You are on page 1of 3

Chapter: Control Inert Page: 1 of 3

Engineering data sheet


Item: Ci Manifold

Ci MT Manifold

Item numbers covered by this datasheet


305601 Ci MT 1 Manifold
305602 Ci MT 2 Manifold
305603 Ci MT 3 Manifold
305604 Ci MT 4 Manifold
305605 Ci MT 5 Manifold
305606 Ci MT 6 Manifold
305607 Ci MT 7 Manifold
305608 Ci MT 8 Manifold
305609 Ci MT 9 Manifold
305610 Ci MT10 Manifold

General
The manifold is as standard supplied with connectors for 1 to 10 cylinders.
Each connection features a check valve which is automatically opened when the hose is connected.
Detail picture shows closed and open check valve.

Text
Document: Ci MT Manifold 1-10.doc 1
2
Product: Id: BH 3
Control Inert Rev: 16.07.07 4
5
6
Vølundsvej 17 7
DK- 3400 Hillerød
Tel +45 7022 2769 8
Fax +45 7023 2769 9
Chapter: Control Inert Page: 2 of 3
Engineering data sheet
Item: Ci Manifold

Specifications
Pressure:
Work: 400 bar (300 bar fill @ 15°C)
Proof (burst): > 1200 bar
Temperature: -40 to +70°C
Flow way: max 380mm2 (ø22mm)
Tread connections:
Hose connection: ISO228 G3/8” (60° seat), male
Pipe connection: ISO7 R1”, male
Additional outlet: ISO G228, female (EN837 compatible)
Materials: Brass, zinc plated steel, Viton
Dimension:
L×D×H: see table ×ø40×51mm
Weight: see table

Table 1
Item Marking Orifice Weight Length
number std.
mm kg mm
305601 Ci-MT 1 ø5 1.2 200
305602 Ci-MT 2 ø7.1 1.4 160
305603 Ci-MT 3 ø8.7 1.6 200
305604 Ci-MT 4 ø10.0 1.8 240
305605 Ci-MT 5 ø11.2 2.0 280
305606 Ci-MT 6 ø12.2 2.2 320
305607 Ci-MT 7 ø13.2 2.4 360
305608 Ci-MT 8 ø14.1 2.6 400
305609 Ci-MT 9 ø15.0 2.8 440
305610 Ci-MT 10 ø15.8 3.0 480

Markings
Fire Eater Logo, Ci-MT##, “Orifice”, Serial number

Text
Document: Ci MT Manifold 1-10.doc 1
2
Product: Id: BH 3
Control Inert Rev: 16.07.07 4
5
6
Vølundsvej 17 7
DK- 3400 Hillerød
Tel +45 7022 2769 8
Fax +45 7023 2769 9
Chapter: Control Inert Page: 3 of 3
Engineering data sheet
Item: Ci Manifold

Installation
The orifice (/manifold adapter) is screwed into the pipe system.
It is important not to damage the markings, therefore the ring under the union should be used for griping.
The manifold is screwed to the orifice by holding it in place and turning the union nut.
Before fixing the manifold it is important to verify that the o-ring is undamaged.

Operating
No operations are necessary.

Maintenance
No requirements.

Routine testing
No requirements.