Ground Grid Summary Report

Rg GPR
Touch Potential Step Potential
Ground Ground
Resistance Potential Rise Tolerable Calculated Calculated Tolerable Calculated Calculated
ohm Volts Volts Volts % Volts Volts %
1.894 3800.0 730.5 1928.5 264.0 2429.7 553.4 22.8

Total Fault Current: 2.000 kA Reflection Factor (K): -0.923

Maximum Grid Current: 2.006 kA Surface Layer Derating Factor (Cs): 0.921

Decrement Factor (Df): 1.003

Warnings:
The maximum Touch Voltage exceeds the tolerable limits
Spacing between parallel conductors is smaller than 2.5 m or greater than 22.5 m