HEI
Thermal Storage Tank Stratification
WARM WATER
THERMOCLINE
COLD WATER
HEI
HEI
Water Diffuser Systems
Tank
HEI
Water Diffuser Systems
OCTAGON “H”
HEI
Water Diffuser Systems
SQUARE
HEI
Froude Number
The Froude Number is the single most important design parameter
in the design of the distribution system. It is the ratio of dynamic
(inertial) forces to weight (buoyancy forces). A low Froude Number
insures that the buoyancy forces predominate over inertia forces
and allow the tank to be stratified.
Buoyancy = Inertia =
HEI
Froude Number
>2000 <2000
HEI
Reynolds Number
HEI
TES Capacity
FREEBOARD
WARM WATER
THERMOCLINE
COLD WATER
HEEL
A = Usable volume
Discharge outlet B = Unusable volume
A+B = Total volume
B
Charge inlet
0 50 100
H = 50'
WARM WATER
WARM WATER
THERMOCLINE
COLD WATER
THERMOCLINE
COLD WATER
COLD WATER
FROM TO
CHILLERS LOAD
During the Charging and Discharging, measure the following every 15 minutes:
• Flow Rate In • Temperature at regular height intervals
• Flow Rate Out • Pressure at inlet
• Temperature of water going in • Pressure at outlet
• Temperature of water going out • Ambient air temperature
HEI
Abu Dhabi Results
HEI
Abu Dhabi Graph
TEMPERATURE °F
Units
HEI
Stanford TES 2011 Graph
TEMPERATURE °F
Units