Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
1
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
2
The organization of the paper is as follows. Section II Fig. 2. The types and capacities of wind farms in Guyuan area
describes the Guyuan wind power system and its SSR events.
Taiping substations. And the compensation degrees are 40%
Section III examines the various distinct features of the SSR
and 45%, respectively.
captured at Guyuan and compares them with those happening
There are three types of WTGs, namely SEIG (Type 2),
elsewhere in the world. In Section IV the field-measured IMs
DFIG (Type 3) and PMSG (Type 4), installed at those wind
are presented and used to verify actual observations with
farms. Among the total 3426.55 MW installed capacity, 82.8%,
previous theoretical results. Section V concludes this paper.
15.4% and 1.8% of the wind power are provided by DFIGs,
PMSGs and SEIGs, respectively. Clearly, DFIG accounts for
II. THE WIND POWER SYSTEM AND ITS SSR EVENTS
most of the proportion. For each wind farm, the installed
A. The Wind Power System capacity and the types of WTG are illustrated in Fig.2. Most
The wind power system in the Guyuan area is located in the wind farms contain only single type of WTG. For example, the
northwest of Hebei Province, China. As show in Fig.1, it has wind farms of Hanjiazhuang, Zhongbao, Muchang and
twenty-four wind farms by the end of 2014. All these wind Qilinshan are entirely made up of DFIGs; while Youyi and
farms distributed throughout the Guyuan area are radially Dongshan are purely PMSG-based. A very few farms, for
connected to the 220kV substations of Guyuan, Chabei, Yiyuan instance, Jinyang, Batou, Hengtai and Bingfeng, contains two
and Bailongshan. Then, the electric power is collected at the or three types of WTGs.
500kV Guyuan substation and next transmitted along two B. SSR Events
500kV corridors, each with double-circuit series-compensated
In the target system, abnormal electrical oscillations had been
transmission lines, to the North-China power grid. Four sets of
observed since the commission of series capacitors in 2010. As
fixed series capacitors (FSCs) are installed on the two parallel
the occurrence was fairly rare and had no obvious impact on the
transmissions connecting Guyuan substation with Hanhai and
normal operation of the system, those oscillations did not cause
sufficient attention initially. However, with more and more new
wind farms put into operation in the area, SSR began to occur
frequently. From December 2012 to December 2013, as many
as 58 SSR events were detected. Such severe SSR would
inevitably disturb the safe operation of the system. The
immediate consequence is that many (even over one thousand
in a case) WTGs were tripped due to the excessive current
caused by the divergent SSR, which resulted in an abrupt and
large decrease of wind power. SSR would also endanger the
performance of power equipment. For instance, it causes large
inter-harmonic currents flowing into transformers, which then
vibrates abnormally and makes unusually loud noise. As a
Fig. 1. Single-line diagram of the wind power system in Guyuan area result, the aging of insulation would be sped up and the loss
would be increased. Therefore, SSR is regarded as a big threat
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
3
to the safety and stability of the whole system and calls for 200
in-depth studies.
To illustrate the phenomena, a typical SSR event is taken as 100
Voltage(kV)
example. It happed on March 19th, 2013. Fig.3 displays the 0
active power flowing through the step-up transformer at
Guyuan substation. The data were recorded by the wide-area -100
monitoring system or WAMS. Initially, the wind power is
-200
relatively low, about 13% of the total capacity. At 14:12:15, the 5 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6
Time(s)
power started to oscillate in a divergent way. The oscillatory
(a) Instantaneous voltage
magnitude increased rapidly. At 14:12:48, the amplitude of
oscillation reached to about 25% of the average power. As a 200
Amplitude (kV)
150
inter-harmonic current. As the number of online WTGs became
less, the average power decreased steadily. However, SSR still 100
existed. Not until 14:14:03, when one of the series capacitors
was bypassed, did SSR cease. The oscillation lasted for 108 50
8.1Hz 91.9Hz
seconds. The wind power decreased from 219.5 MW to 74.5 0
MW, causing a loss of 66% of the initial output. 0 10 20 30 40 50 60 70 80 90 100
Frequency (Hz)
(b) Spectrum of the voltage
Fig. 5. The voltage during a typical SSR event
Fig. 3. The power flow of the step-up transformer during the SSR event III. CHARACTERISTIC ANALYSIS OF THE SSR
Segmental curves of voltage and current of the transformer at A. The necessary conditions for SSR occurrence
the 220kV side are displayed in Fig.4 and Fig.5. As shown in
Fig.4 (a), the current is distorted seriously. The spectrum of the It is an important issue that under what conditions SSR
current is presented in Fig.4 (b), in which the subsynchronous would happen. To find the answer, the different scenarios of the
frequency is observed to be about 8.1Hz. The amplitude of the 58 SSR events were examined carefully, intending to get clues
that led to the oscillations. Several factors, including the state of
series capacitors, the wind speed and/or output level of wind
1
power, are discovered to determine the occurrence of SSR.
0.5 According to the recorded data, all SSR events happened
Current (kA)
0
when the four sets of series capacitors were in service. If one or
more series compensation are out of service or deliberately
-0.5 bypassed, SSR would never occur or be suppressed. Actually,
-1 about 90% cases of dangerous SSR were terminated by timely
5 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6 quitting one of the four sets of series capacitors. Obviously, the
Time (s)
existence of all series compensation is a prerequisite for the
(a) Instantaneous current
0.6
occurrence of SSCI-type SSR. This observation is consistent
with the theoretical results stated in [1].
50Hz
Another pronounced observation is that when SSR occurred,
Amplitude (kA)
0.4 8.1Hz
the output level of wind power was usually small. Among the
58 SSR events, the average wind power output was in the range
0.2 91.9Hz from 88 MW to 360 MW, or 2.6% to 10.5% of the total
installed capacity. The number and percentage of SSR events
0 versus the wind power are illustrated in Fig.6. It can be seen
0 10 20 30 40 50 60 70 80 90 100
Frequency (Hz) that most (about 87%) of the captured SSR incidents happened
(b) Spectrum of the current
Fig. 4. The current during a typical SSR event when the average wind power is between 100MW and 300MW.
Specifically, Fig.7 displays the upstream wind power in
March 2013. During that period, 12 SSR incidents were
recorded and their initial power was also marked in the figure.
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
4
800
700 their frequencies varying from 6 to 8 Hz, accounting for 93.1%.
600
500
However, the natural frequency of the WTG shaft is about 1.8
400 Hz and its complementary frequency is 48.2 Hz [1]. The
300 frequency of the captured SSR is far from the torsional
200
100 frequency. Therefore, this SSR can be ruled out from the
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 traditional torsional interaction. It is a different and new type of
Time (day) SSR without the participation of the mechanical dynamics of
Fig. 7. The power flow through Guyuan Step-up station in March 2013 the turbine shaft.
45
Similarly, most (10 out of 12) SSR events appeared when the 39
40
average wind power is between 100 MW and 300MW. What
Number of SSR events
35
calls for special attention is that SSR started when the power is 30
in a downward trend. In other words, its starting point is on the 25
left side of the power valley. Noticeably, there are some sharp 20
15
downward trends (below 100MW) where the SSR event did not 15
10
occur. This is due to a low limit preset by the system operators. 4
5
Before 2012, when the installed capacity of wind power was 0
much lower, it was discovered that SSR appeared as the power 6~7 7~8 8~9
Frequency (Hz)
was less than 100 MW. Then, to avoid SSR, the system
Fig. 8. The distribution of SSR frequency
operators set a low limit (100MW) for the wind power, which,
if violated for a few seconds, one set of series capacitors would Another evidence is that the frequency of this new SSR is not
be bypassed. As a result, for these occasions when wind power constant in even a single event. To demonstrate this, the
dropped quickly below that limit, no SSR was captured due to frequencies recorded at 15 different wind farms that
the immediate switch-off of series capacitors. So in Fig.7, some experienced the same SSR event are presented in Fig. 9.
of the sharper downward power valleys had no marks for SSR Starting at around 8.5 Hz, when the oscillation become intense
incidents. Of course, this previously set limit was proved to be enough that some WTGs were tripped about 3 seconds later. As
unable to avoid SSR completely. a result, the frequency began to decrease. As the SSR continued,
According to the statistic data provided by North-China Grid, more and more WTGs dropped out and the oscillatory
the in-service rate of WTGs in this area is generally about 80% frequency declined steadily from 8.5 Hz to 8.1 Hz in 10 seconds
or less. Hence, 100 MW and 300MW correspond to about 4% and then to 7.7 Hz in 30 seconds. Despite the continuous
and 11% of the nominal capacity. In the light of the change or decease of the frequency with time, the frequency at
wind-speed-versus-output-power characteristics of the actual different locations is perfectly identical, which means that all
WTGs, it can be derived that unstable SSR happens when the WTGs and the network are engaged in the same SSR mode.
average wind speed is in the rough range of 3 to 5 meters per As pointed out in our previous work [31, 34], the oscillation
second. It is a relatively lower speed. This observation about frequency of this new type of SSR is mainly determined by the
the influence of wind speed on SSR is consistent with the equivalent inductance and capacitance, which involves the
analysis in [1, 5, 6, 31, 34]. However, further decrease of wind number/parameters of both transmissions and WTGs. When the
speed leads to the dropping out of more WTGs. Considering the number of grid-connected WTGs decreases due to the
impact from the number of online WTGs [5], the probability of protective tripping action, the equivalent reactance of the wind
SSR would be reduced instead. farms increases, resulting a decline of oscillatory frequency. So
From the above analyses, it can be concluded that there are the observations from Fig.9 agree very well with existing
two necessary conditions for an unstable SSR incident. They theoretical results [31].
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
5
14:11:50
14:09:00
14:09:10
14:09:20
14:09:30
14:09:40
14:09:50
14:10:00
14:10:10
14:10:20
14:10:30
14:10:40
14:10:50
14:12:00
converters [39]. This is also the case for the SSCI-type SSR due
to the involvement of the converter controls of DFIGs and/or
Time (hh:mm:ss) PMSGs. It has been theoretically proved that the
Fig. 10. The wind power output of Youyi and Hongda during an SSR incident DFIG-associated SSR existing in a series-compensated system
is a particular type of control interaction with the negative
D. Comparison with the SSR in ERCOT and Xcel Energy
damping or resistance mainly contributed by the rotor-side
Similar SSR incidents have been reported for the wind farms converter (RSC) of DFIG [5]. So if IM is available for a WTG
at Guyuan, ERCOT and Xcel Energy. They were all caused by or wind farm, the characteristics of SSR, including the
the interaction between DFIGs and series-compensated
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
6
frequency and damping, could be derived with many mature increase the absolute value of the negative resistance and thus
methods, for instance, the Nyquist stability criterion [38, 39]. contribute a lot to an unstable oscillation [4]. Consequently,
Although the impedance-based theory is well established, there DFIG is made much more vulnerable to the SSCI-type SSR.
is still a lack of empirical evidence for the impedance PMSGs are connected to the grid through full-scale
characteristics of practical wind generators or farms. In this voltage-sourced converters (VSCs). So its IM is quite different
section, the theoretically derived IMs of the above-mentioned from those (Types 1-3) WTGs based on induction machines.
three types of WTGs will be reviewed and their field-measured Extensive work has been done to get its analytic expressions
results will be presented. The cross validation of theoretical and [16, 38]. The IM of PMSG is widely recognized to be jointly
measured impedances further deepens the understanding of the determined by schemes/parameters of its inner/outer-loop
characteristics of the SSR. controllers, phase-locked-loop (PLL), dc dynamic and
interfacing filters. Generally, a wind farm with n identical
A. The IMs of DFIG, PMSG and SEIG
PMSGs can be expressed by:
For a radial system with series capacitors in the main grid Z PMSG ( RPMSG jX PMSG ) / n (3)
and WTGs at the sending terminals, both the grid and the wind
According to [16], at low subsynchronous frequency the
farms can be simply represented with IMs for the purpose of equivalent resistance RPMSG is usually a large and positive
analyzing the SSR characteristics [38]. As shown in Fig. 11, the number and the equivalent impedance XPMSG is a large but
grid is simplified into an R-L-C circuit; while the wind farms negative (capacitive) number.
based on DFIG, PMSG or SEIG can be equivalently replaced Based on the theoretically derived IMs (1)-(3), the total
by resistance in series with inductance or capacitance. If the impedance of the system can be obtained, which is next used to
negative resistance generated by the wind farms overcome the determine the damping (or stability) and frequency of SSR. It is
positive resistance of the grid, unstable SSR would happen and widely believed that the negative-resistance effect of DFIG
the frequency of oscillation is determined by the total makes it the primary cause for this SSCI-type SSR while SEIG
inductance and capacitance [39]. and PMSG usually play passive roles. However, such belief
needs to be verified with field data.
B. Measured impedances
To verify the concept of IMs, we identify their real values
from field measured data by using the following formula:
Z SSR U SSR / I SSR (4)
where U SSR and I SSR are subsynchronous voltage and current
phasors extracted from the recorded data.
For illustration, the IMs of wind farms are identified using
Fig. 11. The IMs of a radial system collecting wind power through the data of the SSR event on March 19, 2013. Some typical
series-compensated transmissions
results are shown in Figs. 12 to 16.
SEIG has no power electronic converter. Its IM is relatively The IMs of Hanjiazhuang (Fig.12), Zhongbao (Fig.13) and
simple, as expressed by: Jiulongquan (Fig. 14) have confirmed that a DFIG-based wind
Z SEIG = ( RSEIG jX SEIG ) / n farm appears as negative resistance and positive reactance.
(1)
( rr / s jSSR Lr ) / /( jSSR Lm ) Rs jSSR Ls / n
Fig.16 displays the IM of a PMSG-based wind farm (Youyi). It
is characterized by positive resistance and capacitive reactance,
where RSEIG (XSEIG) is the equivalent resistance (reactance) of both of which have much large absolute values than those of
the SEIG-based wind farm; rr (Lr) is the rotor resistance DFIG-based wind farms. This has well confirmed PMSG’s
(inductance); Rs (Ls) is the stator resistance (inductance); Lm is passiveness in the SSR dynamics.
the excitation inductance; ωSSR is the angular frequency of SSR; The variation of the impedance over time helps to judge
ωr is the rotor speed; and s = ( SSR - ωr)/ SSR , standing for the whether there are obvious changes in wind speed and/or
slip between SSR and ωr; n is the number of the same type of number of online WTGs during the incident. For instance, Fig.
14 indicates a step change in the reactance of Jiulongquan. It
SEIGs in the wind farm. was caused by the drop-out of DFIGs in that wind farms due to
The IM of a wind farm containing n identical DFIGs can be the excessive oscillatory current, which could be seen in Fig.15.
expressed by [5, 40]:
Z DFIG =( RDFIG jX DFIG ) / n 100
0
the DFIG-based wind farm; Kp is the proportional gain of the
RSC control. -50
As the slip s is generally negative at the SSR frequency, the
first items in both (1) and (2) present negative resistance. -100
0 5 10 15 20 25 30
Noticeably, in (2) there is an additional item or Kp/s caused by Time (s)
the proportional gain (Kp) of the RSC. It would significantly Fig. 12. Measured impedance of Hanjiazhuang (DFIG-based)
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
7
30
R X
20
10
Z(Ω)
0
-10
-20
-30
0 5 10 15 20 25 30
Time(s)
Fig. 13. Measured impedance of Zhongbao (DFIG-based)
50
R X
40
30
Z(Ω)
20
10
0
-10
0 10 20 30 40 50 60 70 80 90 100
Time(s)
Fig. 17. Impedance network of the Guyuan System
Fig. 14. Measured impedance of Jiulongquan (DFIG-based)
0.4 speed was 5.1 m/s and about 90% WTGs were grid-connected.
0.2
The zoomed-in curve of the captured current at Guyuan
substation is plotted in Fig. 18. Using digital Fourier
ia (kA)
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
-0.02 R1 -0.00196 pu
Resis
R2 0.00448
This article has been accepted for publication in a pu
future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
-0.04 R3 0.00587 pu
R4 0.00150 pu Transactions on Energy Conversion
-0.06 8
0.4
Reactance (pu)
0.2
0.04
0.04
0.04 the self-excitation of SSR, even under the context of a very low
0 Case 1
f1 7.58 Hz series compensation. This has been explained by theoretical
(pu)
Resistance (pu)
Resistance (pu)
0.02
0.02
0.02 f 2 6.92 Hz
Case 2
-0.2 0.04
0.04 f 3 7.50 Hz Case 3 analysis and confirmed by field observations.
Resistance
0 00 f 4 5.89 Hz Case 4
2) Theoretically derived and practically measured IMs have
Resistance (pu)
0.02
Resistance (pu)
-0.4
0.02
-0.00196
R11-0.00196
-0.02R1 R -0.00196 pu
pu
5 pu 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
-0.02
-0.02
0.00448
R220.00448
R2 R
0
0 pu pu
0.00448 pu Frequency (Hz) indicated that PMSGs are not actively or just passively engaged
0.00587
R330.00587 R -0.00196 pu in the captured SSR incidents. However, such an observation
-0.04R3 R
-0.04
-0.04 0.00587
-0.02 Rpupu
-0.02 pu
-0.00196 pu
R 0.00448 pu 1
1
R4 R 0.00150
R440.00150
0.00150Rpupupu
0.00448 pu pu 2
-0.06
-0.06
-0.04
R
R 0.00587
0.00587 pu
2
3 should be cautiously examined before applying to other WTGs
-0.06 -0.04 R 0.00150 pu 3
R 0.00150 pu 4
and systems, because of the unlimited possibilities of control
0.40.4
0.4 -0.06 4
-0.06
0.4
0.4 schemes and parameters.
(pu)
Reactance (pu)
Reactance (pu)
Reactance (pu)
0.20.2
0.2 3) Besides the compensation level, wind speed and number
Reactance (pu)
0.2
0.2
Reactance
0 00 Case 11 1
of online DFIGs are two important factors that impact the
0 CaseCase
1 Case
0 f7.58
f1 ff117.58 HzfHz
7.58
7.58
7.58 Hz
HzHz
1 Case 1
Case 2 characteristics of SSR because they directly change the IM of a
f ff 6.92f 6.92
6.92 6.92 Hz Case
f Hz
1
Hz
Case
Case 2 2 22
Case
Hz
2
-0.2 6.92
f Hz Case 3
-0.2-0.2
-0.2 -0.2
2 22
f 7.50
f 3 ff337.50 Hz
2 7.50 Hz Case
3 Case
Case
Case 3 3 33 wind farms, especially the negative resistance. In the case of
7.50f Hz
Hz
7.50Hz
3 5.89 Hz Case 4
f ff 5.89f 5.89
Hz low compensation level, the decrease of wind speed makes the
4
-0.4 4
5.89
5.89
44 Hz
Hz
4Hz Case
Case
Case 4 4 44
Case
-0.4-0.4
-0.4 -0.4 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
5 55 5.55.5 5.5 5 6 665.56.56.5 6
6.5 7 6.5
77 7.577.5 7.5
8 88 88.5
7.5Frequency 8.58.5
8.5
(Hz) 9 999
9.59.5
9.5
9.5 10 10
10 negative slip closer to zero and thus the negative resistance
10
Frequency (Hz)
Frequency
Frequency
Frequency (Hz)
(Hz)(Hz) even larger, indicating a more unstable SSR condition.
Fig. 19. Frequency-dependent impedance (base value = 0.3174 Ω)
4) In a SSR event, the frequency at different locations is
By comparing the impedances of different cases, we could perfectly identical, meaning all WTGs and the network are
make the following observations: engaged in the same SSR mode. But its value is not fixed but
Firstly, the existence of all series capacitors is the necessary keeps changing over time as well as the variation of various
condition for the SSR incidents, because, otherwise, the factors, including network topology, number of online
equivalent resistance at the oscillation frequency shown as the generators, and etc.
pointers '+' would be positive, as shown by Case 2 in Fig. 19,
indicating a well stabilized subsynchronous mode. REFERENCES
Secondly, the control of DFIG is the primary reason for [1] A. Ostadi, A. Yazdani, R. K. Varma, "Modeling and stability analysis of
a DFIG-based wind-power generator interfaced with a
exciting the SSR due to the fact that it greatly enlarges the
series-compensated line," IEEE Transactions on Power Delivery, vol. 24,
negative resistance at the slip frequency, as shown in (2) and no. 3, pp. 1504-1514, Jul. 2009.
confirmed by Figs. 12 -14. The curves of Case 3 in Fig. 19 also [2] L. Fan, R. Kavasseri, Z. Miao, et al., "Modeling of DFIG-based wind
indicate that a slight (20%) decrease of the proportional gain of farms for SSR analysis," IEEE Transactions on Power Delivery, vol. 25,
no. 4, pp. 2073-2082, Oct. 2010.
the RSC would stabilize the originally unstable SSR.
[3] J. Adams, C. Carter, S. H. Huang, "ERCOT experience with
Thirdly, the number of online WTGs and their allocation sub-synchronous control interaction and proposed remediation," IEEE
among different types also affect the damping (stability) and Transmission and Distribution Conference and Exposition, 2012, pp. 1-5.
frequency of SSR. For the Guyuan system, a higher percentage [4] K. Narendra, D. Fedirchuk, R. Midence, "New Microprocessor Based
Relay to Monitor and Protect Power Systems Against Sub-Harmonics,"
of DFIGs would make the system more vulnerable to SSR, as
IEEE Electrical Power and Energy Conference, 2011, pp. 438-443.
illustrated by Case 4 in Fig. 19. And the more the online WTGs [5] L. Wang, X. R. Xie, Q. Jiang , et al., "Investigation of SSR in practical
are, the higher the oscillatory frequency would be, because the DFIG-based wind farms connected to a series-compensated power
reactance of the wind farm become less when more WTGs/IMs system," IEEE Transactions on Power Systems, vol. 30, no. 5, pp.
2772-2779, Sep. 2015.
are connected in parallel.
[6] Z. Miao, "Impedance-model-based SSR analysis for type 3 wind
Last but not the least, DFIG, PMSG and SEIG have different generator and series-compensated network," IEEE Transactions on
degrees of participation into this type of SSR. For the discussed Energy Conversion, vol. 27, no. 4, pp. 984-991, Dec. 2012.
Guyuan system, PMSG and SEIG are not so actively engaged. [7] D. H. R. Suriyaarachchi, U. D. Annakkage, C. Karawita, et al., "A
procedure to study sub-synchronous interactions in wind integrated
However, such an observation, though predicted by some
power systems," IEEE Transactions on Power Systems, vol. 28, no. 1, pp.
theoretical analyses and confirmed by the field measurements 377-384, Feb. 2013.
(see Fig. 10), should be cautiously examined before applying to [8] IEEE Subsynchronous Resonance Working Group, "Countermeasures to
other WTGs and systems. subsynchronous resonance problems," IEEE Transactions on Power
Apparatus and Systems, vol. PAS-99, no. 5, pp. 1810-1818, Sep. 1980.
[9] U. Karaagac, S. O. Faried, J. Mahseredjian, et al., "Coordinated control of
V. CONCLUSION wind energy conversion systems for mitigating subsynchronous
interaction in DFIG-based wind farms," IEEE Transactions on Smart
This paper is aimed to fill the gap between theoretical work
Grid, vol. 5, no. 5, pp. 2440-2449, Sep. 2014.
and practical observations for the newly emerging SSR that is [10] A. E. Leon, J. A. Solsona, "Sub-synchronous interaction damping control
caused by the interaction of DFIGs with series compensation. for DFIG wind turbines," IEEE Transactions on Power Apparatus and
By analyzing the field data of 58 SSR events captured in the Systems, vol. 30, no. 1, pp. 419-428, Jan. 2015.
Guyuan system, north China, and checking the observed [11] L. Fan, Z. Miao, "Mitigating SSR using DFIG-based wind generation,"
IEEE Transactions on Sustainable Energy, vol. 3, no. 3, pp. 349-358, Jul.
dynamics with previous theoretical results, the following 2012.
conclusions can be made: [12] G. Irwin, A. Jindal, A. Isaacs, "Sub-synchronous control interactions
1) This DFIG-associated SSR is a pure electric resonance between type 3 wind turbines and series compensated AC transmission
systems," IEEE Power and Energy Society General Meeting, 2011, pp.
without the involvement of torsional dynamics. It originates
1-6.
from the L-C resonance but is reinforced by the converter [13] C. Zhu, L. Fan, M. Hu, "Control and analysis of DFIG-based wind
control of DFIG. The latter, by greatly enlarging the negative turbines in a series compensated network for SSR damping," IEEE Power
resistance at the slip frequency, serves as the primary reason for and Energy Society General Meeting, 2010, pp. 1-6.
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2676024, IEEE
Transactions on Energy Conversion
9
[14] G. D. Irwin, A. Isaacs, D. Woodford, "Simulation requirements for [32] G. D. Irwin, A. K. Jindal, A. L. Isaacs, "Sub-synchronous control
analysis and mitigation of SSCI phenomena in wind farms," Transmission interactions between type 3 wind turbines and series compensated ac
and Distribution Conference and Exposition, 2012, pp. 1-4. transmission systems," IEEE Power and Energy Society General Meeting,
[15] ABB Inc., ERCOT CREZ reactive power compensation study. [Online]. 2011, pp. 1-6.
Available: [33] A. Moharana, R. K. Varma, R. Seethapathy, "SSR alleviation by
http://www.uwig.org/CREZ_Reactive_Power_Compensation_Study.pd STATCOM in induction-generator-based wind farm connected to series
f compensated line," IEEE Transactions on Sustainable Energy, vol. 5, no.
[16] H. T. Ma, P. B. Brogan, K. H. Jensen, et al., "Sub-synchronous control 3, pp. 947-957, Mar. 2014.
interaction studies between full-converter wind turbines and [34] M. S. El-Moursi, B. Bak-Jensen, M. H. Abdel-Rahman, "Novel
series-compensated AC transmission lines," IEEE Power and Energy STATCOM controller for mitigating SSR and damping power system
Society General Meeting, 2012, pp. 1-4. oscillations in a series compensated wind park," IEEE Transactions on
[17] R. K. Varma, S. Auddy, Y. Semsedini, "Mitigation of subsynchronous Power Electronics, vol. 25, no. 2, pp. 429-441, Feb. 2010.
resonance in a series compensated wind farm using FACTS controllers," [35] S. Golshannavaz, M. Mokhtari, D. Nazarpour, "SSR suppression via
IEEE Transactions on Power Delivery, vol. 23, no. 3, pp. 1645-1654, Jul. STATCOM in series compensated wind farm integrations," Iranian
2008. Conference on Electrical Engineering, 2011, pp. 1-6.
[18] X. R. Xie, L. Wang, X. Guo, et al., "Development and field experiments [36] D. H. R. Suriyaarachchi, U. D. Annakkage, C. Karawita, et al.,
of a generator terminal subsynchronous damper," IEEE Transactions on "Application of an SVC to damp sub-synchronous interaction between
Power Electronics, vol. 29, no. 4, pp. 1693-1701, Apr. 2014. wind farms and series compensated transmission lines," IEEE Power and
[19] Y. Hou, J. Zhong, "Challenges Ahead: Currents Status and Future Energy Society General Meeting, 2012, pp. 1-6.
Prospects for Chinese Energy," IEEE Power and Energy Magazine, vol. [37] A. Moharana, R. K. Varma, "Subsynchronous resonance in single-cage
10, no. 3, pp. 38-47, May. 2012. self-excited-induction-generator-based wind farm connected to
[20] C. Liu, F. Blaabjerg, W. Chen, D. Xu, "Stator Current Harmonic Control series-compensated lines," IET Generation, Transmission & Distribution,
With Resonant Controller for Doubly Fed Induction Generator," IEEE vol. 5, no. 12, pp. 1221-1232, Dec. 2011.
Transactions on Power Electronics, vol. 27, no. 7, pp. 3207-3220, Jul. [38] I. Vieto, H. C. Liu, S. Rogalla, J. Sun, "On the Potential of
2012. Subsynchronous Resonance of Voltage-Source Converters with the
[21] E. Muljadi, M. Singh, V. Gevorgian, "Doubly Fed Induction Generator in Grid," 5th Solar & 14th Wind Integration Workshop, 2015, pp. 438-443.
an Offshore Wind Power Plant Operated at Rated V/Hz," IEEE [39] J. Sun, "Impedance-based stability criterion for grid-connected inverters,"
Transactions on Industry Applications, vol. 49, no. 5, pp. 2197-2205, Sep. IEEE Transactions on Power Electronics, vol. 11, no. 26, pp. 3075-3078,
2013. Nov. 2011.
[22] H. Geng, G. Yang, D. Xu, B. Wu, "Unified Power Control for [40] H. K. Liu, X. R. Xie, C. Y. Zhang, Y. Li, H. Liu, Y. H. Hu, "Quantitative
PMSG-Based WECS Operating Under Different Grid Conditions," IEEE SSR Analysis of Series-Compensated DFIG-Based Wind Farms using
Transactions on Energy Conversion, vol. 26, no. 3, pp. 822-830, Sep. Aggregated RLC Circuit Model," Accepted by IEEE Transactions on
2011. Power Systems.
[23] J. Wen, L. Zhou, K. Smedley, "Minimizing the Circulation Current in
Hexagram Medium-Voltage Variable-Speed Drive by Coupled Xiaorong Xie (M’02, SM’14) received the B.S. degree from Shanghai Jiao
Inductors," IEEE Transactions on Industrial Electronics, vol. 58, no. 8, Tong University, Shanghai, China, in 1996, and the Ph.D. degree from
pp. 3421-3430, Aug. 2010. Tsinghua University, Beijing, China, in 2001. Currently he is an associate
[24] L. Harnefors, X. Wang, A. G. Yepes, F. Blaabjerg, "Passivity-Based professor in the Department of Electrical Engineering, Tsinghua University.
Stability Assessment of Grid-Connected VSCs—An Overview," IEEE His research interests include flexible ac/dc transmission systems,
Journal of Emerging and Selected Topics in Power Electronics, vol. 4, no. subsynchronous interaction and smart grid analysis & control.
1, pp. 116-125, Mar. 2015.
[25] J. Martínez, P. C. Kjær, P. Rodriguez, R. Teodorescu, "Design and Xu Zhang received the B.S., M.S. and Ph.D. degree from North China Electric
Analysis of a Slope Voltage Control for a DFIG Wind Power Plant," Power University, Beijing, China, in 2009, 2012 and 2016, respectively. He is
IEEE Transactions on Energy Conversion, vol. 27, no. 1, pp. 11-20, Mar. currently working as a Postdoctoral researcher in the Department of Electrical
2011. Engineering, Tsinghua University. His research interests include analysis and
[26] R. Pena, R. Cardenas, E. Reyes, J. Clare, "Control of a Doubly Fed control of subsynchronous interaction between multiple converters and large
Induction Generator via an Indirect Matrix Converter With Changing DC power system.
Voltage," IEEE Transactions on Industrial Electronics, vol. 58, no. 10, pp.
4664-4674, Oct. 2011. Huakun Liu received the B.S. degree from Shandong University, Jinan, China,
[27] W. Qiao, X. Yang, X. Gong, "Wind Speed and Rotor Position Sensorless in 2013. He is pursuing the Ph.D. degree at Tsinghua University. His research
Control for Direct-Drive PMG Wind Turbines," IEEE Transactions on interests include power system stability analysis and control.
Industry Applications, vol. 3, no. 11, pp. 3-11, Jan. 2011.
[28] Y. Huang, X. Yuan, J. Hu, "Effect of reactive power control on stability
Hui Liu received the Ph.D. degree in electrical engineering from Tianjin
of DC-link voltage control in VSC connected to weak grid," IEEE Power
University, Tianjin, China, in 2005. He is currently working for North China
and Energy Society General Meeting, 2014, pp. 1-5.
Electric Power Research Institute. His interests include integration of
[29] Z. Liu, B. Liu, S. Duan, et al., "A novel DC capacitor voltage balance
renewables into large power system.
control method for cascade multilevel STATCOM," IEEE Transactions
on Power Electronics, vol. 27, no. 1, pp. 14-27, Jan. 2012.
[30] Y. Cheng, M. Sahni, D. Muthumuni, et al., "Reactance scan Yunhong Li received the M.S. degree in electrical engineering from Tsinghua
crossover-based approach for investigating SSCI concerns for University, Beijing, China, in 2013. She is currently working for North China
DFIG-based wind turbines," IEEE Transactions on Power Delivery, vol. Electric Power Research Institute. Her interests include analysis and control of
28, no. 2, pp. 742-751, Feb. 2013. power systems with high-penetration of renewables.
[31] L. Fan, C. Zhu, Z. Miao, et al., "Modal analysis of a DFIG-based wind
farm interfaced with a series compensated network," IEEE Transactions Chuanyu Zhang received his B.S. degree from Tsinghua University, Beijing,
on Energy Conversion, vol. 26, no. 4, pp. 1010-1020, Apr. 2011. China, in 2014. He is currently pursuing his M.S. degree at the same university.
His research interests include power system stability analysis and control.
0885-8969 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.