Professional Documents
Culture Documents
1077-2618/981$10.0001~~~8
IEEE IEEE Industry Applications Magazine September/October 1998
I
TeK 5OOkS/s 2 Acqs
ties are increasingly enforcing IEEE 519, the
recommended harmonic standard, particularly for
large and industrial customers I t zs znzportant to note
that IEEE 5 19 hamonzcstandards ave only applzcableat
thepoznt of common couplzng (PCC) of the utzlzty-plant
znterface New specificationsoften treat it as an equzp- I /
500A mI
I
ment standard, a clear misapplication.
Since harmonic compensation by itself does not
provide any direct benefit or increased productiv-
ity to the user, except through reduced load out-
ages and reduced susceptibility to harmonic
I related problems, there is seldom any motivation
I
I for users to voluntarily meet IEEE 5 19 harmonic
I
standards In fact, harmonic standards often provide
I Fig. 2. Supply line current waveform i I {200 Aldiu}
I a deterrent to the widespread application of ASDs
I with ASD recrifier fron-end, t=2msldiu.
I
and therefore does not provide the anticipated en-
I ergy savings As a result, some ASD manufacturers mF. The IGBT PWM inverter has a switching fre-
I have started to integrate active filter solutions with
I quency of 2 kHz and drives a high efficiency 503
I ASD front-ends to meet IEEE 5 19 harmonic stan-
I
hp induction motor. Fig. 2 shows an experimental
dards at the utility-plant interface To justify the
supply line current i, waveform for a 460 V supply
additional cost of harmonic compensation, ASD
system with transformer leakage inductance of
manufacturers provide supplementary value-added
L , = 40yH (3.2%). The supply current is quasi-
features such as higher displacement power factor
square and has a total harmonic distortion (THD)
(DPF), line voltage regulation against supply volt-
i of 26.8% at input power of 270 kW. The short cir-
I age sags and swells,compensation for supply voltage
I flicker and unbalance, and mitigation of any possi- cuit current at 460 V transformer secondary is ap-
I
ble sourceisink resonance conditions [l). proximately 17.6 kA. The PCC is defined on the
I
I This article presents an active filter solution for transformer secondary side (Fig. 1).The short cir-
I
a utility interface of an ASD for air-conditioner cuit ratio (SCR) at PCC is 31.0 and IEEE 519 al-
I lowable supply current i, T H D is 8.0%.
I chiller application to meet IEEE 519 harmonic
I standards In the next section we discuss the ASD The ASD manufacturer specifications include,
I
I rectifier front-end characteristics and specifica- to meet IEEE 5 19, harmonic current T H D limits
I tions set by the ASD manufacturer The following at the utility-plant PCC interface with minimum
I supply side inductance of L,= 22 p H , which is
I section details the selection of active filter solution
I based on manufacturers specifications, cost goals 1.76% with a SCR of 58.6 at PCC. Hence, the
I IEEE 5 19 supply current T H D limit is 12%. How-
I and cost structure. Following that, the implemen-
I tation of the parallel active filter system is given ever, there is no specification for maximum supply
I side inductance L , and the system is required to
I The next two sections discuss the synchronous refer-
I ence frame controller and current regulator devel- meet the IEEE 5 19 harmonic current T H D limit for
I all such cases. Note that L , 2 6 5 p H (5.2%) results
I oped along with their hardware based implemen-
I tations for the parallel active filter system The last in a SCRS 20 and in this case the maximum allow-
I
two sections describe, respectively, design consider- able supply current T H D is 5%. Hence, the har-
I
I ations for inverter switching ripple filter and experi- monic filtering solution has to be designed to meet
I mental results for utility interface of an integrated the worst case supply current T H D limit of 5%.
I
I parallel active filter system with a450 kW ASD load The resonant frequency of dc side inductor L,
I and dc link capacitor C, is 47.5 Hz. The PWM in-
I
ASD Rectifier Front-End Topolo y And verter supplying the 503 hp induction motor is
I
I
I
Specifications For Harmonic Fi tering f VoltsiHertz controlled and enters pulse dropping
mode around 52 Hz, which increases the motor
I
I ASD Rectifier Front-end Topology line current THD. Another inadvertent affect of
Fig 1 shows the rectifier front-end topology used the PWM inverter pulse dropping mode is that it
in the 450 kW air-conditioner chiller ASD. It con- causes interaction with the L , - C, dc link filter,
sists of a diode bridge rectifier with dc side induc- which results in the generation of subharmonics in
tor L , = 2 5 0 p H and dc link capacitor C, = 45 the input supply current i, at around 33 Hz. The
presence of the subharmonics can be seen by
slightly unequal supply current i, peak values of
1
Diode Rectifier ,L, PWM Inverter
500 A and 540 A as shown in Fig. 2. Subharmonics
&i
& in the supply current have an adverse impact on the
harmonic filtering solution as well as on the active
filter rating. They result in increased supply cur-
Fig. 1, ASD front-end rectifier topology. rent distortion. The impact of subharmonic supply
I
I
I
I
I
I
I
currents on the design and implementation of par- current limits are to be met up to the 50th I
allel active filter system is discussed later, in the ex- I
harmonic in the supply current. I
perimental results section. The issue of ASD load w Supply current T H D as low as possible for I
induced subharmonics as well as supply side in- voltage harmonic sensitive applications such I
I
duced subharmonics in the supply current has not as for hospital environments. I
yet been addressed in the framework of IEEE 5 17 w Displacement power factor greater than 0.95 I
I
recommended harmonil: standards. from 12.5% to 105% load rating, to match I
This ASD rectifier front-end represents a com- highest possible displacement power factor I
I
mon topology for high power diode and thyristor offered by lowest cost diode rectifier front- I
rectifiers. The dc side inductor L , results in contin- end with dc side capacitor. I
I
uous and quasi-square wave supply line currents, Losses of active filter system lower than 1% of I
with significantly reduced T H D and peak currents, load rating, i.e., less than 4.5 k W oflosses for I
I
compared to the lowest cost diode rectifier-dc side maximum load of 450 kW. I
capacitor solution [a]. Meet given cost goals, including switching I
I
The supply side ac inductance L , at PCC deter- ripple filter and active filter protection and I
mines the overlap anglc during commutation and switchgear cost. I
the maximum dzidt . For ‘stiff ac supply systems or W Meet given size, maximum weight and floor I
I
ac systems with low supply side inductance L , , space area. I
these rectifier front-ends have very small overlap w Meet given packaging constraints, such as the I
I
angle and are beset wii:h very high diidt related active filter system should be mounted and in- I
problems. Consequently., these rectifier front-ends tegrated inside the ASD enclosure to elimi- I
I
require very high bandwidth and high frequency nate on-site installation cost and connections. I
PWM inverters for harmonic filtering to meet W Active filter systems should operate and I
I
IEEE 5 19 harmonic limits, with their concomitant meet IEEE 519 harmonic standards under I
cost penalties. all supply and load conditions such as, in the I
I
The IEEE 5 19 harmonic standards are applica- presence of maximum allowable 5 % supply I
ble only at the utility-plant PCC interface. The voltage harmonics, f 1 0 % supply voltage I
I
utility-plant interface characteristics depend on swellsisags, up to 10% supply voltage un- I
the PCC transformer leakage inductance (which balance and in presence of supply current I
I
determines the SCR at I’CC) and it also depends on subharmonics. I
the ac and dc side filtering elements used with the Active filter systems, including the switching I
I
rectifier front-end. Hence, active filtering of har- ripple filter, should not harmonically interact I
monic front-ends require a systems approach. A with the supply and ASD rectifier front-end. I
simple classification of the harmonic performances The active filter system should also mitigate I
I
of various utility interfke harmonic front-end sys- any supplyiload resonance problems. I
tems and their impact on active filtering require- w An active filter system should nor affect the I
I
ment and rating is given in El], [2]. The dc side and operationofthe ASD, i.e., it should beable to I
ac side filtering elements of the rectifier front-end isolate itself during active filter faults. It I
I
have the following effect on supply current distor- should also be self protecting during system I
tion. The dc side inductor L , smoothes the dc link and ASD faults. I
I
current and minimizes supply voltage unbalance These specifications provide the ASD manufac- I
effects, thus enabling application of cost effective turer with the following value-added supplemen- I
I
active filtering solutions. Supply or ac side induc- tary features in addition to complying with IEEE I
tance reduces supply current i, T H D and peak 5 17 harmonic standards: I
I
value. It also reduces the diidt of supply current z , Displacement power factor greater than 0.95 I
by increasing the commutation overlap period. over the entire load range of 12.5% to 105% I
I
Supply side inductance also provides value-added load rating. I
features such as immunity to supply side transients w Reduced voltage distortion at utility-plant I
due to capacitor switchmgs and ride through capa- PCC interface; this feature increases practical I
I
bilities during supply voltage sagsiswells[ I ) , [2). viability for voltage harmonic sensitive loads I
such as for hospital environments. I
I
Single ASD enclosure, which eliminates in- I
stallation cost and minimizes size, weight I
Specifications for Harmonic Filtering I
and floor space. I
The specifications for harmonic filtering as set by I
the ASD manufacture1 for air-conditioner chiller I
I
ASD application are as follows: Selection of Active Filter I
Supply current T HD to meet IEEE 5 17 har- Topology for Harmonic Filtering I
I
monic limits at utility-plant PCC interface Several active filter topologies, including hybrid I
in presence of maximum allowable 5% sup- active filters, were considered in order to meet I
I
ply voltage distortion. IEEE 5 19 harmonic IEEE 5 19 harmonic standards at the utility-plant
I
I
I
I
I
I
I PCC interface and other specifications set by the damping by the active filter inverter.
I
I ASD manufacturer Since the optimal active filter Start-up, sequencing and active filter system
I solution is application and utility interface specific protection issues, including cost of isolation
I
I [l},the goal was to match the ASD rectifier front- and protection switchgear.
I end characteristics with a harmonic filtering solu- Topology I1 (hybrid series active filter system)
I
I tion to not only meet IEEE 5 19 harmonic stan- and topology I11 (hybrid parallel active filter sys-
I dards, but overall system specifications tem) do not meet the overall displacement power
I
I Design and analysis at a detailed level for the factor specification, requiring additional cou-
I following three topologies El}, 161 were done for pling transformer and complex protection and
I
I cost and performance comparisons isolation switchgear. They also do not meet cost,
I Topology I Parallel active filter system size, weight and floor space goals. Hybrid active
I
I m Topology I1 Hybrid series active filter system filter systems-topologies I1 and 111-provide
I c31, r51 value-added harmonic isolation feature and re-
I Topology 111. Hybrid parallel active filter duced voltage distortion at PCC, which is desir-
I
I system E41 able for voltage harmonic sensitive loads such as
I for hospital environments [l},[3]-[6}. However,
I
I performance and rating of hybrid series and hy-
I brid parallel active filter systems are adversely af-
I The parallel active filter system meets fected by active filter terminal voltage notching
I
I overall speczfications and constitutes the due to rectifier commutation.
I
I optimal harmonic filtering sohtion. The parallel active filter system (topology I)
I meets overall specifications and constitutes the op-
I
I timal harmonic filtering solution for given ASD
I rectifier front-end topology. This is primarily due
I
I The following factors were considered for active to dc side inductor L , which reduces supply cur-
I filter topology selection rent THD and consequently reduces required ac-
I
I Ability to meet IEEE 519 harmonic stan- tive filter kVA rating. This ASD rectifier front-end
I dards, including for ‘stiff supply systems and significantly reduces lower order harmonics ( 5 th
I
I in presence of maximum allowable 5% sup- and 7th), compared to the lowest cost diode recti-
I ply voltage distortion fier front-end with dc side capacitor, and enables
I Impact of voltage notching due to rectifier application of parallel active filter system. A pure
I
I front-end ar the active filter terminal on the active filter solution meets the high displacement
I performance and rating of the active filter power factor requirement over the entire ASD load
I
I kVA rating and cost of active and passive fil- range compared to either the hybrid’series or hy-
I ter components brid parallel active filter approach and it also re-
I
I Overall displacement factor from 12 5% to quires significantly less protection and switchgear
I 105% load rating cost. Line voltage notching due to rectifier commu-
I
I Losses of active filter system, including switch- tation does not adversely impact the performance
I ing ripple filter and rating ofparallel active filter systems, as verified
I
I Ability to provide value-added features such as by experimental results. The ASD manufacturer’s
I harmonic isolation between supply and load, cost emphasis and availability of water cooling for
I
I voltage regulation in presence of *IO% supply inverter devices due to air-conditioner chiller appli-
I voltage swellsisags, immunity to supply and cation constitute important factors that enabled a
I cost competitive parallel active filter system.
I load transients and ride-through capability.
I Ability for maximum integration with the Parallel active filter systems have the following
I
I
ASD-i e , capability of using the same ASD advantages [1}-[12):
I dc bus, one unit packaging to minimize cost, Viable and cost-effective.for low to medium
I size, weight and floor space LVA industrial loads where system engineer-
I
I Sensor requirement and control complexity ing effort is a large part of overall cost.
I Affect of supply voltage distortion, supply Do not create displacement power factor
I
I voltage sagsiswells and unbalances, and sup- problems and utility loading.
I ply side or ASD load induced subharmonics Supply side inductance L , does not affect the
I
I in the supply current, on the performance harmonic compensation capability of parallel
I and rating of the active filter to meet IEEE active filter system.
I
I 5 19 harmonic standards Controlled as a harmonic current source and
I Bandwidth and switching frequency of active its controller implementation is simple.
I
I filter inverter Can damp harmonic propagation in a distri-
I w Damping/mitigation of supplyiload side res- bution feeder or between two distribution
I
I onances, including additional cost and band- feeders 112).
I width requirement for providing active Performance, controlled as a harmonic cur-
la
I
m
l
I
I
I
-w ds - qs de - qe I
I to to
I
I
de - qe ds - qs
I
I
+ ls,ds I
From PLL
I
I cos-e,
sin4
t t f f I
I
I
Voltage Vfc
+
Fig. 4 . Synchronous reference frame controller for parallel active filter system.
y
I
t t
Integrator ResetTSW Tswi2
Measured 1
Active Filter
Terminal
Voltage
3 Phase
2 Phase
svtds
I
I
I
I
I
I
I
I
I
frequency current averaging window as a ratio of and high frequency current averaging in the I
I
switching periodT,w.For iexample,W T =1.O implies presence of these delays can be achieved by propor- I
current averaging over one switching period and tionally changing the 'weighting factor' W T by I
W T < 1.0 implies a current averaging window I
the ratio of total delay Tdele,to a switching period I
greater than Tiw.The charge error is reconverted to T,, greater or less than unity, depending on the I
an equivalent current error AichdrEe
di by dividing by I
sign of the current error Ai ,qd I
T,w.This is then added to sampqed current error The equations describing the current regulator I
Aifqd,from the first parallel path. The result- I
operation in vector notation are:
,
ing quantity is multiplied with L 1% to gen-
I
I
I
erate reference voltage across inductor L , to I
regulate active filter invixter reference current i; . I
I
The inductor reference voltage vector V,, is I
I
given in Eq. 2. I
The inverter reference voltages in the stationary I
I
d ' - g ' frame are generated by adding the I
@ I
feedforward d'- q' active filter terminal voltage I
I
V, signal to the inductsor reference voltage V , , I
and is given in Eq. 3. The feedforward V, signal is I
I
sampled synchronozlsly every Tlw12 period and si- I
multaneously with the current error AiIqd signal. I
where i ,qd, and iiYd,
are measured and reference ac- I
The charge error signal is also synchronowly sam- I
pled every T,w period with all the other signals. tive filter current vectors respectively, and Vi,,,is I
the measured active filter terminal voltage vector. I
However, the same charge error value is added at I
two consecutive T,w12 sampling instants, i.e., at Note that the prefix 's' denotes sampled quantities I
the start and middle of' a sampling period. The in Figs. 5 and 6. The current regulator generates re- I
I
feedforward of active filter terminal voltage V, in quired inductor reference voltage vector v, and I
the current regulator reduces the required gain of inverter reference voltage vector V,,,,,* . e in- & ' I
I
the current control feedback loop, thereby increas- verter reference voltage vector v,:~d< is imple- I
I
ing the stability of current control feedback loop. I
The charge error control serves the following mented by an analog space vector modulator as I
described in the next subsection. The ratio of the I
four functions: I
compensates for current errors due to high actual to nominal dc bus voltage (V, / V i ) is pro- I
frequency reference current change within a vided as a feedforward signal, as in most high per- I
I
switching period and enables high frequency formance current regulators. I
reference current tracking Active filter implementations are characterized I
I
w compe2sates for errors due to mismatch be- by high PWM modulation index operation. The I
tween L , and actual L , -a drawback of con- nominal dc bus voltage is 682 V with active filter I
I
ventional predictive current regulators terminal voltage V, = 460 V. The inverter voltage I
enables high frequency current averaging in available for current regulation is therefore 32 V. I
I
presence of sample and hold (SIH) delays and Consequently, the current regulator saturates I
inverter dead-time delays under high diidt conditions during rectifier com- I
I
compensates for measurement errors of i, mutation periods. In such cases, the average in- I
and V, signals. verter voltage reference vector VzIv is attenuated I
&. I
Errors due to the above mentioned conditions to the maximum PWM modulation index with the I
result in an inverter voltage reference error. This voltage reference vector angle unchanged. This oc- I
I
results in a current tracking error which is cor- c u r s a s a n a t u r a l c o n s e q u e n c e of t h e I
rected in the next (k+l)th switching period implementation of the space vector modulator by an I
I
+
T,w( k I), by the accumulated charge error from analog hardware circuit (to be described next). This
strategy achieves high dynamic response preserving
I
I
the previous kth switching period Tsw ( k ) . The ac- I
the simplicity of the PWM modulator implementa- I
cumulated charge error generates a corrective in-
tion. However, under such conditions the harmonic I
verter reference voltage in the next ( k + l ) t h I
content in the compensated supply current increases. I
switching period T,w( k .t1). The proposed predictive current regulator I
Sample and hold (SIH) delays are typically scheme allows a direct voltage based PWM imple- I
1- 2 ps, and inverter dead-time delays are typically I
mentation by generating an average inverter volt- I
3 - 5 p s . Hence, the total delay T,+ is in the range age reference vector V,:vdi. This facilitates I
of 4 - 7 ps. This total delayTd8,, is significant since I
implementation of constant &itching frequencycar- I
it constitutes 10 - 15% of a 20 kHz PWM switch- rier-based PWM schemessuch as space vector modu- I
ing period T,= 50p.s. Charge error minimization I
lators. Carrier-based PWM schemes, such as space I
Ah
I Filter Current 7 4 7 4
I
I
I
I Sa
I
I
I
I
I
I
I 1 2Phase
sb
I
I
I svTtvds
I to
3Phase
I
I
I Inverter
I ds - q S
I Reference
I Voltages
I or
I Inverter
Output of Predictive Gate
I
I Current Regulator or Natural Signals
I
I Decision
I
I
I
I
I
I
I
I Fig. 6. Andlog implementation of space vector PWM modulator.
I
t
Ch2 1.00 V M2.OOms L i n e J ov
I The current rating of all switching ripple filter
components is small and meets given specifica-
tions of cost, size, weight and packaging. This
also results in a cost-effective design since it elim-
5ljB 1 OOV 2.00ms
inates the need for higher inverter current band-
Fig. 8. Active filter reference current i ; [lo0 Aldiv) and actual current if w i d t h t h a n t h a t r e q u i r e d for h a r m o n i c
{loo Aldiv), t = 2msIdiv. compensation. This design demonstrates that to-
I pology (iv) (Fig. 7) provides a viable and
I cost-effective solution for inverters with fixed
I The specification of a displacement power fac-
I switching frequency PWM schemes.
tor greater than 0 95 at 12 5% load condition con-
I Note that in this application since the value of
I strains the maximum filter capacitor value C =
I 50 pF The inverter switching ripple filter branch capacitor C is small (50pF), the switching ripple
I
I ,
consisting ofL ,C T , R , is designed with the con-
filter does not provide any significant reduction in
active filter terminal voltage V J notch area. This is
I straint that C << C, typically C, < 10 C such
I
that all the fundamental active filter terminal volt- also evident from measured line-line voltage VI
I given in Fig. 11.
I age appears across the capacitor C For a resonant
I For inverters that have a broad-band current
I frequency of 20 kHz and chosen C = 3pF, the
I resonant inductor is calculated as L = 2 1pH The , spectrum, such as those with hysteresis current
I
I
quality factor Q of the tuned L - C branch is , regulators or discrete pulse-width modulated reso-
nant DC link inverters, the switching ripple filter
I around 3000 with R , = 50mQ R , can be either
I an external resistor or equivalent series resistor topology (v) in Fig. 7 provides an effective solu-
I
I ,
(ESR) of inductor L Note that since C < 10 C , , tion. The two parallel branches provide filtering
over two different frequency ranges. The high-pass
I capacitor C does not change the filtering character-
I
I istics of the L i , C ,, R , filter branch The entire ,
filter capacitor C provides filtering within the ac-
I switching frequencyripple current component at 20 tive damping bandwidth or current regulator
I
I kHz therefore flows through the L - C branch , bandwidth of the inverter. The smaller filter capac-
itor C and resistor R , provide damping to supply
I The resistor R, is designed such that it damps any
I and/or load induced resonant frequencies higher
I supply and/or load induced resonances beyond the
I inverter current regulator bandwidth and does not than the inverter current regulator bandwidth. To-
I
require active damping by the inverter pology (v) reduces the design sensitivity of damp-
I
ing resistor R , and associated active filter terminal
I The inverter has a current regulator bandwidth in
I voltage V, distortion concerns.
I excess of 2 1 kHz, since IEEE 519 harmonic limits
I are met up to the 35th harmonic This is validated by
I
I
the experimental results in the next section Conse- Experimental Results
quently, the inverter provides active damping for Experimental results are presented for the parallel
I any supply and/or load induced resonance condi-
I active filter system with the ASD rectifier front-
I tion below 2 1 kHz The damping resistor end operating at an input power of 252 kW The
I R , = 17Q is therefore chosen such that R, < 10 measured supply line-line voltage is 476 V and has
I
I times the impedance of C - L switching ripple a voltage T H D of 2 3%-1 7% of 5th, and 0 7% of
I filter branch above 2 1 kHz, to provide effective
I 7th, harmonic distortion The measured supply
I damping above the inverter current regulator voltage also has a 1.3% negatlve sequence unbal-
I bandwidth This design ofthe damping resistor R, ance. The high percentage of measured negative se-
I
I also ensures that the fundamental current deter- quence supply voltage unbalance demonstrates the
I mined by capacitor C flows through R, and does necessity of the negative sequence SRF controller
I
I not increase the current rating of C and L , for extraction of the fundamental negative se-
I
compensation is devoid 'of any high frequency con- Compensation &yparallel active filter system, t = 2 ms I div ;commutation
tent, as shown in Fig. 10. This result validates the notch width t = 4 0 0 p .
w
I
If€€
Industry Applications Magazine I Sepfember/October 1998
Tek Run: 5OOkS/S H i Res parallel active filter system. The supply current
3
! 1
T H D of 4.1% complies with the worst case allow-
able IEEE 517 T H D limit of 5% for short circuit
ratios less than 20.
Individual supply current harmonic distortions
are given in Fig. 12 along with their IEEE 5 17 har-
monic limits for SCR = 3 1.This result also demon-
strates the high current bandwidth achieved by the
predictive current regulator with charge error con-
trol and implemented by an analog hardware based
space vector PWM modulator. Note that the com-
pensated supply current i, T H D is in the presence
of supply voltage T H D of 2.3%; it also includes
ASD load induced subharmonics at 33 Hz.
The presence of a subharmonic in the supply
current is evident from the measured supply cur-
rent in Fig. 2 and from measured active filter in-
t 1 verter dc bus voltage ripple in Fig. 13. Hence, the
M2.00ms Line% -105V
200mv measured supply current T H D after harmonic
Fig. 11, Active f i l t e r line-line t e r m i n a l voltuge V,. f200 V l d i u ] , t = 2msldiv compensation is under worst case system condi-
u n d commutution notch width t = 400p s. N o t e high frequency content and tions. Note that with the active filter off, the mea-
line notches d u e t o rectifier commututiolz. sured terminal voltage V, T H D is 7.0% (4.0% of
I 5th, 2.2% of7rh, 2.3% of I l t h a n d 2.2% of 13th).
After the active filter is started, the terminal volt-
25.0% age V, T H D is reduced to 2.5% (0.7% of 5th,
0.2% of 7th, 0.6% of 1l t h and 0.6% of 13th). The
V, voltage T H D of 2.5 % is largely due to a back-
%Fund
ground supply voltage distortion of 2.3%. This
demonstrates that other voltage harmonic sensi-
tive loads can be connected at PCC, and the parallel
12.5% active filter system provides a viable solution for
harmonic compensation of voltage harmonic sensi-
tive loads.
Fig. 13 shows the active filter inverter dc bus
voltage variation. Due to the ASD load induced 33
Hz subharmonic component in the supply current,
the dc bus voltage has a 27 H z (60-33 Hz) compo-
0.0%
Fund 5 7 11 13 17 19 23 25 29 31 nent. The peak-peak dc bus voltage ripple in Fig.
Phase A Current Amplitude Spectrum 13 is -approximately 35.0 V. The dc bus voltage
(a) also has a 120 Hz component due to negative se-
quence supply voltage V,unbalance of 1.3%.
2 5%