400C Issue 1
Fire-rated Ceiling Systems
Contents
All materials used in the construction of Boral Screw identification is given as:
Plasterboard ceiling systems must be carefully (min. gauge) - (threads/inch ±1) x (min. length).
stored and protected on the construction site. * For ease of construction with framing steel gauges
Plasterboard is to be stacked flat and protected of less than 0.8mm BMT, use 30mm minimum
from moisture. Boral Firestop Plasterboard must length screws.
not be used where it will be exposed to excessive
moisture. In addition, damaged plasterboard
sheets and accessory materials must not be used. Screws - Plasterboard to Plasterboard
Fasteners Number of Layers of Plasterboard
x Thickness Type L Screws for
Screws Fixing Plasterboard
Plasterboard A Plasterboard B A to B
All screws are to AS3566- 1988 corrosion class 1
and are defined as follows: 1 x 13mm Min. 13mm 10 - 8 x 32mm
• Type S is a double start, needle point, bugle 1 x 16mm Min. 16mm 10 - 8 x 38mm
head gypsum screw for fixing to steel 1 x 16mm Min. 2 x 16mm 6 - 8 x 50mm
gauges of up to 0.80mm BMT.
• Type D is a double start, drill point, bugle Screw identification is given as:
head gypsum screw for fixing to steel (min. gauge) - (threads/inch ±1) x (min. length)
gauges from 0.80mm to 2.00mm BMT.
Fire-rated Ceiling Systems
Top Cross Rail Direct Fixing Clip Furring Channel Suspension Bracket Joiner Direct Fixing Clip
No. 128 No. 226 No. 129 No. 247 No. 139 No. 237
Direct Fixing Clip Suspension Clip Suspension Bracket Shadow Line Trim Steel Angle
No. 394 No. 2534 No. 274 No. P50 No. 554
EQ
DFS = Direct Fixed System with nominal cavity depth of 190mm between ceiling and floor.
FS = Furred System with nominal cavity depth of 220mm between ceiling and floor and
Rondo P.N. 226 Direct Fixing Clip fixed to side of joist with furring channel fixed to clip.
SS = Suspended System with nominal cavity depth of 350mm between ceiling and floor.
PO = Plasterboard Only. The Rw rating is for the number of plasterboard layers specified.
* Acoustic ratings are3. based on ceiling insulation of minimum 100mm thick polyester or
glass wool @ 14kg/m
# Also protection to loaded steel or timber beams above ceiling.
Caution
Boral Plasterboard ceiling systems are not designed to
support the weight of construction or maintenance
personnel, additional plant or storage of goods.
Fire-rated Ceiling Systems
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
Standard Construction 19
35mm min.
1, 2 or 3 Layers of Boral
Firestop Plasterboard
as required
1, 2 or 3 layers of Boral Firestop Timber or steel roof or floor End joints formed on framing members
Plasterboard fixed transverse to framing @ 600mm max. centres and staggered, otherwise end joints on
framing @ 600mm max.centres. first layer must be back blocked. Where
All joints staggered min. 200mm. applicable, second and third layers
should be screw laminated to previous
layer @ 200mm max. centres.
200mm
150mm
Note: Systems using 1, 2 or 3 layers of Boral Firestop Plasterboard provide varying FRL and Acoustic
ratings. Refer to the "System Selector Table" on Page 8 for selection of the required system.
Fire-rated Ceiling Systems
20 Standard Construction
1, 2 or 3 Layers of Boral
Firestop Plasterboard
as required
1, 2 or 3 layers of Boral Firestop Timber or steel roof or floor End joints formed on Furring Channels
Plasterboard fixed transverse to framing @ 1200mm max. centres and staggered, otherwise end joints on
Furring Channels @ 600mm max.centres. first layer must be back blocked. Where
All joints staggered min. 200mm. applicable, second and third layers
should be screw laminated to previous
layer @ 200mm max. centres.
Rondo P.N. 237, 226 or 394
Clip @ 1200mm max. centres
Rondo P.N. 129
Furring Channel
@ 600mm max.
centres
200mm
150mm
Note: Systems using 1, 2 or 3 layers of Boral Firestop Plasterboard provide varying FRL and Acoustic
ratings. Refer to the "System Selector Table" on Page 8 for selection of the required system.
Fire-rated Ceiling Systems
Standard Construction 21
Suspended Systems
Rondo P.N. 274 Suspension Bracket fastened
Rondo P.N. 247 to steel member with min. two 10 x 16 Type D
Suspension Bracket screws or equivalent Roofing or floor
anchored to concrete 35mm min.
soffit to engineer’s detail
Steel or timber floor
or ceiling frame
Rondo P.N. 121
Suspension Rods @
Rondo P.N. 274 Suspension
1200mm max. centres OR OR Bracket fastened to timber
framing with min. two
Rondo P.N. 2534 Clip 2.8 x 30 plasterboard nails
or equivalent
Rondo P.N. 129 Furring
Channel @ 600mm
max. centres Rondo P.N. 128 Top
Cross Rail @ 1200mm
max. centres
1, 2 or 3 layers of Boral
Firestop Plasterboard
as required Rondo P.N. 139 Joiner
1, 2 or 3 layers of Boral Firestop Rondo P.N. 121 End joints formed on Furring Channels and
Plasterboard fixed transverse to Furring Suspension Rods staggered, otherwise end joints on first layer
Channels @ 600mm max.centres. All @ 1200 mm max. must be back blocked. Where applicable,
joints staggered min. 200mm. centres second and third layers should be screw
laminated to previous layer @ 200mm
max. centres.
1200mm max.
Rondo P.N. 128 Top
Rondo P.N. 2534 Cross Rail @ 1200mm
Suspension Clip max. centres
1200mm max.
200mm
150mm
Note: Systems using 1, 2 or 3 layers of Boral Firestop Plasterboard provide varying FRL and Acoustic
ratings. Refer to the "System Selector Table" on Page 8 for selection of the required system. Refer to
Rondo catalogue - "Suspended Grid Design".
Fire-rated Ceiling Systems
22 Standard Construction
Rondo P.N. 394 Clip @ 1200mm 0o to 70o 35mm min. Roofing or floor
max. centres fastened to steel
Timber or steel framing member
framing member
2 x 16mm or 3 x 13mm Boral
Rondo P.N. 129 Furring Channel Firestop Plasterboard
@ 600mm max. centres
Rondo P.N. 129 Furring Channel Rondo P.N. 247 Suspension Bracket
@ 600mm max. centres screw fixed to framing with 12 x 75
type 17 roofing screw
1 x 16mm Boral Firestop Plasterboard Direct
Furred Fastened
Rondo P.N. 247 Suspension Bracket Suspension Rods @ 1200mm
screw fixed to furring channel with max.centres
12 x 40 type 17 roofing screw
Acoustic ceiling total mass not to
2
Acoustic ceiling total mass not to exceed 12Kg/m for direct fastened
exceed 4.95Kg/m2 for furred system system
Roofing or floor
Batten as required
Framing Member
Rondo P.N. 274 Suspension Bracket
Two 100 x 100mm pieces of
16mm Boral Firestop with
Rondo P.N. 121 Suspension Rod lower piece slotted for cable
Cable
Rondo P.N. 2534 Suspension Clip
Rondo P.N. 129 Furring Channel
Rondo P.N. 128 Top Cross Rail Cable set in Boral Cornice
Rondo P.N. 139 Joiner Adhesive or approved
fire-rated sealant
1, 2 or 3 layers of Boral Firestop
Plasterboard as required
Roofing or flooring
Batten
Framing member
Rondo P.N. 128 Top Cross Rail Rod set in Boral Cornice Adhesive
or approved fire-rated sealant
Rondo P.N. 139 Joiner
6-10mm gap
24 Pipe Penetrations
Roofing or flooring
Batten
Cage by Promat Fyreguard
Framing member (refer to Promat Fyreguard tests)
Rondo P.N. 274 Suspension Bracket 50 x 20mm Promaseal IBS
by Promat Fyreguard
Rondo P.N. 121 Suspension Rod
Rondo P.N. 129 Furring Channel
Promaseal Fire Mastic
Rondo P.N. 2534 Suspension Clip by Promat Fyreguard
520mm
13mm max.
Rondo P.N. 128 Top Cross Rail 15mm min.
Typical Copper Pipe Penetration Detail - FRL 30/30/30 and FRL 60/60/60
Roofing or flooring
Batten
Framing member
Rondo P.N. 274 Suspension Bracket
uPVC Pipe independently supported
above ceiling
Rondo P.N. 121 Suspension Rod
Roofing or flooring
Batten
Framing member
Rondo P.N. 274 Suspension Bracket
Ceilings to a Radius 25
Roofing or flooring
Batten as required
Framing member
6000 e of pla
to fa
mm
Caulk all perimeter junctions c
1, 2 or 3 layers of Boral
with Boral Cornice Adhesive min erboard Firestop Plasterboard
as required
. rad
st
Taped Joint
ius
Fire-rated Ceiling Systems
26 Change of Pitch
Roofing or flooring
Batten as required
Framing member
Rondo P.N. 121
Suspension Rod @ Rondo P.N. 274
1200mm centres max. Suspension Bracket
Detail A
Roofing or flooring
Batten as required
Framing member
Rondo P.N. 274
Suspension Bracket Rondo P.N. 2534
Suspension Clip
Rondo P.N. 121 Rondo P.N. 128 Top
Suspension Rod @ Cross Rail
1200mm centres max.
Rondo P.N. 139 Joiner
Angle Cleat pop riveted to Top
0-90
0 Cross Rail
Continuous Angle 0.75
Rondo P.N. 129 Furring
B.M.T. Galv. M.S. 50mm
Channel
min. leg length
1, 2 or 3 layers of Boral
600mm
Firestop Plasterboard max.
as required
Cornice Adhesive 20mm max. Tape and set joint
Detail B
Roofing or flooring
Batten as required
Framing member
Rondo P.N. 274 Suitable screw on high
Suspension Bracket side of each clip to
prevent suspension clip
Rondo P.N. 121 sliding up Top Cross Rail
Suspension Rod @
1200mm centres max. Rondo P.N. 139 Joiner
20mm 20mm riveted to Top Cross Rail
Rondo P.N. 2534 max. max.
Suspension Clip Rondo P.N. 128 Top
Cross Rail
Angle Cleat
Rondo P.N. 129 Furring
Channel
Continuous Angle 0.75
B.M.T. Galv. M.S. 50mm 1, 2 or 3 layers of Boral
min. leg length 0-180 0 Firestop Plasterboard
as required
Tape and set joint Cornice Adhesive
Detail C
Fire-rated Ceiling Systems
Bulkheads 27
Roofing or flooring
Framing Member
Roofing or flooring
Framing Member
75 x 75 x 0.75mm BMT
Continuous Galvanised Rondo P.N. 129 Furring Channel
Steel Angle
1, 2 or 3 layers of Boral
Firestop Plasterboard
Corner Bead if Required
as required
Typical Bulkhead - Detail B
Fire-rated Ceiling Systems
28 Bulkheads
Skylight Dome
Skylight Framing
Flashing
Upstand Framing
Roofing as required
Framing Member
Rondo P.N. 274
Suspension Bracket
1, 2 or 3 layers of Boral
Rondo P.N. 121 600mm Firestop Plasterboard
Suspension Rod max. drop as required
Light Recess 29
Flooring or Roof
Framing Member
Rondo P.N. 274
Rondo P.N. 121 Suspension Bracket
Suspension Rod
spaced to support
any additional mass 450mm Rondo P.N. 302
due to light fitting Light Stirrup
100mm
Rondo P.N. 2534
Suspension Clip Light Fitting Box
1, 2 or 3 layers of Boral
Firestop Plasterboard Support Mounting
as required
Timber Floor
Floor Joist
Trimmer
Trimmer
1, 2 or 3 layers of Boral
Firestop Plasterboard Light Fitting
as required
Floor or Ceiling
Structure
Rondo P.N. 274
Rondo P.N. 121 Suspension Bracket
Suspension Rod
75 x75 x 0.75mm Additional Rondo
spaced to support
Galv. Steel Angle P.N. 121 Suspension
any additional mass
100mm Rod
due to light fitting
Rondo P.N. 2534 64CS Stud Frame
Suspension Clip @ 600mm centres
Rondo P.N. 128
50 x 50 x 0.75mm
Top Cross Rail
Angle fixed to Stud
and Top Cross Rail
Rondo P.N. 139 Rondo P.N. 129
Joiner Furring Channel
1, 2 or 3 layers of Boral Light Fitting Box
Firestop Plasterboard 50 x 50 x 0.75mm
Galv. Steel Angle Support Mounting
as required
30 Access Hatch
B B
750mm
900mm
540mm
50 400mm 50
mm mm
600mm
390mm
50 50
mm mm
300mm
450mm
670mm
Section A-A
Access Hatch 31
Roofing or flooring
Batten as required
32 Beam Protection
Roofing or Flooring
Framing member
Steel Beam
Rondo P.N. 226
or 394 Direct Fixing
Clip
1, 2 or 3 layers of 1, 2 or 3 layers of
Boral Firestop Boral Firestop
Plasterboard as Plasterboard as
required required
Corner Bead
if required
Framing members
@ 600mm centres
Steel Beam
1, 2 or 3 layers of
Boral Firestop
Plasterboard as
required
50 x 50 x 0.75mm or
75 x 75 x 0.75mm
continuous Galv.
Steel Angles as
Corner Beads required
if required Furring Channel
Stirrups @ 600mm
centres
50 x 50 x 0.75mm
1, 2 or 3 layers of continuous Galv.
Boral Firestop Type S screws as required Steel Angles
Plasterboard as @ 200mm max. centres
required
Beam Protection 33
Timber Floor
Framing member
Timber Beam
Rondo P.N. 226 or
50 x 50 x 0.75mm or 394 Direct Fixing
75 x 75 x 0.75mm Clip
continuous Galv.
Steel Angles as
required Rondo P.N. 129
Furring Channel
1, 2 or 3 layers of
1, 2 or 3 layers of Boral Firestop
Boral Firestop Plasterboard as
Plasterboard as required - max.
required span of 600mm for
ceiling layers
Roofing or Flooring
Rondo P.N. 226 or
394 Direct Fixing
Clip
1, 2 or 3 layers of
Boral Firestop
Plasterboard as
required Rondo P.N. 129
Furring Channel
50 x 50 x 0.75mm or
Corner Beads 75 x 75 x 0.75mm
if required continuous Galv.
Steel Angles as
required
34 Beam Protection
Timber Floor
Framing member
1, 2 or 3 layers of
1, 2 or 3 layers of Boral Firestop
Boral Firestop Plasterboard as
Plasterboard as required - max.
required span of 600mm for
ceiling layers
Framing members
@ max. 600mm
centres
Roofing or Flooring
1, 2 or 3 layers of
Boral Firestop
Plasterboard as
required
50 x 50 x 0.75mm or
75 x 75 x 0.75mm
continuous Galv.
Corner Beads Steel Angles as
if required required
Timber Beam of
not less than
1, 2 or 3 layers of 500kg/m3 average
Boral Firestop Plasterboard Nails as required
density
Plasterboard as @ 200mm centres
required
Typical Timber Beam Protection - Perspective View - Direct Fixed System
Fire-rated Ceiling Systems
Joints 35
Roofing or flooring
Framing member
Plasterboard as required
10-12
mm
Note: 1. Locate joint centrally between framing members when parallel to framing.
2. Minimum of one layer of Boral Firestop Plasterboard continuous over joint.
3. Ensure single layer system is back blocked.
36 Perimeter Details
Roofing or flooring
Batten as required
Framing member
Rondo P.N. 274 Suspension Bracket
Rondo P.N. 121 Suspension Rod
@ 1200mm max. centres
Approved Sealant
1 x 16mm Boral Firestop Plasterboard
100mm
max.
6-10
1 x 16mm Boral Firestop Plasterboard
mm
Alternative Detail
Perimeter Details 37
Roofing or flooring
Batten as required
Framing member
Rondo P.N. 274 Suspension Bracket
25 x 25mm fillet of
5mm max. Cornice Adhesive
Plasterboard Cornice
o/hang
38 Perimeter Details
Roofing or flooring
Framing member
Rondo P.N. 274 Suspension Bracket
100mm max.
6-10mm
Framing
Plasterboard Cornice or
taped square set finish
Alternative Detail
CL 200mm
CL 200mm
50-75mm
CL
Adhesive Fixing
CL
CL
Back-blocking pieces
of Boral Plasterboard Back-blocking Butt Joints
sheet 200mm wide Back-block butt joints as follows (see Figure 3):
min. glued with • Fix ceiling sheets with ends butted neatly
Cornice Adhesive together. The butt joint should fall within
50mm of the mid-span point between
framing members.
• Use battens and packers to support and
deflect the sheet ends upwards about 2mm.
Roof truss
Boral Plasterboard
ceiling
Figure 1.
Non Fire-rated Ceiling Systems
Back-block
Rafter or joist Architectural Specification
Boral Plasterboard Ceilings shown in the relevant
drawings shall consist of materials supplied by
Boral Plasterboard, fixed and finished in
accordance with the instructions contained in
Boral Plasterboard Technical Manuals and in
Cornice adhesive TecSYS - a comprehensive technical catalogue on
Temporary battens
CD-ROM (see back cover for details).
Plasterboard Packing strip
Temporary nailing As drawings are updated from time to time, users
are advised to check drawing currency before
Figure 3. adopting the procedures and details noted
thereon.
44 System Selector
System Fire-Rating
No. FRL (mins) Description and Physical Data
(Test Ref.)
Standard Construction 45
Direct Fixed Systems
Back blocks laminated to face sheet with End joints formed on Timber or steel roof or
Note: All joints not formed
cornice adhesive on all longitudinal framing members and floor framing @ 600mm
on a framing member must
joints and on butt or end joints staggered max. centres (450mm max.
be back blocked
centres for 10mm Standard
Core Plasterboard).
200mm
300mm
46 Standard Construction
200mm
300mm
Standard Construction 47
Suspended Systems
200mm
300mm
Screws 10mm to
16mm from edges Screw fastening is illustrated using min.
Tape and finish with
1 layer of 10mm or 13mm Boral 6 x 25 Type S or Type D screws. Screws to
preferred Boral
Standard Core Plasterboard or be max. 300mm centres in field and 200mm
Plasterboard joining
10mm Boral Unispan fixed max. centres on end joints (staggered).
system
transverse to Furring Channels Refer to “Plasterboard Application” on
Page 40 for details of adhesive or nail fixing.
Non Fire-rated Ceiling Systems
Rondo P.N. 129 Rondo P.N. 127 Top Rondo P.N. 2534
Furring Channel Cross Rail Suspension Clip Rondo P.N. 121
Suspension Rod
Rondo P.N. 139
Rondo P.N. 139 Joiner
Joiner
Pop rivet
Corner Bead
if required
Corner Bead
if required
Introduction 49
Introduction Installation
The QuietZone™ systems have been designed to The Boral Acoustic Ceiling Mount is designed for
reduce unwanted noise from specific areas of a use in Rondo's Key-Lock Ceiling Suspension
home. There are three QuietZone™ ceiling System. Refer to the Rondo catalogue for the
systems designed to suit varying budgets and spanning and spacing options for furring channels
design considerations - these three systems are and primary rails.
identified as "Quiet", "Quieter" and "Quietest".
Direct Fix Application
Building a QuietZone™ ceiling requires a little Components
more care and attention to detail than standard
systems. Each component in a QuietZone™ • Furring Channel Clip;
System must be securely fixed, necessary services • Rubber Element; and
strategically placed and all plasterboard perimeter • Screw (supplied by others):
edges and openings adequately sealed. - 14-10 x min. 65 mm Type 17 roof screw
into timber;
Note: QuietZone™ is a registered trademark of - 12 or 14 gauge x min. 45 mm drill point
Amatek Limited trading as Insulation Solutions. roofing screw into light gauge steel; or
- “Tapcon” screw into concrete.
Boral Acoustic Ceiling Mount Procedure
The Boral Acoustic Ceiling Mount is used in the Assemble the mount as shown in the following
QuietZone™ systems and provides a cost effective illustration.
solution to impact sound insulation for ceilings
direct fixed or suspended to either concrete
soffits, timber floor joists, roof purlins and the like.
• footfalls;
• rain; and Furring
• equipment Channel Clip
Note: An FRL 90/90/90 system is also available using 2 layers of enhanced firegrade plasterboard.
Contact your Boral Plasterboard Sales Office for details.
QuietZone™ Ceiling Systems
Acoustic Selector 51
Floor/ Rating
System Number and Floor Ceiling With Insulation
Insulation
Assembly Details Covering Depth (Test Ref.)
mm Rw IIC*
QZ4 A bare floor (A) or with a covering of carpet and A 287 50 (AO100) 44 (AO100) 75 mm Noise
underlay (B) or with ceramic tiles on cement Control Batts
sheet (C) - on 190mm x 35mm timber floor joists @ 450mm or B 50 (AO100) 62 (AO100) (glass wool
600mm centres. Furring channel fixed with "blue dot" Acoustic @ nominal
3
Ceiling Mounts(1) to underside of every third joist spaced at C 50 (AO100) 44 (AO100) 14 kg /m )
450mm or every second joist spaced at 600mm. 1 layer of
10mm Boral Plasterboard SoundStop™screw fixed to furring
channel. Insulation in floor/ceiling cavity. Joints finished.
Perimeters acoustically sealed.
A B C
Quiet Ceiling
System
Quieter
Ceiling
System
Quietest
Ceiling
System
* The Impact Insulation Class (IIC) shown as a single number representing impact insulation.
(1) Resilient channel, at 450mm centres directly fixed to underside of joists, may be used instead of furring channel
fixed with acoustic ceiling mounts. Use of resilient channel will result in lower Rw and IIC ratings.
QuietZone™ Ceiling Systems
52 QuietZone™ Installation
Quiet Ceilings
The "Quiet" ceiling system consists of one sheet of 10mm Boral Plasterboard SoundStop fixed to underside
of floor/ceiling joists with Furring Channel (Rondo P.N.129) and Boral Plasterboard Acoustic Ceiling Mount.
QuietZone™ performance
• Rw 50 - Loud speech can be heard but not understood.
• IIC 62 - With floor covering of carpet and underlay, walking is heard as low thump.
For ceiling joists @ 450mm centres, fix ceiling mount to every third joist.
For joists @ 600mm centres, fix ceiling mount to every second joist.
Flooring
Floor joists
TM
75mm Noise Control Batts
QuietZone™ Installation 53
Quieter Ceilings
The "Quieter" ceiling system consists of two sheets of 10mm Boral Plasterboard SoundStop fixed to
underside of floor/ceiling joists with Furring Channel (Rondo P.N.129) and Boral Plasterboard Acoustic
Ceiling Mount.
QuietZone™ performance
• Rw 54 - Very hard to hear loud speech.
• IIC 68 - With floor covering of carpet and underlay, heavy walking heard as low thump.
For ceiling joists @ 450mm centres, fix ceiling mount to every third joist
For joists @ 600mm centres, fix ceiling mount to every second joist
Flooring
Floor joists
TM
75mm Noise Control Batts
First layer
of Boral Plasterboard
SoundStop screw fastened to
Furring Channels
54 QuietZone™ Installation
Quietest Ceilings
The "Quietest" ceiling system consists of two sheets of 10mm Boral Plasterboard SoundStop fixed
to underside of floor/ceiling joists with Furring Channel (Rondo P.N.129) and Boral Plasterboard
Acoustic Ceiling Mount. Two additional layers of 10mm Boral Plasterboard SoundStop are fixed to
underside of flooring with cleats, ensuring a snug fit between joists.
QuietZone™ performance
• Rw 59 - Loud speech cannot be heard.
• IIC 74 - With floor covering of carpet and underlay, heavy walking heard as very low thump.
For ceiling joists @ 450mm centres, fix ceiling mount to every third joist
For joists @ 600mm centres, fix ceiling mount to every second joist
2 x 10mm layers of
Boral Plasterboard SoundStop
to underside of flooring.
Hold in place with plasterboard
Floor joists
cleats nailed to side of floor joists
TM
75mm Noise Control Batts
Flooring
First layer of
Boral Plasterboard SoundStop
screw fastened to Furring Channels
55
Guarantee
Products manufactured and supplied by Boral Australian The information contained in this brochure is available
Gypsum Limited (BAGL) A.C.N. 004 231 976, trading as on TecSYS - a comprehensive technical catalogue on
Boral Plasterboard, are guaranteed to be of consistent CD-ROM.
quality and free from any defects.
Boral Plasterboard products must be installed using the
components and accessories specified and in
accordance with the instructions detailed in Boral
Plasterboard’s technical literature.
Our products are manufactured to suit the requirements
of the building industry in Australia.
Boral Plasterboard may limit its liability under this
guarantee to, at its option, the replacement or payment
of the cost of replacing OR supplying equivalent or
payment of the cost of supplying equivalent OR the
repair or payment of the cost of repairing products found
to be defective.
Important Note
The technical information contained within this manual available electronically on TecSYS (our technical
was correct at the time of printing. Building Systems and catalogue on CD) or the Boral Plasterboard Website.
details are, however, subject to change. To ensure the Alternatively, contact your nearest Boral Plasterboard
information you are using is current, Boral Plasterboard Sales Office or TecASSIST (see details below).
recommends you review the latest building information