Concealed Ceiling Unit

FXMQ-PVE
technical data

air conditioning systems


Concealed Ceiling Unit

FXMQ-PVE
• Indoor Units • Conceiled ceiling unit • FXMQ-PVE

TABLE OF CONTENTS
FXMQ-PVE

1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Electrical Specifications (50Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling capacity tables .............................................. 8
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 12


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

7 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

8 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

10 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

• VRV®systems • Indoor Units


• • •

1 Specifications
Technical Specifications FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE
Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6
Heating kW 2.5 3.2 4.0 5.0 6.3
Power Input Cooling kW 0.081 0.081 0.085 0.194 0.215
(50Hz) Heating kW 0.069 0.069 0.073 0.182 0.203
Power Input Cooling kW 0.080 0.080 0.084 0.193 0.214

1 (60Hz)
Casing
Dimensions
Heating
Material
Unit Height
kW

mm
0.069

300
0.069

300
0.073
Galvanised steel plate
300
0.182

300
0.203

300
1 Width mm 550 550 550 700 1,000
Depth mm 700 700 700 700 700
Weight Machine weight kg 25 25 25 28 36
Heat Specifications N° of rows 3 3 3 3 3
Exchanger Fin pitch mm 1.75 1.75 1.75 1.75 1.75
Face area m² 0.098 0.098 0.098 0.148 0.249
N° of stages 16 16 16 16 16
Fan Type Sirocco fan
Air Flow Rate Cooling High high m³/min 9 9 9.5 16 18
High m³/min 7.5 7.5 8 13 16.5
Low m³/min 6.5 6.5 7 11 15
External static High Pa 100 100 100 160 200
pressure (Max)
Standard Pa 50 50 50 100 100
Low Pa 30 30 30 30 50
Motor Output (high) W 90 90 90 140 350
Drive Direct drive
Sound Level Cooling Sound High High dBA 33 33 34 39 41
pressure High dBA 31 31 32 37 39
Low dBA 29 29 30 35 37
Piping Liquid (OD) Type Flare connection
Connections Diameter mm 6.35 6.35 6.35 6.35 6.35
Gas (OD) Type Flare connection
Diameter mm 12.7 12.7 12.7 12.7 12.7
Drain (OD) Diameter mm VP25 (I.D. 32/O.D. 25)
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices Fuse
Fan driver overload protector
Standard accessories Operation manual
Installation manual
Drain hose
Sealing pads
Clamps
Washer
Screws
Insulation for fitting
Clamp metal
Air discharge flange
Air suction flange
Notes Nominal cooling capacities are based on following conditions: return air temperature:
27°CDB/19°CWB; outdoor temperature: 35°CDB; standard external static pressure: 100Pa;
equivalent refrigerant piping: 7.5m (horizontal)
Nominal heating capacities are based on following conditions: return air temperature:
20°CDB; outdoor temperature: 7°CDB/6°CWB; standard external static pressure: 100Pa;
equivalent refrigerant piping: 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan
motor heat.
External static pressure is changeable in 7 stages (20, 25, 32 class); 13 stages (40 class);
14 stages (50, 63, 80, 100, 125 class) within the range of the remote control.
Air filter is not standard accessory, but please mount it in the duct system of the suction
side. Select its colorimetric method(gravity method) 50% or more.

1 • •
• • •

1 Specifications
Electrical Specifications (50Hz) FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE
Power Supply Name
Phase
Frequency Hz
VE
1~
50
VE
1~
50
VE
1~
50
VE
1~
50
VE
1~
50
3
Voltage V 220-240 220-240 220-240 220-240 220-240
Current Minimum circuit amps (MCA) A 0.6 0.6 0.6 1.4 1.6
Maximum fuse amps (MFA) A 16 16 16 16 16
Full load amps (FLA)
Voltage range Minimum
A
V
0.5
-10%
0.5
-10%
0.5
-10%
1.1
-10%
1.3
-10%
1
Maximum V +10% +10% +10% +10% +10% 1
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to
unit terminals is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

Electrical Specifications (60Hz) FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE


Power Supply Name VE VE VE VE VE
Phase 1~ 1~ 1~ 1~ 1~
Frequency Hz 60 60 60 60 60
Voltage V 220 220 220 220 220
Current Minimum circuit amps (MCA) A 0.6 0.6 0.6 1.4 1.6
Maximum fuse amps (MFA) A 16 16 16 16 16
Full load amps (FLA) A 0.5 0.5 0.5 1.1 1.3
Voltage range Minimum V -10% -10% -10% -10% -10%
Maximum V +10% +10% +10% +10% +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to
unit terminals is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

• • 2
• • •

1 Specifications
Technical Specifications FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE
Capacity Cooling kW 7.1 9.0 11.2 14.0
Heating kW 8.0 10.0 12.5 16.0
Power Input Cooling kW 0.230 0.298 0.376 0.461
(50Hz) Heating kW 0.218 0.286 0.364 0.449
Power Input Cooling kW 0.229 0.297 0.375 0.460
1 (60Hz)
Casing
Heating
Material
kW 0.218 0.286 0.364
Galvanised steel plate
0.449

1 Dimensions Unit Height mm 300 300 300 300


Width mm 1,000 1,000 1,400 1,400
Depth mm 700 700 700 700
Weight Machine weight kg 36 36 46 46
Heat Specifications N° of rows 3 3 3 3
Exchanger Fin pitch mm 1.75 1.75 1.75 1.75
Face area m² 0.249 0.249 0.383 0.383
N° of stages 16 16 16 16
Fan Type Sirocco fan
Air Flow Rate Cooling High high m³/min 19.5 25 32 39
High m³/min 17.5 22.5 27 33
Low m³/min 16 20 23 28
External static High Pa 200 200 200 200
pressure (Max)
Standard Pa 100 100 100 100
Low Pa 50 50 50 50
Motor Output (high) W 350 350 350 350
Drive Direct drive
Sound Level Cooling Sound High High dBA 42 43 43 44
pressure High dBA 40 41 41 42
Low dBA 38 39 39 40
Piping Liquid (OD) Type Flare connection
Connections Diameter mm 9.52 9.52 9.52 9.52
Gas (OD) Type Flare connection
Diameter mm 15.9 15.9 15.9 15.9
Drain (OD) Diameter mm VP25 (I.D. 32/O.D. 25)
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices Fuse
Fan driver overload protector
Standard accessories Operation manual
Installation manual
Drain hose
Sealing pads
Clamps
Washer
Screws
Insulation for fitting
Clamp metal
Air discharge flange
Air suction flange
Notes Nominal cooling capacities are based on following conditions: return air
temperature: 27°CDB/19°CWB; outdoor temperature: 35°CDB; standard
external static pressure: 100Pa; equivalent refrigerant piping: 7.5m
(horizontal)
Nominal heating capacities are based on following conditions: return air
temperature: 20°CDB; outdoor temperature: 7°CDB/6°CWB; standard
external static pressure: 100Pa; equivalent refrigerant piping: 7.5m
(horizontal)
Capacities are net, including a deduction for cooling (an addition for
heating) for indoor fan motor heat.
External static pressure is changeable in 7 stages (20, 25, 32 class); 13
stages (40 class); 14 stages (50, 63, 80, 100, 125 class) within the range
of the remote control.
Air filter is not standard accessory, but please mount it in the duct system
of the suction side. Select its colorimetric method(gravity method) 50% or
more.

3 • •
• • •

1 Specifications
Electrical Specifications (50Hz) FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE
Power Supply Name
Phase
Frequency Hz
VE
1~
50
VE
1~
50
VE
1~
50
VE
1~
50
3
Voltage V 220-240 220-240 220-240 220-240
Current Minimum circuit amps (MCA) A 1.8 2.3 2.9 3.4
Maximum fuse amps (MFA)
Full load amps (FLA)
A
A
16
1.4
16
1.8
16
2.3
16
2.7 1
Voltage range Minimum V -10% -10% -10% -10%
Maximum V +10% +10% +10% +10%
1
Notes Voltage range : units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or above listed range
limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

Electrical Specifications (60Hz) FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE


Power Supply Name VE VE VE VE
Phase 1~ 1~ 1~ 1~
Frequency Hz 60 60 60 60
Voltage V 220 220 220 220
Current Minimum circuit amps (MCA) A 1.8 2.3 2.9 3.4
Maximum fuse amps (MFA) A 16 16 16 16
Full load amps (FLA) A 1.4 1.8 2.3 2.7
Voltage range Minimum V -10% -10% -10% -10%
Maximum V +10% +10% +10% +10%
Notes Voltage range : units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or above listed range
limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

• • 4
• • •

2 Safety device settings

Safety devices 20 25 32 40 50 63 80 100 125


PC board fuse 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A

1 FXMQ-P PC board fuse (Fan driver)


Drain pump thermal fuse
°C
°C
250V 5A
145
250V 5A
145
250V 5A
145
250V 5A
145
250V 6.3A
145
250V 6.3A
145
250V 6.3A
145
250V 6.3A
145
250V 6.3A
145
2 3D034597G

5 • •
• • •

3 Options

FXMQ-P
Model < DUCT TYPE>
3
Item FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160
High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160
Filter chamber
Long life replacement filter
Long life replacement filter chamber kit
KDDF37AA36
KAF371AA36
KAF375AA36
KDDF37AA56
KAF371AA56
KAF375AA56
KDDF37AA80
KAF371AA80
KAF375AA80
KDDF37AA160
KAF371AA160
KAF375AA160
1
Service panel
KTBJ25K36W
KTBJ25K36F
KTBJ25K56W
KTBJ25K56F
KTBJ25K80W
KTBJ25K80F
KTBJ25K160W
KTBJ25K160F
3
KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Air discharge adapter KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A

3D060443C

NOTE

1 See the latest for the modification marks.

• • 6
• • •

4 Control systems

FXMQ-P
1
4

Type
No. FXMQ~PVE
Item
H/P BRC4C65
Wireless
1 Remote control C/O BRC4C66
Wired BRC1D52
2 Simplified remote control BRC2C51
3 Remote control for hotel use BRC3A61
4 Adaptor for wiring !KRP1C64
5-1 Wiring adaptor for electrical appendices (1) !KRP2A61
5-1 Wiring adaptor for electrical appendices (2) !KRP4AA51
6 Remote sensor KRCS01-1B
Note 2, 3
7 Mounting plate for adapter PCB
KRP4A96
8 Central remote control DCS302CA61
8-1 Electrical box with earth terminal (3 blocks) KJB311AA
9 Unified on/off control DSC301BA61
9-1 Electrical box with earth terminal (2 blocks) KJB212AA
Noise filter
9-2 KEK26-1A
(for electromagnetic interface use only)
10 Schedule timer DST301BA61
External control adaptor for outdoor unit
11 !DTA104A61
(Must be installed on indoor units)

NOTES
1 Mounting plate (No.7) is necessary for each adapter marked !.
2 Up to 2 adapters can be fixed for each mounting plate.
3 Only one mounting plate can be installed for each indoor unit.

3D060455

7 • •
• • •

5 Capacity tables
5-1 Cooling capacity tables
FXMQ-P
TC: Total Capacity; kW - SHC: Sensible heat capacity; kW
3
Outdoor 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB
Nominal air temp.
Unit size 20.0DB 23.0DB 26.0DB 27.0DB 28.0DB 30.0DB 32.0DB
capacity
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 2.2 10.0
12.0
14.0
1.5
1.5
1.5
1.5
1.5
1.5
1.8
1.8
1.8
1.8
1.8
1.8
2.1
2.1
2.1
1.9
1.9
1.9
2.2
2.2
2.2
1.9
1.9
1.9
2.3
2.3
2.3
1.9
1.9
1.9
2.6
2.6
2.6
2.0
2.0
2.0
2.8
2.7
2.7
2.1
2.0
2.0
1
16.0
18.0
1.5
1.5
1.5
1.5
1.8
1.8
1.8
1.8
2.1
2.1
1.9
1.9
2.2
2.2
1.9
1.9
2.3
2.3
1.9
1.9
2.6
2.6
2.0
2.0
2.7
2.6
2.0
2.0
5
20.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.5 1.9 2.6 2.0
21.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.5 1.9 2.6 2.0
23.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.5 1.9 2.5 1.9
25.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.5 1.9 2.5 1.9
27.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.9
29.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 1.8 2.4 1.9
31.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 1.8 2.4 1.8
33.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.3 1.8 2.4 1.8
35.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
37.0 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.2 1.8 2.2 1.7 2.3 1.8
39.0 1.5 1.5 1.8 1.8 2.1 1.9 2.1 1.9 2.2 1.8 2.2 1.7 2.3 1.8
42.0 1.5 1.5 1.8 1.8 2.0 1.9 2.1 1.8 2.1 1.8 2.2 1.7 2.2 1.7
44.0 1.5 1.5 1.8 1.8 2.0 1.9 2.0 1.8 2.1 1.7 2.1 1.7 2.2 1.7
46.0 1.5 1.5 1.8 1.8 1.9 1.8 1.9 1.7 1.9 1.6 1.9 1.5 1.9 1.5
25 2.8 10.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.3 2.4 3.5 2.4
12.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.3 2.4 3.5 2.4
14.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.3 2.4 3.4 2.4
16.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.3 2.4 3.4 2.4
18.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.3 2.4 3.4 2.4
20.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.2 2.3 3.3 2.3
21.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.2 2.3 3.3 2.3
23.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.2 2.3 3.2 2.3
25.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.1 2.3 3.2 2.3
27.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.1 2.2 3.2 2.3
29.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 3.0 2.3 3.0 2.2 3.1 2.2
31.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.9 2.3 3.0 2.2 3.1 2.2
33.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.9 2.3 2.9 2.2 3.0 2.2
35.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
37.0 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.8 2.2 2.9 2.1 2.9 2.1
39.0 1.9 1.8 2.3 2.0 2.6 2.3 2.7 2.2 2.7 2.2 2.8 2.1 2.9 2.1
42.0 1.9 1.8 2.3 2.0 2.6 2.3 2.6 2.2 2.7 2.1 2.7 2.1 2.8 2.1
44.0 1.9 1.8 2.3 2.0 2.6 2.2 2.6 2.2 2.6 2.1 2.7 2.0 2.8 2.0
46.0 1.9 1.8 2.3 2.0 2.4 2.1 2.4 2.1 2.4 2.0 2.4 1.9 2.4 1.9
32 3.6 10.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.3 3.0 4.6 3.0
12.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.3 3.0 4.5 3.0
14.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.3 3.0 4.4 3.0
16.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.3 3.0 4.4 3.0
18.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.2 3.0 4.3 2.9
20.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.2 2.9 4.3 2.9
21.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.1 2.9 4.2 2.9
23.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.1 2.9 4.2 2.9
25.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.0 2.9 4.1 2.8
27.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 4.0 2.8 4.1 2.8
29.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 3.9 2.8 4.0 2.8
31.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.8 2.9 3.8 2.8 3.9 2.7
33.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.7 2.8 3.8 2.7 3.9 2.7
35.0 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.6 2.8 3.7 2.7 3.8 2.7
37.0 2.4 2.2 2.9 2.5 3.4 2.8 3.5 2.8 3.6 2.8 3.7 2.7 3.8 2.7
39.0 2.4 2.2 2.9 2.5 3.4 2.8 3.5 2.8 3.5 2.7 3.6 2.6 3.7 2.6
42.0 2.4 2.2 2.9 2.5 3.4 2.8 3.4 2.7 3.4 2.7 3.5 2.6 3.6 2.6
44.0 2.4 2.2 2.9 2.5 3.3 2.8 3.3 2.7 3.4 2.6 3.5 2.6 3.6 2.6
46.0 2.4 2.2 2.9 2.5 3.1 2.7 3.1 2.6 3.1 2.5 3.1 2.3 3.1 2.3
40 4.5 10.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.4 3.9 5.7 4.0
12.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.4 3.9 5.6 4.0
14.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.4 3.9 5.5 4.0
16.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.4 3.9 5.5 3.9
18.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.3 3.9 5.4 3.9
20.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.2 3.8 5.3 3.9
21.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.2 3.8 5.3 3.8
23.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.1 3.8 5.2 3.8
25.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.0 3.7 5.1 3.8
27.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 5.0 3.7 5.1 3.7
29.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.8 3.8 4.9 3.7 5.0 3.7
31.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.7 3.8 4.8 3.6 4.9 3.6
33.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.6 3.7 4.7 3.6 4.8 3.6
35.0 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
37.0 3.0 2.9 3.6 3.4 4.2 3.8 4.4 3.8 4.5 3.6 4.6 3.5 4.7 3.5
39.0 3.0 2.9 3.6 3.4 4.2 3.8 4.4 3.7 4.4 3.6 4.5 3.4 4.6 3.5
42.0 3.0 2.9 3.6 3.4 4.2 3.8 4.2 3.6 4.3 3.5 4.4 3.4 4.5 3.4
44.0 3.0 2.9 3.6 3.4 4.1 3.7 4.2 3.6 4.2 3.5 4.3 3.3 4.4 3.4
46.0 3.0 2.9 3.6 3.4 3.9 3.6 3.9 3.4 3.9 3.3 3.9 3.0 3.9 3.1
CA08A050B1

• • 8
• • •

5 Capacity tables
5-1 Cooling capacity tables
FXMQ-P
TC: Total Capacity; kW - SHC: Sensible heat capacity; kW
Outdoor 14.0WB 16.0WB 18.0WB 19.0WB 20.0WB 22.0WB 24.0WB
Nominal air temp.
Unit size 20.0DB 23.0DB 26.0DB 27.0DB 28.0DB 30.0DB 32.0DB
capacity
°CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC

1 50 5.6 10.0
12.0
14.0
3.8
3.8
3.8
3.6
3.6
3.6
4.5
4.5
4.5
4.1
4.1
4.1
5.2
5.2
5.2
4.5
4.5
4.5
5.6
5.6
5.6
4.6
4.6
4.6
6.0
6.0
6.0
4.6
4.6
4.6
6.7
6.7
6.7
4.8
4.8
4.8
7.1
7.0
6.9
4.3
4.3
4.2
5 16.0
18.0
3.8
3.8
3.6
3.6
4.5
4.5
4.1
4.1
5.2
5.2
4.5
4.5
5.6
5.6
4.6
4.6
6.0
6.0
4.6
4.6
6.7
6.6
4.8
4.7
6.8
6.7
4.1
4.1
20.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 6.0 4.6 6.5 4.7 6.6 4.0
21.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 6.0 4.6 6.4 4.6 6.6 4.0
23.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 6.0 4.6 6.4 4.6 6.5 4.0
25.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 6.0 4.6 6.3 4.5 6.4 3.9
27.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 6.0 4.6 6.2 4.5 6.3 3.8
29.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.9 4.6 6.1 4.4 6.2 3.8
31.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.9 4.6 6.0 4.4 6.1 3.7
33.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.8 4.5 5.9 4.3 6.0 3.7
35.0 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
37.0 3.8 3.6 4.5 4.1 5.2 4.5 5.5 4.6 5.6 4.4 5.7 4.2 5.8 3.6
39.0 3.8 3.6 4.5 4.1 5.2 4.5 5.4 4.5 5.5 4.4 5.6 4.2 5.8 3.5
42.0 3.8 3.6 4.5 4.1 5.2 4.5 5.3 4.4 5.3 4.3 5.5 4.1 5.6 3.4
44.0 3.8 3.6 4.5 4.1 5.1 4.5 5.2 4.4 5.3 4.2 5.4 4.1 5.5 3.4
46.0 3.8 3.6 4.5 4.1 4.8 4.3 4.8 4.1 4.8 4.0 4.8 3.7 4.9 2.9
63 7.1 10.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.5 5.8 9.0 6.4
12.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.5 5.8 8.9 6.3
14.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.5 5.8 8.7 6.3
16.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.5 5.8 8.6 6.3
18.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.3 5.8 8.5 6.2
20.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.2 5.7 8.4 6.2
21.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.2 5.7 8.3 6.2
23.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 8.1 5.6 8.2 6.1
25.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 7.9 5.6 8.1 6.1
27.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.6 5.6 7.8 5.5 8.0 6.1
29.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.5 5.6 7.7 5.4 7.9 6.0
31.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.4 5.5 7.6 5.4 7.8 6.0
33.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.3 5.5 7.5 5.3 7.6 5.9
35.0 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.2 5.4 7.4 5.3 7.5 5.9
37.0 4.8 4.2 5.7 4.9 6.6 5.4 7.0 5.5 7.1 5.4 7.2 5.2 7.4 5.9
39.0 4.8 4.2 5.7 4.9 6.6 5.4 6.9 5.4 7.0 5.3 7.1 5.1 7.3 5.8
42.0 4.8 4.2 5.7 4.9 6.6 5.4 6.7 5.3 6.8 5.2 7.0 5.0 7.1 5.7
44.0 4.8 4.2 5.7 4.9 6.5 5.4 6.6 5.2 6.7 5.1 6.8 5.0 7.0 5.7
46.0 4.8 4.2 5.7 4.9 6.1 5.1 6.1 5.0 6.1 4.8 6.1 4.6 6.2 5.3
80 9.0 10.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.8 7.4 11.4 7.4
12.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.8 7.4 11.2 7.4
14.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.8 7.4 11.1 7.3
16.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.7 7.4 10.9 7.2
18.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.6 7.3 10.8 7.2
20.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.4 7.2 10.6 7.1
21.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.4 7.2 10.6 7.1
23.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.2 7.1 10.4 7.0
25.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 10.1 7.0 10.3 6.9
27.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.6 7.1 9.9 7.0 10.1 6.9
29.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.5 7.1 9.8 6.9 10.0 6.8
31.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.4 7.0 9.6 6.8 9.8 6.7
33.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.3 7.0 9.5 6.7 9.7 6.7
35.0 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
37.0 6.1 5.3 7.2 6.1 8.4 6.9 8.9 6.9 9.0 6.8 9.2 6.6 9.4 6.5
39.0 6.1 5.3 7.2 6.1 8.4 6.9 8.7 6.8 8.8 6.7 9.0 6.5 9.3 6.5
42.0 6.1 5.3 7.2 6.1 8.4 6.8 8.5 6.7 8.6 6.6 8.8 6.4 9.0 6.4
44.0 6.1 5.3 7.2 6.1 8.2 6.8 8.3 6.6 8.5 6.5 8.7 6.3 8.9 6.3
46.0 6.1 5.3 7.2 6.1 7.7 6.5 7.7 6.3 7.8 6.1 7.8 5.8 7.8 5.7
100 11.2 10.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 13.4 9.0 14.2 8.9
12.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 13.4 9.0 14.0 8.9
14.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 13.4 9.0 13.8 8.8
16.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 13.3 9.0 13.6 8.7
18.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 13.2 8.9 13.4 8.6
20.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 13.0 8.8 13.2 8.5
21.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 12.9 8.8 13.2 8.5
23.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 12.7 8.7 13.0 8.4
25.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 12.5 8.6 12.8 8.3
27.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.7 12.3 8.5 12.6 8.2
29.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.9 8.6 12.2 8.4 12.4 8.1
31.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.7 8.5 12.0 8.3 12.2 8.0
33.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.5 8.5 11.8 8.2 12.1 7.9
35.0 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.8
37.0 7.6 6.4 9.0 7.3 10.5 8.3 11.0 8.4 11.2 8.3 11.4 8.0 11.7 7.7
39.0 7.6 6.4 9.0 7.3 10.5 8.3 10.8 8.3 11.0 8.2 11.2 7.9 11.5 7.6
42.0 7.6 6.4 9.0 7.3 10.4 8.2 10.6 8.1 10.7 8.1 11.0 7.8 11.2 7.5
44.0 7.6 6.4 9.0 7.3 10.2 8.1 10.4 8.1 10.5 8.0 10.8 7.7 11.1 7.4
46.0 7.6 6.4 9.0 7.3 9.6 7.8 9.6 7.7 9.7 7.5 9.7 7.1 9.7 6.6
125 14.0 10.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.7 11.1 17.7 11.1
12.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.7 11.1 17.5 11.0
14.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.7 11.1 17.2 10.9
16.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.7 11.1 17.0 10.8
18.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.4 11.0 16.8 10.7
20.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.2 10.9 16.6 10.6
21.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 16.1 10.9 16.4 10.5
23.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 15.9 10.8 16.2 10.4
25.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 15.6 10.6 16.0 10.3
27.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.8 15.4 10.5 15.8 10.2
29.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.9 10.7 15.2 10.4 15.5 10.1
31.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.6 10.6 15.0 10.3 15.3 10.0
33.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.4 10.5 14.7 10.2 15.1 9.8
35.0 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.2 10.4 14.5 10.1 14.9 9.7
37.0 9.4 8.0 11.3 9.2 13.1 10.3 13.8 10.4 13.9 10.3 14.3 10.0 14.6 9.6
39.0 9.4 8.0 11.3 9.2 13.1 10.3 13.5 10.3 13.7 10.2 14.1 9.9 14.4 9.5
42.0 9.4 8.0 11.3 9.2 13.0 10.3 13.2 10.2 13.4 10.0 13.7 9.8 14.1 9.3
44.0 9.4 8.0 11.3 9.2 12.8 10.2 13.0 10.1 13.1 9.9 13.5 9.7 13.8 9.2
46.0 9.4 8.0 11.3 9.2 12.0 9.8 12.1 9.6 12.1 9.4 12.1 9.0 12.2 8.3
CA08A050B1

9 • •
• • •

5 Capacity tables
5-2 Heating capacity tables
FXMQ-P 3
Outdoor Indoor air temp. (°CDB)
Unit size air temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CDB °CWB kW kW kW kW kW kW
20 -19.8
-18.8
-16.7
-20.0
-19.0
-17.0
1.5
1.5
1.6
1.5
1.5
1.6
1.5
1.5
1.6
1.5
1.5
1.6
1.5
1.5
1.6
1.5
1.5
1.6
1
-13.7
-11.8
-15.0
-13.0
1.7
1.8
1.7
1.8
1.7
1.8
1.7
1.8
1.7
1.8
1.7
1.8
5
-9.8 -11.0 1.9 1.9 1.9 1.9 1.9 1.9
-9.5 -10.0 1.9 1.9 1.9 1.9 1.9 1.9
-8.5 -9.1 2.0 2.0 1.9 1.9 1.9 1.9
-7.0 -7.6 2.0 2.0 2.0 2.0 2.0 2.0
-5.0 -5.6 2.1 2.1 2.1 2.1 2.1 2.1
-3.0 -3.7 2.2 2.2 2.2 2.2 2.2 2.2
0.0 -0.7 2.3 2.3 2.3 2.3 2.3 2.2
3.0 2.2 2.5 2.5 2.4 2.4 2.3 2.2
5.0 4.1 2.5 2.5 2.5 2.4 2.3 2.2
7.0 6.0 2.6 2.6 2.5 2.4 2.3 2.2
9.0 7.9 2.7 2.7 2.5 2.4 2.3 2.2
11.0 9.8 2.8 2.7 2.5 2.4 2.3 2.2
13.0 11.8 2.8 2.7 2.5 2.4 2.3 2.2
15.0 13.7 2.8 2.7 2.5 2.4 2.3 2.2
25 -19.8 -20.0 1.9 1.9 1.9 1.9 1.9 1.9
-18.8 -19.0 1.9 1.9 1.9 1.9 1.9 1.9
-16.7 -17.0 2.1 2.1 2.0 2.0 2.0 2.0
-13.7 -15.0 2.2 2.2 2.2 2.2 2.2 2.1
-11.8 -13.0 2.3 2.3 2.3 2.3 2.3 2.3
-9.8 -11.0 2.4 2.4 2.4 2.4 2.4 2.4
-9.5 -10.0 2.5 2.4 2.4 2.4 2.4 2.4
-8.5 -9.1 2.5 2.5 2.5 2.5 2.5 2.5
-7.0 -7.6 2.6 2.6 2.6 2.6 2.6 2.6
-5.0 -5.6 2.7 2.7 2.7 2.7 2.7 2.7
-3.0 -3.7 2.8 2.8 2.8 2.8 2.8 2.8
0.0 -0.7 3.0 3.0 3.0 3.0 3.0 2.8
3.0 2.2 3.1 3.1 3.1 3.1 3.0 2.8
5.0 4.1 3.3 3.2 3.2 3.1 3.0 2.8
7.0 6.0 3.4 3.4 3.2 3.1 3.0 2.8
9.0 7.9 3.5 3.4 3.2 3.1 3.0 2.8
11.0 9.8 3.6 3.4 3.2 3.1 3.0 2.8
13.0 11.8 3.6 3.4 3.2 3.1 3.0 2.8
15.0 13.7 3.6 3.4 3.2 3.1 3.0 2.8
32 -19.8 -20.0 2.4 2.4 2.3 2.3 2.3 2.3
-18.8 -19.0 2.4 2.4 2.4 2.4 2.4 2.4
-16.7 -17.0 2.6 2.6 2.6 2.6 2.6 2.5
-13.7 -15.0 2.7 2.7 2.7 2.7 2.7 2.7
-11.8 -13.0 2.9 2.8 2.8 2.8 2.8 2.8
-9.8 -11.0 3.0 3.0 3.0 3.0 3.0 3.0
-9.5 -10.0 3.1 3.1 3.1 3.1 3.0 3.0
-8.5 -9.1 3.1 3.1 3.1 3.1 3.1 3.1
-7.0 -7.6 3.2 3.2 3.2 3.2 3.2 3.2
-5.0 -5.6 3.4 3.4 3.4 3.4 3.4 3.4
-3.0 -3.7 3.5 3.5 3.5 3.5 3.5 3.5
0.0 -0.7 3.7 3.7 3.7 3.7 3.7 3.5
3.0 2.2 3.9 3.9 3.9 3.9 3.7 3.5
5.0 4.1 4.1 4.1 4.0 3.9 3.7 3.5
7.0 6.0 4.2 4.2 4.0 3.9 3.7 3.5
9.0 7.9 4.3 4.3 4.0 3.9 3.7 3.5
11.0 9.8 4.5 4.3 4.0 3.9 3.7 3.5
13.0 11.8 4.5 4.3 4.0 3.9 3.7 3.5
15.0 13.7 4.5 4.3 4.0 3.9 3.7 3.5
40 -19.8 -20.0 3.0 2.9 2.9 2.9 2.9 2.9
-18.8 -19.0 3.0 3.0 3.0 3.0 3.0 3.0
-16.7 -17.0 3.2 3.2 3.2 3.2 3.2 3.2
-13.7 -15.0 3.4 3.4 3.4 3.4 3.4 3.4
-11.8 -13.0 3.6 3.6 3.6 3.5 3.5 3.5
-9.8 -11.0 3.7 3.7 3.7 3.7 3.7 3.7
-9.5 -10.0 3.8 3.8 3.8 3.8 3.8 3.8
-8.5 -9.1 3.9 3.9 3.9 3.9 3.9 3.9
-7.0 -7.6 4.0 4.0 4.0 4.0 4.0 4.0
-5.0 -5.6 4.2 4.2 4.2 4.2 4.2 4.2
-3.0 -3.7 4.4 4.4 4.4 4.4 4.4 4.4
0.0 -0.7 4.7 4.6 4.6 4.6 4.6 4.4
3.0 2.2 4.9 4.9 4.9 4.8 4.7 4.4
5.0 4.1 5.1 5.1 5.0 4.8 4.7 4.4
7.0 6.0 5.2 5.2 5.0 4.8 4.7 4.4
9.0 7.9 5.4 5.3 5.0 4.8 4.7 4.4
11.0 9.8 5.6 5.3 5.0 4.8 4.7 4.4
13.0 11.8 5.6 5.3 5.0 4.8 4.7 4.4
15.0 13.7 5.6 5.3 5.0 4.8 4.7 4.4
CA05A056

• • 10
• • •

5 Capacity tables
5-2 Heating capacity tables
FXMQ-P

Outdoor Indoor air temp. (°CDB)


Unit size air temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CDB °CWB kW kW kW kW kW kW

1 50 -19,8
-18,8
-16,7
-20,0
-19,0
-17,0
3,7
3,8
4,1
3,7
3,8
4,0
3,7
3,8
4,0
3,7
3,8
4,0
3,7
3,8
4,0
3,7
3,8
4,0
5 -13,7
-11,8
-15,0
-13,0
4,3
4,5
4,3
4,5
4,3
4,5
4,2
4,5
4,2
4,5
4,2
4,5
-9,8 -11,0 4,7 4,7 4,7 4,7 4,7 4,7
-9,5 -10,0 4,8 4,8 4,8 4,8 4,8 4,8
-8,5 -9,1 4,9 4,9 4,9 4,9 4,9 4,9
-7,0 -7,6 5,1 5,1 5,1 5,1 5,1 5,1
-5,0 -5,6 5,3 5,3 5,3 5,3 5,3 5,3
-3,0 -3,7 5,5 5,5 5,5 5,5 5,5 5,5
0.0 -0,7 5,9 5,9 5,8 5,8 5,8 5,5
3,0 2,2 6,2 6,2 6,2 6,1 5,9 5,5
5,0 4,1 6,4 6,4 6,3 6,1 5,9 5,5
7,0 6,0 6,6 6,6 6,3 6,1 5,9 5,5
9,0 7,9 6,8 6,7 6,3 6,1 5,9 5,5
11,0 9,8 7,0 6,7 6,3 6,1 5,9 5,5
13,0 11,8 7,1 6,7 6,3 6,1 5,9 5,5
15,0 13,7 7,1 6,7 6,3 6,1 5,9 5,5
63 -19,8 -20,0 4,7 4,7 4,7 4,7 4,7 4,7
-18,8 -19,0 4,9 4,9 4,8 4,8 4,8 4,8
-16,7 -17,0 5,1 5,1 5,1 5,1 5,1 5,1
-13,7 -15,0 5,4 5,4 5,4 5,4 5,4 5,4
-11,8 -13,0 5,7 5,7 5,7 5,7 5,7 5,7
-9,8 -11,0 6,0 6,0 6,0 6,0 6,0 5,9
-9,5 -10,0 6,1 6,1 6,1 6,1 6,1 6,1
-8,5 -9,1 6,3 6,3 6,2 6,2 6,2 6,2
-7,0 -7,6 6,5 6,5 6,4 6,4 6,4 6,4
-5,0 -5,6 6,8 6,7 6,7 6,7 6,7 6,7
-3,0 -3,7 7,0 7,0 7,0 7,0 7,0 7,0
0.0 -0,7 7,5 7,4 7,4 7,4 7,4 7,0
3,0 2,2 7,9 7,8 7,8 7,7 7,5 7,0
5,0 4,1 8,1 8,1 8,0 7,7 7,5 7,0
7,0 6,0 8,4 8,4 8,0 7,7 7,5 7,0
9,0 7,9 8,7 8,5 8,0 7,7 7,5 7,0
11,0 9,8 8,9 8,5 8,0 7,7 7,5 7,0
13,0 11,8 9,0 8,5 8,0 7,7 7,5 7,0
15,0 13,7 9,0 8,5 8,0 7,7 7,5 7,0
80 -19,8 -20,0 5,9 5,9 5,9 5,9 5,9 5,8
-18,8 -19,0 6,1 6,1 6,0 6,0 6,0 6,0
-16,7 -17,0 6,4 6,4 6,4 6,4 6,4 6,4
-13,7 -15,0 6,8 6,8 6,8 6,7 6,7 6,7
-11,8 -13,0 7,1 7,1 7,1 7,1 7,1 7,1
-9,8 -11,0 7,5 7,5 7,5 7,5 7,4 7,4
-9,5 -10,0 7,7 7,7 7,6 7,6 7,6 7,6
-8,5 -9,1 7,8 7,8 7,8 7,8 7,8 7,8
-7,0 -7,6 8,1 8,1 8,1 8,1 8,0 8,0
-5,0 -5,6 8,4 8,4 8,4 8,4 8,4 8,4
-3,0 -3,7 8,8 8,8 8,7 8,7 8,7 8,7
0.0 -0,7 9,3 9,3 9,3 9,3 9,3 8,7
3,0 2,2 9,8 9,8 9,8 9,7 9,4 8,7
5,0 4,1 10,2 10,1 10,0 9,7 9,4 8,7
7,0 6,0 10,5 10,5 10,0 9,7 9,4 8,7
9,0 7,9 10,8 10,6 10,0 9,7 9,4 8,7
11,0 9,8 11,2 10,6 10,0 9,7 9,4 8,7
13,0 11,8 11,3 10,6 10,0 9,7 9,4 8,7
15,0 13,7 11,3 10,6 10,0 9,7 9,4 8,7
100 -19,8 -20,0 7,4 7,4 7,3 7,3 7,3 7,3
-18,8 -19,0 7,6 7,6 7,6 7,5 7,5 7,5
-16,7 -17,0 8,0 8,0 8,0 8,0 8,0 8,0
-13,7 -15,0 8,5 8,5 8,4 8,4 8,4 8,4
-11,8 -13,0 8,9 8,9 8,9 8,9 8,9 8,8
-9,8 -11,0 9,4 9,3 9,3 9,3 9,3 9,3
-9,5 -10,0 9,6 9,6 9,5 9,5 9,5 9,5
-8,5 -9,1 9,8 9,8 9,7 9,7 9,7 9,7
-7,0 -7,6 10,1 10,1 10,1 10,1 10,1 10,0
-5,0 -5,6 10,6 10,5 10,5 10,5 10,5 10,5
-3,0 -3,7 11,0 11,0 10,9 10,9 10,9 10,9
0.0 -0,7 11,6 11,6 11,6 11,6 11,6 10,9
3,0 2,2 12,3 12,3 12,2 12,1 11,7 10,9
5,0 4,1 12,7 12,7 12,5 12,1 11,7 10,9
7,0 6,0 13,1 13,1 12,5 12,1 11,7 10,9
9,0 7,9 13,5 13,3 12,5 12,1 11,7 10,9
11,0 9,8 14,0 13,3 12,5 12,1 11,7 10,9
13,0 11,8 14,1 13,3 12,5 12,1 11,7 10,9
15,0 13,7 14,1 13,3 12,5 12,1 11,7 10,9
125 -19,8 -20,0 9,4 9,4 9,4 9,4 9,4 9,3
-18,8 -19,0 9,7 9,7 9,7 9,7 9,6 9,6
-16,7 -17,0 10,3 10,3 10,2 10,2 10,2 10,2
-13,7 -15,0 10,9 10,8 10,8 10,8 10,8 10,7
-11,8 -13,0 11,4 11,4 11,4 11,4 11,3 11,3
-9,8 -11,0 12,0 12,0 11,9 11,9 11,9 11,9
-9,5 -10,0 12,3 12,2 12,2 12,2 12,2 12,2
-8,5 -9,1 12,5 12,5 12,5 12,5 12,4 12,4
-7,0 -7,6 13,0 12,9 12,9 12,9 12,9 12,8
-5,0 -5,6 13,5 13,5 13,5 13,4 13,4 13,4
-3,0 -3,7 14,1 14,0 14,0 14,0 14,0 13,9
0.0 -0,7 14,9 14,9 14,8 14,8 14,8 13,9
3,0 2,2 15,7 15,7 15,7 15,5 15,0 13,9
5,0 4,1 16,3 16,2 16,0 15,5 15,0 13,9
7,0 6,0 16,8 16,8 16,0 15,5 15,0 13,9
9,0 7,9 17,3 17,0 16,0 15,5 15,0 13,9
11,0 9,8 17,9 17,0 16,0 15,5 15,0 13,9
13,0 11,8 18,1 17,0 16,0 15,5 15,0 13,9
15,0 13,7 18,1 17,0 16,0 15,5 15,0 13,9
CA05A056

11 • •
• • •

6 Dimensional drawing & centre of gravity


6-1 Dimensional drawing
FXMQ20,25,32P 3
NOTES
(All around) (Suspention bolt position)
1 Location of manufacture’s label:
Control box surface.
oblong hole
2 Mount the air folter at the suction side.
(Select its colorimethod (gravity 1
(Suspention bolt

(All around) Inspection hatch 1


Air outlet Air inlet Case 1)
method) 50% or more.
Control box
6
position)

Control box 3 Do not locate things should not be wet

or less
or more
under the indoor unit. Dews may drop
when humidity reaches over 80%, or a
Unit base drain gets stuck, or air filters are not
(or less)

Inspection hatch Ceiling


hole Air outlet Air inlet clean.
(Service space)

(All around) Fig. A 4 Space for Service Works


or more

Inspection hatch 1 According to any one of below


Case 2), 3) 1)~3), secure a space for
Control box Control box service works, such as checking
Inspection hatch 3 and maintenance of control box
View (Same as the indoor unit size +300 and drain pumps, etc.

or more
or more)
or more (From the Air outlet) 1)One inspection hatch (450x450) on

or more or less
Control box
(Service space) the control box side and a space of
Inspection hatch 450 or more

or more
300mm or more under the unit.
Ceiling (figA)
Inspection hatch
2)One inspection hatch (450x450) on
Inspection hatch 2 or more or more the control box side and 2 (two)
Adjustable

(Same as the indoor unit size or more)


or less)
or less

View B-1 View B-2 inspection hatches under the unit.


Air inlet
(Note 2) (arrow view B-1)
or less
Air outlet 3)3 (three) inspection hatches under
the unit and the control box. (Arrow
view B-2)

oblong hole
or more
(Note 4)

(A case without

(All around)
or more

the ceiling)

Ceiling (From the air inlet)


Floor surface

N° PART NAME REMARK N° PART NAME REMARK


1 Liquid pipe connection ø6.4 flare connection 7 Power supply connection
2 Gas pipe connection ø12.7 flare connection 8 Air discharge flange
3 Drain pipe connection VP25 (O.D. ø32, I.D. ø25) 9 Air suction flange
4 Ground terminal (Terminal in control box) M4 10 Hook For M10
5 Control box (Inside) 11 Socket (For maintenance) VP25 (O.D. ø32, I.D. ø25)
6 Interunit wiring connection 12 Drain hose (Accessory) O.D. ø32 (Outlet)

3D062541A

FXMQ40P
NOTES
1 Location of MANUFACTURE’S LABEL: Control box 4 Space for Service Works
surface
According to any one of below 1) - 3), secure a space for service works, such as,
2 Mount the air filter at the suction side. checking and maintenance of control box and drain pumps, etc.
20-ø 4.7 hole (Select its colorimethod (gravity method) 50% or more)
3 Do not locate things should not be wet under the indoor 1) One inspection hatch (450x450) on the control box side and a space of 300mm or
(All around) (Suspention bolt position)
unit. more under the unit. (Fig.A)
2) One inspection hatch (450x450) on the control box side and 2 (two) inspection
Dews may droop when humidity reaches over 80%, or a
hatches under the unit (Arrow view B-1)
drain gets stuck, or air filters are not clean.
3) 3 (three) inspection hatches under the unit and the control box. (Arrow view B-2)

12 - 8x12 oblong hole


(All around) <Inspection hatch>
Air Outlet Air Inlet (Ceiling opening)
Control box Control box
or less

26-ø 4.7 hole Inspection hatch Ceiling Ceiling


(All around)
(service space)

Inspection hatch
450 or more

Inspection hatch (°450) Inspection hatch (450mmx450mm)


Control box Control box
Inspection hatch 3
Control box
or less

View
700 or more
or more

(From the Air Outlet)


or more

Inspection hatch 450 or more (service space)


Air Air
outlet inlet
Fig. A or more
Inspection hatch 2
View B-1 View B-2
(467 or less)
700 or more
Adjustable

Air Inlet 12 Drain hose (accessory) O.D. ø 32 (outlet)


(Note 2) 300 or less
11 Socket (for maintenance) VP25 (O.D. ø 32 /I.D. ø 25)
Air outlet
10 Hook For M10
9 Air suction flange
8 Air discharge flange
7 Power supply connection
14 - 8x12 oblong hole 6 Interunit wiring connection
(A case without the
300 or more

(All around) 5 Control box (inside)


(Note 4)

ceiling)

4 Ground terminal (in control box) M4


3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
2 Gas pipe connection ø 12.7 flale connection
Ceiling (From the air inlet)
Floor surface 1 Liquid pipe connection ø 6.4 flale connection
ITEM PART NAME REMARK

3D060160

• • 12
• • •

6 Dimensional drawing & centre of gravity


6-1 Dimensional drawing
FXMQ50,63,80P
NOTES
1 Location of MANUFACTURE’S LABEL: Control box 4 Space for Service Works
surface

1
According to any one of below 1) - 3), secure a space for service works, such
2 Mount the air filter at the suction side. as, checking and maintenance of control box and drain pumps, etc.
(Select its colorimethod (gravity method) 50% or
more) 1) One inspection hatch (450x450) on the control box side and a space of
30-ø 4.7 hole
300mm or more under the unit. (Fig.A)
6 (All around) (Suspention bolt position)
36-ø 4.7 hole
(All around)
3 Do not locate things should not be wet under the
indoor unit. 2) One inspection hatch (450x450) on the control box side and 2 (two)
inspection hatches under the unit (Arrow view B-1)
Dews may droop when humidity reaches over 80%,
3) 3 (three) inspection hatches under the unit and the control box. (Arrow view B-2)
or a drain gets stuck, or air filters are not clean.

<Inspection hatch>
(Ceiling opening)
Control box Control box
Air Outlet Air Inlet

16 - 8x12 oblong hole


(All around)
Inspection hatch Ceiling Ceiling
Inspection hatch
Inspection hatch (°450) Inspection hatch (450mmx450mm)
or less

Control box Control box


Inspection hatch 3
(service space)
450 or more

Control box

or less

or more
or more
Air Air
outlet inlet
View Fig. A or more
700 or more (From the Air Outlet) Inspection hatch 2
(service space) View B-1 View B-2
Inspection hatch 450 or more
18 - 8x12 oblong hole
(All around) 12 Drain hose (accessory) O.D. ø 32 (outlet)
(467 or more)
700 or Less
Adjustable

300 or less
Air Inlet 11 Socket (for maintenance) VP25 (O.D. ø 32 /I.D. ø 25)
Air outlet (Note 2) 10 Hook For M10
9 Air suction flange
8 Air discharge flange
7 Power supply connection
6 Interunit wiring connection
(A case without the
300 or more

2500 or more

5 Control box (inside)


(Note 4)

ceiling)

4 Ground terminal (in control box) M4


3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
2 Gas pipe connection ø 15.9 flale connection
Ceiling (From the air inlet)
Floor surface 1 Liquid pipe connection ø 9.5 flale connection
ITEM PART NAME REMARK

3D060161

FXMQ100,125P
NOTES
1 Location of MANUFACTURE’S LABEL: 4 Space for Service Works
Control box surface
According to any one of below 1) - 3), secure a space for service works, such
2 Mount the air filter at the suction side. as, checking and maintenance of control box and drain pumps, etc.
(Select its colorimethod (gravity method) 50% or
40-ø 4.7 hole more) 1) One inspection hatch (450x450) on the control box side and a space of
(All around) (Suspention bolt position) 300mm or more under the unit. (Fig.A)
48-ø 4.7 hole 3 Do not locate things should not be wet under the
(All around) 2) One inspection hatch (450x450) on the control box side and 2 (two)
indoor unit.
inspection hatches under the unit (Arrow view B-1)
Dews may droop when humidity reaches over 80%,
3) 3 (three) inspection hatches under the unit and the control box. (Arrow view B-2)
or a drain gets stuck, or air filters are not clean.

<Inspection hatch>
(Ceiling opening)
Control box Control box

Air Outlet Air Inlet


Inspection hatch Ceiling Ceiling
Inspection hatch
Inspection hatch (°450) Inspection hatch (450mmx450mm)
20 - 8x12 oblong hole Control box
(All around) Control box
Inspection hatch 3
(service space)
450 or more

Control box
or less
or less

or more
or more

Air Air
outlet inlet
Fig. A or more
Inspection hatch 2
View B-1 View B-2
700 or more
(service space) View 12 Drain hose (accessory) O.D. ø 32 (outlet)
Inspection hatch 450 or more
(From the Air Outlet) 11 Socket (for maintenance) VP25 (O.D. ø 32 /I.D. ø 25)
(467 or more)

20 - 8x12 oblong hole


700 or Less
Adjustable

300 or less 10 Hook For M10


Air Inlet (All around)
Air outlet (Note 2) 9 Air suction flange
8 Air discharge flange
7 Power supply connection
6 Interunit wiring connection
(A case without the

5 Control box (inside)


300 or more

2500 or more
(Note 4)

ceiling)

4 Ground terminal (in control box) M4


3 Drain pipe connection VP25 (O.D. ø 32 /I.D. ø 25)
2 Gas pipe connection ø 15.9 flale connection
(From the air inlet)
Ceiling Floor surface 1 Liquid pipe connection ø 9.5 flale connection
ITEM PART NAME REMARK

3D060162

13 • •
• • •

6 Dimensional drawing & centre of gravity


6-2 Dimensional drawing and accessories
FXMQ-P 3
NOTE
1 Remote control cord and staple are not attached. They are field
supplied parts.
1
6
• Specifications of cord
• REMOTE CONTROL DIMENSIONS For Australia For other countries
Shield wire Vinyl cord with sheath or cable
Type
(insulated thickness: 1mm or more) (insulated thickness: 1mm or more)
Size 0.75~1.25mm²
Total
500m
length

Cord oulet hole

• INSTALLATION METHOD

EXPOSED BODY, EXPOSED CORD EXPOSED BODY, EMBEDDED CORD EXPOSED BODY, EMBEDDED CODE
Conduit
Staple
Remote control
Remote control Remote control

(Between Through hole


remote control
and control box)
Control box

3D028952

FXMQ-P

• REMOTE CONTROL DIMENSIONS • RECEIVER DETAIL


Transmitting part

Switch box
(Field supplied parts)
2 - 5x9 Slot

• REMOTE CONTROL HOLDER


INSTALLATION PROCEDURE
(INSTALLATION TO WALL SURFACE)

Liquid crystal remote


(Ceiling opening)

79
control (wireless)

• Service space for ceiling installation


(Service space)
more than 90

Remote control holder

NOTE
1 Do not install more than 3 receivers in the vicinity of one another.
(Ceiling opening)
With 4 or more units, there is always the possibility of malfunction.

3D007898B

• • 14
• • •

6 Dimensional drawing & centre of gravity


6-3 Centre of gravity

FXMQ-P

1
6

Model Name A B
FXMQ20,25,32P 550 210
FXMQ40P 700 280
FXMQ50,63,80P 1000 460
FXMQ100,125P 1400 600

4D060438A

15 • •
• • •

7 Piping diagram

FXMQ-P 3

Heat exchanger
Gas pipe connection port 1
7

Fan

Liquid pipe connection port

Filter Filter

Electronic expansion valve

4D034245C

• • 16
• • •

8 Wiring diagram
8-1 Wiring diagram
FXMQ-P
WIRING DIAGRAM
Power

1 supply

8
Input from outside
Note 2.

Transmission wiring
central remote
For FXMQ50PVE • 63PVE • 80PVE • 100PVE • 125PVE control
To X70A(A1P) Note 1.

For FXMQ20PVE • 25PVE •320PVE •40PVE

To X1M Wired remote control


(optional accessory)

EL. COMPO. BOX (INDOOR)


❈ Only FXMQ50PVE • 63PVE • 80PVE • 100PVE • 125PVE

Indoor unit Connector optional accessory


A1P Printed circuit board R1 Resistor (current limiting) X28A Connector (power supply for wiring)
A2P Printed circuit board (Fan) R2 Current sensing device X33A Connector (for wiring)
A3P Printed circuit board (Capacitor) R3, R4 Resistor (electric discharge) X35A Connector (adapter)
C1,C2,C3 Capacitor R1T Thermistor (suction air)
F1U Fuse (T, 3,15A, 250V) R2T Thermistor (liquid) Wired remote control
F2U Fuse (T, 5A, 250V) R3T Thermistor (gas) R1T Thermistor (air)
F3U Fuse (T, 6,3A, 250V) R4T Thermistor (discharge air) SS1 Selector switch (main/sub)
F4U Fuse (T, 6,3A, 250V) S1L Float switch
HAP Light emitting diode (service monitor-green) (A1P, A2P) V1R Diode bridge
KPR Magnetic relay V2R Power module
K1R Magnetic relay X1M Terminal strip (power supply)
L1R Reactor X2M Terminal strip (control)
M1F Motor (fan) Y1E Electronic expansion valve
M1P Motor (drain pump) Z1C,Z2C Noise filter (ferrite core)
PS Switching power supply (A1P, A2P) Z1F Noise filter

: Terminal Colors: RED: Red BRN: Brown ORG: Orange


: Connector BLK: Black GRY: Gray GRN: Green
: Field wiring WHT: White BLU: Blue
YLW: Yellow PNK: Pink
3D058783

NOTES
1 In case of using central remote control, connect it to the unit in accordance with the attached installation manual.
2 When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached the unit.

17 • •
• • •

9 Sound data
9-1 Sound pressure spectrum
FXMQ20,25P FXMQ32P 3
Octave band sound pressure level dB(0dB=0.0002µbar)

Octave band sound pressure level dB(0dB=0.0002µbar)


9

Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise

Octave band center frequency (Hz) Octave band center frequency (Hz)
4D062535 4D062536

NOTES NOTES
1 Operating conditons: 1 Operating conditons:
Power source: 220~240V 50Hz / 220V 60Hz Power source: 220~240V 50Hz / 220V 60Hz
Cooling: Return air temperature: 27°CDB, 19°CWB Cooling: Return air temperature: 27°CDB, 19°CWB
Outdoor temperature: 35°CDB, 24°CWD Outdoor temperature: 35°CDB, 24°CWD
Heating: Return air temperature: 20°CDB, 15°CWB Heating: Return air temperature: 20°CDB, 15°CWB
Outdoor temperature: 7°CDB, 6°CWB Outdoor temperature: 7°CDB, 6°CWB
External static pressure: 50Pa External static pressure: 50Pa
2 Measuring place 5 Over all (dB) 2 Measuring place 5 Over all (dB)
Anechoic chamber Air flow rate Anechoic chamber Air flow rate
3 Location of microphone Scale 3 Location of microphone Scale
HH H L HH H L
A 33.0 31.0 29.0 A 34.0 32.0 30.0
Discharge Duct Duct Suction C 42.0 40.0 38.0 Discharge Duct Duct Suction C 43.0 41.0 38.0
(B, G, N is already rectified) (B, G, N is already rectified)

Microphone Microphone
4 Operation noise differs with operation and ambient conditions 4 Operation noise differs with operation and ambient conditions

FXMQ40P FXMQ50P
Octave band sound pressure level dB(0dB=0.0002µ bar)

Octave band sound pressure level dB(0dB=0.0002µ bar)

Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise

Octave band center frequency (Hz) Octave band center frequency (Hz)
4D060446 4D060428

NOTES NOTES
Air flow rate Air flow rate
Scale Scale
1 Over All (dB): HH H L 1 Over All (dB): HH H L
A 39.0 37.0 35.0 A 41.0 39.0 37.0
(B, G, N is already rectified) (B, G, N is already rectified)
C 45.0 42.0 41.0 C 46.0 44.0 42.0
2 Operating conditons: 2 Operating conditons:
• Power source: 220-240V 50Hz / 220V 60Hz • Power source: 220-240V 50Hz / 220V 60Hz
• Cooling - Return air temperature: 27°C DB, 19°C WB • Cooling - Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB Outdoor temperature: 35°C DB, 24°C WB
• Heating - Return air temperature: 20°C DB, 15°C WB • Heating - Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB Outdoor temperature: 7°C DB, 6°C WB
• External static Pressure: 100Pa • External static Pressure: 100Pa
3 Measuring place: Anechoic chamber 3 Measuring place: Anechoic chamber
4 Location of microphone 2m 1m 4 Location of microphone 2m 1m

Discharge Duct Duct Suction Discharge Duct Duct Suction


1,5m

1,5m

Microphone Microphone
5 Operation noise differs with operation and ambient options 5 Operation noise differs with operation and ambient conditions.

• • 18
• • •

9 Sound data
9-1 Sound pressure spectrum
FXMQ63P FXMQ80P
Octave band sound pressure level dB(0dB=0.0002µ bar)

Octave band sound pressure level dB(0dB=0.0002µ bar)


1
9

Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise

Octave band center frequency (Hz) Octave band center frequency (Hz)
4D060447 4D060429

NOTES NOTES
Air flow rate Air flow rate
Scale Scale
1 Over All (dB): HH H L 1 Over All (dB): HH H L
A 42.0 40.0 38.0 A 43.0 41.0 39.0
(B, G, N is already rectified) (B, G, N is already rectified)
C 48.0 46.0 44.0 C 49.0 47.0 45.0
2 Operating conditons: 2 Operating conditons:
• Power source: 220-240V 50Hz / 220V 60Hz • Power source: 220-240V 50Hz / 220V 60Hz
• Cooling: Return air temperature: 27°C DB, 19°C WB • Cooling: Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB Outdoor temperature: 35°C DB, 24°C WB
• Heating: Return air temperature: 20°C DB, 15°C WB • Heating: Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB Outdoor temperature: 7°C DB, 6°C WB
• External static Pressure: 100Pa • External static Pressure: 100Pa
3 Measuring place: Anechoic chamber 3 Measuring place: Anechoic chamber
4 Location of microphone 2m 1m 4 Location of microphone 2m 1m

Discharge Duct Duct Suction Discharge Duct Duct Suction


1,5m

1,5m
Microphone Microphone
5 Operation noise differs with operation and ambient conditions. 5 Operation noise differs with operation and ambient conditions.

FXMQ100P FXMQ125P
Octave band sound pressure level dB(0dB=0.0002µ bar)

Octave band sound pressure level dB(0dB=0.0002µ bar)

Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise

Octave band center frequency (Hz) Octave band center frequency (Hz)
4D060448 4D060449

NOTES NOTES
Air flow rate Air flow rate
Scale Scale
1 Over All (dB): HH H L 1 Over All (dB): HH H L
A 43.0 41.0 39.0 A 44.0 42.0 40.0
(B, G, N is already rectified) (B, G, N is already rectified)
C 49.0 46.0 44.0 C 50.0 48.0 45.0
2 Operating conditons: 2 Operating conditons:
• Power source: 220-240V 50Hz / 220V 60Hz • Power source: 220-240V 50Hz / 220V 60Hz
• Cooling: Return air temperature: 27°C DB, 19°C WB • Cooling: Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB Outdoor temperature: 35°C DB, 24°C WB
• Heating: Return air temperature: 20°C DB, 15°C WB • Heating: Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB Outdoor temperature: 7°C DB, 6°C WB
• External static Pressure: 100Pa • External static Pressure: 100Pa
3 Measuring place: Anechoic chamber 3 Measuring place: Anechoic chamber
4 Location of microphone 2m 1m 4 Location of microphone 2m 1m
Discharge Duct Duct Suction Discharge Duct Duct Suction
1,5m

1,5m

Microphone Microphone
5 Operation noise differs with operation and ambient conditions. 5 Operation noise differs with operation and ambient conditions.

19 • •
• • •

10 Fan characteristics

FXMQ20,25P 3

Fan characteristics 1 Fan characteristics 2


(For field setting of remote control) NOTES
1
Range of available air flow rate in
1 As for this machine, setting is possible 10
by 8 position of ESP.
(mm H20) (Pa) (mm H20) (mm H20) (Pa) [HH] (mm H20) 2 Fan characteristics 1 shows a fan
characteristic at the time of the
“maximum ESP” “rating ESP”
3 “minimum ESP” as a representative.
4 Fan characteristics 2 (for field setting
of remote control) shows a fan
characteristic of each ESP of field
)
te 6
(No

setting possible air flow “HH”.


5 Please choose ESP setting by using
Fan characteristics 1 and Fan
characteristics 2 by the resistance of a
S P
P) f E

connected duct.
ES it o
ax lim
External static pressure

External static pressure


6 The remote control can be used to
(m pper

HH change “HH” “H” and “L”


U

(max ESP)
ES
P 100Pa 7 ESP: external static pressure
of max ESP 8 The value in this figure shows ESP in
mit
er li SP) rating air flow.
Low ax E 90Pa
(m
80Pa
SP
fE
it o 70Pa
e r limESP) H
p (max ESP)
Up ting
(ra SP HH 60Pa
of E (rating ESP)
mit
er li ) H (min ESP) of ES
P
Upp ESP r limit
50Pa (Note 7)
(min Lowe g ESP) HH rating ESP
(ratin (min ESP)
L (rating ESP) L 40Pa
L (min ESP) (max ESP)
H 30Pa
(rating ESP) min ESP

(mm H20) (Pa) Air flow (m3/min) Lower limit of ESP (mm H20) (mm H20) (Pa) Air flow (m3/min) (mm H20)
(min ESP)

3D062537

FXMQ20,25P
(Pa)
(mm H20) (mm H20)

NOTES
Upper limit of
ESP by 1 As for this machine, less than 10% of the
Upper limit for ESP airflow auto volume of blow-off air is automatically
(Note 8) adjustment adjusted to the rated quantity by airflow
auto adjustment at the time of
installation.
2 After duct constructing completion,
please perform local setting “airflow auto
adjustment” by remote control.
3 About the local setting method of the
“airflow auto adjustment”, look at the
installation manual which is attached to
an indoor unit.
4 External static pressure that can adjust
External static pressure

by “airflow auto adjustment” function is


30Pa - 100Pa (When air flow is HH).
5 It is not operated auto adjustment,
operated in air flow that is different from
rated quantity in the case of use out of
external static pressure range mentioned
above.
6 This figure shows a fan characteristics at
the time of “HH” “H” and “L”.
7 The remote control can be used to
change “HH” “H” and “L”.
Lower limit of 8 ESP: external static pressure.
ESP by airflow
auto adjustment

ESP
Lower limit for

(mm H20) (Pa) Air flow (m3/min) (mm H20)

3D062539
• • 20
• • •

10 Fan characteristics

FXMQ32P

1 Fan characteristics Fan characteristics 2 NOTES


For field setting of remote control
10 1 As for this machine, setting is possible by
8 position of ESP.
Range of available air flow rate in
(mm H20) (Pa) (mm H20) (mm H20) (Pa) [HH] (mm H20) 2 Fan characteristics 1 shows a fan
characteristic at the time of the
3 “maximum ESP” “rating ESP”
4 “minimum ESP” as a representative.
5 Fan characteristics 2 (for field setting of
remote control) shows a fan characteristic
of each ESP of field setting possible air
)
te 6

flow “HH”.
(No

6 Please choose ESP setting by using Fan


characteristics 1 and Fan
characteristics 2 by the resistance of a
SP

connected duct.
P) f E
ES it o

7 The remote control can be used to


ax lim
External static pressure

External static pressure


(m pper

HH
change “HH” “H” and “L”
U

(max ESP) 8 ESP: external static pressure


SP 100Pa
fE max ESP 9 The value in this figure shows ESP in
it o
e r limSP) rating air flow.
Low ax E 90Pa
(m
80Pa
SP
fE
it o 70Pa
r lim P) H
p p e g ES (max ESP)
U atin
(r ESP HH 60Pa
it of (rating ESP)
p er lim P)
Up in ES H (min ESP) ESP 50Pa (Note 7)
(m limit of rating ESP
Lower ESP) L
L (rating ESP) (rating (max ESP)
HH 40Pa
L (min ESP) (min ESP)
H 30Pa
(rating ESP) min ESP

(mm H20) (Pa) Air flow (m3/min) Lower limit of ESP (mm H20) (mm H20) (Pa) Air flow (m3/min) (mm H20)
(min ESP)

3D062538

FXMQ32PVE

(mm H20) (Pa) (mm H20)

NOTES
1 As for this machine, less than 10% of the
Upper limit for ESP volume of blow-off air is automatically
(Note 8) Upper limit of
ESP by adjusted to the rated quantity by airflow
airflow auto auto adjustment at the time of installation.
adjustment 2 After duct constructing completion,
please perform local setting “airflow auto
adjustment” by remote control.
3 About the local setting method of the
“airflow auto adjustment”, look at the
installation manual which is attached to
an indoor unit.
4 External static pressure that can adjust by
External static pressure

“airflow auto adjustment” function is 30Pa


- 100Pa (When air flow is HH).
5 It is not operated auto adjustment,
operated in air flow that is different from
rated quantity in the case of use out of
external static pressure range mentioned
above.
6 This figure shows a fan characteristics at
the time of “HH” “H” and “L”.
7 The remote control can be used to
change “HH” “H” and “L”.
8 ESP: external static pressure.
Lower limit of
ESP by airflow
auto adjustment

ESP
Lower limit for

(mm H20) (Pa) Air flow (m3/min) (mm H20)

3D062540

21 • •
• • •

10 Fan characteristics

FXMQ40P

Fan characteristics Fan characteristics

1 (mmH2O) (Pa) (mmH2O) (mmH2O) (Pa)


(For local setting of remote control)
Range of available air flow rate in !HH"
(mmH2O) 1
NOTES
As for this machine, setting is possible
10 2
by 13 position of ESP
Fan characteristics ! shows a fan
characteristic at the time of the
“maximum ESP” “rating ESP”
“minimum ESP” as a representative.
3 Fan characteristics " (for field setting
of remote control) shows a fan
te6 )

characteristic of each ESP of field


(No

setting possible air flow “HH”.


P) ESP

4 Please choose ESP setting by using


x E S of
(ma er limit

HH (note7)
fan characteristics ! and fan
(max ESP)
max ESP characteristics " by the resistance of
U pp

a connect duct.
P) f ES

5 The remote control can be used to


ES o
ax mit

External static pressure


External static pressure

change “HH” “H” and “L”.


(m wer li

6 ESP: External Static Pressure


Lo
P) SP

7 The value in this figure shows ESP in


ES of E

rating air flow.


ing mit
(ratpper li
U

HH
SP (rating ESP)
fE
to
mi )
L(rating ESP)
e r li ESP H
w g (max ESP) rating EPS
Lo atin
(r

SP
fE
to
mi
e r li P ) H (min ESP) H
(rating ESP) min EPS
p S
Up in E L (min ESP)
(m L
(max ESP)
of ESP
Lower limit HH
(min ESP) (min ESP)

(mmH2O) Air flow (m3/min) (mmH2O) (mmH2O) Air flow (m3/min) (mmH2O)

3D060456

FXMQ40P

NOTES
(mmH2O) (Pa) (mmH2O) 1 As for this machine, less than 10% of the volume of blow-off air is
automatically adjusted to the rated quantity by airflow auto
adjustment at the time of the installation.
Upper limit of
Upper limit of ESP (Note 8) ESP by airflow 2 After duct construction completion, please perform local setting “
auto adjustment airflow auto adjustment “ by remote control.
3 About the local setting method of the “airflow auto adjustment“, look
at the installation manual which is attached to an indoor unit .
4 External static pressure that can adjust by “airflow auto adjustment“
function is 30Pa - 160Pa (When air flow is HH).
5 It is not operated auto adjustment, operated in air flow that is different
from rated quantity in the case of use out of external static pressure
External static pressure

range mentioned above.


6 This figure shows a fan characteristics at the time of “HH” “H” and “L”.
7 The remote control can be used to change “HH” “H” and “L”.
8 ESP: external static pressure.

Lower limit of
ESP by airflow
auto adjustment

of ESP
Lower limit

(mmH2O)
(mmH2O) (Pa) Air flow (m3/min)

3D060577

• • 22
• • •

10 Fan characteristics

FXMQ50P

Fan characteristics Fan characteristics

1 (mmH2O) (Pa) (mmH2O) (mmH2O) (Pa)


(For local setting of remote control)
Range of available air flow rate in !HH"
(mmH2O) 1
NOTES
As for this machine, setting is possible
10 2
by 14 position of ESP
Fan characteristics ! shows a fan
characteristic at the time of the
“maximum ESP” “rating ESP”
“minimum ESP” as a representative.
3 Fan characteristics " (for field setting
of remote control) shows a fan
characteristic of each ESP of field
setting possible air flow “HH”.
)
te6

HH (note7)
P

(max ESP) 4 Please choose ESP setting by using


(No

S
P) of E

max ESP
fan characteristics ! and fan
SP

ES it
a x lim
SP of E

characteristics " by the resistance of


(m ower
x E mit

a connect duct.
)

L
(ma per li

H 5 The remote control can be used to


Up

(max ESP) External static pressure


External static pressure

(note7) change “HH” “H” and “L”.


max ESP 6 ESP: External Static Pressure
7 The value in this figure shows ESP in
rating air flow.
L
(max ESP)

S P
fE HH
it o (rating ESP)
r lim SP) SP
rating EPS
pe g E of E
Up ratin mit
( er li SP)
Low ting E H
(ra (rating ESP)

L
of ESP (rating ESP)
mit
er li ) of ESP HH
Upp ESP it
Lower limP) (min ESP) min EPS
(min (min ES H
(min ESP)
L
(min ESP)

(mmH2O) Air flow (m3/min) (mmH2O) (mmH2O) Air flow (m3/min) (mmH2O)

3D060457

FXMQ50P

NOTES
(mmH2O) (Pa) (mmH2O) 1 As for this machine, less than 10% of the volume of blow-off air is
automatically adjusted to the rated quantity by airflow auto
adjustment at the time of the installation.
2 After duct construction completion, please perform local setting
Upper limit of ESP (Note 8)
“airflow auto adjustment“ by remote control.
3 About the local setting method of the “airflow auto adjustment“, look
at the installation manual which is attached to an indoor unit .
4 External static pressure that can adjust by “ airflow auto adjustment
Upper limit of
ESP by airflow “ function is 50Pa - 200Pa (When air flow is HH).
auto adjustment 5 It is not operated auto adjustment, operated in air flow that is different
from rated quantity in the case of use out of external static pressure
External static pressure

range mentioned above.


6 This figure shows a fan characteristics at the time of “HH” “H” and “L”.
7 The remote control can be used to change “HH” “H” and “L”.
8 ESP: external static pressure.

Lower limit of
ESP by airflow
auto adjustment

P
it of ES
Lower lim

(mmH2O) (Pa) Air flow (m3/min) (mmH2O)

3D060578

23 • •
• • •

10 Fan characteristics

FXMQ63P 3
Fan characteristics Fan characteristics

(mmH2O) (Pa) (mmH2O) (mmH2O) (Pa)


(For local setting of remote control)
Range of available air flow rate in !HH"
(mmH2O) 1
NOTES
As for this machine, setting is possible
1
2
by 14 position of ESP
Fan characteristics ! shows a fan
10
characteristic at the time of the
“maximum ESP” “rating ESP”
“minimum ESP” as a representative.
3 Fan characteristics " (for field setting
of remote control) shows a fan
characteristic of each ESP of field
setting possible air flow “HH”.
ote 6)

HH (note7) 4 Please choose ESP setting by using


P (N

(max ESP) max ESP


fan characteristics ! and fan
SP) ES

characteristics " by the resistance of


x E it of

a connect duct.
(ma per lim

5 The remote control can be used to


P S
P) of E

External static pressure


Up
External static pressure

change “HH” “H” and “L”.


ES it
a x lim

H 6 ESP: External Static Pressure


(m w e r

(max ESP)
7 The value in this figure shows ESP in
Lo

rating air flow.

L
(max ESP)
P
) ES
SP it of

HH
g E im

SP (rating ESP)
tin r l

rating EPS
fE
(ra p p e

it o
U

e r lim SP)
Low ting E
(ra H
(rating ESP)
SP
fE
it o
lim L
per P ) P
Up in ES of ES (rating ESP)
m r limit
( Lowe ESP) HH
(min ESP) min EPS
(min
H
(min ESP)
L
(min ESP)

(mmH2O) Air flow (m3/min) (mmH2O) (mmH2O) Air flow (m3/min) (mmH2O)

3D060458

FXMQ63P

NOTES
1 As for this machine, less than 10% of the volume of blow-off air is
(mmH2O) (Pa) (mmH2O)
automatically adjusted to the rated quantity by airflow auto
adjustment at the time of the installation.
2 After duct construction completion, please perform local setting
Upper limit of ESP (Note 8)
“airflow auto adjustment“ by remote control.
3 About the local setting method of the “airflow auto adjustment“, look
at the installation manual which is attached to an indoor unit .
4 External static pressure that can adjust by “ airflow auto adjustment
Upper limit of “ function is 50Pa - 200Pa (When air flow is HH).
ESP by airflow
auto adjustment 5 It is not operated auto adjustment, operated in air flow that is different
from rated quantity in the case of use out of external static pressure
External static pressure

range mentioned above.


6 This figure shows a fan characteristics at the time of “HH” “H” and “L”.
7 The remote control can be used to change “HH” “H” and “L”.
8 ESP: external static pressure.

Lower limit of
ESP by airflow
auto adjustment

P
of ES
r limit
Lowe

(mmH2O) (Pa) Air flow (m3/min) (mmH2O)

3D060579

• • 24
• • •

10 Fan characteristics

FXMQ80P

Fan characteristics Fan characteristics

1 (mmH2O) (Pa) (mmH2O) (mmH2O) (Pa)


(For local setting of remote control)
Range of available air flow rate in !HH"
(mmH2O) 1
NOTES
As for this machine, setting is possible
10 2
by 14 position of ESP
Fan characteristics ! shows a fan
characteristic at the time of the
“maximum ESP” “rating ESP”
“minimum ESP” as a representative.
3 Fan characteristics " (for field setting
of remote control) shows a fan
characteristic of each ESP of field
setting possible air flow “HH”.
)
te6

4 Please choose ESP setting by using


( No

HH (note7)
(max ESP) fan characteristics ! and fan
SP

max ESP
SP f E

characteristics " by the resistance of


x E it o

a connect duct.
(ma per lim
)

5 The remote control can be used to


Up

External static pressure


External static pressure

change “HH” “H” and “L”.


SP
E

6 ESP: External Static Pressure


P) of
ES mit

H
7 The value in this figure shows ESP in
ax r li

(max ESP)
(m owe

rating air flow.


L

SP
fE
to L
mi ) (max ESP)
e r l i ESP
p g HH
Up atin (rating ESP) rating EPS
(r SP
of E
mit
er li P)
Lowting ES
(ra
SP H
of E (rating ESP)
mit
er li )
Uppin ESP
(m HH
it of ESP
Lower limP) (min ESP) min EPS
(min ES
L (min ESP)

(mmH2O) Air flow (m3/min) (mmH2O) (mmH2O) Air flow (m3/min) (mmH2O)

3D060459

FXMQ80P

NOTES
(mmH2O) (Pa) 1 As for this machine, less than 10% of the volume of blow-off air is
(mmH2O)
automatically adjusted to the rated quantity by airflow auto
adjustment at the time of the installation.
Upper limit of ESP (Note 8) 2 After duct construction completion, please perform local setting
“airflow auto adjustment“ by remote control.
3 About the local setting method of the “airflow auto adjustment“, look
at the installation manual which is attached to an indoor unit .
4 External static pressure that can adjust by “ airflow auto adjustment
Upper limit of
ESP by airflow “ function is 50Pa - 200Pa (When air flow is HH).
auto adjustment 5 It is not operated auto adjustment, operated in air flow that is different
from rated quantity in the case of use out of external static pressure
External static pressure

range mentioned above.


6 This figure shows a fan characteristics at the time of “HH” “H” and “L”.
7 The remote control can be used to change “HH” “H” and “L”.
8 ESP: external static pressure.

Lower limit of
ESP by airflow
auto adjustment

it of ESP
Lower lim

(mmH2O) Air flow (m3/min) (mmH2O)

3D060580

25 • •
• • •

10 Fan characteristics

FXMQ100P 3
Fan characteristics Fan characteristics

(mmH2O) (Pa) (mmH2O) (mmH2O) (Pa)


(For local setting of remote control)
Range of available air flow rate in !HH"
(mmH2O) 1
NOTES
As for this machine, setting is possible
1
2
by 14 position of ESP
Fan characteristics ! shows a fan
10
characteristic at the time of the
“maximum ESP” “rating ESP”
“minimum ESP” as a representative.
3 Fan characteristics " (for field setting
of remote control) shows a fan
characteristic of each ESP of field
) 6
Note

setting possible air flow “HH”.


P(

HH 4 Please choose ESP setting by using


SP) ES

(max ESP) (note7) fan characteristics ! and fan


SP
x E it of

max ESP
P) f E

characteristics " by the resistance of


ES it o
(ma per lim

ax lim

a connect duct.
(m wer
Up

5 The remote control can be used to


Lo

External static pressure


External static pressure

change “HH” “H” and “L”.


6 ESP: External Static Pressure
7 The value in this figure shows ESP in
H rating air flow.
(max ESP)

SP HH
fE
it o (rating ESP) rating EPS
lim )
er ESP
Low ting
P
) ES

(ra L
SP it of

(max ESP)
g E im
tin r l
(ra p p e

L(rating ESP)
U

H
(rating ESP)
SP H (min ESP)
of E
mit
er li ) P HH
Uppin ESP of ES (min ESP)
r limit min EPS
(m Lowe ESP)
(min
L (min ESP)

(mmH2O) Air flow (m3/min) (mmH2O) (mmH2O) Air flow (m3/min) (mmH2O)

3D060460

FXMQ100P

NOTES
(mmH2O) (Pa) 1 As for this machine, less than 10% of the volume of blow-off air is
(mmH2O)
automatically adjusted to the rated quantity by airflow auto
adjustment at the time of the installation.
2 After duct construction completion, please perform local setting
Upper limit of ESP (Note 8)
“airflow auto adjustment“ by remote control.
3 About the local setting method of the “airflow auto adjustment“, look
at the installation manual which is attached to an indoor unit .
4 External static pressure that can adjust by “ airflow auto adjustment
Upper limit of “ function is 50Pa - 200Pa (When air flow is HH).
ESP by airflow
auto adjustment 5 It is not operated auto adjustment, operated in air flow that is different
from rated quantity in the case of use out of external static pressure
External static pressure

range mentioned above.


6 This figure shows a fan characteristics at the time of “HH” “H” and “L”.
7 The remote control can be used to change “HH” “H” and “L”.
8 ESP: external static pressure.

Lower limit of
ESP by airflow
auto adjustment

P
of ES
r limit
Lowe

(mmH2O) (Pa) Air flow (m3/min) (mmH2O)

3D060581

• • 26
• • •

10 Fan characteristics

FXMQ125P

Fan characteristics Fan characteristics

1 (mmH2O) (Pa) (mmH2O) (mmH2O) (Pa)


(For local setting of remote control)
Range of available air flow rate in !HH"
(mmH2O) 1
NOTES
As for this machine, setting is possible
10 2
by 14 position of ESP
Fan characteristics ! shows a fan
characteristic at the time of the
“maximum ESP” “rating ESP”
“minimum ESP” as a representative.
3 Fan characteristics " (for field setting
of remote control) shows a fan
6 )
Note

characteristic of each ESP of field


P(

setting possible air flow “HH”.


SP) ES

HH 4 Please choose ESP setting by using


x E it of

(max ESP) (note7) fan characteristics ! and fan


(ma per lim

SP

max ESP
P) f E

characteristics " by the resistance of


ES it o
Up

a connect duct.
ax lim
(m wer

5 The remote control can be used to


Lo

External static pressure


External static pressure

change “HH” “H” and “L”.


6 ESP: External Static Pressure
7 The value in this figure shows ESP in
H
rating air flow.
(max ESP)

SP
fE
P

it o
) ES

rating EPS
lim )
SP it of

er ESP
Low ting
g E im
tin r l

(ra
(ra ppe

L(rating ESP) L
U

(max ESP)
SP H
of E H (min ESP) (rating ESP)
mit
er li )
Uppin ESP P HH
(m of ES (min ESP) min EPS
r limit
Lowe ESP)
(min
L (min ESP)

(mmH2O) Air flow (m3/min) (mmH2O) (mmH2O) Air flow (m3/min) (mmH2O)

3D060461

FXMQ125P

NOTES
(mmH2O) (Pa) (mmH2O)
1 As for this machine, less than 10% of the volume of blow-off air is
automatically adjusted to the rated quantity by airflow auto
adjustment at the time of the installation.
Upper limit of
ESP by airflow 2 After duct construction completion, please perform local setting
Upper limit of ESP (Note 8) auto adjustment “airflow auto adjustment“ by remote control.
3 About the local setting method of the “airflow auto adjustment“, look
at the installation manual which is attached to an indoor unit .
4 External static pressure that can adjust by “ airflow auto adjustment
“ function is 50Pa - 200Pa (When air flow is HH).
5 It is not operated auto adjustment, operated in air flow that is different
from rated quantity in the case of use out of external static pressure
External static pressure

range mentioned above.


6 This figure shows a fan characteristics at the time of “HH” “H” and “L”.
7 The remote control can be used to change “HH” “H” and “L”.
8 ESP: external static pressure.

Lower limit of
ESP by airflow
auto adjustment

P
of ES
r limit
Lowe

(mmH2O) Air flow (m3/min) (mmH2O)

3D060582

27 • •
Daikin’s unique position as a manufacturer of air Daikin Europe N.V. is approved by LRQA for its Quality The present publication is drawn up by way of information only and does not
conditioning equipment, compressors and Management System in accordance with the ISO9001 constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
refrigerants has led to its close involvement in standard. ISO9001 pertains to quality assurance regarding compiled the content of this publication to the best of its knowledge. No
environmental issues. For several years Daikin has design, development, manufacturing as well as to services express or implied warranty is given for the completeness, accuracy,
had the intension to become a leader in the provision related to the product. reliability or fitness for particular purpose of its content and the products and
of products that have limited impact on the services presented therein. Specifications are subject to change without
environment. This challenge demands the eco design prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or
and development of a wide range of products and an indirect damage, in the broadest sense, arising from or related to the use
energy management system, resulting in energy and/or interpretation of this publication. All content is copyrighted by Daikin
conservation and a reduction of waste. Europe N.V..
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for

Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende

ISO14001 assures an effective environmental


management system in order to help protect human health
and the environment from the potential impact of our
activities, products and services and to assist in
maintaining and improving the quality of the environment.
the environmont is set in the EMAS and ISO 14001 systems.

Daikin units comply with the European regulations that


guarantee the safety of the product.

Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
VRV® products are not within the scope of the Eurovent
www.daikin.eu certification programme.
BTW: BE 0412 120 336