Local Turbine Control


Technical Data Sheets

A 23.12.2011 First Issue RS PP JM


REV DATE DESCRIPTION PREPARED APPROVED RELEASED

Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

Contents

Chapter No Page

8. Technical Data Sheets 3


8.1. Controller ALSTOM Smart Control SX-SAIA 3
8.2. DC/DC Power supplies PHOENIX 4
8.3. Converter PHOENIX 5
8.4. Interface Relay PHOENIX 6
8.5. Relay COMAT 7
8.6. Mini Circuit Breaker ABB 8

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A



Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

8. Technical Data Sheets

8.1. Controller ALSTOM Smart Control SX-SAIA

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A


Technical information

Saia® PCD3.Mxxx0� – PLC series


�� ���� ������
high performance, compact, modular
Controls Division

By the combination of a fast microprocessor generation with the component-based Saia® NT


operating system, the Saia® PCD3 controller series sets highest benchmarks at functionality and
performance.
The PCD3 controller series consists of 11 equipment variants. Up to four flash- and/or intelligent
modules can be connected directly with the main processor, thus means «unlimited» memory
capacity and extremely effective communication.
Programmable with PG5 from Saia-Burgess Controls

Latest CPU technology


 Future-safe processor technology, up to 1024 Kbytes memory on board plus optional flash modules
combined with the Saia® NT operating system, transform a simply packed PLC into a very high performance,
enormously low-priced PLC of the middle class
 Profibus- and Ethernet-TCP/IP-interface in the base unit. Integrated Web server
Maximum peripheral connections
 Up to 1023 central inputs/outputs plus 2 interrupt inputs on board
 Additional remote inputs/outputs in RIO nodes via Profibus and/or Saia® Profi-S-Net
Efficient Saia® programming tools
 Convenient and efficient programming with comprehensive application components of PG5 Controls Suite
 HMI: HMI editor for PLC based displays; Web editor for Web-Panels
 FBox builder: adapt Fboxes to reqirements or create new FBoxes in order to save own know how
 A coordinating combination of operating system and programming tool achieves maximum speed,  
reliability and functionality
High performance processor,
high performance Saia® NT operating system,
high performance programming tool PG5
The Saia® PCD3 series unites continuity with innovative ideas and new technology.  
As a result, it covers the performance/function spectrum of several convention device series.  
It achieves this through a high degree of modularity in hardware and firmware.

The fast main processor has been incorporated in the back-plate of the device, unlike comparable systems.
Its capacity can be increased individually with plug-in co-processor modules and/or intelligent I/O modules.
These have a direct, very fast bus connection to the main processor. The Saia® PCD3 series is therefore
excellently prepared for the rapidly increasing demands on performance that are to be expected.

Fast CPUs with COLDFIRE processor CF5272


 Can be used in time-critical applications to replace the formerly most
powerful PCD multiprocessor technology
 Use of convenient graphical software is possible, due to the fast CPU and 
large memory capacity
 Ideally suited for use as master controller in large installations with many 
remote inputs/outputs and intelligent actuators and sensors

Characteristics of the Saia® PCD operating system


 Program portability across the entire PCD family
 Short reaction times, due to the instruction sets proximity to hardware, efficient
addressing modes, direct access to I/Os, and other features
 The open architecture of the component-based Saia® NT operating system provides
a basis for problem-free adaption to future developments, thereby guaranteeing
maximum investment protection

Programming, project planning and configuration of Saia® PCD


Advantages of the PG5 Controls Suite  (Details see TI 26/362 and SI 26/422)
 Program portability: PG5 programs can run on all Saia® PCD platforms
 Program organization by files (containing several program blocks) simplifies the
shared use of program files between several Saia® PCD controllers
 Programming and debugging environments united in the same program editor
 Simple programming of terminal displays with the integral HMI Editor
 Creation of Java based Web sites with the Saia® S-Web editor
 Powerful instruction set supported by macros and assembler directives

Features of the PG5 Controls Suite


 Symbol Manager administers all local, global and network symbols or symbol
groups. Automatic address allocation largely dispenses with the need for fixed
addressing.
 Project Manager administers complex installations of networked PCDs,
including displays and documentation
 Online functions for commissioning and error detection via Ethernet-TCP/IP,
Saia® S-Bus, modem etc.
 Integrated programming environments: 
  Fupla (function block diagram) 
  S-Edit (instruction list IL) 
 Graftec (sequential function chart)
 Integrated network editors for Saia® S-Bus, Saia®  S-Net, Profibus DP
 Extensive additional libraries broaden the scope of PG5 functions

www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modula


 |
r
Manifold system resources

Block diagram of resources by the example of PCD3.M5540

F1xx + F2xx modules I/O in Base unit I/O in Extensions


Supply slots 0…3 slots 0…3 PCD3.C100/.C110/.C200
Serial data interfaces / Addresses 0…63 Addresses 64…1023
connections of fieldbus

I/O Bus I/O Bus I/O Bus

RUN
M
STOP T F E E DB
vol vol E M

Interrupt
CPU R
nvol
P
R
O
R
Y TX
Backup
C F O M
inputs nvol nvol M A P User
P
memory
User media User
Date-Time memory
nvol

R register
T timer
Watch-Dog C Counter
F flag
vol volatile
nvol non volatile
P program
RS 485 COM/PGU USB connection for TX text
S-Net/ Ethernet Modem RS 232 programming unit DB data block
MPI TCP/IP “full handshaking”

User memory

1 MByte
Total available user memory can practi-
cally be divided at will into sectors for
program, text and data blocks. This ena-
bles the requirements of any particular
Data blocks (DB)

Memory starting with : application to be met in the best possible


way. With the instructions available, data
- HW version D
- Firmware ≥ 031 can be transferred under the other user
- Software ≥ PG5 1.4.120
media, such as flags, registers, timers
and counters. The following values are
valid:
512 KByte
 1 register content (32 bit) occupies
4 bytes in the data block range and
character

8 bytes in the text range


Text-
(TX)

 1 text character occupies 1 byte


1 MByte Flash card pluggable

 1 program line occupies 4 bytes


512 KByte on board Flash

1 MByte on board Flash

(Details see Flyer 26/458)


512 KByte RAM

Program

128 KByte
1 MByte RAM
on board Flash
Backup

Backup

Backup

Backup

(P)
128 KByte

128 KByte
RAM

PCD3.M3020 PCD3.M3230 PCD3.M5340 PCD3.M6240


PCD3.M3120 PCD3.M3330 PCD3.M5440 PCD3.M6340
PCD3.M5540 PCD3.M6440
PCD3.M6540

Saia® PCD3.Mxxx0 - high performance, compact, modula www.saia-pcd.com


|
r

Compact Saia® PCD3 series | Performance overview

Fast CPUs with COLDFIRE CF5272 


■ Outstanding communications features
■ can be used in time-critical applications to
replace the formerly most powerful PCD multi-
processor technology
■ Use of convenient graphical software is pos-
sible, due to the fast CPU and large memory
capacity

PDC3 Basic
M3020  M3230 
On board Ethernet 10/100 MBit/s M3120 M3330
Number of inputs/outputs ≤ 64 ≤ 1023 1)
Number of I/O module sockets 4 ≤ 64 1)
Extension module holder connector no yes
Interrupt inputs 2 2
On board memory
User memory (RAM)  128 KByte 512 KByte 2)
for program, text/DB
Backup memory (Flash) 128 KByte 512 KByte
File-System memory (Flash) Optionen: ≥ 3 MByte mit PCD3/PCD7.R55xM04,  
≤ 2 GByte mit PCD3.R600 & PCD7.R-SD512
8 hours with SuperCap  
Data protection
Optional: battery kit PCD3.R010
On Board integral ports
On terminal block
RS 485 for free protocols or ≤ 115.2 kBit/s
Multi Master, Profi-S-Net ≤ 187.5 kBit/
On D-Sub connector
RS 232 –
RS 422/ 485 –
Profibus DP slave, Profi-S-Net –
Contr. Area Network CAN 2.0B –
Profibus DP Master –
Optional  
  RS 232, RS 485, RS 422, TTY/20 mA, Belimo MP-Bus
   
1 port PCD3.F1xx only used on I/O slot 0
≤ 8 ports PCD3.F2xx  I/O slots 0…3
BACnet modul PCD3.R56x  I/O slots 0…3 of PCD3.M3120/.M3330 
BACnet card PCD7.R56x Slot M1/M2 of PCD3.M5340/. M5540/ .M6340 & .M6540
Integral with all PCD3.Mxxxx Web- & FTP-server, Watchdog, Real time clock
Programmable via USB 1.1 or Ethernet PG5 starting from version 1.4.100 PG5 staring from version 1.3.100
Processing time ■ bit operation 0.3…1.5 μs
■ word operation 0.9 μs

General technical data / Operating conditions


Current supply Mechanical data
Supply voltage 3) 24 VDC  -20 / +25% Type of mounting DIN rail 35 mm
incl. 5% ripples
Current /  typ. 175 mA / 4.2 W / Protection level IP 20
Power consumption max. 500 mA / 12 W
Load-carrying ability    
Flame resistance UL94 V0
5V / 24V internal max. 600 mA / 100 mA
Short voltage interruptions )3
≤ 10 ms with interval ≥ 1 s Vibration ) 3
0.075 mm / 1.0 g sinusoidally
Watchdog relay closing contact 48 VAC or VDC 4), 1A Shock 3) 15 g / 11 ms sine half wave
Environmental influences
Storage temperature 3) -25...+70 °C 3
) according to EN / IEC 61131-2

Ambient temperature operating ) 3


0...+55 °C ) or 0...+40 °C
5 4
) mount a free-wheeling diode over the load when switching DC tension
5
) mounted on vertical surface
Relative air humidity ) 3
10...95 % r.h. non-condensing

www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modula


 |
r
Extended CAN DP Master
  M5440  M6240  M6440 
M5340 M5540 M6340 M6540
≤ 1023 1)
≤ 64 1)
yes
2

1024 KByte 2)

1024 KByte or optional: PCD7.R500/.R5x1(M04) Flash card


Optionen: ≥ 3 MByte with PCD3/PCD7.R55xM04,  
≤ 2 GByte with PCD3.R600 & PCD7.R-SD512

1…3 years with battery

≤ 115.2 kBit/s ≤ 115.2 kBit/s  ≤ 115.2 kBit/s ≤ 115.2 kBit/s


≤ 187.5 kBit/ – ≤ 187.5 kBit/ ≤ 187.5 kBit/

≤ 115.2 kBit/s ≤ 115.2 kBit/s ≤ 115.2 kBit/s ≤ 115.2 kBit/s


≤ 115.2 kBit/s – – –
– ≤ 1.5 MBit/s – –
– – ≤ 1 MBit/s –
– – – ≤ 12 MBit/s

RS 232, RS 485, RS 422, TTY/20 mA, Belimo MP-Bus

only used on I/O slot 0
I/O slots 0…3
I/O slot 0…3 of PCD3.M3120/.M3330 
Slot M1/M2 of PCD3.M5340/. M5540/ .M6340 & .M6540
Web- & FTP-Server, Watchdog, Real time clock
PG5 staring from version 1.4.120 PG5 staring from version 1.3.100 PG5 staring from version 1.4.100 PG5 staring from version 1.4.120
0.3…1.5 μs
0.9 μs

System resources
Flags 8 192 × 1 bit, volatile or non-volatile,   Timing range 31 bit, unsigned (0…2 147 483 647)  
division programmable timing signals, selectable (10 ms to 10 s)
Registers 16 384 × 32 bits, non volatile Texts and DBs 8 192
Indexregisters 17 × 13 bit (1 each per COB and XOB) Date-time (RTC) Time values: s / min / h, week / day of week,
month / day of month, year
Timers/Counters 1600 volatile timers or non-volatile counters, Accuracy better than 1 min/month
division programmable
Counting range 31 bit, unsigned (0…2 147 483 647) Power reserve PCD3.M3xx0: 8 hours
PCD3.M5xx0 and PCD3.M6xx0: 1 to 3 years
Computational   Integers: –2 147 483 648…+2 147 483 647
ranges (–231…+231–1) 
Floating-point numbers:  
±9.223 37 × 1018…±5.421 01 × 10–20 
Formats: decimal, binary, BCD,  
hexadecimal or floating point

Saia® PCD3.Mxxx0 - high performance, compact, modula www.saia-pcd.com


|
r

Slots | Ports | Communication possibilities
(Communication possibilities see SI 26/381)

With its fast COLDFIRE processor, expansion to 1023 central I/Os and large memory capacity, 
the PCD3.Mxxx0 offer a powerful controller platform for multiprocessor operation and data recording, 
date management and data transfer.
PCD3.Mxxx0 have four times the number of registers and up to 5 interfaces built into the base unit.
With add-on modules 8 additional serial ports can be achieved. The operating system supports different
protocols, naturally Saia® S-Bus and field busses, such as Profibus and Ethernet TCP/IP.  
The Profibus layer 2 (FDL) based Saia® private control network Profi-S-Net includes special features,  
as multiprotocol operation (e.g. DP, MPI and HTTP), multimaster communication, the transmission of
plugins (active slaves) and web access.

PCD3.M5540 with opened cover, Flash Card (optional) and battery module (PCD .M5440 without Ethernet)

PCD3.F1xx in: Slot 0, Port 1

PCD3.F2xx in:
Slot 0, Port 100 and 101 
Slot 1, Port 110 and 111 
PCD3.R600  
Slot 2, Port 120 and 121 
for SD flash or Slot 3, Port 130 and 131
PCD7.R-SD256
or
PCD7.R-SD512
I /O bus extension  
(up to 1023 digital I/Os)
with connectoror cable

Port 2
Port 3 or 10
Port 0

Port 9

RS 485
Ethernet-TCP/IP integrated
USB
RS 485/S-Net
RS 232/PGU
PCD3.M3330 (PCD3.M3020 und PCD3.M3230 without Ethernet, not expandable)
Slot 0, Port 1

PCD3.R600
for SD flash or
PCD7.R-SD256
or
PCD7.R-SD512 I /O bus extension  
(up to 1023 digital I/Os)
with connectoror cable

Port 2
Port 9

www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modular


 |
Integral ports in all base units
■ USB 1.1 (slave device) interface, for use as programming interface
■ RS 485 port, up to 115.2 kbit/s, usable as free user interface  
or Profi-S-Net up to 187.5 kbit/s
■ Ethernet-TCP/IP - with PCD3.M3120 / M3330 / M5340 / M5540 / M6340 and M6540

With PCD3.M5xxx or PCD3.M6xxx there are addditional serial interfaces :


PG ■ RS 232
 ■ RS 422/RS 485 (with PCD3.M5340)
■ Profi-S-Net (S-IO, S-Bus) - with PCD3.M5340 / M5x40 and M6x40 - up to 1.5 Mbit/s
■ Controller Area Network (CAN 2.0B) - with PCD3.M6240 and PCD3.M6340
■ Profibus DP Master - with PCD3.M6440 and PCD3.M654

Optional:
■ PCD3.F1xx: 1 × RS 422 with RTS/CTS or RS 485 electrically connected or  
1 × RS 232 with RTS/CTS, DTR/DSR, DCD or 1 × TTY/20 mA or  
1 × RS 485 electrically isolated or 1 × Belimo MP-Bus for 8 drives
■ PCD3.F2xx: Up to 4 PCD3.F2xxx modules with: 
up to 4 × RS 422 with RTS/CTS or. RS 485 electrically connected and/or  
up to 4 × RS 232 with RTS/CTS, DTR/DSR, DCD  
(each with a slot for 1 × PCD7.F1xx)
Memory / Backup flash card / BACnet / Battery module (see pages 8,9 and 20)

With all PCD3 types


Terminal block for supply, watchdog, interrupt inputs and Port 2
RS 485  
terminator switch Pin Signal Explanation Profibus signal Profibus wiring

1 D Port 2; RS 485 up to 115.2 kbit/s usable as RxD/TxD-N A green


free user interface or Profi-S-Bus up to
187.5 kbits/s (PCD3.M3xxx only)
2 /D Attention 5 V ! RxD/TxD-P B red

3 Int0 2 interrupt inputs or 1 fast counter 


Attention 24 V !
RS 485 terminator switch
4 Int1
5 WD Switch
Watchdog Designation Meaning
6 WD position
without  
7 +24V left O
termination resistors
Power Supply
with 
8 GND right C
termination resistors

Communication PCD3.M5xx0 PCD3.M5440 PCD3.M6240  PCD3.M6440 


interfaces PCD3.M6xx0 PCD3.M5340 PCD3.M5540 PCD3.M6340 PCD3.M6540
Port 0 Port 3 Port 10 Port 10 Port 10
PCD3.M5xx0/M6xx0 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 1 2 3 4 5 5 4 3 2 1

9 8 7 6 10 9 8 7 6 11 9 8 7 6 6 7 8 9 9 8 7 6

D-Sub PGU / RS 232 RS 422 /  RS 485 S-Net  / RS 485 CAN Profibus DP


Pin Signal Signal Signal Signal Master - Signal
1 DCD /RXD GND n.c. n.c.
2 RXD /CTS M24 CAN_L 3) GND 4)
3 TXD /TXD /RXD – /TxD RxD  / TxD-P ) 2
GND B red
4 DTR /RTS RTS CNTR-P2) n.c. En
5 GND DGND DGND DGND2) n.c. GND_BUS 5)
6 DSR RXD VP2) n.c. +5V_BUS 5)
7 RTS CTS P24 CAN_H ) 3
+24V 4)
8 CTS TXD RxD – TxD RxD / TxD-N ) 2
n.c. A green
9 n.c. RTS n.c. n.c. n.c.
PGND (10 + 11) 1)
Port 0 Port 3 or 1)
������������������������������������������
Screw terminals of D-Sub connector housing
Port 10 2)
Mandatory signals (the user must absolutely make available)
3)
Electrically isolated 4) Electrically connected
5)
Pins 5 and 6 can be used for termination only, potential for data transfer

Saia® PCD3.Mxxx0 - high performance, compact, modular www.saia-pcd.com


|
Communication interfaces | Protocols supported
(Communication possibilities see SI 26/381)

OnBoard interfaces Optional interfaces

Run- / Stop-Switch PCD3.F1xx   PCD3.F221 ➜ RS 232


Battery module for slot 0, port 1   PCD3.F210 ➜ RS 422/RS 485  
1
2
F for slots 0…3, ports 100…131

F
0

2
M1 M2 Port 1 RS 232

2
Both modules can

1
or RS 422 be equipped with a
or RS 485 PCD7.F1xx module for
or CL 20 mA an additional serial
F
or MP-Bus interface.
1
2
1

F

1
2
1
Profibus DP / 
Profi S-Net / 
RS 485 / 422
PGU / RS 232

CAN-Bus

Ethernet

RS 485
USB



Protocols supported 
Optional interfaces can be used to run the following When determining the maximum communications 
protocols: power per PCD3 system, the following should be 
  Modem communication with the PCD FBox library taken into account:
 HMI editor applications with PCD7.Dxxx text terminals   The communications volume is determined by periph-
(only with RS 232 interface) eral devices connected. For example, this is the case
  Seriell S Net   Belimo MP-Bus if the PCD3 is being used as an S-Bus slave station. 
  JCI N2 - Bus   KNX® S-Mode / EIB   If a PCD3 controller is bombarded with heavy tele-
  DALI   EnOcean gram traffic at high baud rates, there will not be much
Other protocols (drivers from third-party suppli- CPU capacity left for processing the actual applica-
ers) are in the responsibility of the manufacturer  tion. The following rules apply here: The use of 8 in-
(e.g. restriction mode only up to 9600 bps). terfaces with 9.6 kbps will take up approx. 50 percent
of CPU capacity. Two interfaces with 57.6 kbps will
Transmission rates supported: also take up approx. 50 percent of CPU capacity. Two
  1200, 2400, 4800, 9600, 19200, 38400, 57600,115200 bps. interfaces with 115 kbps will need around 60 percent
of CPU capacity.

System-dependent characteristics of    If the PCD3 is the initiator of communication, i.e.


PCD3.F2xx modules: PCD3 used as master station, the volume of com-
The following points should be noted when using munication and with it the communication capac-
PCD3.F2xx interface modules. ity is determined by the user program in the PCD3.
 For each PCD system, a max. of 4 PCD3.F2xx mod- In theory, all interfaces can run at the top transmis-
ules (8 interfaces) can be inserted in slots 0…3. sion rate of 115 kbps. Actual data throughput, how-
 The PCD3 system has a powerful processor to ever, depends on the user program and number of
look after both the application and the serial in- interfaces, and may therefore be small. It is crucial
terfaces. Processing the interface modules re- for any peripheral devices to be capable of running
quires adequate CPU power. with the chosen configuration and communica-
tions capacity.

For these reasons we recommend that communica-


tions applications with a large number of interfaces
and high transmission rates should first be discussed
with a local Saia® agent.

www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modula


 |
r
Slots | Flash cards and modules
(See Flyer 26/458)

PCD3.M5xx0  PCD3.M3xx0
PCD3.M6xx0 PCD3.R55xM04 PCD3.R55xM04 Battery kit
PCD3.R500 PCD3.R56x   PCD3.R600   PCD3.R500 PCD3.R56x   PCD3.R600   PCD3.R010  

M1 M2

5
SE

SE
R

R
$

$
IA

IA
G

G
7

7
RI

RI
TE

TE

"


"
USY

USY
!

!
CT

CT
IV

IV
ITY

ITY
or PCD7.R55xM04 

or PCD7.R55xM04 
or PCD7.R56x

or PCD7.R56x
PCD7.R500  

PCD7.R500 

for slots 0…3 for slots 0…3


for slot 3



Flash memory card or module for program and data backup


PCD7.R500

PCD7.R500 1 MByte flash card on slot M1 or M2 of PCD3.M5xx0 and PCD3.M6xx0 


PCD3.R500 1 MByte flash module on any I/O slot of all PCD3.M3xx0  
PCD3.R500

Only ������������������������������������
one module can be used per PCD3 CPU

Note: PCD7.R500 cards can also be fitted into PCD3.F1xx communication interface modules

Flash memory with file system, program- and data-backup, BACnet option
PCD7.R55xM04

Pluggable flash cards PCD7.R5xx on slot M1 or/and M2 of PCD3.M5xx0 and PCD3.M6xx0


PCD7.R550M04 4 MByte flash cards with file system (Up to 2 modules can be used per PCD3 PLC.) 
PCD7.R56x

PCD7.R551M04 4 MByte flash cards with 3 MByte file system and 1 MByte program backup
PCD7.R560 2 MByte flash cards with BACnet option 
PCD7.R561 2 MByte flash cards with BACnet option, 1 MByte file system  
and 1 MByte program backup

Pluggable flash modules PCD3.R5xx on any I/O module slots of all PCD3.Mxxx0
PCD3.R550M04 4 MByte flash module with file system (Up to 4 modules can be used per PCD3 PLC.) 
PCD3.R551M04 4 MByte flash module with 3 MByte file system and 1 MByte program backup  
PCD3.R55xM04 


PCD3.R560 2 MByte flash module with BACnet option 
PCD3.R56x

PCD3.R561 2 MByte flash module with BACnet option, 1 MByte file system  
and 1 MByte program backup

Note: PCD7.R55x cards can also be fitted into PCD3.F1xx communication interface modules
5
SE
R
$
IA
G
7
RIT
E

PCD3 basic module for SD flash memory cards with file system
"
US
Y
!
CTI
VIT
Y

PCD3.R600 Up to 4 modules can be fitted into the CPU I/O slots 0…3
PCD3.R600

PCD7.R-SD256 Saia® SD flash memory card 256 MByte with file system
PCD7.R-SD512 Saia® SD flash memory card 512 MByte with file system

Backup
Program backup into flash memory
PG5 can be used to load an application program

into flash memory. All hardware settings will also FLASH Externe
RAM onboard FLASH
be saved to flash. A flash card has priority over the
on board flash.

Restore
Saia® PCD3.Mxxx0 - high performance, compact, modula www.saia-pcd.com
|
r


Counting, measuring and motion control

Overview for axis control


Positioning action via Positioning action via Positioning action via
three-phase AC motors with stepper motors with servomotors (DC / BL / AC) with
frequency inverter motion control module motion control module
M M M

PCD3.M5540


Local positioning action controlled via
serial port RS 232, RS 422 or RS 485

M M M
Path detection via direct count input (max. 1 kHz)

Whether the drive is analogue or digital, whether there is a frequency inverter, stepper and servomotors
(DC/BL/AC), whether positioning action takes place centrally in the PCD or locally in an intelligent drive: the
PCD offers an efficient solution for every technology and topology. By close coupling of the PCD and the driving
controller, even complex motion sequences and their associated peripheral control functions can be realized
with the comfort and diagnostic capabilities of PCD programming.

Performance level Low Cost   Mid range  High End 


Control in CPU Positioning action in motion control module Positioning action in drive
Drive type Frequency inverter   Stepper motor Servodrive and   Intelligent drive
with AC motor servomotor
Velocity setpoint Fixed velocities triggered  Monophase pulse string  ±100% setpoint with  By power component, 
with digital signals and direction signal   ±10 V analogue signal motion control via DP 
up to 20 kHz or RS 485 serial data port
Path detection Incremental or SSI  - Incremental or SSI   In power component
absolute value encoder absolute value encoder
Modules PCD3.H110/..H150  PCD3.H210 PCD3.H31x PCD3.F1xx
PCD3.A400

Optimum solution for every counting and measuring task


Every PCD3 has 1600 counting registers with a counting capacity of 2 147 483 647 (31 bit). Via the interrupt inputs
counting frequencies of 1 kHz are achieved with the help of counting registers.

PCD3.H100 counting module PCD3.H110 counting and measuring module


The PCD3.H100 counting module counts pulses up to This universal module not only enables counting func-
20 kHz with 16-bit resolution (counting capacity 0…65 535; tions up to 100 kHz but also the precise measurement
can be used in tandem with CPU counter). The module of frequencies up to 100 kHz and the duration of periods
has two inputs A and B and recognizes the direction of and pulses up to one hour. For this purpose a FPGA
incremental shaft encoders. The counter can be enabled (Field Programmable Gate Array) component is used. 
via an external enable signal. The CCO output (counter The two counting inputs A and B allow the direction
controlled output) is directly controlled by the counter of incremental shaft encoders to be recognized and the
and can, for example, be used to trigger precise external simultaneous use of counting and measuring functions
switch operations or to release an interrupt. in the same module. The two fast outputs: CCO (counter
The module is suitable for counting revolutions, dis- controlled output) and TCO (timer controlled output) can,
tances, volumes etc. and for measuring by counting the for example, be used to trigger precise external switch
pulses. operations or to release an interrupt.
www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modular
10 |
Counting, measuring and motion control 
BACnet® | Interface for open building automation

Overview of PCD3.-modules for axis control

Module /   Description Frequency Number of   Output Count range /   Number Internal cur- I/O
Velocity profile Encoder I/Os/A position   of   rent draw connector
distance axes )
1
5V )2
type 3)
PCD3.H100 Pulse counter   ≤ 20 kHz 3 I 16 bit max. 16 90 mA A or B
up to 20 kHz + 1 O digital (65 535)

PCD3.H110 Pulse counting /  ≤ 100 kHz 3 I 24 bit max. 16 90 mA A or B


frequency measurement   + 1 O digital (16 777 215)
up to 100 kHz
Measurement of period-  
and pulse length
PCD3.H150 SSI Interface   ≤ 500 kHz 1 I SSI4) 8…29 bit max. 16 25 mA A or B
up to 500 kHz SSI + 1 O SSI   selectable
+ 4 O digital
SYNCHRONOUS SERIAL INTERFACE

PCD3.H210 Motion control module   ≤ 19.5 kHz 4 I + 4 O square 24 bit max. 16 85 mA A or B
for stepper motors pulse (16 777 215)

PCD3.H310  Motion control module   ≤ 100 kHz  4 I + 1 O  analogue 30 bit max. 16 140 mA  A or B
  for servo drives  24 VDC    ±10 V,   + 1 sign    
  (path acquisition,       12 bit bit  
  up to 100 kHz counting     (±1 073 741 824)  
  frequency)       
PCD3.H311         
as H310 but with RS 422  5 VDC    6 I + 1 O 160 mA
encoder inputs  RS 422
¹) No ..H..-module can be used at I/O base address 240 (conflict with WD at 255).
2
) Max. loading capacity: PCD3.Mxxx0: max. 600 mA, PCD3.T76x: max. 650 mA and PCD3.C200: max. 1500 mA (from HW version C)
3
) Plug-in I/O terminal blocks and cables) are not included with I/O modules. They must be ordered separately (see page 20)
4
) The SSI input is electrical isolated

BACnet® | Interface for open, interoperable building automation


Open systems are the prerequisites for integrated building technology. Saia-Burgess Controls wishes to take
this fact into account and has therefore developed the new Saia® PCD3 product family as BACnet® Building  
Controller (B-BC) following ANSI /ASHRAE 135-2001.
(See Flyer BACnet 26/442)

PCD3 as BTL certified BACnet® controller


  Supported BACnet® data-link-layers
  BACnet® / IP
  BACnet® / P TP based on RS 232 (incl. halfrouter  
functionality for modem communication) Management station
  BACnet® / IP Broadcast Management Device (BBMD)   Visi.Plus via OPC or
supports Foreign Device registration (FD) external system
  Standard functionality of the Saia® PCD3 remains untouched
BACnet® / IP
PCD3 as BACnet® Building Controller (B-BC)
The PCD3 supports 23 data objects,  
according to the standard ANSI ASHRAE 135-2004:
Data exchange:   Analogue input, output and value 
  Binary input, output and value  P PC
External system CD3 D3
  Multistate input, output and value
BACnet services:   Bidirectional connection via modem 
®

  Backup / restore according to B-BC requirement 


  Time synchronisation, UTC time synchronisation (as master and slave) 
  Flexible definition of write and read access, according to a priority mechanism 
  User-programmable client configuration for exchanging data with other automation stations 
BACnet® program: Accumulator, averaging, calendar, command, device, file, group, loop,program, pulse converter, 
schedule, event enrolment, notification class, and trendlog object
Saia® PCD3.Mxxx0 - high performance, compact, modular www.saia-pcd.com
| 11
PCD3 for centralized and decentralized automation tasks
(Details see TI 26/388 and TI 26/389)

PCD3.Cxxx can be used for centralized I/O extension on the I/O bus of PCD2-/PCD3 controllers  
and/or with PCD3.T76x RIOs for decentralized automation tasks via Profibus or Profi-S-Net.

Extension to the PCD3.Mxxxx CPU via I/O bus


for single or double-row assembly

PCD3.M5xxx or PCD3.M3xxx PCD3.C100

E E E E B B B A
1 1 1 5 1 1 1 2
1 1 1 0 0 0 0 0
0 0 0 0 0 0 0 0
Profi-S-Net

Profibus

5540 100
Profibus DP slave, 1.5 Mbit/s I/O bus connector PCD3.K010
Extension via Profi-S-Net Up to 1023 centralized digital I/Os
I/O bus
connecting cable
PCD3.K106/K116
Extension to a PCD2.Mxxx
CPU via I/O bus PCD3.C200 PCD3.C100

W800 W800 A810 A860 E165 E110 B100 B100


I256
A/M320 A/M16
A/M336 O352
Switch I272 I288 I304
O368 I257
I258
I273 I279 I305
Val320 Val16
Val336 I259
O353
Switch I260 E
I274 B
I/O280 E
I/O306
I261
A/M321 A/M17
A/M337
O369
I262 1
I275 1
I/O281
1
I/O307
O354 I263
I264 1 0 1
Val321 Val17
Val337 I276 I/O282 I/O308
O355
I265
I266
0 0 0
I277 I/O283 I/O309
A/M322 A/M18
A/M338 I267
I268
I278 O284 O310
I269
Val322 Val18
Val338 I270
I279 O284 O311
I271
Slot #20 Slot
Slot #21
#1 Slot #22 Slot #23

I/O bus
Slot #16 Slot #17 Slot #18 Slot #19

connecting cable
PCD2.K106
200 100

PCD3.C200 PCD3.C110
Extension via Profibus (PCD2.Mxxx)
or Profi-S-Net (PCD2.M480 only) E110 B100 H110 H210 A200 A220

I/O bus I384 I400 A I432 O448 O464

I385 I401 B I433 O449 O465


connecting cable I386 I/O402 EnC I434 A
O450 O466
2
PCD3.K106/K116 I387
I388
I/O403

I/O404
EnM

CCO
I435

PUL
O451
0
O467

O468
0
I389 I/O405 TCO DIR O469

I390 O406 O434

I391 O407 O435

Slot #24 Slot #25 Slot #26 Slot #27 Slot #28 Slot #29

 #

Up to 1023 centralized digital I/Os

PCD3.T 76x PCD3.C110

E E W E E A
1 6 3 1 1 4
6 1 1 1 6 6
5 0 5 0 0 0

Extension via PCD3.T76x RIO


via Profibus or Profi-S-Net

? #

Up to 256 decentralized digital I/Os per RIO node, 


(extension via I/O bus connector or I/O bus cable) 

www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modular


12 |
PCD3 series – devices and components
(Details see TI 26/388 and TI 26/389)

Up to 15 module holders PCD3.Cxxx can be attached to the PCD3.Mxxx0 (except M3x20). Thus allows the user
to connect up to 64 I/O-modules or 1023 digital I/O points. Every base unit has room for 4 I/O-modules.

Description of the PCD3 series


  PCD3.Mxxxx CPU with 4 PCD3 module slots
  PCD3.Txxx RIO head station with 4 PCD3 I/O module slots
  PCD3.Cxxx Module holder with 2 or 4 PCD3 I/O module slots
  PCD3.A/E/W/B/Hxxx PCD3 I/O modules in cassette form
  PCD3.Kxxx Extension cables and connectors

PCD3.C100 module holder


  4 I/O module slots
  Extension module holder for PCD3.Mxxxx/.Txxx/.Cxxx and PCD2.Mxxx
  Additional PCD3.Cxxx devices connectable via connection plug or extension cable
  Indication of internal 5 V supply voltage via LED

PCD3.C200 module holder with connecting terminals for 24 VDC power supply
  4 I/O module slots
  Extension module holder for PCD3.Mxxxx/.Txxx/.Cxxx and PCD2.Mxxx
  Additional PCD3.Cxxx devices connectable via connection plug or extension cable
  Max. loading capacity: from internal 5 V bus 1500 mA,
from internal +24 V bus 200…630 mA (from HW version C)
  Indication of internal 5 V supply voltage via LED
 Connecting terminals for 24 VDC power supply for all connected PCD3 I/O modules,  
plus any downstream PCD3.Cxxx module holders

PCD3.C110 module holder


  2 I/O module slots
  Extension module holder for PCD3.Mxxxx/.Txxx/.Cxxx and PCD2.Mxxx
  Indication of internal 5 V supply voltage via LED

PCD3 modules in cassette form (PCD3.Axxx/Exxx/Wxxx/Bxxx/Hxxx/Rxxx/Fxxx)


  More than 50 modules available with differing functionalities
  Status of digital signals indicated via LEDs
  Uniform PG5 and STEP®7 support in all CPUs and RIOs via FBs and FBoxes

Connection technology: plug-in spring or screw terminal blocks, or system cable


Connection of the I/O level is either via plug-in screw terminals or spring terminal blocks, or with
plug-in system cable, or across a ribbon cable ↔ screw terminal adapter  (see TI 26/388).

  Typ A 10-pole spring terminal block up to 2.5 mm2, labelled 0 to 9,


for I/O modules with 4, 6 or 8 I/Os
  Typ B 10-pole screw terminal block up to 2.5 mm2, labelled 0 to 9,
for I/O modules with 4, 6 or 8 I/Os
A   Typ C 24-pole spring terminal block up to 1 mm2, labelled 0 to 23,
B for I/O modules with 16 I/O or relay module A251
C   Typ E 14-pole spring terminal block up to 1.5 mm2, labelled 0 to 13,
for some analogue modules
E
  Typ D PCD2.K22x Sheathed, round cable with 32 strands of 0.25 mm²
PCD2.K23x Sheathed, half-round cable with 34 strands of 0.09 mm²,
with 34-pole ribbon connector at both ends
PCD2.K24x Sheathed, half-round cable with 34 strands of 0.09 mm²
D   Typen F, G, H, J, K and matching cable for manual control modules (see pages 20)
50 mm 50 mm

2 1

Durchmesser = 11 mm
2 1
I/O terminal blocks and system cables are NOT included with I/O modules.  
Steckeransicht

Etikette

They must be ordered separately (see pages 20)


von unten

PCD2.K231

Gummitülle Gummitülle
The PCD3.W745 temperature module is delivered with connector.
34 33 34 33

Länge = 1.0 m bzw. 2.0 m

Connection plug and cable


  PCD2.K106: Connection cable 0.7 m PCD2.Mxxx ↔ PCD3.Cxxx
  PCD3.K010: Connection plug PCD3.Mxxxx/T76x/Cxxx ↔ PCD3.Cxxx
  PCD3.K106: Connection cable 0.7 m PCD3.Mxxxx/T76x/Cxxx ↔ PCD3.Cxxx
  PCD3.K116: Connection cable 1.2 m PCD3.Mxxxx/T76x/Cxxx ↔ PCD3.Cxxx

Saia® PCD3.Mxxx0 - high performance, compact, modular www.saia-pcd.com


| 13
Maximum number of I/O modules per PCD
PCD type Maximum number of I/O modules Maximum number of digital I/Os
Base CPU/RIO PCD3.Cxxx extension Total Base CPU/RIO PCD3.Cxxx extension Total
PCD2.M12x  
8  8 16 128 127   255
PCD2.M15x 
PCD2.M17x  8 24 32 128 382   510
PCD2.M48x 
8 56 64 128 895 1023
PCD2.M5xxx
PCD3.M3x3x 
PCD3.M5xxx  4 60 64   64 959 1023
PCD3.M6xxx
PCD3.T76x (RIO) 4 12 16   64 191   256

Overview of digital input/output modules PCD3


Internal I/O
Input Output breaking capacity Input Electrical current draw
Type Total I/Os connector-
voltage DC AC filter isolation
5 V 1) 24 V 2) type� 3)
PCD3.E110 8I 15 … 30 VDC 8 ms 12 mA A or B
PCD3.E111 8I 15 … 30 VDC 0.2 ms 12 mA A or B
PCD3.E112 8I 7.5 … 15 VDC 9 ms 12 mA A or B
PCD3.E116 8I 3.5 … 7 VDC 0.2 ms 12 mA A or B
PCD3.E160 16 I 15 … 30 VDC 8 ms 8 mA D
PCD3.E161 16 I 15 … 30 VDC 0.2 ms 8 mA D
PCD3.E165 16 I 15 … 30 VDC 8 ms 8 mA C
PCD3.E166 16 I 15 … 30 VDC 0.2 ms 8 mA C
PCD3.E500 6 I 80 … 250 VAC 20 ms ■ 1 mA A or B
PCD3.E610 8 I 15 … 30 VDC 10 ms ■ 12 mA A or B
PCD3.E613 8 I 30 … 60 VDC 9 ms ■ 12 mA A or B
PCD3.A200 4 O, relay (make/no) 2 A/50 VDC 2 A/250 VAC ■ 10 mA A or B
PCD3.A210 4 O, relay (break/nc) 2 A/50 VDC 2 A/250 VAC ■ 10 mA A or B
PCD3.A220 6 O, relay (make/no) 2 A/50 VDC 2 A/250 VAC ■ 10 mA A or B
PCD3.A251 8 O, relay (6 changeover/ 2 A/50 VDC 2 A/48 VAC ■ 15 mA C
co + 2 make/no)
PCD3.A300 6 O, transistor 2 A/10 … 32 VDC 15 mA A or B
PCD3.A400 8 O, transistor 0.5 A/5 … 32 VDC 15 mA A or B
PCD3.A410 8 O, transistor 0.5 A/5 … 32 VDC ■ 15 mA A or B
PCD3.A460 16 O, transistor 0.5 A/10 … 32 VDC 8 mA D
PCD3.A465 16 O, transistor 0.5 A/10 … 32 VDC 8 mA C
PCD3.A810 4 A, relay (2 changeover/ 2 A/50 VDC 5 A/250 VAC ■ 40 mA F
co + 2 make/no)
manual control 2 A/50 VDC 6 A/250 VAC ■

PCD3.A860 2 O, relay (make/no) - 12A/250 VAC ■ 18 mA G


2I
manual control 15 … 30 VDC 8 ms H
PCD3.B100 2 I + 2 O + I:15 … 32 VDC 0.5 A/5 … 32 VDC 8 ms 15 mA A or B
4 selectable I or O
1
) Typical current draw from internal 5 V bus. Max. loading capacity: PCD3.Mxxx0: max. 600 mA, PCD3.T76x: max. 650 mA and PCD3.C200: max. 1500 mA (from HW version C)
2
) Typical current draw from internal +V bus. Max. loading capacity: PCD3.Mxxx0, PCD3.T76x max. 100 mA and PCD3.C200: 200…630 mA (from HW version C)
3
) Plug-in I/O terminal blocks and cables (see page 20) are not included with I/O modules. They must be ordered separately
Important: For an easy way to calculate required electric current, please use the Excel calculation table provided  
under http://www.sbc-support.ch or under http://www.saia-burgess-controls.de

Digital and analogue relay modules with manual control


PCD3.A810 PCD3.A860  PCD3.W800  
Relay outputs, Light and shade   4 Analogue outputs 
2 changeover/co and relay outputs (3 channels with
2 make/no contacts  2 make/no contacts manual control)
and 2 inputs

Details see P+P26/388

www.saia-pcd.com Saia  PCD3.Mxxx0 - high performance, compact, modula


®

14 |
r
Overview of analogue input/output modules PCD3
Internal I/O
Total Signal ranges Electrical current draw connector
Type Resolution
I/Os isolation type� 3)
5 V  ) 24 V 2)�)
1

PCD3.W200 8I 0…+10 V 10 Bit 8 mA 5 mA A or B


PCD3.W210 8I 0…20 mA 10 Bit 8 mA 5 mA A or B
PCD3.W220 8I Pt 1000: –50 °C…400 °C/Ni 1000: –50 °C…+200 °C 10 Bit 8 mA 16 mA A or B
PCD3.W220Z03 8I NTC 10 temperature sensor 10 Bit A or B
PCD3.W220Z12 4I+ 4 I: 0…10 V 10 Bit A or B
4I 4 I: Pt 1000: –50 °C…400 °C/Ni 1000: –50 °C…+200 °C 10 Bit A or B
PCD3.W300 8 I 0…+10 V 12 Bit 8 mA 5 mA A or B
PCD3.W310 8 I 0…20 mA 12 Bit 8 mA 5 mA A or B
PCD3.W340 8 I 0…+10 V/0…20 mA� 4) 12 Bit 8 mA 20 mA A or B
Pt 1000: –50 °C…400 °C/Ni 1000: –50 °C…+200 °C
PCD3.W350 8 I Pt 100: –50 °C…+600 °C/Ni 100: –50 °C…+250 °C 12 Bit 8 mA 30 mA A or B
PCD3.W360 8 I Pt 1000: –50 °C…+150 °C 12 Bit 8 mA 20 mA A or B
PCD3.W305 7 I 0…+10 V 12 Bit ■ 60 mA 0 mA E
PCD3.W315 7 I 0…20 mA/4…20 mA parameters can be set 12 Bit ■ 60 mA 0 mA E
PCD3.W325 7 I –10 V…+10 V 12 Bit ■ 60 mA 0 mA E
PCD3.W400 4 O 0…+10 V 8 Bit 1 mA 30 mA A or B
PCD3.W410 4 O 0…+10 V/0…20 mA/4…20 mA jumper selectable 8 Bit 1 mA 30 mA A or B
PCD3.W600 4 O 0…+10 V 12 Bit 4 mA 20 mA A or B
PCD3.W610 4 O 0…+10 V/–10 V…+10 V/0…20 mA/4…20 mA   12 Bit 110 mA 0 mA A or B
jumper selectable
PCD3.W605 6 O 0…+10� �V
� 10 Bit ■ 110 mA 0 mA E
PCD3.W615 4 O 0…20 mA/4…20 mA parameters can be set 10 Bit ■ 55 mA 0 mA E
PCD3.W625 6 O –10� �������
V…+10�
�������
 �
V
� 10 Bit ■ 110 mA 0 mA E
PCD2.W525 4 I +   I: 0…10 V, 0(4)…20 mA, Pt 1000, Pt 500 or Ni 1000   I: 14 Bit ■ 40 mA 0 mA E
(selectable by DIP switch)
2O O: 0…10 V or 0(4)…20 mA   O: 12 Bit
(selectable by software (FBox, FB)
PCD3.W745 4 I Temperature module for TC and 4-wire Pt/Ni 16 Bit ■ 200 mA 0 mA 6
)
PCD3.W800 4 O 0…+10 V, short circuit proofed 10 Bit 45 mA 35 mA�  ) 5
J
3 of them manually operated
1
) ��������������������������
Typical current draw from internal
����������������������������������������������������������������������������������������������������������������������������������������
5 V bus. Max. loading capacity: PCD3.Mxxx0: max. 600 mA, PCD3.T76x: max. 650 mA and PCD3.C200: max. 1500 mA (from HW version C)
2
) Typical current draw from internal +V bus. Max. loading capacity: PCD3.Mxxx0, PCD3.T76x max. 100 mA and PCD3.C200: 200…630 mA (from HW version C)
3
) Plug-in I/O terminal blocks and cables (see page 13) are not included with I/O modules. They must be ordered separately (see page 20)
)�� 4 … 20 mA via user program 5) At 100 % output value and 3 kΩ load 6) With soldered I/O spring terminal block
4

Important: For an easy way to calculate required electric current, please use the Excel calculation table provided  
under http://www.sbc-support.ch or under http://www.saia-burgess-controls.de

PCD3.R010 battery kit (for PCD3.M3xxx)

Consists of:
■ Battery module for slot #3 only
■ Lithium battery ��������������������������������
CR 2032�������������������������
(buffer time 1…3 years)

Saia® PCD3.Mxxx0 - high performance, compact, modula www.saia-pcd.com


| 15
r
Labelling Input-/ Output modules

Addressing and marking I/O modules and module holders


I/O module slots in the module holder are labelled ei-
ther with numbers
■ 0…3 (PCD3.Mxxxx  / T76x / C100, C200)
■ 0…1 (PCD3.C110)
➊ (4 310 8686 0) ➋ (4 329 4819 0)
The inscription carrier supplied ➋ can either be used
for additional labelling of the module holders, or for
the I/O modules themselves. They are blank and, de-
pending on requirements, may either be inscribed by
➌ ➌ hand or by means of preprinted adhesive strips ➊ .
➍ The connection diagram printed on the side of each
I/O module ➌ not only makes wiring easier, it also
helps during commissioning. On the opposite side
of the cassette sufficient space is available ➍ for the
user to add his own labelling.
E
6
1
➎ (4 310 8723 0)
0 ➎ Additional labelling on front panel 
Since summer 2005 all PCD3 module types can be la-
belled on the front panel.
Optional, neutral labels with a snap-on cover (clip) are
available for this purpose.
Without Clip Withit Clip

Fast labelling of I/O modules with the Saia® Label Creator


This software tool is used to inscribe PCD3 label clips effi ciently. The user enters unique data-point texts
in the tool. These can then be printed on the A4 master sheet. For the different types of PCD3 modules, the
user selects formats with the corresponding spacing. Text entered and all standard text parameters (such
as size, colour and font) can then be stored and reused as a master.

E
6
1 E
0 6
1
0
Without Clip With Clip

The Saia® Label Creator is supplied with PG5 Controls-Suite, but may also be downloaded from the  
Internet support site: www­.sbc-support.ch

16 |
www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modular
Web-HMI | Control & monitoring beyond system boundaries,  
thanks to browser technology
(Details see TI 26/430, SI 26/432 and SI 26/428)

Imagine: Saia® S-Web-Editor


■ You create a visualization or operation project
just once, and can then display and operate it
on any device with a browser, whether it is a
PC, PDA, Saia® Windows-Panel (6.4…15.4 inch)
or one of our small Saia® PCD Micro-Browser
devices (3.5…5.7 inch). PC
Access Point
■ Without spending any more on engineering or
software, you can use a web server from a single Saia® Web-Panel eXP
F1
PDA
display/operator device to control and monitor Micro-Browser
F7 F2

F8 F3
ESC F4
F9
F10 F5

F11 F6
Shif
t
F12

Ente
r

all the automation equipment connected in a net-


Saia Web-Panel MB
® ESC

work.
F1
Shi

1

ft F5 F2

2
F6 F3

ab
gh
5,7“

c
i
7

3
F7
 F4

pq

de
jkl
rs

f
,

8
.

6
F8

mn
tuv

o
0

9
wx

yz
+

-
En
ter
C

■ You can simultaneously access every automation

Te
xt
The Saia® S-Web concept
device with practically any control and display Saia® Web-Panel MB
stands for this to work reli- 3,5“
device. ably and efficiently, even in complex
➤ That is Web-HMI applications, without Java knowledge.

Windows in automation
even without plug-in cards and drivers
(Details see SI 26/456)

For critical control circuits and logic functions in


general automation, PLC hardware with a dedi-
cated PLC operating system is the best platform.
For other tasks Windows devices; whether as
P
TT
H/
et

office PCs, IPCs, PDAs or touch-panels are favour-


rn
e
th
E
H
T
T
P

ably.
d

us
ir

-B
e

us
S
ct

t/

fib
B

ne
S

ro
U

er

P
th

USB and Ethernet connect the field technol-


W on

E
C
e n

-L fi-
k
b e

S ro
in
- c

ll
ie
er
t
S

S
-C

Ja
ogy to the Windows platform. Plugin cards with
o

va
n
I
G

n
C

e
L

ct
TM
H

t
le

appropriate drivers, which follow the lifecycle of


pp
A

Windows versions, are no longer necessary.


I
G
C

.N
L

et
TM

ct
H

ne

Ja
on

va
-C
S

.N
et
W atf
in or
pl

do m
w
s
Fi

Saia® PCD Windows® touch-panels in the CE version are also


el
d
PL

le
ve

open to your own application program


C

l
pl
at
R
em

fo
S ro f i b E I

B
ot

-B fi u B

rm
P ro N /
e

S
u S s- /..
I/

P O

t
s -B D .
O

e
s

rn

For use in the field Saia®  offers a wide range


u P

e
s /C

th
E
A

of touch-panels with an open Windows® CE or


N

embedded XP operating system. Devices are deliv-


C
P
U

ered fully configured and loaded with software,


Tight and secure coupling to the Windows world via   onto which you may also integrate your own .NET
USB and Ethernet applications.
Saia® PCD3.Mxxx0 - high performance, compact, modula www.saia-pcd.com
r
| 17
Dimension drawings

Dimensions drawing 
PCD3.M3xx0 







 

Dimensions drawing
PCD3.M5xx0 / PCD3.M6xx0








 

www.saia-pcd.com Saia® PCD3.Mxxx0 - high performance, compact, modular


18 |
Ordering information

Type Description
Base units for 4 modules
PCD3.M3020 PLC with 128 KBytes of user memory, backup with 128 KBytes on board Flash memory,
up to 64 digital I/O (not expandable), 2 interrupts, web-server,
USB port for PG5, RS 485 for Profi-S-Net or S-Bus, 8 hours data protection with SuperCap
PCD3.M3120 like PCD3.M3020 but with Ethernet TCP/IP
PCD3.M3230 PLC with 512 KBytes of user memory, backup with 512 KBytes on board Flash memory,
up to 1023 digital I/O (with PCD3.Cxxx), 2 interrupts, web-server,
USB port for PG5, RS 485 for Profi-S-Net or S-Bus, 8 hours data protection with SuperCap
PCD3.M3330 like PCD3.M3230 but with Ethernet TCP/IP
PCD3.M5340 PLC with 1 MByte of user memory, backup with 1 MByte on board Flash memory,
up to 1023 digital I/O (with PCD3.Cxxx), 2 interrupts, web-server,
USB port for PG5, RS 232, RS 422/485 for Profi-S-Net and RS 485 for S-Bus, Ethernet TCP/IP
Run/Stop switch, 2 slots for PCD7.Rxxx, 1…3 years data protection with lithium battery
PCD3.M5440 PLC with 1 MByte of user memory, backup with 1 MByte on board Flash memory,
up to 1023 digital I/O (with PCD3.Cxxx), 2 interrupts, web-server,
USB port for PG5, RS 232, 2 × RS 485 for Profi-S-Net/MPI/S-Bus,
Run/Stop switch, 2 slots for PCD7.Rxxx, 1…3 years data protection with lithium battery
PCD3.M5540 like PCD3.M5440 but with Ethernet TCP/IP
PCD3.M6240 PLC with 1 MByte of user memory, backup with 1 MByte on board Flash memory,
up to 1023 digital I/O (with PCD3.Cxxx), 2 interrupts, web-server,
USB port for PG5, RS 232, RS 485 for Profi-S-Net/MPI/S-Bus, CAN interface
Run/Stop switch, 2 slots for PCD7.Rxxx, 1…3 years data protection with lithium battery
PCD3.M6340 like PCD3.M6240 but with Ethernet TCP/IP
PCD3.M6440 PLC with 1 MByte of user memory, backup with 1 MByte on board Flash memory,
up to 1023 digital I/O (with PCD3.Cxxx), 2 interrupts, web-server,
USB port for PG5, RS 232, RS 485 for Profi-S-Net/MPI/S-Bus, Profibus DP Master
Run/Stop switch, 2 slots for PCD7.Rxxx, 1…3 years data protection with lithium battery
PCD3.M6540 like PCD3.M6440 but with Ethernet TCP/IP
Flash memory modules and cards
PCD3.R500 1 MByte flash module on any I/O slot of all PCD3.M3xx0
PCD7.R500 1 MByte flash card for program and data backup on slot M1 or M2 of PCD3.M5xx0 and PCD3.M6xx0
PCD3.R550M04 4 MByte flash module with file system on any I/O slot of all PCD3.Mxxx0
PCD7.R550M04 4 MByte flash card with file system on slot M1 or M2 of PCD3.M5xx0 and PCD3.M6xx0
PCD3.R551M04 4 MByte flash module with 3 MByte file system and 1 MByte program backup on any I/O slot of all PCD3.Mxxx0
PCD7.R551M04 4 MByte flash card with 3 MB file system and 1 MB program backup on slot M1 or M2 of PCD3.M5xx0 and PCD3.M6xx0
PCD3.R560 *) 2 MByte BACnet flash module on any I/O slot of all PCD3.Mxxx0
PCD7.R560 *) 2 MByte BACnet flash card on Slot M1 or M2 of PCD3.M5xx0/M6xx0
PCD3.R561 *) 2 MByte BACnet flash module with 1 MB file system and 1 MB program backup on any I/O slot of all PCD3.Mxxx0
PCD7.R561 *) 2 MByte BACnet flash card with 1 MB file system and 1 MB program backup on Slot M1 or M2 of PCD3.M5xx0/M6xx0
PCD3.R600 PCD3 base module for SD flash memory cards with file system on any I/O slot of all PCD3.Mxxx0
PCD7.R-SD256 256 MByte Saia® SD flash memory card with file system
PCD7.R-SD512 512 MByte Saia® SD flash memory cards with file system
Data protection
PCD3.R010 Battery kit for PCD3.M3xx0 on I/O slot 3
4 507 4817 0 Lithium battery for PCD CPUs and PCD7.D73 to .D78 terminals (RENATA button type CR 2032)
4 639 4898 0 Battery holder for PCD3.M5xxx and PCD3.M6xxx
I/O Module holder, connection plug and connection cables
PCD3.C100 Module holder for 4 I/O modules
PCD3.C110 Module holder for 2 I/O modules
PCD3.C200 Module holder for 4 I/O modules with screw terminal block for external 24 VDC power supply
4 104 4952 0 Screw terminal block 2-pole for external 24 VDC power supply of PCD3.C200
4 104 5005 0 Bolting device to screw terminal block 2-pole for external 24 VDC power supply of PCD3.C200
PCD3.K010 Connection plug PCD3 ↔ PCD3
PCD3.K106 Connection cable 0.7 m PCD3 ↔ PCD3
PCD3.K116 Connection cable 1.2 m PCD3 ↔ PCD3

*) The BACnet option is only available for PCD3 controller with Ethernet

Saia® PCD3.Mxxx0 - high performance, compact, modula www.saia-pcd.com


| 19
r
Ordering information

Communications modules on I/O slot 0 – terminal blocks (type A or B) must be ordered separately
PCD3.F110 with RS 422 / RS 485 interface (electrically connected), terminal block type A or B
PCD3.F121 with RS 232 interface (suitable for modem), terminal block type A or B
PCD3.F130 with 20 mA current loop interface, terminal block type A or B
PCD3.F150 with RS 485 interface (electrically isolated), terminal block type A or B
PCD3.F180 Belimo MP-Bus for up to 8 actuators, terminal block type A or B
Communications modules on I/O slots 0…3
PCD3.F210 with RS 422 / RS 485 interface with socket for PCD7.F1xx module, terminal block type K included
PCD3.F221 with RS 232 interface with socket for PCD7.F1xx module, terminal block type K included
PCD3.F281 with 1 x Belimo MP-Bus and 1 socket for PCD7.F1xx module
Accessories
Type A Type B Type C Type E Type F Type G Type H Type J Type K

Plug-in system cables for manual control and light & shade modules
PCD3.K800 1.0 mm², 2.5 m long, PCD side: 8-pole, plug-in spring terminal block type J; process side: strand ends free, numbered
PCD3.K810 1.0 mm², 2.5 m long, PCD side: 12-pole, plug-in spring terminal block type F; process side: strand ends free, numbered
PCD3.K860 1.5 mm², 2.5 m long, PCD side: 4-pole, plug-in spring terminal block type G; process side: strand ends free, numbered
PCD3.K861 0.75 mm², 2.5 m long, PCD side: 6-pole, plug-in spring terminal block type H; process side: strand ends free, numbered
Spring terminal block 8-pole for all PCD3.Mxxxx
4'405'4995'0 Spring terminal block 8-pole for power supply, RS 485, Interrupt inputs and Watch dog of all PCD3.Mxxx0
Terminal blocks, Inscription
4'405'4954'0 Plug-in I/O spring terminal block (type A), 10-pole for wiring up to 2.5 mm2, numbered from 0…9
4'405'4955'0 Plug-in I/O screw terminal block (type B), 10-pole for wiring up to 2.5 mm2, numbered from 0…9
4'405'4956'0 Plug-in I/O spring terminal block (type C), 24-pole for wiring up to 1.0 mm2, numbered from 0…23
4'405'4998'0 Plug-in I/O spring terminal block (type E), 14-pole for wiring up to 1.5 mm2, numbered from 0…13
4'405'4936'0 Plug-in I/O spring terminal block (type F), 12-pole for PCD3.A810 for wiring up to 1.5 mm2, numbered from 0…12
4'405'5027'0 Plug-in I/O spring terminal block (type G), 4-pole for PCD3.A860 for wiring up to 2.5 mm2, numbered from 0…4
4'405'5028'0 Plug-in I/O spring terminal block (type H), 6-pole for PCD3.A860 for wiring up to 1.0 mm2, numbered from 1…6
4'405'4934'0 Plug-in I/O spring terminal block (type J), 8-pole for PCD3.W800 for wiring up to 1.5 mm2, numbered from 1…8
4'405'5048'0 Plug-in I/O spring terminal block (type K), 10-pole for wiring up to 1.0 mm2, numbered from 0…9
Addressing and marking I/O modules and module holders
4'329'4819'0 Set of 10 pcs.: Inscription labels for PCD3 I/O
4'310'8686'0 Set of 10 pcs.: Preprinted adhesive strips for PCD3 I/O
4'310'8723'0 Set of 10 pcs.: cover including neutral inscription labels (2 × DIN A4)
Dummy module and covers
PCD3.E009 Dummy module, as contact protection for unequipped PCD3 sockets
4'104'7493'0 Cover for flash card and battery slots of PCD3.M5xxx and ..M6xxx
4'104'7502'0 Slot cover for PCD3 I/O‘s (neutral),
4'104'7515'0 Slot cover for PCD3 I/O‘s (with logo – Saia® PCD3)

Contact
Switzerland and international This brochure was received from:
Saia-Burgess Controls Ltd.  
Bahnhofstrasse 18  
CH-3280 Murten / ������������
Switzerland  
T +41 26 / 672 71 11  
F +41 26 / 672 74 99  
pcd@saia-burgess.com  
www.saia-pcd.com

Product support,  
Technical reference website:  www.sbc-support.ch

P+P26/397 E10  09. 2008
Subject to change without notice.

Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

8.2. DC/DC Power supplies PHOENIX

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A


Extract from the online
catalog
   
QUINT-PS-100-240AC/24DC/ 5

   
DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1-
phase.

Product notes
WEEE/RoHS-compliant since:
Commercial data 03/21/2006
EAN
4 017918 890520

Pack 1 Pcs.
Customs tariff 85044082
Product key CMPP13 http://
www.download.phoenixcontact.com
Catalog page information Page 480 (IF-2007) Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.

Product description

QUINT POWER is the powerful 60 - 960 W DC power supply unit for universal use. With its wide-range input, single and
three-phase versions, and international approval package, this solution is unrivalled. QUINT POWER provides reliable
power supply: generously dimensioned capacitors ensure mains buffering of over 20 ms at full load. Full output power
is provided by all three-phase devices, even in the event of a permanent phase failure. The Power Boost power reserve
easily starts loads with high inrush currents and ensures that fuses are reliably tripped. Preventive function monitoring
diagnoses impermissible operating states and minimizes downtimes in your system. Remote monitoring is provided by
an active transistor switching output and a floating relay contact. All devices are idling-proof and short-circuit-proof, and
are available with a regulated and adjustable output voltage of 12, 24, and 48 V DC with output currents of 2.5, 5, 10, 20,

PHOENIX CONTACT Inc., USA


http://www.phoenixcon.com
QUINT-PS-100-240AC/24DC/ 5

30, and 40 A. Power supply units for use in Ex zone 2, uninterruptible solutions, AS-i power supply units, and a QUINT
diode complete this comprehensive product range.

Technical data

Input data
Nominal input voltage 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
DC input voltage range 90 V DC ... 350 V DC
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Current consumption Approx. 1.6 A (120 V AC)
Approx. 0.84 A (230 V AC)
Nominal power consumption 120 W
Inrush surge current < 20 A (typical)
Power failure bypass > 30 ms (120 V AC)
> 130 ms (230 V AC)
Input fuse 5 A (slow-blow, internal)
Permissible backup fuse B6
B10
B16
Type of protection Transient surge protection
Protective circuit/component Varistor

Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 28.5 V DC
Output current 5 A (up to 60°C)
7.5 A (with POWER BOOST)
Derating 60 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Max. capacitive load Unlimited
Current limitation Approx. IBOOST = 7.5 A (for short-circuit)
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 10 mVPP (with nominal values)

PHOENIX CONTACT Inc., USA


http://www.phoenixcon.com
QUINT-PS-100-240AC/24DC/ 5

Peak switching voltages nominal load < 30 mVPP (20 MHz)


Maximum power dissipation NO-Load <2W
Power loss nominal load max. < 14 W

General data
Width 55 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
58 mm
Net weight 0.83 kg
Operating voltage display Green LED
Efficiency > 89 %
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Degree of protection IP20
Protection class I, with PE connection
MTBF (IEC 61709, SN 29500) > 500000 h
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility Conformance with EMC directive 89/336/EC
Noise emission EN 50081-2
Noise immunity EN 61000-6-2:2005
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Shipbuilding approval Germanischer Lloyd (EMC 2), ABS
Standard – Electronic equipment for use in EN 50178/VDE 0160 (PELV)
electrical power installations and their assembly
into electrical power installations
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)

PHOENIX CONTACT Inc., USA


http://www.phoenixcon.com
QUINT-PS-100-240AC/24DC/ 5

Standard - Safe isolation DIN VDE 0100-410


DIN VDE 0106-1010
Standard – Protection against electric shock DIN 57100-410
Standard – Protection against shock currents, DIN VDE 0106-101
basic requirements for protective separation in
electrical equipment
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Equipment safety GS (tested safety)
Certificate CB Scheme
UL approvals UL/C-UL Recognized UL 60950
UL/C-UL listed UL 508
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
Surge voltage category III

Connection data, input


Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Stripping length 7 mm
Screw thread M3

Connection data, output


Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Stripping length 7 mm

Signaling
Output name DC OK active
Output description UOUT > 0.9 x UN: High signal

PHOENIX CONTACT Inc., USA


http://www.phoenixcon.com
QUINT-PS-100-240AC/24DC/ 5

Maximum switching voltage ≤ 24 V


Output voltage + 24 V DC (signal)
Maximum inrush current ≤ 40 mA
Continuous load current ≤ 40 mA
Status display "DC OK" LED green
Note on status display UOUT < 0.9 x UN: LED flashing
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Screw thread M3
Output name DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Maximum inrush current ≤1A
Continuous load current ≤1A
Status display "DC OK" LED green

Certificates / Approvals

Certification CB, CUL, CUL Listed, DNV, GL, GOST, UL, UL Listed

Certification Ex: CUL-EX LIS, UL-EX LIS

PHOENIX CONTACT Inc., USA


http://www.phoenixcon.com
QUINT-PS-100-240AC/24DC/ 5

Drawings

Block diagram

Diagram

PHOENIX CONTACT Inc., USA


http://www.phoenixcon.com

Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

8.3. Converter PHOENIX

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A


MINI MCR-SL-RPS-I-I(-SP)

Repeater Power Supply

Data Sheet 11/2004

Product Description Features


The MINI MCR-SL-RPS-I-I(-SP) repeater power
supplies have the task of supplying 2 or 3-conductor
transmitters located in the field and electrically
isolating the input signal from the output signal.
On the input and output side, the analog standard
signals 0...20 mA or 4...20 mA are available,
electrically isolated.
The voltage supply (19.2...30 V DC) can either be
provided via connecting terminal blocks "7"/"8" of the
modules, or together, via the DIN rail bus connector
(see Figure 5 on page 6). Please also observe "Power
Supply" on page 7.

Figure 1 Features

1 Input: Standard signals


2 Output: Transmitter supply voltage
3 Transparent cover
4 Groove for ZBF 6 Zack marker strip
5 Output: Standard signals
6 Supply voltage
7 Connection option for DIN rail bus connector
8 Universal snap-on foot for EN mounting rails
MINI MCR-SL-RPS-I-I(-SP)

Technical Data
General Data
Supply voltage UB 19.2...30 V DC
Current consumption at 24 V DC < 40 mA
(incl. 20 mA load current)
Power consumption < 600 mW
Transmission error < 0.2% of end value
Temperature coefficient
max. < 0.01%/K
typ. < 0.002%/K
Cut-off frequency (3 dB) 100 Hz
Step response (10...90 %) 3.5 ms
Test voltage (input / output / supply) 1.5 kV, 50 Hz, 1 min.
Ambient temperature range
Operation -20°C…+60°C (-4°F...140°F)
Storage -40°C…+85°C (-40°F...185°F)
Dimensions (W x H x D) 6.2 mm x 93.1 mm x 102.5 mm
(0.244 in. x 3.665 in. x 4.035 in.)
Conductor cross section 0.2...2.5 mm2 (AWG 24...12)
Stripping length
Screw connection 12 mm
Spring-cage connection 8 mm
Housing design Polybutylenterephthalate PBT, green
Tests / Approvals
cu
U PROCESS CONTROL EQUIPMENT FOR
HAZARDOUS LOCATIONS
LISTED 31ZN
Class I Div 2 Groups A, B, C, D T5
A) This equipment is suitable for use in Class I,
Division 2, Groups A, B, C and D or non-hazardous
locations only.
B) Warning - explosion hazard - substitution of
components may impair suitability for Class 1,
Division 2.
C) Warning - explosion hazard - do not disconnect
equipment unless power has been switched off or the
area is known to be non-hazardous.
MINI MCR-SL-RPS-I-I(-SP)

Input (see Figure 1, detail 1) IIN


Input signal range 0...20 mA, 4...20 mA
Input resistance approx. 50 Ω
Transmitter supply voltage UB – (max. 4.5 V)
Transmitter supply current < 28 mA
Overcurrent detection approx. 28 mA

Output (see Figure 1, details 2 and 5) IOUT


Output signal range 0...20 mA, 4...20 mA
Load (at I = 20 mA) < 500 Ω
Ripple < 20 mVss
Max. output signal (non-load voltage approx.) 28 mA / 12.5 V

Conformance With EMC Guideline 89/336/EEC And Low Voltage Directive 73/23/EEC
Immunity to Interference According to EN 61000-6-21
Discharge of static electricity (ESD) EN 61000-4-2 Criterion B2
Electromagnetic HF field EN 61000-4-3 Criterion A3
Fast transients (Burst) EN 61000-4-4 Criterion B2
Surge voltage capacities (Surge) EN 61000-4-5 Criterion B2
Conducted disturbance EN 61000-4-6 Criterion A3
Noise Emission According to EN 50081-2
Noise emission of housing EN 550114 Class A5
1
EN 61000 corresponds to IEC 1000
2
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
3 Criterion A: Normal operating behavior within the defined limits.
4
EN 55011 corresponds to CISPR11
5
Class A: Area of application industry.
MINI MCR-SL-RPS-I-I(-SP)

Ordering Data
Description Order Designation Order No.
Repeater power supply MINI MCR-SL-RPS-I-I 28 64 42 2
Screw terminal block
Repeater power supply MINI MCR-SL-RPS-I-I-SP 28 64 75 2
Spring-cage terminal block

Accessories
Description Order Designation Order No.
DIN rail bus connectors ME 6,2 TBUS-2 1,5/5-ST-3,81 GN 28 69 72 8
Power terminal block with screw connection MINI MCR-SL-PTB 28 64 13 4
Power terminal block with spring-cage connection MINI MCR-SL-PTB-SP 28 64 14 7
System power supply MINI-SYS-PS-100-240AC/24DC/1,5 28 66 98 3
MINI MCR-SL-RPS-I-I(-SP)

Screw Connection Spring-Cage Connection

Figure 2 MINI MCR-SL-RPS-I-I Figure 3 MINI MCR-SL-RPS-I-I-SP

Installation
The device may only be installed and put
into operation by qualified personnel.
The corresponding national regulations
(e.g. VDE, DIN) must be observed.

The assignment of the connecting terminal blocks is


shown in Figure 4.

Block Diagram

Figure 4 Block Diagram

The MINI Analog module can be snapped onto all


35 mm DIN rails corresponding to EN 60715.

Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

8.4. Interface Relay PHOENIX

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A


Extract from the online
catalog
   
PLC-RSC- 24UC/21

The illustration shows the version PLC-RSC-24DC/21

   
PLC relay, consisting of base terminal block PLC-BSC.../21 with screw
connection and pluggable miniature relay with power contact, for
assembly on DIN rail NS 35/7.5, 1 PDT, input voltage 24 V AC/DC

Product notes
WEEE/RoHS-compliant since:
Commercial data 23/01/2006
EAN
4 017918 130725

Pack 10
Customs tariff 85364190
Country of Origin DE Please note that the data given
here has been taken from the
Catalog page information Page 82 (IF-2011) online catalog. For comprehensive
information and data, please refer
to the user documentation at http://
www.download.phoenixcontact.com.
The General Terms and Conditions
of Use apply to Internet downloads.

Technical data

Coil side
Nominal input voltage UN 24 V AC/DC
Nominal input current at UIN 11 mA (at UN = 24 V AC)
8.5 mA (at UN = 24 V DC)
Typical response time 6 ms

PHOENIX CONTACT Ltd


http://www.phoenixcontact.co.uk
PLC-RSC- 24UC/21

Typical release time 15 ms


Operating voltage display Yellow LED
Protective circuit Bridge rectifier Bridge rectifier

Contact side
Contact type Single contact, 1-PDT
Contact material AgSnO
Maximum switching voltage 250 V AC/DC (The separating plate PLC-ATP should be installed
for voltages larger than 250 V (L1, L2, L3) between identical
terminal blocks in adjacent modules. Potential bridging is then
carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage 5 V (at 100 mA)
Maximum inrush current (on request)
Min. switching current 10 mA (at 12 V)
Limiting continuous current 6A
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W (for 48 V DC)
18 W (for 60 V DC)
23 W (for 110 V DC)
40 W (for 220 V DC)
1500 VA (for 250 V AC)

General data
Width 6.2 mm
Height 80 mm
Depth 94 mm
Test voltage relay winding/relay contact 4 kV AC (50 Hz, 1 min.)
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Operating mode 100% operating factor
Mechanical service life 7
2 x 10 cycles
Inflammability class according to UL 94 V0
Name Standards/regulations
Standards/regulations IEC 60664
EN 50178
IEC 62103
Pollution degree 3

PHOENIX CONTACT Ltd


http://www.phoenixcontact.co.uk
PLC-RSC- 24UC/21

Surge voltage category III


Mounting position Any
Assembly instructions In rows with zero spacing

Connection data
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 26
Conductor cross section AWG/kcmil max 14
Stripping length 8 mm
Screw thread M3

Certificates

Certification CUL, CUL Listed, GL, GOST, UL, UL Listed

Drawings

Diagram

Interrupting rating

PHOENIX CONTACT Ltd


http://www.phoenixcontact.co.uk
PLC-RSC- 24UC/21

Circuit diagram

PHOENIX CONTACT Ltd


http://www.phoenixcontact.co.uk

Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

8.5. Relay COMAT

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A


Power relay Control relay Signal relay Remanence relay
11 10 Au
C3

WH: 35 x 35 AC230VA

58

C3-A30 C3-T31 C3-T32 C3-R20


3-pole miniature industrial relays Universal Relay like ..A30, but Relay like ..T31, but Remanence relay 10A
according to IEC 67-1 power relay 10A with doubel contacts 6A 10 gold plated contacts with AC or DC coil
• lockable manual operation With 3 power changeover- The control relay with highest The twin contact relay with A1(2)=ON; A3(6)=OFF.
• mechanical flag indicator contacts this is the robust switching reliablility for control highest switching reliability for Minim. triggering time 50ms,
Test voltage: 2500V 2500V relay for AC and DC circuits and signal circuits ranging signal circuits ranging from permanent triggering admis-
ranging from 10mA10V. from 5mA 5V. 1mA 5V. sible.
Tamb. operation/
Recommend. upto 0,2A 30V.
storage: -40..+60/ - 40..+ 85°C
Without option X.
MAX 10A 250V A 6A 250V A 6A 250V A 10A 250V A
MIN 10mA 10V 5mA 5V 1mA 5V 10mA 10V

Connection No. on socket ➞ 9 8 7 5 3 4 9 8 7 5 3 4 9 8 7 5 3 4 9 8 3 4


Designation according to DIN/EN 50011 ➞ 34 32 24 22 14 12 34 32 24 22 14 12 34 32 24 22 14 12 24 22 14 12

Connection with sockets z z z z


EC-11, C11A, C12B
OFF ON
= contact opening < 3mm + + + + +
A2 31 21 11 A1 A2 31 21 11 A1 A2 31 21 11 A1 A2 21 A3 11 A1
10 11 6 1 2 10 11 6 1 2 10 11 6 1 2 10 11 6 1 2
Data at Tamb. =20°C (standard coil )
Contact material AgNi AgNi+0,2 z Au AgNi+10 z Au AgNi
Switching load AC1/DC1 2500VA/...250W 1200VA/...150W 1200VA/...150W 2500VA/...250W
Peak inrush power 30A(20ms) 15A(20ms) 15A(20ms) 30A(20ms)
Switching cycles mech./electr. (AC1) 20x106/ ≥ 5 x105 20x106/ ≥ 2x105 20x106/ ≥ 2x105 20x106/ ≥ 3 x105
Operation voltage AC50Hz/DC 0,8...1,2UN 0,8...1,2UN 0,8...1,2UN 0,8...1,2UN
Power consumption AC / DC 2,2VA/1,3W 2,2VA/1,3W 2,2VA/1,3W ON/OFF 1,5/0,5 VA//W
Triggering delay / release time 16 /8 ms 16/8ms 16/8ms 16/10ms ( >50ms)

AC 24, 48, 115, 230 24, 48, 115, 230 24, 48, 115, 230 24, 48, 115, 230
Standard
50/60Hz C3-A30 X / AC ..... V C3-T31 X / AC ..... V C3-T32 X / AC ..... V C3-R20 / AC ..... V

DC 12, 24, 48, 110, 125, 220 12, 24, 48, 110, 125, 220 12, 24, 48, 110, 125, 220 12, 24, 48, 110, 125
Standard
≤ 10% C3-A30 / DC ..... V C3-T31 / DC ..... V C3-T32 / DC ..... V C3-R20 / DC ..... V

DC 12, 24, 48, 110, 125, 220 12, 24, 48, 110, 125, 220 12, 24, 48, 110, 125, 220
D, DX
≤ 10% C3-A30D X / DC ..... V C3-T31D X / DC ..... V C3-T32D X / DC ..... V

= Type “X” (option) Option X = with

System socket C11A *)


9 8 7 5 3 4
For suitable coil wirings
Economy socket EC-11
see “R-modules” → 34 32 24 22 14 12
02

9 8 7 5 3 4
10A 250V A

34 32 24 22 14 12
30
SWISS

6 EC-11 10A 10A


7 5 400V 300V
10A
8 4 400V Listed
75

9 3
04

10 2
Clip S3-C
Ordering example C 11 A 11 1
10A
400V A

CONNECTOR C-A2 C-A2 Clip S3-C


• Relay C3-A30 X / AC 230 V *) with plugged-in
32

• Socket EC-11 or C11A SD -1W neutral conductor


A2 31 21 11 A1
A2 31 21 11 A1
connector C-A2
• Retaining clip S3-C (option) 10 11 6 1 2 (standard delivery). 10 11 6 1 2

38 4 20 38 4 22

COMAT AG CH-3076 WORB CR 4.01/4.00-1 E This edition replaces all previous issues. Availability, errors and specification subject to change without notice.
3

Revision: Language:
AH S - K R S - 0 0 - O E A- D A- 0 0 - 0 0 1
A EN

8.6. Mini Circuit Breaker ABB

Kariba: AHS-KRS-00-OEA-DA-00-001_Technical DataSheets _REV A


Technical catalogue
SmiSSline electrical protective devices
in a system
SmiSSline – The original
Shaping the future

SmiSSline protection devices are simply snapped into a


plug-in socket system. The arduous task of power supply and
connection is done. in addition to savings in time and mon-
ey, another advantage of the system is the quick and easy
exchangeability of the devices. if the corresponding spare
capacity is planned, subsequent expansion consists merely of
plugging in and connecting additional devices.
The new generation of electrical protective devices
in a system:

− Flexible, fast and modular


− Free choice for concept and layout
− Time-saving by planning and assembly

0/2 Overview | Technical catalogue SmiSSline


Avoid uneven loads
The phase connection can be identified without removing the
devices.

Flexibility up to the last minute


SmiSSline makes it possible to press ahead with planning,
even before all the details of a system are known. loads can
be easily reassigned. even if the usage of an entire installation
is completely changed, the effort in-volved remains small.

Freedom to design and arrange


SmiSSline gives you freedom of choice: mixed-pole arrange-
ment of all devices next to each other.

Technical catalogue SmiSSline | Overview 0/3


Six protection devices in one system

1 2 3 4 5 6 7 8 9 10

1 Surge arrester

2 High performance manual motor starter

3 miniature circuit breaker 3 pole

4 miniature circuit breaker 2 pole

5 4-pole residual current operated circuit breaker with overcurrent protection

6 miniature circuit breaker 1 pole

7 2-pole residual current operated circuit breaker with overcurrent protection

8 2-pole residual current operated circuit breaker

9 4-pole residual current operated circuit breaker

10 Switch disconnector

0/4 Overview | Technical catalogue SmiSSline


Table of contents
SMISSlINe
miniature circuit breaker S400
Miniature circuit breaker S400 M–B 1/2
Miniature circuit breaker S400 M–C 1/3
Miniature circuit breaker S400 M–D 1/4
Miniature circuit breaker S400 M–K 1/5
Miniature circuit breaker S400 M–B 1/6
with protected neutral
Miniature circuit breaker S400 M–C 1/7
with protected neutral
Miniature circuit breaker S400 M–D 1/8
with protected neutral
Miniature circuit breaker S400 M–K 1/9
with protected neutral
Miniature circuit breaker S400 UC 1/10
Miniature circuit breaker S400 UU, DC application 1/11

Residual current operated circuit breaker


with over current protection (RCBO)
2-pole residual current opterated circuit breaker 1/12
with overcurrent protection FS401
4-pole residual current operated circuit breaker 1/13
with over current protection FS403

Residual current operated circuit breaker F404, F402


2-pole and 4-pole residual current 1/14
operated circuit breaker F402, F404

Overcurrent arrester OVR404, switch disconnnector


iS404
Surge arrester, Switch disconnector 1/15

High performance motor starter mS325


Adapter for motor starter MS325 1/15

Accessory
Auxiliary switch and signal contacts 1/16
Dummy, housing, Neutral disconnector, shunt trip 1/17
F4C-ARI motor operating devices 1/18

Busbar system
Starter pack 1/19
Sockets, Additional socket 1/20
Additional socket, terminals 1/21–22
Incoming terminal block and components 1/23
Socket accessories 1/24
Combi module 32 A 1/25
32 A and 63 A universal adapters 1/26–27
Miscellaneous accessories 1/27