Professional Documents
Culture Documents
Session - II II - Paper
Paper 77 II - 47
1
GM., 2Manager, 3Vice-President, EMCO LTD.
I. Introduction
Many industrial loads require controlled DC power
or high frequency AC power. Normal 50 Hz or 60
Hz power available in grid needs to be modified
using power electronic circuits to feed such loads.
These circuits are more efficient than previous
types of controls, and being applied in many types
of every day use. They are used in steel, copper,
aluminum, electrochemical and cement industry.
They are also used in variable speed drives for
motor controls which find application in almost
all areas of industrial loads. The transformers
connected to such loads are generally referred to
as converter / rectifier transformers.
Fig. 1 : Three phase bridge rectifier circuit connected to
Power electronic circuit presented new problem 3-phase AC power supply
of harmonics. The operation of rectifier produces
II. Harmonics & Higher Pulse Rectifier
harmonic voltages and currents. The current
harmonics are currents at higher frequencies than Fourier analysis and energy balance of square wave
form confirms that each harmonic in DC voltage
the fundamental frequency of transformer. These
requires harmonic currents of frequencies of 6n+1 &
higher frequency currents cause overheating 6n-1 in AC lines. The magnitude of harmonic current
of transformer, cables, motors, generator and is inversely proportional to the harmonic number or
capacitor connected to same power supply. a value of 1/n.
In transformer, harmonic currents cause high Thus a 6-pulse rectifier converter will begin to
levels of eddy current losses and other stray generate harmonic from 5th & 7th and higher order
harmonics, similarly a 12-pulse rectifier consisting
losses in different parts of transformer and result
of 2-bridge rectifier having power supplies 30°
in overheating of insulation which may cause early
apart will begin to generate harmonic from 11th &
failure of transformer. 13th and higher order. A generalized formula for
A three phase bridge rectifier connected to 3-phase harmonic number can be given for different pulse
number rectifier converter as
AC supply (Fig-1) converts AC power to DC power.
The periodic switching causes DC voltage to be H = Kq ±1
superimposed with high frequency ripple. The where, K = Any integer,
ripple voltage consists of supply voltage with a q = Rectifier converter pulse no.
frequency of multiples of six times the fundamental
The Table-1 shows a variety of harmonics generated
frequency.
by various pulse number rectifier converters. From the
diminishing harmonic orders with the increase in the
rectifier pulse number, it could be deduced that the
total harmonic distortion reduces significantly with
II - 48 Session - II Design - II
increase in pulse numbers. The rectifier converters rectifier converter. The 2 secondary windings will
produce better input and output characteristics with have 30° phase shift and will generate 12-pulses
increasing pulse numbers. per cycle. In order to achieve higher pulse number,
additional phase shifts are required and these are
The Table-1 shows the theoretical magnitudes, while
accomplished using extended delta and zig-zag
in practice the harmonics are greatly reduced due to
(interstar) windings (Fig.2a & 2b).
impedance of system and its elements which restrict
the flow of harmonic currents.
TABLE I
Harmonic current present in input current of
rectifier converter
Har- Rectifier Pulse Number/Harmonic Current
monic (p.u.)
Order 6 12 18 24 36 48
5 0.2000 - - - - -
7 0.1429 - - - - -
11 0.0909 0.0909 - - - -
a) Extended delta shift b) Zig-zag shift
13 0.769 0.769 - - - -
Fig.2
17 0.0588 - 0.0588 - - - The shifts in winding could be 7.5° 10°, 15°, 20°,
19 0.0526 - 0.0526 - - - depending on the requirement. However, depending
on the usage, other shifts are also possible. The below
23 0.0435 0.0435 - 0.0435 - - mentioned different combinations were used for
25 0.400 0.400 - 0.400 - - achieving pulse number for rectifier converter.
a) 6-pulse: The winding feeding to rectifier converter
29 0.0345 - - - - -
could be star or delta.
31 0.0323 - - - - - b) 12-pulse:
35 0.0286 0.0286 0.0286 - 0.0286 - i) The 2 secondary windings feeding to 2 rectifier
converters must be one in star and other in
37 0.027 0.027 0.027 - 0.027 - delta.
41 0.0244 - - - - - ii) Winding feeding to 2 rectifier connection must
be one delta (-7.5°) and other delta (22.5°)
43 0.0233 - - - - -
c) 18-pulse: The 3 secondary windings feeding to 3
47 0.0213 0.0213 - 0.0213 - 0.0213 rectifier converters could be delta (+20°), delta
and delta (-20°) (refer Fig. 3). Another possible
49 0.0204 0.0204 - 0.0204 - 0.0204
combination is delta (+10°), delta (-10°) and star.
In some cases the harmonic currents are greater
than the magnitude defined. Such systems are
equipped with power factor correction capacitors
and filters. In fact sometimes it is not easy to predict
the behavior of filters. This has led to shift in focus
towards multi-secondary transformer, which allows
the use of higher pulse rectifier converter circuits.
the incoming supply yard of the user. The winding The transformers at (a) & (b) have phase shift in
configuration of the transformer is shown in primary winding. The primary winding is also provided
Fig. 8. with ± 5%, ± 2.5% off circuit taps. The phase shift of
normal tap is nearly perfect, however at other taps it is
As discussed earlier, there are numerous
not feasible to perfectly match the desired phase shift.
possibilities of providing phase shift. So far we
It is rather recommended that such transformer may
have discussed phase shift provided in secondary
not be provided with off circuit taps at all and voltage
winding only. It is possible to provide phase shift
profile be maintained before transformer preferably at
in primary winding also. EMCO has designed,
incoming supply station of the industry itself.
manufactured and tested transformer for
rectifier converter duty where primary winding The transformer supplied at (c) consisted of zig-zag
was provided with phase shift. The 4 MVA winding on secondary side. Zig-zag winding placement
transformers with following vector group were and lead location increases complexity of transformer
supplied to customers (a) D (+7.5°) d0y11; (b) D it is therefore recommend that zig-zag winding should
(-7.5°) d2y1 & (c) Dyn11zn0. be used for affecting phase shift in the transformer.
The desired 300 phase shift could have been provided
by using delta winding in place of zig-zag winding.
V. Conclusions
All the above transformers have been designed and
supplied as per customer specification. We must keep
in mind that multi-winding transformers are costlier
than the same rating power transformers, even without
considering the overrating due to harmonic loading.
The emphasis should be on selecting a configuration
which is simple so that unnecessary cost overruns
could be avoided. Broadly, may keep following points
in mind.
1. As the choice of turns is limited on secondary side
due to low voltage, the phase shift is desirable in
primary circuits wherever feasible.
2. For achieving the desired phase shift, extended
delta and zig-zag winding connections are used.
Fig. 8 : Connection diagram of 12MVA, 33/ 4X0.612kV,
24-pulse transformer manufactured at EMCO 3. Whenever the phase shift is provided in the
primary winding, avoid taps on transformer as it
The typical winding arrangement inside the transformer is not always possible to achieve the same phase
tank for 12MVA, 33/4 x 0.612 kV, 24-pulse transformer shift on all taps also.
is shown in below Fig. 9.
4. It may be noted that lower order harmonic
cancellation is generally not perfect due to various
factors, such as turns ratio error (star & delta), and
extended delta causing inaccurate phase shift,
unbalanced loading, tap changes and difference
in impedance of various pairs of windings. It is
common to assume 5% contribution for lower
harmonics.
5. Ground shield: Grounded shield between primary
and secondary winding is recommended as it
provides capacitance de-coupling of windings. It
also helps in reducing the transfer of transients
from primary side to secondary side and also
in minimizing the transfer of high frequency
disturbances to transformer primary side from
Fig. 9: Winding placement over core (24-pulse transformer) rectifier converter.
Session - II Paper 7 II - 51