PLS-CADD Version 15.01x64 9:11:47 a. m.

martes, 24 de abril de 2018


Empresa de Energia de Bogota - Colombia
Project Name: 'd:\replanteo la loma\ll_ep lidar 10m
07122017variantesloan_prueba_info_isatech_600.DON'

Criteria Notes:
Según lo especificado por el GEB, para el proyecto particular.

IEEE Standard 738-2012 method of calculation

Air temperature is 39.00 (deg C)


Wind speed is 0.70 (m/s)
Angle between wind and conductor is 90 (deg)
Conductor elevation above sea level is 150 (m)
Conductor bearing is 90 (deg) (user specified bearing, may not be value
producing maximum solar heating)
Sun time is 11 hours (solar altitude is 75 deg. and solar azimuth is 112
deg.)
Conductor latitude is 30.0 (deg)
Atmosphere is Clear
Day of year is 172 (corresponds to junio 21 in year 2018) (day of the
year with most solar heating)

Conductor description: 700 kcmil 30/7 Strands ACAR - Adapted from 1970's
Publicly Available Data
Conductor diameter is 2.446 (cm)
CORE STRANDS:
Homogenous non-ferrous
Radial Thermal Conductivity is 2.00 (W/m-K)
Conductor AC resistance is 0.0946 (Ohm/km) at 50.0 (deg C)
and 0.1025 (Ohm/km) at 75.0 (deg C)
Conductor resistance is computed using average of core and surface
temperatures.
Emissivity is 0.5 and solar absorptivity is 0.5

Solar heat input is 12.414 (Watt/m) (corresponds to Global Solar


Radiation of 1015.077 (Watt/m^2) - which was calculated)
Radiation cooling is 11.315 (Watt/m)
Convective cooling is 48.790 (Watt/m)

Given a maximum conductor temperature of 75.0 (deg C),


The steady-state thermal rating is 681.1 amperes
PLS-CADD Version 15.01x64 9:12:50 a. m. martes, 24 de abril de 2018
Empresa de Energia de Bogota - Colombia
Project Name: 'd:\replanteo la loma\ll_ep lidar 10m
07122017variantesloan_prueba_info_isatech_600.DON'

Criteria Notes:
Según lo especificado por el GEB, para el proyecto particular.

IEEE Standard 738-2012 method of calculation

Air temperature is 39.00 (deg C)


Wind speed is 0.70 (m/s)
Angle between wind and conductor is 90 (deg)
Conductor elevation above sea level is 150 (m)
Conductor bearing is 90 (deg) (user specified bearing, may not be value
producing maximum solar heating)
Sun time is 11 hours (solar altitude is 75 deg. and solar azimuth is 112
deg.)
Conductor latitude is 30.0 (deg)
Atmosphere is Clear
Day of year is 172 (corresponds to junio 21 in year 2018) (day of the
year with most solar heating)

Conductor description: 700 kcmil 30/7 Strands ACAR - Adapted from 1970's
Publicly Available Data
Conductor diameter is 2.446 (cm)
CORE STRANDS:
Homogenous non-ferrous
Radial Thermal Conductivity is 2.00 (W/m-K)
Conductor AC resistance is 0.0946 (Ohm/km) at 50.0 (deg C)
and 0.1025 (Ohm/km) at 75.0 (deg C)
Conductor resistance is computed using average of core and surface
temperatures.
Emissivity is 0.5 and solar absorptivity is 0.5

Solar heat input is 12.414 (Watt/m) (corresponds to Global Solar


Radiation of 1015.077 (Watt/m^2) - which was calculated)
Radiation cooling is 13.192 (Watt/m)
Convective cooling is 55.553 (Watt/m)

Given a maximum conductor temperature of 80.0 (deg C),


The steady-state thermal rating is 734.4 amperes