You are on page 1of 7

Service Information Letter SIL # 014

Agastat To Siemens Timer


Conversion

Equipment: Agastat timer SSFR90A, Astec P/N 039998 Date Issued: 7-31-2003
Revised: no
Additional none Revision #: 0
Reference:
By: R. L. Worth Jr. , Service Support Coordinator Astec Service Department

PURPOSE:

The purpose of this letter is provide instructions for replacing an Agastat SSFR90A, universal timing
relay, with a Siemens 3RP1505-1BQ30.

This conversion should only be performed by qualified individuals.

PARTS REQUIRED (for each replacement):

Quantity Astec part number Description


1 054734 Siemens Sirius relay, Siemens item # 3RP1505-1BQ30.
1 054735 3RP1901-QB, Label

GETTING STARTED:

Before un-wiring and removing the Agastat timer, make sure all wires are labeled.

Remove the Agastat timer from the DIN rail. Mount the Siemens in it’s place.

Use your current electrical schematics to determine the current configuration you have. The terminal
numbers on the new Siemens relay are identified differently than those on the Agastat. Refer to the
following examples for wiring instructions. After the conversion is made it will be helpful to note the
changes on your electrical schematics.

The new Siemens relay will perform the same as the Agastat, once it is configured properly. Please
refer to the following examples for configuration instructions.

EXAMPLES:
RELAY FUNCTION EXAMPLE # PAGE #
ON DELAY #1 2
OFF DELAY #2 3
LATCHED #3 4
PULSE SHAPING #4 5-6

For identification of the Siemens relay components, please refer to the figure on page 7.
1
EXAMPLE # 1, On Delay:

AGASTAT (OLD STYLE TIMER)


1 2

TRIGGER 9
10
TR 7 ON DELAY TIMER
SSFR90A
0 – 300 SEC.
TT ON DELAY
1 2 TO LOAD

SIEMENS (NEW STYLE TIMER)


1 2

TRIGGER
A1
TR A2 ON DELAY TIMER
3RP1505-1BQ30
3RP1901-QB

TT
15 18 TO LOAD

For ON Delay:

With power to the relay off.

Set the MODE SELECTOR SWITCH to A. This configures the relay as an ON Delay.

Then select the desired TIME RANGE SELECTOR to the desired time range.

Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL.

Turn power back on.

2
EXAMPLE # 2, OFF Delay:

1 2
AGASTAT (OLD STYLE TIMER)

TRIGGER

9
10 7 OFF DELAY
TR
SSFR90A TIMER
0 – 300 SEC.
TT OFF DELAY
1 2
TO LOAD

1 2
SIEMENS (NEW STYLE TIMER)

TRIGGER

B1
A1 A2 OFF DELAY
TR TIMER
3RP1505-1BQ30
3RP1901-QB
TT 0 – 300 SEC.
OFF DELAY (B)

15 18
TO LOAD

For OFF Delay:

With power to the relay off.

Set the MODE SELECTOR SWITCH to B. This configures the relay as an OFF Delay.

Then select the desired TIME RANGE SELECTOR to the desired time range.

Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL.

Turn power back on for changes to take place.

3
EXAMPLE # 3, IMPULSE OFF

1 2
AGASTAT (OLD STYLE TIMER)

TRIGGER
120 VAC

9
10 7 IMPULSE OFF
TR
SSFR90A TIMER
.3 - 10 SEC.
TT IMPULSE OFF
1 2
TO LOAD

1 2
SIEMENS (NEW STYLE TIMER)

TRIGGER
120 VAC

B1
A1 A2 IMPULSE OFF
TR TIMER
3RP1505-1BQ30
3RP1901-QB
TT .3 – 10 SEC.
IMPULSE OFF (F)

15 16
TO LOAD

For IMPULSE OFF TIMER:

With power to the relay off.

Set the MODE SELECTOR SWITCH to F. This configures the relay as an IMPULSE OFF TIMER.

Then select the desired TIME RANGE SELECTOR to the desired time range.

Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL.

Turn power back on for changes to take place.

4
EXAMPLE # 4, LATCHED INTERVAL / PULSE SHAPING:

1 2
AGASTAT (OLD STYLE TIMER)

TRIGGER 9
10 7
TR
SSFR90A
INTERVAL
45 SEC.
1 2
A
SLV

5 6

1 2
SIEMENS (NEW STYLE TIMER)

TRIGGER

B1
A1 A2
TR
3RP1505-1BQ30
3RP1901-QB
TT 45 SEC.
PULSE SHAPING (G)

15 18
A
SLV

25 26

5
For PULSE SHAPING (replaces latched interval):

With power to the relay off.

Set the MODE SELECTOR SWITCH to G. This configures the relay for PULSE SHAPING.

Then select the desired TIME RANGE SELECTOR to the desired time range.

Then select the proper PERCENT (%) of time range, on the PERCENT OF TIME RANGE DIAL.

Turn power back on for changes to take place.

If you have any questions please contact the Astec service department.

Please refer to the following figure for a general description of the Siemens relay components.

6
Siemens relay component identification:

AC + (Hot) TRIGGER COMMON TERMINAL, # 15 & 17,


(for NC # 16 and NO # 18)

A1 B1 15/17C
Lower
Level

Power Terminals
for use with low A3+ B3+ 21/25/27C
voltage circuits
COMMON TERMINAL, # 21,
only … make no
25, & 17, (for NC # 22 & 26,
connection SIEMENS and NO # 24 & 28)
SIRIUS 3R

PERCENT OF
TIME RANGE
DIAL

TIME RANGE
SELECTOR Top of
##
(Rotary Dial and Relay
Window)

MODE SELECTOR
SWITCH ##

(Rotary Dial and


Window)

22/26NC 24/28NO

Lower
Level
16NC 18NO A2-

AC –
(Negative)

 Astec, Inc. 2003