K 1.5 400V
K 1.1 525V
K 0.9 690V
3500
58.33333
Isc = Ir/Usc%
Widly accepted thumb Rule to find out transformer full load amp = KVA x 1.4
It is based on with P.F 1.0, 400V.
3.402 3402
428.5282909091
http://jhdq-zj.com/index-en.html
Tyoical Impedence in %
Oil-immersed Cast-resin dry type
4 6
6 6
Continous Current-Carrying of copper conductor (DIN 43671/4370)
Ambient Temp 35C conductor Temp 65C conductor width vertical Clearance between conductor equal to conductor thickness
Continuous Current in A a.c. up to 60Hz ACB
Sizing Cross Section Weight ACB Main Busbar Interconnection
Painted no of conductors
12 x 5 59.5 0.53 1.74 203 345 411 Component Copper Size Cable Size
12 x 10 119.5 1.06 3.49 326 605 879 Amp mm mmSq.
20 x 5 99.1 0.88 2.89 319 560 728 1
20 x 10 199 1.77 5.81 497 924 1320 1.5
30 x 5 149 1.33 4.36 447 760 944 1-10 15x3 2.5
30 x 10 299 2.66 8.73 676 1200 1670 15-20 15x3 4
40 x 5 199 1.77 5.81 573 952 1140 25-32 15x3 6
40 x 10 399 3.55 11.65 850 1470 2000 2580 35-40 15x3 10
50 x 5 249 2.22 7.28 679 1140 1330 2010 50-63 15x3 16
50 x 10 499 4.44 14.57 1020 1720 2320 2950 65-80 15x3 25
60 x 5 299 2.66 8.73 826 1330 1510 2310 85-105 15x3 35
60 x 10 599 5.33 17.49 1180 1960 2610 3290 110-150 15x3 50
80 x 5 399 3.55 11.65 1070 1680 1830 2830 155-175 15x3 70
80 x 10 799 7.11 23.33 1500 2410 3170 3930 180-200 20x5 95
100 x 5 499 4.44 14.57 1300 2010 2150 3300 225-250 20x5 NA
100 x 10 988 8.89 29.17 1810 2850 3720 4530 300 25x5 NA
120 x 10 1200 10.70 35.10 2110 3280 4270 5130 400 30x5 NA
160 x 10 1600 14.20 46.59 2700 4130 5360 6320 500 40x5 NA
200 x 10 2000 17.80 58.40 3290 4970 6430 7490 630 50x5 NA