Annexure-G

TYPICAL ARCHITECTURAL DRAWING


OF
SUBSTATION AUTOMATION SYSTEM

/conversion/tmp/scratch/414155339.doc
Router Station HMI Gateway GPS
HMI View Node
DR Work Station Clock

Redundant Managed
Ethernet Station Bus IEC 61850

IEC 61850

Switch Switch Switch Switch


for Dia for Dia. for Dia. for Dia.
1 2 3 N

Fibre optic
Connection
IEC 61850

IEDs for
IEDs for IEDs for IEDs for
Control & Control & Control &
protection protection Control &
protection
protection

Note:
1. The redundant managed bus shall be realized by high speed optical bus using
industrial grade components and shall be as per IEC 61850.
2. (Applicable only for 400 kV and 220 kV AIS): The IEDs and switches for
each of the dia. of 765kV and 400kV shall have separate kiosk. For 220kV,
132kV, 66kV yards, IEDs for two adjacent bays can be housed in one Kiosk
along with its switch. For 220/33kV T/F, IEDs for four adjacent 33kV bays can
be housed in one Kiosk along with its switches and For 132/33kV T/F, IEDs for
all 33kV bays of a T/F can be housed in one Kiosk along with its switches.
Note: For 132 kV and 66 kV substations the control and relay panels shall
be housed in the control room building itself.
3. Inside the sub-station, all connections shall be realized as per IEC 61850
protocol.
4. For gateway, it shall communicate with Remote Supervisory Control Centre
(RSCC) on IEC 60870-5-101 protocol.
5. The router to Remote Control Centre (RCC) shall communicate on IEC 60870-
5-101 protocol.
6. The printer as required shall be connected to station bus directly and can be
managed either from station HMI, HMI view node or disturbance recorder work
station. 84