Professional Documents
Culture Documents
FBX
Gas Insulated Ring Main Unit - Up to 24 kV
Medium Voltage Distribution
FBX/schneider-electric.com
General contents
Overview 8
FBX range 24
Components 56
Tools 104
Reliability
Efficiency
Connected
Electrical utilities
HV/MV
MV/LV
Peace
+ Eff. of mind
Power
management
Wide range of options are avaiable, please contact us for more details
PM107113
Pre wired cables
PM107114
Single location for
Terminal blocks
••Reduced wiring time
PM107115
PM107112
Field of application 10
Reliability 13
Efficiency 16
DM106971
CCT1
PM103309
CCCT2
PM107117
CCT2
PM107118
CBb
CC
T2
M
CCT2 CT2CT2
CCT2 CC CCC
RE
T2
M
T2 T2
Private metering
PM107119
DE59773
Switching large site
PM107120
T1 function
PM107124
• Both earthing switches are connected mechanically and are activated with a
single operating mechanism
• The switch-disconnector is equipped with a spring-loaded mechanism for the
closing operations and a stored energy mechanism for breaking operations
which is mechanically pre-loaded
• A pushbutton for tripping and tripping coil to open the switch are available as
options
• The earthing function is operated with a separate spring mechanism
T2 function
• The disconnector and earthing switch with making capacity are activated by a
spring-loaded mechanism
• The vacuum circuit-breaker is equipped with an energy accumulation spring
loaded mechanism
• The operating sequence in case of the use of a motorized mechanism is the
following: O – 3 min. – CO
Switchgear status • The vacuum circuit-breaker can be tripped manually by a pushbutton or
Padlocking facilities
• Access to the switch or circuit breaker operating
CBb function
shaft This function uses the same vacuum circuit breaker and mechanism as the CB
• Access to the earthing switch operating shaft function
DM106973
Protection index (IP) -- Reduction of losses thanks to the low value of lower value of power dissipation
(the fuse-switches of a 1000 kVA transformer feeder can dissipate 100 W)
• Main electrical circuits: IP67
• Reduced maintenance costs with no need for fuse replacement
• Fuse compartment: IP65 (option: IP67)
• Operating mechanisms: IP2X (option: IP33)
• Cable connection compartment: IP2XC
• Busbar: 1250 A on top of unit: IP67
• Switchgear: IK07
Flood proof (option): Successfully tested under • The fuses are located within plugged and
water for 24 hours at 24 kV / 50 Hz insulated fuse-holders
IAC Class
Evacuation of gaz in the event of
AF A-FL A-FLR
overpressure
16 kA 1s 20 kA 1s 25 kA 1s 16 kA 1s 20 kA 1s 25 kA 1s 16 kA 1s 20 kA 1s
Side Gas Bottom
Exhaust Deflector Up to Un = Up to Un = Up to
panel cooler plate
24 kV 12 kV 24 kV 12 kV 24 kV
With
Rear
With
Downwards Without (1) Without
With Without
Without
Rear and With (2) Without
downwards
Double With Without
side panel With (2) Without
Chimney
Top Without Without
and base
Gas cooler placed on the cable duct / Gas cooler placed on rear side
Extension on site
PE58534
and/or on premise
IT
Easergy T300
PM106310
VPIS
PM107127
PM106311
LPVT
PM106309
Measurement CTs
DM106998
Grid
Apps,
Analytics
& Services
EcoStruxure EcoStruxure EcoStruxure
Asset Advisor Microgrid Advisor ADMS
End-to-end cybersecurity
Edge
Control
EcoStruxure EcoStruxure EcoStruxure
Substation Operation Microgrid Operation Advanced Metering Operation
T300
FBX
Protection / Metering
Network management
PM106669
Power management
DM106977
Protection
DM106978
Install
Life Cycle Services
Life Cycle Services Schneider Electric will help you to install efficient, reliable and secured solutions
based on your plans.
DB408843
Install
How do I install and commission? Operate
Schneider Electric helps you maximize your installation uptime and control your
capital expenditure through its service offer.
Operate
How do I operate and maintain? • Asset operation solutions: Provide the information you need to enhance
installation performance, and optimize asset maintenance and investment
• Advantage service plans: Customize service plans that cover preventive,
predictive and corrective maintenance
Optimize
How do I optimize? • On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
• Spare parts management: Ensure spare parts availability and optimized
maintenance budget of your spare parts
Renew • Technical training: Build the necessary skills and competencies to properly
How do I renew my solution? and efficiently operate your installations
Optimize
Schneider Electric can make recommendations for improved availability, reliability
and quality.
• MP4 electrical assessment of customer installation: Define an improvement
and risk management program
Renew
Schneider Electric extends the life of your system while providing upgrades.
We offer to take full responsibility for the end-of-life processing of old electrical
equipment.
• ECOFIT™: Keep up to date and improve the performance of your electrical
installations (LV, MV, protection relays, etc.)
• MV product end of life: Recycle and recover outdated equipment with end-of-
life services
Quality assurance
Schneider Electric incorporates a functional organization into each of its business
ISO 9001 ISO 9002
Qualité Qualité
units and manufacturing plants, the purpose of which is to provide a means of
AFNOR CERTIFICATION AFNOR CERTIFICATION checking quality and monitoring compliance with standards.
This procedure is:
• Uniform throughout all departments
• Recognized by many customers and approved organizations
But above all, its strict application has allowed us to obtain the recognition of
AFNOR certification, an independant organisation delivering AFAQ quality mark.
The quality system for the design and manufacture of circuit breakers has been
certified in conformity with the requirements of the ISO 9001:2015 quality assurance
model.
Premium
TM
RoHS
Schneider Electric products are subject to RoHS requirements at
a worldwide level, even for the many products that are not required
to comply with the terms of the regulation. Compliance certificates are
Green Premium is the only label that allows you to available for products that fulfil the criteria of this European initiative,
effectively develop and promote an environmental policy which aims to eliminate hazardous substances.
whilst preserving your business efficiency.
This ecolabel guarantees compliance with up-to-date REACh
environmental regulations, but it does more than this. Schneider Electric applies the strict REACh regulation on its products at
a worldwide level, and discloses extensive information concerning the
presence of SVHC (Substances of Very High Concern) in all of these
products.
PE58548
• Dielectric check
The volume of the insulating gas used in FBX valve
• Electrical tests is equivalent to 0.5% of the total weight of the
The quality control department records and signs switchboard. At the end of the switchboard’s service
the results obtained on the test certificate for life, gas can be evacuated via the valve to be recycled
each device. thanks to a process developped by gas suppliers.
Waste processing
Recommended
Type of waste Destination
processing
Recovery, storage and
SF6 gas Supplier
regeneration
Shredding, sorting and
Steel & stainless steel Local recovery agent
recycling
Shredding, sorting and
Non-ferrous metals Local recovery agent
recycling
Revalorisation at a lower
Epoxy resin Cement plant
added value
Thermoplastics Local recovery agent Incineration
Molecular sieve Authorised network Elimination
Soiled protective equipment Authorised network Incineration
Separation of sheathing
Cables Local recovery agent
and conductors
General characteristics 26
Overview 26
Product description 27
User interface description 28
Interlocks 31
Cable compartment 32
Extensibility 34
Fuse compartment 35
Sb Busbar switch-disconnector • The flexibility and modularity of FBX-E make FBX an ideal MV switchboard for
applications in the industrial sector, or for those liable to change in time such as
CB Outgoing feeder protection with
public distribution network.
vacuum circuit-breaker
CBb Busbar protection with
vacuum circuit-breaker
M Metering functional unit
PE58608
PE58606
PE58607
7 6
9
2 5 2
1 2 1
3 1
8
4
4
4
1. Hermetically-sealed stainless steel tank filled with gas to insulate the main circuit
2. Operating mechanism compartment and mimic diagram
3. Fuse compartment
4. Cables compartment door
5. Vacuum circuit-breaker
6. Tank pressure manometer
7. Voltage presence detection system and low voltage part
8. Cable plug-in connections
9. 3-position switch-disconnector
Switchboard
Each switching device is equipped with an access point for the control lever
Thanks to its clear mimic diagram, the
and an indicator of the mechanical position.
user interface makes it easy and safe
The two earthing switches, both upstream and downstream from the MV
to operate FBX.
fuse holders on the T1 switch-disconnector fuse combination, are activated
simultaneously by a common mechanism.
The switch-disconnectors and vacuum circuit-breakers can be equipped,
as an option, by a motorised control mechanism. In this case, a mechanical
back-up crank handle is provided.
DE59965
DE59963
DE59964
and disconnector
12. Protection relay tripping indicator
13. Interlocking between the disconnector 11
0
and earthing switch 8 12
14. Lever hub socket for the disconnector 6 13
15. Disconnector position indicator 16 2
16. Optional: lever hub socket for the manual
back-up operation of the switch-disconnector 1
motorised mechanism (in this case, the opening Direct incoming feeder 14
without earthing switch (R)
7 or 4 is blocked off at the factory) 6
DE59962
15
1. Lever hub socket for the earthing switch Feeder cable protection with vacuum circuit-breaker (CB)
2. Earthing switch position indicator
19 17 20 18
6. Interlocking between the cable compartment
DM103195
door and the earthing switch
10. Interlocking of the vacuum circuit-breaker
and disconnector 9 21
11. Protection relay tripping indicator
11
13. Lever hub socket for the disconnector
14. Disconnector position indicator 2 3
1 14
15. Optional: lever hub socket for the manual
13
back-up operation of the switch-disconnector 15
motorised mechanism (in this case, the opening 6
7 or 4 is blocked off at the factory)
17. Operations counter
18. Lever hub for circuit-breaker spring arming
19. Indicator showing the status of the spring (
primed or released)
Padlocking 19 17 20 18
The actuator’s operating hub can be controlled
DM 103196
by padlock.
PM 103927
9
21
11
13
1 15
14
2
Obstruction of the lever
hub socket by padlock
3
2
1
13
14
M M M M
E
B B
C C
A A
Function Function
A Technical data
M1 M3
D D D rating plate
B Voltage transformers
C Current transformers
D Cable connections
E Busbar connections
E E E
B B
C C
A A
Function Function
D M2 M4
Access to the cables compartment and to the fuses is only possible if the
appropriate outgoing feeder is connected to earth.
The switchboards are equipped in production series with the following interlocks:
Functional unit with switch-disconnector and earthing switch, switch-disconnector fuse combination
(C, T1 and Sb functions)
Interrupting Position Interlock status
mechanism
Switch-disconnector Closed – Locked Locked
Open – Unlocked Locked, if earthing switch is open
Earthing switch (ES) Closed Locked – Unlocked
Open Unlocked – Locked
Cable or fuses Removed Locked Locked –
compartment panel Fitted • Unlocked, if earthing switch is open Unlocked –
(Sb function not • Locked, if earthing switch is closed
concerned)
Switch-disconnector Earthing switch Cables compartment panel or fuses
Option: switch-disconnector – locking of the cables compartment panel, for example, for the cable tests.
• Completely insulated
• In metallic housing
• Partially insulated.
R / RE C T1 T2 / CB
1
– – –
4
1. Sliding contact pin
3
2. Support plate
T1 (as standard):
PF250 plug-in bushing 3. Mounting flange
NF EN 50181, with A type connection 4. Mounting device
(Ir: 250 A; contact finger Ø M7.9 +0.02/-0.05 mm)
2
2 3 Connector cone Type C (630 A)
1 Switchboard function
DE59970b
1
R / RE C T1 T2 / CB
(optional)
4 3
1. Cross member - Male
Screw depth 2. Support plate
20-35 mm 3. Screw contact
Type of connection
FBX cable compartment is spacious and allows for various connections
(cf. § Selection of cables):
• Single cable per phase
• Two cables per phase
• Single cable per phase + surge arresters
• A triple cable per phase connection is also available (please consult us)
• No cable - bushing protected by insulating plug.
DE59985
DE59987
Extensibility of FBX-E
PE58534
Fuse compartment
PE58615
The fuses are located within plugged and insulated fuse-holders. These fuse
holders are integrated into the gas tank and offer the following advantages:
• The electrical field is placed in the SF6 gas,
• The fuse-holder plugs are placed outside the electrical field which is contained
in the tank filled with SF6 gas,
• The fuse-holder is located in the tank and cannot be affected by outside
elements,
• The dielectric strength of the plug is thus not ensured by the compression of a
seal but by an insulating distance.
Fuse tripping
FBX with fuse protection The stored energy mechanism and the tripping striker open all three phases thanks
to the switch-disconnector. If the striker on a single HV fuse is actuated, all three
phases are disconnected.
Fuse replacement
The interlocking guarantees maximum safety for the personnel during the replacement of fuses. The fuse compartment panel can only
be opened if it has been earthed correctly. Inversely, the earthing can only be removed once the fuse compartment panel is closed and
locked.
Two earthing switches with making capacity (both upstream and downstream from the fuses) allow the fuses to be replaced
without using auxiliary equipment. The two earthing switches with making capacity are operated by a common spring loaded
mechanism.
PE58616
PE58617
PE58618
It is recommended that you replace Do not turn the gripping surfaces Removal of the fuse
all three fuses at the same time but use them to pull the fuse out
FBX performances meet the definition of a “sealed pressure system” as laid down
in the IEC recommendations.
FBX tank is filled with SF6 rated pressure at 20°C: 0.03 MPa, and sealed for life
after filling. Its tightness, which is systematically checked at the factory, gives the
switchgear a high life expectancy.
Operating conditions
• Temperature classification: –5°C indoors (option: –25°C)
• Ambient temperature: from –5°C to +40°C (option: –25°C)
Reduction of the current assigned in continuous service
according to the maximum ambient temperature (option: up to +55°C for reduced service currents)
Acceptable current (A) • Average value over 24 hours (max.): +35°C
640
DE59992
(1) PM class according to IEC 62271-200 edition 2: metallic partitioning between compartments.
(2) Based on IEC62271-200 edition 2, FBX is now classified as LSC2 apart from the functions (R,RE
& M) which are LSC1.
IEC 62271-200
(A.C. metal enclosed switchgear and controlgear for rated voltage above
1 kV and up to and including 52 kV)
• Switchgear classification: PM class (metallic partitioning)
• Loss of service continuity: LSC2 class as per IEC 2011 edition 2 (apart from
functions R, RE, M which are LSC1)
Other applicable • Internal arc classification up to A-FLR 20kA 1 sec. (Please refer to section
referring to internal arc performance for precise values)
standards
IEC 62271-100 (high voltage alternating current
circuit breakers) Switch-disconnectors
• S
witch-fuse combinations: IEC 62271-105:
IEC 62271-103 (high voltage switches for rated voltage above 1 kV and less
alternating current switch-fuse combination.
than 52 kV)
• E
arthing switch: IEC 62271-102: alternating current
• Class M1/E3 /C1
disconnectors and earthing switches.
• 100 CO cycles at rated current and 0.7 p.f.
• Electrical relays: IEC 60255.
• 1 000 mechanical opening operations.
C, Sb, R, RE functions 45
T1 function 46
T2 function 47
M function 49
Mechanism operations 50
Maximum number of mechanism operations 50
Choice of mechanisms and equipment 51
SFU/SU, SF/SU operating mechanisms 53
C 150 operating mechanisms 54
C function T2 function
• The interrupting mechanisms are located in the • The transformer outgoing feeder with vacuum circuit-breaker can be used
sealed-for-life tank filled with gas. for applications where the load current is too high for the use of a switch-
• The three-position switch is equipped with a disconnector fuse combination.
spring-loaded closing mechanism • A typical application is the protection of distribution transformers and wind farm
for the switch-disconnector function and the installations up to a theoretical power of 21 MVA for 24 kV.
earthing switch function. • The T2 three-phase transformer protection comprises a vacuum circuit-breaker
(located upstream) and a 3-position disconnector carrying out the sectionalizing
of the line.
T1 function • The disconnector and earthing switch with making capacity are activated by
a spring-loaded mechanism.
• To make the replacement of HV fuses secure, • The vacuum circuit-breaker is equipped with an energy accumulation spring-
earthing switches are placed both upstream and loaded mechanism.
downstream from the fuses.
• The operating sequence in case of the use of a motorized mechanism
• Both earthing switches are connected mechanically is the following: O – 3 min. – CO.
and are activated with a single operating
• The vacuum circuit-breaker can be tripped manually by a pushbutton or
mechanism.
automatically by a motorized mechanism controlled by a protection relay
• The switch-disconnector is equipped with a spring- (standard equipment – other relays available on request). The latter analyses
loaded mechanism for the metering data captured by the current transformers on each phase and is
the closing operations and a stored energy triggered at pre-defined threshold levels.
mechanism for breaking operations which is
• Other non-autonomous relays can be used by fitting a low voltage cabinet with
mechanically pre-loaded.
the current transformers fitted either to the withdrawable terminals or onto the
• When the striker pin trips on the blowing of one of outgoing feeder cables.
the HV fuses, the switch-disconnector is opened
• Fault trips require no auxiliary voltage if an autonomous relay is used.
mechanically on all three phases.
• An indicator on the front panel of the FBX visually
signals the interruption due to
a fuse blowing.
R function
• A pushbutton for tripping the opening of the switch • This function allows for the direct connection of a cable incoming feeder
is available as an option. to the busbar of the FBX switchboard.
• An opening by tripping coil is also possible.
• The earthing function is operated with a separate
spring mechanism. RE function
• This function, which is equipped with an earthing switch, allows for the direct
connection of a cable incoming feeder to the busbar of the FBX switchboard.
CB function
• The CB function includes a vacuum circuit-breaker M function
and a three-position disconnector switch.
• Fast auto-reclosing operating cycle: • This function allows for metering of electricity consumption thanks to its current
O - 0.3 s - CO - 15 s - CO. and voltage transformers.
• The earthing switch with making capacity is • To fit all possible configurations, four metering panel versions exist with different
activated by a spring-loaded mechanism. busbar positions. In the M1 to M4 versions, the current and voltage transformers
can be switched between each other.
• The vacuum circuit-breaker is equipped with a
double-latch energy accumulation spring-loaded
Options:
mechanism and can be pre-loaded manually or
electrically for a complete OCO cycle. • Flooring for M1, M2 and M3 with a rubber grommet for the passage of the
cables.
• An integrated protection relay is linked to the
circuit-breaker. • Flooring completely closed, but with overpressure escape devices.
or
M4 Version
or
DE59973
1 function
DE59976
DE59977
DE59978
DE59979
DE59980
Versions Versions
C C C C C
C T1 C C T1 Versions Versions Version Version Version
C T2 C C T2
C T1 Sb CBb CB
RE T1 C RE T1
R T2
RE T2 C RE T2
RE
R RE T1
R RE T2
RE R T1 2 functions 3 functions 4 functions
RE R T2
DE59981
DE59982
DE59983
4 functions 5 functions
DE59974
DE59975
1 function
DM106981
DM106982
DM106983
DM106984
M2 1 380 490
1 720 1 005
M3 1 380 490
(1) General use switch. The characteristics of the switch-disconnector are not applicable to the R and RE functions.
(2) For the first cable test on a new unit. Later tests can be carried out at 67 kV.
T1 function
• Transformer protection
with switch-disconnector fuse combination
T2 function
• Outgoing feeder
• Busbar protection
protection with I>
with vacuum I>
vacuum I>>
circuit-breaker
circuit-breaker I>>
M function
• Metering
h1
Remarks:
• Installation of current and voltage metering devices
is possible with or without
a selector switch, e2 e2
• Option: a voltage indicator can be added
40
• Pre-assembled cable connections can be
purchased as an option
e1
b1
b1
e1
Dimensions Um (kV)
12 kV version 24 kV version
b1 148 mm 178 mm 120
e1 125 mm 150 mm
e2 270 mm 280 mm
Current transformer (C) Single phase voltage transformer (W)
h1 220 mm 280 mm (DIN 42600, Section 8) (DIN 42600, Section 9)
500 500
operations
1 000
n
500
operations
of breaking
100 100
50 50
breaking
100
Number
50
Number of
10 10
10
10
50
50
100
100
500
500
630
630
1000
1000
10 Breaking current Ia (A)
Breaking current Ia (A)
10
50
100
500
630
1000
T1 function T1 function
Transformer protectionTransformer
with switch-disconnector
protection with switch-disconnector Transformer protection
Transformer
with switch-disconnector
protection with switch-disconnector
DM103203EN
DM103203EN
operations
operations
n
n
operations
operations
of breaking
of breaking
breaking
breaking
Number
Number
Number of
Number of
1100
1100
2000
2000
DM103204EN
5 000 5 000
100 100
100 100 50
50
50 50
10 10 10 10
20
1
25
1
5
0,1
5
0,4
0,5
0,6
10
50
0,4
0,5
0,6
10
50
20
1
25
1
5
0,1
5
0,4
0,5
0,6
10
50
0,4
0,5
0,6
10
50
Rated short
Rated short circuit breaking circuit
current breaking current Ia (kA)
Ia (kA) Rated short
Rated short circuit breaking circuit
current breaking current Ia (kA)
Ia (kA)
SU (tumbler)
It is a tumbler mechanism for closing operation.
The opening is manual and dependent of the operator, a spring is loaded and
stores energy for next closing.
The closing is independent of the operator, the energy is released from the spring
and closes the earthing switch in a snap operation.
C 150 mechanism
These operating mechanisms use the energy stored by springs to close and open
the circuit-breaker on the CB and CBb functions. There are two types:
• Manual: the operator manually operates to load the control mechanism’s spring.
The spring is held in place by a latch, freed manually by a mechanical button,
causing:
- the release of the spring
- the closing of the CB
- the arming of the trip spring, now held in place by a latch.
It is thus possible to open the circuit-breaker by freeing the trip spring latch
manually (mechanical button) or electrically (electro-magnet).
Note: with the circuit-breaker closed, it is possible to rearm the closing spring,
which authorises a rapid re-closure cycle.
• Motorized: the closing spring is armed by a motor (arming time < 7 s).
Opening and closure operations are carried out electrically (magnets).
Note: It is possible to manually arm, close and trip the circuit-breakers.
Functions
Type of operating mechanism C T1 T2 R RE CB CBb Sb
Switch-disconnector SFU – – –
SF – – – – –
Earthing switch SU –
Circuit-breaker SF – – – – – – –
C150 – – – – – –
Equipment C T1 T2 R RE CB CBb Sb
Manual opening and closing –
Mechanical position indicator –
Motorization – –
Trip coil – – –
if SF drive
2nd trip coil – – – – –
Autonomous tripping device without any auxiliary source
– – – – – –
(striker)
Undervoltage tripping coil – – (1) – – –
Closing coil – – – – – –
Operating counter – – – – –
Auxiliary contacts C T1 T2 R RE CB CBb Sb
Switch-disconnector Manual: 2 NO + 2 NC
– –
position Motorized: 2 NO + 2 NC
Earthing switch position 1 NO + 1NC –
Vacuum circuit-breaker Manual: 2 NO + 2 NC
– – – – –
position Motorized: 2 NO + 2 NC
Fuse blown indicators 2 micro switches (NO + NC) – – – – – – –
Legend: Standard / Option (1) Consult us for availability
Note:
The connection and wiring diagrams for the motorized mechanism, the magnetic
tripping devices and auxiliary contacts are supplied in the event of an order .
Protection relays 61
DPX-1 autonomous protection relay 61
Key locking 69
Accessories 75
Fuses 76
1 250 A busbar 79
Generator ATS 82
• M
odular architecture with very small footprint, power supply back-up and
up to 24 FBX functions and 3 transformers management.
• P
owerful communication with Standard and secure protocol, open P2P
communication for decentralized automation, easy to upgrade on site.
• A
dvanced MV and LV network control with directional fault detection for
distributed generation networks, MV & LV power measurement (IEC 61557-12),
power quality measurement (IEC 61000-4-30 Class S), MV voltage monitoring
(VPIS, VDS, LPVT, VT), PLC framework IEC61131-3 for automation design,
MV broken conductor detection…
• Embedded cyber security per Cyber Regulation (IEEE P1686, IEC 62351).
• U
ser interface technology with web server compatibility with PC, smartphone
and digital tablet.
Network
Control Center
SCADA / DMS
MDM / AMM
Other Services
communication gateway
• Flexible communication to control center and other customer
IT applications
–– Standard and security-focused protocols: IEC 101/104, DNP3, IEC 61850(*),
Modbus(*)
–– Open peer-to-peer communication to self-healing application
–– Flexible communication media (Ethernet, USB, GPRS, 2G, 3G, 4G, radio)
• Cyber security management
• Open to third-party devices with many protocol capabilities
• Built-in webserver for commissioning and maintenance with local and remote
access, compatible with PC, tablet and smartphone devices
• Embedded IEC 601131-3 PLC for automation design
Voltage monitoring
• Transformer temperature measurement and monitoring
• Voltage, current and power measurement according to IEC 61557-12
• Broken conductor detection (one phase lost MV or LV)
• Power quality according to IEC 61000-4-30 class S
The DPX-1 system, consisting of a compact protection relay and a toroidal type
current transformer, has been specially developed for compact medium voltage
PE58627
Standard current
transformer Protection characteristics
Description Conversion Rated Degree of • Protection independent from the line current at two levels (UMZ).
power precision • Inverse time delay characteristics with an independent time short circuit current
CT1 30/1 A 10P5 element:
CT2 50/1 A - Normal Inverse (NINV)
CT3 100/1 A
1 VA - Very Inverse (VINV)
CT4 200/1 A 5P10
- Extremely Inverse (EINV)
CT5 400/1 A
CT6 800/1 A - Long Inverse (LINV)
These standard current transformers are available in these
- RI-Inverse (RIINV)
versions. • The system of protection enables a tripping time of 40 ms.
• The tripping time in the event of a fault varies, depending on the fault current
level.
PE58628
DE59991b-1
DE59991b-2
1000
100
I>
0.5 2.5 100
10 a=
10.0
t[s] 8.0
t[s] 300 6.0
10 4.0
tI> 3.0
1
2.0
0.04 1.4
I>> 1.0
1.0 20 0.8
3 0.6
0.5
tI>> 1 0.4
0.1 0.3
0.2
0.04
0.1
0.05
0.01 0.1
1 10 1 2 3 4 5 6 7 8 910 20
DE59991b-4 1000
1000
100
100
a=
t[s] t[s] 10
10
10.0
a= 8.0
6.0
10.0 4.0
8.0 3.0
6.0
1 4.0 2.0
3.0 1 1.4
2.0 1.0
1.4 0.8
1.0 0.6
0.8 0.5
0.6 0.4
0.1 0.5 0.3
0.4
0.3 0.2
0.05 0.1 0.2 0.1
0.1
0.05
0.01
1 2 3 4 5 6 7 8 910 20 1 2 3 4 5 6 7 8 910 20
DE59991b-6
a=
10.0
8.0
7.0
1000 6.0
5.0
4.0
10 3.0
2.0
100
a=
t[s] 10.0
8.0
t[s]
1.0
6.0
5.0 0.8
4.0 0.7
3.0 0.6
2.0 0.5
10 0.4
1.0 1 0.3
0.8
0.6
0.5
0.4 0.2
0.3
0.2
1
0.1
0.1
0.05
0.05
0.1 0.1
1 2 3 4 5 6 7 8 910 20 1 2 3 4 5 6 7 8 910 20
Easergy Flair indicators work with all types of neutral networks and benefit from
LCD displays for high visibility of the information. Optional external outdoor
Easergy Flair 21D indicating lamp.
Functions
• Indication of phase-phase and phase-earth faults
PE57784
PM107115
Easy to use and reliable
Easergy Flair 23D • Automatic setting on site
• Fault indication by LED, LCD and outdoor light
indicator (optional)
• Battery life of 15 years (Easergy Flair 22D)
PE57787
networks, FBX can be equipped with directional fault indicators such as:
Characteristics
Flair 21D Flair 22D & 23D Flair 23DM
Frequency (auto-detection) 50 Hz and 60 Hz 50 Hz and 60 Hz 50 Hz and 60 Hz
Operating voltage Un: 3 to 36 kV - Vn: 1,7 to Un: 3 to 36 kV - Vn: 1,7 to Un: 3 to 36 kV - Vn: 1,7 to
24 kV 24 kV 24 kV
Neutral Phase-to-phase fault All systems All systems All systems
Phase-to-earth fault Impedance-earthed, Impedance-earthed, directly compensated, isolated
directly earthed Flair 22D: (type B), Flair 23D, type (B,C) (3)
Measurements
Load Minimum current >2A >2A >2A
Current (A) For each phase Ammeter Ammeter OFF or AUTO or 100 to
(resolution 1 A) Accuracy: ± (2% Maximeter Maximeter 800 A (50A increments)
+ 2 digits)
Voltage (% of rated With VPIS-VO option Phase-to-neutral or
voltage) Accuracy: ±1% phase-to-phase voltage
Fault detection
Threshold configuration Via microswitches Via front panel buttons Via front panel buttons
Overcurrent fault Auto-calibration Yes Yes Yes
Accuracy ±10% Thresholds AUTO or 200, 400, 600, OFF or AUTO or 100 to OFF or AUTO or 100 to
800 A 800 A 800 A
(50 A increments) (50 A increments)
Earth fault Auto-calibration Yes Yes Yes
With 3 phase CTs Algorithm Σ 3I + di / dt Σ 3I + di / dt Σ 3I + di / dt
Accuracy ±10% Thresholds OFF or AUTO or 40, 60, 80, OFF or 5 (2) to 30 A (5 A increments) and 30 to 200 A
100, 120, 160 A (10 A increments)
Earth fault Auto-calibration - No No
With zero sequence CT Thresholds - OFF or AUTO (4) or 5 to 30 A (5 A increments) and from
Accuracy ±10% or ±1 A 30 to 200 A
(10 A increments) (1)
Fault acknowledge time delay 60 ms
Fault confirmation time delay 70 s 3 s, 70 s or OFF
Inrush Time delay 3 s, 70 s or OFF
Reset Automatic Upon current return 2 A Upon current return 2 A
(70 s or OFF) (3 s, 70 s or OFF)
Manual via front panel Yes Yes Yes
External contact Yes Yes Yes
Deferred 4 h 1, 2, 3, 4, 8, 12, 16, 20, 24 h. Factory setting = 4 h
Indications LED Yes Yes Yes
External contact Yes Yes Yes
External indicator lamp Yes (with battery) Yes (without battery) Yes (without battery)
Phase indication Yes Yes Yes
Communication
RS485 2-wire, connector with LEDs No No Yes
Speed: auto-detection 9600, 19200, 38400 bits/s - Class A05
• Accessible data: Phase and earth faults; Fault passage counters including transient faults
• Current measurements (I1, I2, I3, I0), max. current, voltage (U, V, residual)
• Resetting of fault indication, counters and max. values
• Fault and voltage presence/absence detection parameters
• Communication parameters
• Time synchronisation and time-tagged events
(1) The minimum threshold 5 A can only be reached with the earth CT ref CTRH2200.
(2) 20 A minimum for resistive neutral type,
5A minimum for isolated or compensated neutral type
(3) Type C mounting is not available on compensated neutral
(4) only with isolated and compensated neutra
system
• The VPIS V2 is a self-powered voltage presence indicating system, in
VPIS v2, Voltage Presence Indicator System
compliance with the IEC 62271-206 standard
• Connectors on the front panel allow the use of a phase comparator
PE58144
VD23 can display the MV network voltage (in % of service voltage), active the
relay output R1 to monitor a loss of voltage on 1 phase at least and active the relay
output R2 to monitor a presence of voltage on 1 phase at least.
• Auxilary power supply: from 24 to 48 Vdc
• Assembly: compact DIN format, mounted in the same place as fault passage
indicator (format DIN, integrated in switchgear), terminal connexion fi tted with
VPIS-Voltage Output
- Compatible with all neutral earthing systems.
LPVT options
PM107132
FBX can now be specified with compact high accuracy Low Power Voltage
Transformers (LPVT). These innovative sensors are ideal for the new generation of
electronic protection devices and are the only way to measure energy in secondary
MV loops.
• Up to Class 0.5 accuracy levels for metering
• Linear wide spectrum voltage range with no ferro resonance characteristics.
• Low power consumption and reduced size - ideal for new or retrofit solutions
• Excellent harmonic performance for Power Quality monitoring
• Increased quality and safety under over-voltage, open circuit, or short circuit
conditions
• Easy to install, operate and test - no need to disconnect for cable testing
42 kV / 15 min
• Comply to international standard : IEC 60044-7
De-energizing:
• Open load-break switch C2.
1 2
• Push the locking tab to the right.
• Lock the load-break switch with key 2 C1 C2
• Recover Key 2. Go to C1
• Open load-break switch
• Push the locking tab to the right
2 1
• Lock the load-break switch with key 1
• Recover Key 1
• Introduce Key 2 into the earthing switch lock
and unlock it immediately
• Check that there is no voltage across the
voltage indicator units
• Close the earthing switch ⊂ ⊂
• Return to C2
• Introduce Key 1 into the earthing switch lock
and unlock immediately
• Verify that there is no voltage across the voltage ∩ ∩
indicator units
• Close the earthing switch
3 3 1
2
C1 C2 C3
2 1
1
⊂ ⊂ ⊂
⊂
∩ ∩ ∩ ∩
Low Voltage
T1 function 2 3 4
DM106990
3
Case C: 1
Transformer
(with enclosure) > 2000 kVA
or with external plug-in
or terminals 4
1 Low Voltage
2 3
1
Case B:
Transformer with a
double lock fitted 23
or
⊂
Low Voltage
∩ 2
1
Case A:
Insulated transformer
or
Case A: Case B: 1
Insulated transformer Transformer with a GE
Generator Unit
• Unlock transformer double lock fitting
access (or plug-in • Introduce Key 2 into
terminals) using the transfer lock De-energising:
Key 2 • Recover Key 3 to • Open the load-break switch of T1 function.
gain access to the • Go to the LV switchboard, open and unplug the
transformer main CB.
Case C: • Lock this CB in its ”withdrawn” position using
Transformer (with metal-clad enclosure), Key 1.
> 2 000 kVA, or with external plug-in terminals • Recover Key 1 and go back to T1 function.
• Introduce Key 1 into the earthing switch lock
• Introduce Key 2 into the transfer lock,
and unlock it immediately.
• Recover Key 3 to gain access to the transformer
• Check that there is no voltage across the
• Recover Key 4 to gain access to the transformer
voltage indicator units.
or the plug-in terminals
• Close the earthing switch. Lock earthing switch
using Key 2.
• Go to the transformer
Low Voltage
T2 function 2 3 4
DM106991
3
Case C: 1
Transformer
× or
(with enclosure) > 2000 kVA
or with external plug-in
terminals 4
Low Voltage
3
1
Case B:
Transformer with a
double lock fitted 23
1 ⊂ or
2 Low Voltage
2
∩ 1
Case A:
Insulated transformer
or
Case A: Case B: 1
Insulated transformer Transformer with a GE
Generator Unit
• Unlock transformer double lock fitting
access (or plug-in • Unlock transformer
terminals) using access with Key 2 De-energising:
Key 2 • Recover Key 3 to • Trip the circuit breaker
unlock the plug-in • Open the line isolator
terminals • Go to the LV switchboard, open and unplug the
Case C: master circuit breaker
Transformer (with metal-clad enclosure), • Lock this circuit breaker in its ”withdrawn”
> 2 000 kVA, or with external plug-in terminals position using Key 1
• Recover Key 1 and go back to T2 function
• Introduce Key 2 into the transfer lock
• Introduce Key 1 into the earthing switch lock
• Recover Key 3 to gain access to the transformer
and unlock it immediately
• Recover Key 4 to gain access to the transformer
• Check that there is no voltage across the
or the plug-in terminals
voltage indicator units
• Close the earthing switch. Lock earthing switch
using Key 2
• Go to the transformer
Backup schemes
Interlock between two C function units
DM106992
FBX 1: C-... FBX 2: C-...
1 2
C1 C2
2 1
⊂ ⊂
∩ ∩
3 3 1 2
C1 C2 C3
2 1
⊂ ⊂ ⊂
⊂
∩ ∩ ∩ ∩
DM106994
Low Voltage
T1 function 2 3 4
33
Case C: 1
Transformer
(with enclosure) > 2000 kVA
or with external plug-in
or terminals 44
11 Low Voltage
22 33
1
Case B:
Transformer with a
double lock fitted 2 3
or
⊂
Low Voltage
∩ 2
1
Case A:
Insulated transformer
or
1
GE
Generator Unit
Low Voltage
T2, CB & CBb functions 2 3 4
33
Case C: 1
Transformer
Low Voltage
33
1
Case B:
Transformer with a
double lock fitted 22 3
1 or
⊂
2 Low Voltage
2
∩ 1
Case A:
Insulated transformer
or
Manometer
PE58625
PE58626
• The interrupting mechanisms are installed in stainless steel tanks filled with
gas. During the service life of the switchboard, the addition of SF6 gas is not
necessary.
• The gas pressure in the hermetically sealed tank is indicated, as an option,
by a relative or absolute pressure manometer for uses at high altitude.
Relative pressure gauge Absolute pressure gauge • An auxiliary contact can be fitted to the manometers (optional).
Accessories
Standard accessories supplied with FBX switchboard are:
PE58632
PE58633
• A set of operating levers
• A set of keys to lock fuse compartment
• In case of motorized mechanisms, an emergency back-up handle.
Extended version
PE58630
Standard
Standard
Operating lever for the earthing switch Operating lever for the CB and CBb
Operating lever for the disconnector,
circuit-breaker
switch disconnector, and T2 circuit-breaker
Ø 45±1
Ø 20 max. Ratings for fuses for transformer protection depend, among other points, on the
following criteria:
A B Striker
33+2 Ø 88 max. Ø 88 max. 33+2
• Service voltage
Ø 50 min. • Transformer rating
• Thermal dissipation of the fuses
• Fuse melting curves.
Voltage D (mm)
Up to 12 kV 292 (with adaptor to extend to Correct operation of the transformer may be not fulfilled when using fuses
442 mm) out of the below choice tables.
Up to 12 kV 442
17.5 kV 442
24 kV 442
Necessary data when placing an order
The following data must be specified:
• Transformer power
• Transformer service voltage.
Spare fuses Rated current of suitable HV fuses is then given by the selection tables.
If not applicable, please consult us.
Spare fuses must meet the following requirements:
• Dimensions in compliance with technical data
sheet 1 (type 1, line 1), IEC 60282-1 publication,
radius A and B < 3 mm.
• “Medium” type of striker with a maximum initial
Technical characteristics
tripping force of 80 N.
The fuses meet the following standards:
• When using spare fuses without tripping with a
thermal limitation integrated striker, the following • Protection of the distribution transformers in compliance with the IEC 60787
requirements must be fulfilled: standard.
- in case of overcurrents, the interruption must be • Fuses in compliance with the IEC 60282-1 standard.
carried out by LV fuses • Specifications of the IEC 62271-105 standard.
• Maximum ambient temperature for the switchboards: 40°C in accordance
- if the switchboard is installed in an exposed
with standards IEC 62271-1. Temperature must be considered when calculating
area, in which the fuse links may be submitted to
fuse power losses. For higher temperature conditions, please consult us.
damage due to transient events (e.g. lightning),
• HV fuses can bear 1.3 times the transformer’s rated current for a minimum
all the fuses must be replaced in accordance with
of ten hours.
the appropriate maintenance intervals.
• The interruption is made at 1.5 times the transformer’s rated current for two
If these requirements are not fulfilled, only the hours.
backup HV fuses with integrated tripping of the
striker and thermal limitation must be used in the FBX
switchboard to protect from a thermal overload.
12 10 – – 10 10 16 20 25 25 31.5 40 50 63 80 63(2) 80 – – – – –
(1) (2)
HV Fuse selection with integrated thermal limitation MERSEN (PTD) or EFEN (ULA)
Transformer 10/11 kV 10/11 kV 15 kV 20/22 kV
Ucc power Fuse rating L292 Fuse rating L442 Fuse rating L442 Fuse rating L442
kVA 6/12 kV 10/24 kV
25
50
63
80
100 16 (1) 16 (1) 10,0 10 (1)
125 16.0 16.0 10 (2) 10 (1)
4%
160 20.0 20.0 16.0 10( 1)
200 25.0 25.0 20.0 16.0
250 25.0 31,5 20.0 16.0
315 31.5 31,5 25.0 20.0
400 40.0 40.0 31.5 25.0
500 50.0 63.0 40.0 31.5
630 63.0 63.0 50.0 31.5
630 50 (2) 40 (1) (2) 31.5 (1) (2)
800 63 (2) 50 (1) (2) 31.5 (2)
6%
1 000 80 (2) 50 (1) (2)
1 250 63 (1) (2)
(1) With time delay stricker
(2) Transformer inrush current limited to 10 times
PE58619
PE58602
For your peace of mind, FBX gives automatic control and management
Because a MV power supply of power sources in your Medium Voltage secondary distribution network
interruption may be critical in some with a short transfer time.
applications, an automatic system is
required for MV source transfer.
Automatic control is performed by Easergy T300
This T300 device can also be used for remote control with a wide range of modems
and protocols.
By default, the T300 is provided with the RS232 modem and the Modbus/IP
protocol.
DM106996
PM107111
M M
Line 1 Line 2
Changeover between 2 MV
DE59768
As soon as voltage returns on the main line (SW1), the ATS changes back to the
main line after a time delay (T2).
DM106951
Line G
Changeover between a distribution
DE59769
SW SWG
system line and a generator
3 operating modes (selected from the T300 Web server)
1. Auto SW mode
In the event of a voltage loss on the distribution line in service (SW), after a time
delay T1, the ATS sends the opening command to SW and at the same time the
Generator start-up order.
• C ase 1 “Generator channel closing after Generator power on”: the Generator
channel closing order is sent only when Generator voltage is detected.
• Case 2 “Generator channel closing after Generator start-up order”:
Generator ATS - Auto SW mode immediately after sending the Generator start-up order, the closing order is
DM106952
Characteristics
TR: switch response time
• T ime delay before changeover (T1): configurable from 0 s to 200 s in increments
of 100 ms (factory setting = 1 s).
This time delay is also used to delay return to the initial channel in Semi-Auto
mode SWXVSWG
• Time delay before return to the initial channel (T2)
• (Auto mode only). Configurable from 0 s to 30 min. in increments of 5 s (factory
setting = 15 s).
• Tg1: Generator start-up, depending on the generator type, not configurable
(max. waiting time: 60 s). If Tg1 is greater than 60 s, changeover is suspended.
• Tg2: Generator stoppage, depending on the generator type, not configurable
(max. waiting time: 30 s).
Note: the generator stoppage command is sent 6 s after the end of changeover.
1. Standard mode
In the event of a voltage loss on the distribution line in service (SW1), the ATS
changes over to the backup line (SW2) after a configurable time delay (T1).
[opening of SW1, closing of SW3]
As soon as voltage returns on the main line (SW1), the ATS changes back to
the main line after a time delay (T2).
SW1 SW3 SW2 [opening of SW3, closing of SW1 if the paralleling option is not activated]
[closing of SW1, opening of SW3 if the paralleling option is activated]
Vn
SW2 voltage
0
Characteristics
Vn
SW1 voltage
0 TR: switch response time
C • T ime delay before changeover (T1)
T1 TR SW1 TR
0 Configurable from 100 ms to 60 s in increments of 100 ms (factory setting = 5 s).
T3
C • Time delay before return to the initial channel (T2)
TR SW3 T2 TR
0 Configurable from 5 s to 300 s in increments of 1 s (factory setting = 10 s)
• Monitoring time (T3)
Configurable from 100 ms to 3 s in increments of 100 ms (factory setting = 1 s)
Changeover conditions
• Validation of the ATS (from the configurator)
• The ATS is in operation (local control panel or remote control)
• The external closing digital input is OFF
• The switch for the main line is closed and the backup line switch is open
• No fault detected on the line in service
• The earthing switch is open on both switches
Other functions
ATS in ON/OFF mode
The ATS system can be switched on or off from the local control panel (T300)
or remotely (Scada system).
When the ATS is OFF, the FBX switches can be electrically actuated by local
or remote control (operation in parallel mode is therefore possible).
Applications:
• Periodic maintenance tests of the ATS/Generator system
• Switch on Generator when the Network is overloaded.
During peak hours, and if network is overloaded, Utility can send a remote order
that will activate Generator. Having this facility, it will allow a private customer to
negotiate better tariff of electricity.
FBX-E cubicles 91
Indoor installation 97
Distance between the cubicle and the building’s wall 97
Evacuation of overpressures 98
C-C-T1 configuration
DM100103
1381.5
100 Rear
of FBX
DM100102
643
691 1000
484
64.1 63.5
379.5
425
37.5
C-T1-C-T1 configuration
1381.5
1320
C-C-T2 configuration
DM100107
0
1382.3
100 Rear
of FBX
DM100106
593
691 1000
95 95 95 95
480
375.5
65 60 100 100
336
224.5
63.5 63.5
72.5 67.5
752 1325
DM100109
1381.5
100 Rear
of FBX
593
691 1320
Tank 1299
DM100110
95 95 95 95 95 95
480
375.5
65 65 60 100 100
336
72.5 67.5
1385.1
1287.5
100 Rear
of FBX
643
9
691 17.5 1000 360 17.5
K = 95 mm
I = 381 mm (400 A)
K1 K1 K2 K2 K3 K3 K4 K4 379.5 mm (630 A)
J = 484 mm
168 320 320 (369) 168
J
I
37.5
752 512
FBX-E, 1 function switchboard
DM100113
284 116 116 492
T1 configuration
1385.1
1287.5
100 Rear
of FBX
643
Plug-in type
bushing 250 A
202.5 95 95 72.5
484
425
37.5
DM100116
284 116 116 495
T2 configuration
1381.5
1287.5
DM100115
Plug-in type
bushing 630 A
340
37.5
DM100120
600
284 116 116
DM100118
DM100119
1981.5
0
(1381.5)
1287.5
DM103198
CB configuration 34.5 399 116 116 495
DM103199
100 Rear
of FBX
1381.5
1287.5
150
593
Plug-in type
bushing 630 A
340
37.5
1381.5
150
1287.5
150 150
334
625
691
DM100126
648
648
648
60 60 115 254 115 20 254 20
60 115 254 20
283
1380
1380
1287.5
1287.5
254 254
1380
1287.5
254
580
580
580
325
Ø16 Ø16
19.5
55
19.5
325
Ø16 25 25
9 9 1000 1000
55
19.5
25
9 1000
DE59993
Functions and distances Space
(mm)
A Unit 1 function M1, M2, M3, M4 1 000
D
Unit 2 functions 680
Unit 3 functions 1 000
Unit 4 functions 1 320
752
B Unit 1 function C, R, RE 360
Unit 1 function T1, T2, CB 490
Unit 1 function CBb 625
Unit 1 function Sb 680
17.5 9 9 17.5
C Distance with the side wall 450
of the building for extensions C B A A C
at the extremity of the switchboard
D Distance Release of 100
E
Clearance
under
ceiling
1578
1380
Walk-in
corridor
DE59994
With double side panel With side panel With side panel
PE58638
Lateral
Side panel instalation,
PE58635
with or without
wall
Heigth of room
u 2000
With mounting base and gas exhaust duct With chimney and base
DE59995
PE58636
≥ 600
1780
100 100
870
With or
without wall
Overpressure
exhaust
Rear panel
Gas cooler*
not supplied
V u 0.8 m3 at 20 kA
V u 0.8 m3 at 16 kA
* Duct cross section > 0.3 m2 at 16 and 20 kA
Note: All the above connector selection are based on the standard FBX (Height:1380mm). Please consult us for the selection for FBX with low cable compartment
(Height:1040mm)
Note: the IAC 25 kA option is not available if 3 cables are used per phase.
The cables mounting support must be specified when ordering the FBX.
A surge arrester may be installed instead of a third cable connection. These mounting supports are available on request. Conforming with the manufacturer’s
technical data and mounting instructions.
Storage Packaging
FBX must be packaged depending on the • For road and rail transport:
requirements for its planned storage duration. FBX switchboard is packaged under protective sheeting. It is delivered fixed on
FBX must be preserved intact in its factory origin to a wooden pallet by two plastic tapes.
packaging.
• For maritime transport:
The storage area must not have any sharp and
FBX is packaged in a heat-sealed cover with bags of desiccant, then enclosed
important changes in temperature. Consult us for
in a wooden case with a solid leaktight bottom (including transport by container).
any particular storage condition.
• For air transport:
FBX switchboard is packaged in a wooden boxes (crates) with solid walls
* and a protective cover (dust cover).
DE59997b-N
+40°C
Handling
–5°C
The FBX must be transported vertically:
• When moving using a forklift: Only move the device on a pallet
Option – 15° C
– 25° C • When moving without a pallet: A lifting sling must be hooked on to the
switchboard’s lifting rings. The angle withthe lifting sling must be at least 45°
1 to 4 functions 1 to 4 functions
DE59996a
DE59996b
Ls
> 45°
X
LV
cabinet
100 mm
Switchboard
with LV cabinet
1 C/RE/R 370 Ls
T1/T2/CB 500
2 All types, except T1-T1/T2-T2 690 This switchboard can be transported:
• either using slings, attached to the
990
4 lifting rings
3 All types 1 010
• or, by two hand trolleys, one at either
4 All types 1 330 end.
5 C-C-C-C-C/C-C-C-C-T1/C-C-C- 1 685
T1-T1
C-T1-C-T1-T1 1 815
PM107133
For commissioning and maintenance
purposes FBX cubicle are manufactured
with dedicated QR code.
DM106997
Inspection
2017
744
Year
Serial
Number *DG-2017-W40-1-0041*
Service
Order number S000106568
Customer ID 3500990930
Position 011XX Diagram
Type FBX-C/12-20/C-C-T1
IEC 62271-200 Instruction
Ur 12 kV Ir 630 A fr 50 Hz
Up 75 kV Ik 21 kA tk 1 s
Ud 28 kV IAC sans sealed pressure system
Pre 0.03 Mpa Pae 0.02 Mpa Acc. IEC 62271-1
SF6 2.73 kg Pme 0.02 Mpa CO2e 62,244 t
C function T1 function
IEC 62271-103 IEC 62271-105
Ir 630 A Pref W
Ik 21kA 1 s Ir acc. fuses choice grid
PM107134
*AMT005470/10656801*
Mâcon AMT France AMT0114501-01
www.schneider-electric.com
NRJED311061EN
©2018 Schneider Electric SE. All Rights Reserved.
All Schneider Electric trademarks and service marks are the property of Schneider Electric SE, its subsidiaries and affiliated companies.