedure)
Part 2: Enclosed Simple Low-Rise Buildings
#4. Determine the design wind loads for the three story house below.
1. Mean roof height h = 10.732m
2. Enclosure Classification, Enclosed Sec 207A.10
3. Approximate natural frequency Eq. 207A.9-3
na  43.5 / h 0.9
 43.5 /10.372 0.9
 5.30 Hz
Building is Rigid
4. Occupancy IV Table 103-1
5. Basic Wind Speed, V = 260 kph Figure 207A.5-1A
7. Exposure Category : Exposure B
8. Topographic Factor, Kzt = 1.00 Sec 207A.8
9. Adjustment Factor, λ=1.4433 Figure 207C.6-1
SECTION 207C – Buildings MWFRS (Envelope Procedure)
Part 2: Enclosed Simple Low-Rise Buildings
#4. Determine the design wind loads for the three story house below.
10. Design pressure at h=9m and Exposure B, Ps30 or Ps9 Figure 207C.6-1

Ps30/Ps9
Basic Zones
Roof
Wind Load Horizontal Pressures Vertical Pressures Overhangs
Anlge
Speed Case
(degrees) A B C D E F G H EOH GOH
(kph)
1 2.06 1.41 1.64 1.13 0.16 -1.25 0.05 -1.07 -0.72 -0.83
250 30
2 2.06 1.41 1.64 1.13 0.79 -0.62 0.68 -0.44 -0.72 -0.83
1 2.24 1.53 1.78 1.23 0.17 -1.4 0.06 -1.2 -0.8 -0.9
260 30
2 2.24 1.53 1.78 1.23 0.86 -0.7 0.74 -0.5 -0.8 -0.9
1 2.97 2.03 2.36 1.62 0.23 -1.80 0.08 -1.55 -1.04 -1.19
300 30
2 2.97 2.03 2.36 1.62 1.14 -0.89 0.99 -0.63 -1.04 -1.19
SECTION 207C – Buildings MWFRS (Envelope Procedure)
Part 2: Enclosed Simple Low-Rise Buildings
#4. Determine the design wind loads for the three story house below.
11. Simplified design pressure, Ps Equation 207C.6-1
ps   K zt pS 30

Zones
Load Overhan
Horizontal Pressures Vertical Pressures
Case gs
A B C D E F G H EOH GO
H
Ps30/Ps9 2.24 1.53 1.78 1.23 0.17 -1.40 0.06 -1.20 -0.80 -0.90
1
Ps 3.23 2.21 2.57 1.78 0.25 -2.02 0.09 -1.73 -1.15 -1.30
Ps30/Ps9 2.24 1.53 1.78 1.23 0.86 -0.70 0.74 -0.50 -0.80 -0.90
2
Ps 3.23 2.21 2.57 1.78 1.24 -1.01 1.07 -0.72 -1.15 -1.30
SECTION 207C – Buildings MWFRS (Envelope Procedure)
Part 2: Enclosed Simple Low-Rise Buildings
#4. Determine the design wind loads for the three story house below.

LOAD CASE 1
SECTION 207C – Buildings MWFRS (Envelope Procedure)
Part 2: Enclosed Simple Low-Rise Buildings
#4. Determine the design wind loads for the three story house below.

LOAD CASE 2