Professional Documents
Culture Documents
Classroom Training
Participant’s Guide Version 1.1
This product is for TRAINING PURPOSES only. Do not use this material in place of the current
revision of controlled documents such as technical manuals, operator’s manuals or other work
instructions. The information contained herein is confidential and proprietary to Cummins Inc.
and its affiliates. No unauthorized disclosures may be made without the written permission of
Cummins Inc. or one of its affiliated entities.
Table of Contents
Course Overview ........................................................................................................................................... 4
Lesson 1: Introduction .................................................................................................................................. 5
Lesson 2: PCC Controls Safety ..................................................................................................................... 15
Lesson 3: Controls Subsystems ................................................................................................................... 29
Lesson 4: PCC 1302 Hardware .................................................................................................................... 55
Lesson 5: Operator Menus .......................................................................................................................... 67
Lesson 6: Service Menus ............................................................................................................................. 77
Lesson 7: Sequence of Operations ............................................................................................................ 111
Lesson 8: InPower Service Tool................................................................................................................. 131
Lesson 9: Troubleshooting PowerCommand Controls ............................................................................. 157
Taking Notes
It is highly recommended to take notes and make sketches during the class. For most people, the act of
writing and drawing helps you remember what you’ve heard.
Asking Questions
One of the most important parts of this course is for you to ask any questions and for the instructor to give
you a good answer. Feel free to ask a question any time. If you have any unanswered questions at the end
of a lesson, ask them then or write them on the Question Parking Lot.
Lesson 1: Introduction
Objectives Lesson Length : 1 hour
Introduce commercial generator set
controllers
Describe what makes a PowerCommand
Control
Understand how to download service
literature
A generator set is comprised of three main systems:
Genset Controls • Prime Mover
Genset Controller
• Alternator
• Genset Controller
The genset controller is responsible for controlling the alternator and prime mover to produce consistent,
reliable, and usable electricity for the customer. The genset controller collects numerous inputs from the
prime mover, the alternator, and the customer itself. This data tells the genset controller many things
such as the speed of the engine, the voltage of the alternator output, the coolant temperature, etc.
The genset controller uses that input data, and compares it to preconfigured setpoints and programming
and responds with outputs. Those outputs could be to increase the excitation voltage, increase the speed
of the engine, annunciate a warning message, or shutdown the genset altogether.
The genset controller is responsible for these features and many more.
Notes:
Finally, even as all of these things are happening at once, the control is responsible for protecting the
generator set. The control is monitoring many sensors and inputs from the engine, alternator, and other
systems to make sure the generator set is operating in appropriate environments. If the control begins to
detect a scenario which may be dangerous for the generator set, it may issue a warning. If the condition
persists, it may shut the generator set down completely.
What makes a generator set controller a
History of PowerCommand Controls “PowerCommand Control”? That is the inclusion of
microprocessors.
With the advent of the microprocessor, Cummins Power Generation was able to consolidate all of the
decision making, timing, protections, and control into a computer chip. This eliminated the need for
internal hard-wired circuitry for genset control and monitoring.
Thus, the total footprint of a PowerCommand Control was drastically reduced. A paralleling control, which
was needed for every generator set, was reduced from the size of a refrigerator to the size of a
microwave.
Notes:
One way is by using the Service Menus offered by the HMI. The HMI displays different menus, and the
operator can adjust different parameters based on which menu is being shown. The operator can scroll
through different menus until he/she finds the correct parameter they are looking for. Then, by using the
HMI pushbuttons he/she can configure the parameter to the desired value.
Another way to configure the PowerCommand Control is by using Cummins Power Generation’s
electronic service tool “InPower”. InPower is an application on a personal computer that allows the
technician to access all of the monitoring and configurable parameters associated with the
PowerCommand Controls. The operator can change the parameter using the application and save the
new parameter to the control.
The PowerCommand Control is also responsible for
Protections protecting the engine and the alternator of the
generator set. It does this by monitoring sensors
inputted into the PowerCommand Control. It
compares the data from those sensors against
PowerCommand
Auto NOT IN AUTO
SHUTDOWN
configured protection setpoints.
! WARNING
Fault
At: 123.2 Hrs REMOTE START
Notes:
A BMS is usually a central computer that controls all of the power distribution in a customer’s facility. This
system can control, monitor, start, and stop every piece of equipment including backup power
generators.
An ATS is a device that senses when utility power has been lost locally at a facility, start an emergency
generator set, and transfer electrical power automatically over to the emergency power.
Each PowerCommand Control has slightly different
Basic Genset Operation ways in which it controls a generator set through a
sequence of operations, but in general, they all
Start Type Input (Mode Selection)
follow a similar process.
Start Input
Start Relay/Run Relay
Start Type Input
Start Disconnect
A generator set control in order to know how to
Speed Governing
operate the generator set, first must know which
Automatic Voltage Regulation start type input it is looking for. There are several
Protections modes of a generator set that we will expand upon
Shutdown Sequence later on: Off, Manual, and Auto. Depending on
which mode the generator set control is in, the
11 7/7/2014 Cummins Confidential control will look for different start inputs and ignore
others.
Start Input
Once the start type is determined, the generator set is waiting for a start input. Once that start input is
active, the generator set control begins its controlled start sequence.
Speed Governing
Either the Engine Control Module (ECM) or the PCC will now have to govern the speed of the engine to
the appropriate RPM. RPM is tied directly to frequency of the alternator output, so this is crucial. The
ECM or PCC does this by controlling the amount of fuel allowed into the fuel system by using a governor.
Voltage Regulation
The PCC (or a third party Automatic Voltage Regulator) must also control the output voltage of the
alternator to the appropriate voltage needed by the customer. It does this by controlling the excitation
voltage of the exciter stator. The more excitation voltage which is applied to the exciter stator, the more
voltage is produced by the alternator.
Protections
Part of the PCC’s job is to protect the engine and the alternator from damage. It does this by monitoring
many sensors for pressure, temperature, voltage, and current. If one of those sensors detects a value that
is above or below a certain threshold, the generator set may be shut down to protect itself from damage.
Shutdown Sequence
Once the generator set is no longer needed for power, it can be shut down. Similarly to the start input,
shutdown input will be dependent on the mode of the generator set control. In some instances the
generator set will be shut down immediately (E-stop, for example). In other instances, such as shutdown
in Auto mode, the PCC will control a shutdown to cool the engine down at rated or idle speed.
The PCC 3100 was the original PowerCommand
PCC 3100 Control. This was the first fully integrated paralleling
control that Cummins Power Generation offered.
Notes:
The PC1.X was the first in the latest generation of generator set controls, and the first control to utilize
the “Common Connector Harness”. The common connector harness allows for relatively simple upgrading
or downgrading of PCX.X controls. For example, the generator set voltage connection on the PCC 1302
control board has the same name and connection points on the PCC 2300 control board and the PCC 3300
control board.
The PC1.X can communicate with other generator sets and networking equipment using an open source
language called Modbus.
The PC2.X control can be used on either Hydra-
PC2.X mechanical or CAN connected ECM based
application.
Instructions:
1. Go to www.quickserve.cummins.com
2. Login using your wwid and password (or create an account if needed)
3. Using the Generator/Alternator Content search function download the Service Manual for the
PowerCommand 1.X control.
Work on Cummins PowerCommand Controls will also fall under corporate policy:
• Cummins Procedure for Energized Electrical work on systems with rated voltage of less than 1000
VAC or 1500 VDC (CORP 09-04-06-02)
• Permit to Work and Authorization levels (CWI 09-04-06-01)
These documents can be accessed via http://mycummins.cummins.com/ and search for “Electrical
Safety”.
Unqualified
An “Unqualified Person” is one that may work with low voltage electrical equipment and has received
training on how to recognize that electrical exposure may exists and how to avoid risk of injury.
Unqualified persons may enter electrical areas or use electrical equipment as a part of their function, but
may not perform work on electrical equipment or perform switching operations on distribution
equipment.
A “Qualified Person” is one who has been trained to recognize and avoid the hazards associated with
work on or near exposed energized electrical parts. He/she has been trained on the equipment, work
methods, precautionary techniques, PPE, and special tools to perform safe work. This training can include
a qualified NFPA 70E safety course, and continued, supervised on-the-job training.
An “Authorized Person” is one who has been Qualified as above, but has been authorized in writing by
Cummins to work on electrical equipment.
Just because a technician is Authorized on certain electrical systems does not mean that he/she is
Authorized on all systems. Training and Authorization must match the level of work to be performed (i.e.
Low Voltage and High Voltage).
Notes:
For more information and definitions about establishing an electrical safe work condition, go to NFPA 70E
section 120
If de-energizing the equipment is not feasible, an
Energized Work Permit Energized Electrical Work permit must be filled out
and authorized by the company. There will need to
be justification for not de-energizing the equipment.
For more information and definitions regarding Energized Work Permits go to NFPA 70E section 130.2(B).
The Energized Work Permit used by CPG can be found on http://mycummins.cummins.com/ on the
Electrical Safety page.
Notes:
Limited Approach
Limited Approach Boundary: An approach limit at a
distance from an exposed energized electrical
Exposed, Restricted Approach conductor or circuit part within which a shock
energized
conductor
hazard exists. Entered only by Authorized Persons or
Prohibited Approach Qualified/Unqualified persons escorted by an
Authorized Person
Restricted Approach Boundary: An approach limit at a distance from which there is an increased risk of
shock, due to electrical arc over combined with inadvertent movement for personnel working in close
proximity to the energized electrical conductor or circuit part. Entered only by Authorized Persons
required to use shock protection techniques and equipment
Prohibited Approach Boundary: An approach limit at a distance from exposed electrical conductor or
circuit part within which work is considered the same as making contact with the electrical conductor or
circuit part. Entered only by Authorized Persons requiring same shock protection as if in direct contact
with live parts.
Notes:
50 – 300 V 3’ – 6” Avoid Contact Avoid Contact Limited Approach boundary is 3’-6”. The Restricted
301 – 750 V 3’ – 6” 1’ – 0” 0’ – 1” and Prohibited approach boundaries are simply
listed as “Avoid Contact”.
For more information and definitions regarding Approach Boundaries go to NFPA 70E section 130.4
Arc flash is where a flashover of electric current
Arc Flash/Blast leaves its intended path and travels through the air
from one conductor to another, or to ground.
The Authorized person will use the Hazard/Risk Category on this label to select the proper Personal
Protective Equipment.
Notes:
In addition to this, based on the hazard category as defined by the Arc Flash and Shock Hazard analysis,
there may be additional PPE required.
If Rubber Insulating Gloves are required when
Rubber Insulating Gloves entering the shock Restricted Approach Boundary,
they must be used properly:
• Gloves shall be rated for the proper system
voltage
• Leather Protectors shall be worn over the
gloves
• Gloves must be visually inspected and
checked for leaks prior to each use (roll-up
test)
Leather Protector
Rubber Insulating Glove
Gloves rated by voltage:
• Class 00 = 500 volts max.
• Class 0 = 1000 volts max.
• Class 1 = 10 kV max.
Notes:
Category 0: The Cummins standard personal protective equipment is sufficient for work on H/R Cat 0
equipment/procedures.
Category 1: Standard Cummins required PPE plus a 4 cal/cm2 minimum rated face shield and hard hat.
Category 2: Standard Cummins required PPE plus an 8 cal/cm2 minimum rated face shield, hard hat, and
balaclava.
For more information and definitions of Arc Flash Hazard/Risk Categories and PPE recommendations go to
NFPA 70E Section 130.7 (2012 edition).
In NFPA 70E, there is a look-up table that defines
Table 130.7(C) Hazard/Risk Category is present based on the type
of equipment, nominal voltage, and the description
of work being performed.
Notes:
Notes:
If the control cabinet is accessed or opened, even if the genset is not running, there are a certain electrical
hazards to be aware of.
Bus Voltage
This only applies to paralleling controls. Even when the genset is not running there could be voltage
present at the Bus Voltage sensing input to a paralleling control.
Genset Voltage
This is the sensing input for PCC Controls. When the genset is running and producing voltage (even when
the genset breaker is open) there will be rated voltage at this terminal block.
CT Inputs
This is the sensing input for the Current Transformers which the PCC control measures how much current
the load is drawing from the genset. There could be up to 5 amps of current present at this plug.
Any and all of these points should be used to define the Shock Hazard Approach Boundaries.
Notes:
If the LOTO emergency stop sleeve is not place, it is good practice to remove the battery cable from the
generator set starting batteries and place a LOTO terminal cover and lock around the battery cable
terminal. This will prevent anyone from reconnecting the generator set battery while service is being
performed.
All work on energized electrical systems and
Insulated Tools equipment performed inside the Limited Approach
Boundary shall be performed using only properly
certified insulated tools rated at a minimum of 1000
VAC. These tools should be inspected before each
use for the integrity of the electrical insulation.
Notes:
Category I: Electronic level. This device is intended to be used on protected electronic equipment.
Category II: Single phase-receptacle connected loads. This multimeter is intended to be used on AC
appliances, household outlets, etc.
Category III: Three phase distribution. This multimeter is intended to be used in switch gear, transfer
switches, feeder breakers, etc. This is the category of multimeter that will be required for work on most
CPG energized transfer switches.
Category IV: Three phase at utility connection. This multimeter is intended to be used in switching
stations, outside service entrances, utility main breakers, etc.
Notes:
Activity 2-1
Skills Exercise
Voltage Measurement
Required Materials
• Running genset or working generator set simulator
• Multimeter
• Proper PPE
• NFPA 70E
Measure Voltage
3. Select a multimeter capable of performing voltage measurements on a three phase generator set
Category of Multimeter:________________
4. Measure voltage at the PowerCommand Control using the multimeter while wearing the proper
PPE
a. L1-L2 _________
b. L2-L3 _________
c. L1-L3 _________
d. L1-N _________
e. L2-N _________
f. L3-N _________
• Graphical Display
• Soft pushbuttons
• Hard pushbuttons
• Switches
38 7/8/2014 Cummins Confidential • Bar Graph
• Emergency Stop(s)
Notes:
Genset Info
Description Lines
set battery voltage, engine temperature, oil
pressure, and engine run time. This information is
39 7/8/2014 Cummins Confidential gathered by various sensors by either the Engine
Control Module (ECM) and sent to the
PowerCommand Control through a data link, or the
sensors are wired directly to the PCC.
Alternator Monitoring Menus
Again, each PCC may show different alternator information based on application, but typically the
operator can find information such as line-to-line voltage, line-to-neutral voltage, frequency, current, kW,
kVA, and Power Factor. This information is typically gathered by voltage and current sensing inputs wired
to the PowerCommand Control
Configuration/Service Menus
The graphical display also is used to display configuration menus. The configuration menus allow the
operator to input new configuration settings to the PCC which will change the way in which the PCC
operates the generator set.
Notes:
Remote Start
This green LED is only lit when there is a Remote Start signal present. The remote start is a connection
point that a customer will make to start the generator set automatically, without input from the operator.
Note that the Remote Start LED can be lit even if the generator set is not running.
Not in Auto
This red LED is flashing when the generator set is not in Auto mode. In Auto mode, the generator set can
be started remotely by the remote start input. Any time that the generator set is not in Auto (Off Mode,
Manual Mode, Shutdown condition) the light will flash.
Shutdown
This red LED is lit when there is a shutdown condition. Part of the PCCs job is to protect the engine and
alternator it is controlling, so when there is a condition that may be harmful to the generator set, the PCC
may shut down.
Warning
This amber LED is lit when there is a warning condition. Similar to the shutdown LED, this is to alert the
operator when there is a potential condition that could be harmful to the generator set. In this condition,
the PCC will keep the generator set running.
Configurable LEDs
Some PowerCommand Control’s HMIs have configurable LEDs. These LEDs can be set to light when
certain programmable events occur.
Notes:
Genset
Operation
The PCC can communicate with the operator using the graphical displays and LEDs, but the operator can
communicate to the PCC using pushbuttons on the HMI. Each PCCs HMI may be different but there are
similarities and consistencies throughout the entire product line.
Menu Navigation
These buttons are used to navigate through the menu structure of the HMI’s graphical display. Some of
these buttons may be “hard pushbuttons” and some may be “soft pushbuttons”. Hard pushbuttons have
a function that does not change (such as the Home button shown on the visual). Soft pushbuttons may
change depending on what is shown on the graphical display (such as the 4 unlabeled buttons below the
display).
Genset Operation
These buttons are used by the operator to control the generator set’s operation. These buttons are used
to select the generator set’s mode, and start and stop the generator set manually. Some PowerCommand
Control’s HMIs also have breaker operation where the generator set’s electrically operated circuit breaker
can be opened or closed in the manual mode.
Fault Reset
Some HMIs combine this button with the “Off” button, but every PCC must have a way to reset shut down
faults. When in off mode, a shutdown fault can be cleared by pushing this button.
Lamp Test
Most HMIs have this pushbutton which allows the operator to test the LEDs on the HMI for proper
functionality
Emergency Stop
The local Emergency Stop is considered part of the HMI. The Emergency Stop has several functions, the
primary one being shutting down the generator set immediately in the case of an emergency. The E-stop
can also be used to prevent the generator set from starting if service is being done on the generator set.
The E-stop also controls the Keyswitch to the ECM, and usually induces a data-save when engaged.
Therefore, do not remove battery power for at least 30 to 60 seconds after depressing the E-stop on a
genset which uses an engine with an ECM (refer to engine’s service manual for exact time). Note: The E-
stop is not to be used for usual manual stopping of the generator set. Manual stopping, when done
correctly, usually will include the proper cooldown time delays, whereas using the E-stop will shut the
engine down hot.
PowerCommand Controls also have a Remote
HMI: Emergency Stops Emergency Stop input. When either the Local or
Local E-STOP
Remote E-stops are engaged, a signal is sent to the
Remote E-STOP
generator controller to prevent operation. As
additional safety, the E-stops physically interrupt B+
from getting to the FSO and Start relay coils. In
B+
order to do this, a second e-stop contact is added in
series with B+ and the FSO and Start relay coils.
Auto Mode
When the generator set is in Auto mode, the generator set can be started with a remote signal only.
When in Auto mode, the generator set can start at any time without any operator input (or warning). If
the generator set is running in Auto Mode, and the Off button is pressed or the remote start signal is
removed, the control initiates a normal shutdown sequence.
Notes:
Remote HMI
Some PCCs offer a remote HMI option. A remote
Remote HMI
Annunciator HMI often has most of the functionality of a local
HMI, besides some functions which the PCC will
require to be done by an operator locally – such as
fault resets.
Bar Graph
Bar Graph
A bar graph is another optional display device. A bargraph offers a graphical LED display of common
alternator outputs such as amperage, kW, power factor, frequency and voltage. All of the information
presented by a bar graph can be found using the monitoring menus as well.
Annunciator
An annunciator displays a number of different conditions of a generator set through colorized LEDs.
Annunciators are networked devices which can be placed up to many thousand meters away from the
generator set.
Analog Gauges
Some PCC devices support analog gauges as well for monitoring parameters such as battery voltage and
oil pressure. Similar to the bar graph however, all of the information presented by the analog gauges can
also be found in the monitoring menus.
Notes:
With this linear relationship between the primary and secondary amperage, the PCC can monitor the
secondary current, and determine the primary current.
CTs typically have a dot on them that represents the polarity of the CT. The CT should always be installed
with the dot facing the source of power (in this case the alternator). Failure to do so will result in most
PowerCommand Controls shutting down on “reverse power”.
Notes:
As the magnetic field increases (by increasing the DC current supplied by the AVR), the alternator output
voltage increases. As the magnetic field decreases (by decreasing the DC current supplied by the AVR), the
alternator output voltage decreases.
The PCC monitors the output voltage of the main alternator. It compares that input voltage against the
nominal value it has been programmed to regulate to. If there is an error between the actual voltage
output of the alternator and the desired voltage, it will have to adjust the DC current (“field”) output to
correct the error; if the PCC increases the field output the alternator voltage will increase, if the PCC
decreases the field output the alternator voltage will decrease.
So if the AVR senses AC power and responds with a
AVR Input (Self Excited) DC pulse width field output to the exciter stator,
where does the power for the DC field output come
from? That depends on the type of input to the AVR
AC
circuit.
Main Stator Output There are two types of excitation systems – self
(Auxiliary Windings)
excited and separately excited.
Main Rotor
In a self-excited system, AC voltage directly from the
alternator is sent to the AVR circuitry. This is a
separate connection from that voltage which was
48 9/10/2014 Cummins Confidential sent to the PCC for voltage sensing, this is only for
AVR Power. It is this AC power that will be
controlled and “sent back” to the excitation system
on the field windings.
Notes:
AC
Main Rotor
PMG
Notes:
voltage?
• Derivative
52 7/8/2014 Cummins Confidential
Most PCC use a closed-loop, PID algorithm to calculate the field output voltage. PID stands for
Proportional, Integral, and Derivative. These are three coefficients in an equation. We don’t need to know
exactly how or what the equation is, but we need to know how each coefficient changes how the PCC
reacts to voltage changes.
Proportional
The Proportional coefficient is looking at the present error – that is the current difference between the
nominal voltage and the actual alternator output.
Integral
The Integral coefficient is looking at the past errors – that is the accumulation of all the differences
between the nominal voltage and the alternator output over time.
Derivative
The Derivative coefficient is looking at the prediction of future errors – that is, as the alternator output
voltage is recovering towards the programmed nominal voltage, making sure it is not on pace to “over
correct”.
Notes:
Alternator
The PowerCommand Control can also sense the
L1 L2 L3 N
frequency of the alternator by monitoring the
Voltage (frequency) input
voltage inputs to the control. The alternator
produces alternating current, where the current
alternates between positive and negative while still
doing work. You can think of alternating current like
a lumberjack sawing through a piece of wood by
going both forwards and backwards.
Alternator
Output
Like the lumberjack’s saw, when the current is turning directions, there will be a moment in time where
the current has zero potential. This is known as a “zero crossing” point for voltage, and monitoring these
points where voltage equals zero is how the PCC monitors frequency.
Frequency (in hertz) is directly related to the engine speed because the alternator is typically on the same
shaft as the crankshaft of the engine.
Notes:
Engine Interface
ECM Connection
If the engine that the PCC is controlling has an Electronic Control Module/Unit (ECM or ECU, respectively),
the PCC will not need electronic governing output to the governor actuator. The PCC will simply send
signals to the ECU, and the ECU will send signals back to the PCC over a data link. Typically this is a J1939,
twisted pair data link. All of the communication between the PCC and the ECU will be sent over this
communication protocol.
If the generator set is a hydra mechanical unit, then the PCC must monitor all of the engine sensors, and
monitor and govern engine speed.
Magnetic Pickup
The magnetic pickup is a device which the ECM or PCC uses to monitor engine speed.
Engine Sensors
If the PCC is controlling an engine with no ECM, the engine sensors that the PCC will need to monitor to
protect the engine (Oil Pressure, Engine Temp, etc.) will be wired directly to the PCC. If there is an ECM,
they will be connected to the ECM, and transmitted to the PCC over the CAN data link.
The PCC can determine the engine speed from either the Hz of the alternator or the pulses of the MPU. If
the engine speeds do not match, a speed/hertz mismatch fault will occur.
By pulsing the DC signal off and on very rapidly, the PCC can control the fuel rate very closely, since the
short pulses of DC power trying to open the valve will balance the spring force trying to close the valve.
Most PCC main base boards do not have the current capacity to control the governor actuator directly. So
a governor output module, essentially a signal amplifier, is used to amplify the pulse width signal from the
PCC to a strong enough DC pulse to control the spring loaded governor actuator.
Notes:
Again, the PCC use a closed-loop, PID algorithm to calculate the governor actuator output. PID stands for
Proportional, Integral, and Derivative. These are three coefficients in an equation. Again, we don’t need to
know exactly how or what the equation is, but we need to know how each coefficient changes how the
PCC reacts to voltage changes.
Proportional
The Proportional coefficient is looking at the present error – that is the current difference between the
nominal engine speed and the actual engine speed.
Integral
The Integral coefficient is looking at the past errors – that is the accumulation of all the differences
between the nominal engine speed and the actual engine speed over time.
Derivative
The Derivative coefficient is looking at the prediction of future errors – that is, as the actual engine speed
is recovering towards the programmed nominal speed, making sure it is not on pace to “over correct”.
Notes:
The PCC and ECM typically speak over a J1939 data communication “backbone”. This is two-way
communication between the PCC and the ECM:
• Fault annunciation from the ECM to PCC. The PCC will still display the warning/shutdown and a
fault code, but the fault itself will be coming from the ECM, not the PCC
• Engine monitoring data from the ECM to the PCC. The PCC will display engine monitoring
parameters in the operator menus, but the sensors from which the data is gathered are actually
being sent from the ECM.
• Start/Stop Commands from the PCC to the ECM.
• Speed bias from the PCC to the ECM (in some cases). Many times the RPM setpoint will be set in
the ECM only, and can only be adjusted using the ECM’s service tool.
Physically, the J1939 data link is a twisted pair, shielded data cable. On either end, where the connections
are made to the PCC and the ECM, a 120 ohm terminating resistor is used to absorb electrical noise on the
data link. If those 120 ohm resistors are removed, the connection between the PCC and ECM could be
corrupted.
Notes:
At each end of the backbone there needs to be a terminating resistor with a nominal resistance of
120ohms (these have a blue cap). This minimizes the reflections within the datalink.
If you need to extend the length of the backbone, you can do so by removing the terminating resistor on
the end you wish to extend, add the required length of backbone (remember this extension plus the
original backbone cannot exceed 40 meters in length) and replace the terminating resistor at the end of
the extended piece. You may need to extend the backbone if you are removing the controller pedestal
from the genset and mount it elsewhere.
If there are unused connectors to the datalink, they must have plugs put in place (these typically have an
orange cap).
Since the messages are sent by a voltage differential, it is essential that all devices are on the same
ground plain.
If the grounds of two ECM’s are different, then a low voltage differential of one ECM may appear to be a
high voltage differential to another. Hence messages get corrupted and communication is lost.
Notes:
Start Relay
The start relay output is a driver for the Start Relay. The start relay controls battery power to the starter
solenoid. When the start relay output is active, the Start Relay engages, sending battery power directly to
the starter and the starter solenoid. This will engage the starter into the flywheel of the engine causing it
to crank.
Run Relay
The run relay output is a driver for the Run Relay. The run relay controls the fuel shut off valve (FSO).
When the run relay output is active, the Run Relay engages, which opens the FSO. When the FSO is
opened, fuel can enter into the fuel system of the engine. With conditions right, and the engine is
cranking, the fuel will cause the engine to start to run.
Switched B+ Relay
The Switched B+ relay output is a driver for a Switched B+ Relay. Switched B+ is battery power that is only
available when the genset is running. When the genset reaches its start disconnect speed, the switched
B+ relay output becomes active, which activates the Switched B+ Relay. This relay then sends battery
power to various locations.
Battery Input
PowerCommand controls require battery power to operate. Unlike Switched B+, regular battery power
(B+) is available any time the generator set battery is connected and powered. This power enables the
PCC to operate in standby mode when the generator set is not running.
Low Low Acceptable High High Each parameter that a PCC monitors is different and
has different monitoring thresholds, but in general,
Shutdown Warning Operating Warning Shutdown
Range
When a parameter is acceptable, it is near its “nominal” set point, and the condition is operating in a
completely normal condition. As the parameter moves away from nominal it may near a warning
threshold. Often there are both high and low warning thresholds, which warn the operator of conditions
that are both above and below normal operating conditions. The PCC typically keeps the generator set
running when the parameter enters a warning condition.
As the parameter continues to move away from nominal, it may enter a shutdown threshold. Once the
condition has wandered this far from nominal, the PCC will shut down the generator set as this is a
potentially harmful condition for the generator set to be in.
A PowerCommand Control typically handles shut
Protections: Shutdowns and Warnings down conditions and warning conditions differently.
Warning
When the PCC detects a condition that requires a
warning response, the PCC will light the warning LED
and display the fault and description on the
graphical display. This lets the operator know that
the generator set may be in a condition that may
become harmful. The generator set continues to run
Shutdown Fault Warning Condition
and produce power during warning conditions. If
the conditions were to improve out of the warning
61 7/8/2014 Cummins Confidential condition and return back to normal, the PCC would
clear the warning on its own.
Shutdown
When the PCC detects a condition that requires a shutdown response, the PCC will light the shutdown
LED and display the fault number and description on the graphical display. In addition, the PCC may
immediately shut the generator set down (if the condition could be harmful to the engine) or shutdown
with cool down time delays under no electrical load (if the condition could be harmful to the alternator).
Shutdown faults must be reset manually; they will not clear on their own. Typically this requires an
operator on site to clear the faults.
Notes:
Fault Numbers
Fault Type
Engine
A PowerCommand Control will give information
Run Time about why it has shut down or why it is displaying a
Fault Number warning condition. Each PowerCommand Control is
different in this fault annunciation, but typically a
Description PCC’s HMI will display the fault type, the run time
the fault occurred, a fault number, and a description
of the fault.
Fault Type
Typically, a PCC will display whether this is an active fault or an acknowledged fault. Acknowledged faults
will typically only be found in the fault history. Active faults will be displayed on the front screen until they
are acknowledged/reset (in the case of shut down faults) or the warning condition has been correct (in
the case of warning faults).
Fault Number
The fault number is a very good troubleshooting tool. The fault number can be looked up in the service
manual of the generator set or the control, and likely causes can be investigated.
Fault Description
The HMI will also typically display a description of what the logic is behind the fault.
Notes:
Over current Warning/Shutdown – Shutdown set to be below alternator damage curve up until maximal
measureable point. Currents above the maximal measureable point shutdown after the HCT Shutdown
Time Delay. Warning level set to half of the shutdown threshold.
Under/Over Frequency - Under frequency default to - 6Hz of the 50 Hz / 60 Hz frequency for 10 seconds
time delays. Over frequency default to + 6Hz of the 50 Hz / 60 Hz frequency for 10 seconds time delays.
Loss Of Sensing AC Voltage Shutdown – Loss of sensing AC voltage detects the loss of voltage sensing or
senses the loss of zero crosses. This fault will also be the primary way to detect short circuit conditions.
Over excitation Shutdown – Over excitation is used to detect short circuit alternator faults.
Notes:
1 10 Amps ( x rated)
64 7/8/2014 Cummins Confidential
The alternator thermal damage curve provides the amount of 3-phase amperage (based on a multiplier of
the rated max amperage) that the alternator can withstand for a certain period of time before significant
deterioration in life starts to occur.
Basically, if you chart the current flow with respect to time, you’re OK as long as you never pass over the
red line. Once the PCC sees the current go over that red line (3 phase amps for a certain period of time) it
will disable excitation.
Note that x axis is current in multiples of rating, and y axis is time and both are logarithmic scales.
This graph shows typical protections for a typical
Protections – AmpSentry™ molded case circuit breaker, AmpSentry protection,
and a typical alternator thermal damage curve.
Typical Alternator
Thermal Damage
1
unnecessarily at high steady state current levels
TIME (SECONDS)
Typical Circuit
Breaker Protection (time greater than 10 seconds) and in instantaneous
conditions (time less than 0.05 seconds). Also, in
(blue)
0.1
0.05
between, it offers no protection; it will not trip until
1 3 10 100
the current draw is well beyond the alternator
thermal damage curve.
AMPS (TIMES RATED)
Since PCC monitors volts and amps in real time, it knows everything it needs to know to provide its own
overcurrent protection without the need of a physical circuit breaker. In addition, the PCC is not
influenced by ambient temperature conditions like a thermally operated circuit breaker would be.
The PCC with AmpSentry also provides better coordination (tripping the protection device closest to the
fault itself) because it does not have an instantaneous region (the big block regions on the curve).
Alternators do not need instantaneous regions; the reason that breakers have them is not to protect the
alternator but to protect the breaker itself.
Notes:
Over Speed Shutdown – Engine Over Speed default setting is 115% of the rated engine speed nominal.
Control includes time delays to prevent nuisance shutdown signals.
Low Lube Oil Pressure Warning/Shutdown - Level is preset (configurable with a PC based service tool) to
match the capabilities of the engine used. Control includes time delays to prevent nuisance
warning/shutdown signals.
High Engine Temperature Warning/Shutdown - Level is preset (configurable with PC based service tool)
to match the capabilities of the engine used. Control includes time delays to prevent nuisance
warning/shutdown signals.
Low Coolant Temperature Warning - Indicates that engine temperature may not be high enough for a 10-
second start or proper load pickup. Level is preset (configurable with a PC based service tool) to match
the capabilities of the engine used. Control includes time delays to prevent nuisance warning signals.
Low Battery Voltage Warning - Indicates battery charging system failure by continuously monitoring
battery voltage. Control includes time delays to prevent nuisance warning signals.
High Battery Voltage Warning – Indicates battery charging system is of higher level by continuously
monitoring battery voltage. Control includes time delays to prevent nuisance warning signals.
Weak Battery Voltage Warning - Control system will test the battery bank each time the generator set is
signaled to start, and indicate a warning if the generator set battery indicates impending failure. Control
includes time delays to prevent nuisance warning signals.
Fail to Start (Overcrank) Shutdown. – Control system runs out of crank cycles before the engine starts.
Fail to Crank Shutdown - Control has signaled starter to crank the engine but engine does not rotate.
Cranking Lockout - The control will not allow the starter to attempt to engage or to crank the engine
when the engine is rotating (when control senses the valid engine RPM above the noise threshold value.)
Sensor Failure Indication – Out of range high / low diagnostic logic is provided on the base control to
detect analog sensor or interconnecting wiring failures.
Customer Connections
The PowerCommand Control also has to interact
Data/Network
with the Customer’s equipment. Customer
Ready to Load interconnection can be thought of as another
Configurable Outputs subsystem of a PowerCommand Control.
Configurable Inputs
Remote Connections Customer Connections can be thought of as those
that are used by things that are outside of the
PCC Control Board
generator set. Often, these connections would be
needed to be made by the technician in the field
when the generator set is first installed on site.
67 7/8/2014 Cummins Confidential
Data/Network Connections
Often, a generator set needs to be able to communicate with other gensets, Building Management
Systems (BMS), or remote monitoring devices. This is done using network cable. This course is not going
to cover networking, but the connections for networking are made at the Customer Connection terminal
block. For example, a customer wants to know when the genset is running, and what the engine speed is.
Instead of wiring directly from the magnetic pickup and from the B+ relay, that information is broken
down by the PCC control, and sent as packets of information over the network. Depending on what
network protocol is used, there may be one or two pairs of data cable, as well as a shield wire.
Configurable Inputs/Outputs
In addition to all of the Inputs and Outputs that we have been talking about that the control uses to
control and protect the generator set, there are often additional inputs and outputs that can be
configured later to customer specifications
Remote E-Stop
In addition to the local Emergency Stop that is located near the HMI of the control, there can also be a
Remote E-Stop. This E-Stop is typically wired in series w/ the Local E-Stop so that either E-stop will shut
down the genset. Also, both have to be restored in order to start the genset again. The remote E-stop can
be located on the exterior of the generator set’s container, or any other location the customer wishes.
www.cummins.com/survey/servicetraining
Cummins Inc. | Page 53 of 163
Configurable Inputs
Configurable Input Power Command Controls can also accept
Configurable Inputs. This input is typically an
Customer input causes event to occur in PCC
(warning/shutdown/etc)
isolated ground (common) input. When common is
Active Open or Closed
applied to the configurable input, then that input
becomes active. That input can be configured to
TB
cause a warning or a shutdown of the generator set.
Cust.
Input Genset Control
Typical configurable inputs that can be used are:
COM
Low Fuel in the Day Tank, Low Coolant
Temperature, etc. These inputs would typically be
used by sensors or switches that are not standard
68 7/8/2014 Cummins Confidential on the generator set, but the customer would want
to be used to control and protect the generator set.
Configurable Outputs
Configurable Outputs Typically on a Power Command Control there are
small relays that can be programmed to activate
Event occurs in PCC causing configurable relay to
change states
when certain events are active.
The HMI 211 is the display that we will learn in the most depth here in Fundamentals of Power Command
Controls, but the principles of menu navigation, soft push buttons, hard pushbuttons and LED indicators
will carry through to most all of the Power Command Controls that Cummins has to offer.
The HMI 211 has many features that allow the technician to see what the control is doing, as well as input
information into the control to operate the generator set or change configuration.
Graphical Display
The graphical display is used to view all of the different menus of the control system, read fault codes,
and other information.
LED Indicators
The HMI display panel has 6 LED indicators.
• Not in Auto (Red) is lit when the control is not set in Auto Mode.
• Shutdown (Red) is lit when the control detects a shutdown condition. The genset cannot be
started when this lamp is lit. After the condition has been corrected, the lamp can be reset by
pressing the Off button.
• Warning (Amber) is lit whenever the control detects a warning condition. This lamp is
automatically shut off when the warning condition no longer exists.
• Remote Start (Green) is lit when the control is receiving a remote run signal.
• Auto (Green) is lit when the control is in Auto mode.
• Manual Run (Green) is lit when the genset is running after being started in Manual mode.
These six LED indicators are very standard, and will appear on most of the Power Command Controls to
annunciate the state of the generator sets.
The rear of the HMI 211 contains two connection
HMI 211 Rear points. These two connection points are essentially
identical. One of the connectors, typically J1,
connects to the PCC control board.
Notes:
All connectors use a tension or mechanical latch to hold the harness jack in place. All connectors are
keyed so the harness jack cannot easily be inserted incorrectly.
Pin 16
• 2 – PCCNet B signal (network)
TB1-3 PCCNet Shield / B+ return
TB1-4 Ready to Load 20ma Low Side relay driver
Configurable Outputs
Control includes two relay outputs rated at 2 amps. These outputs can be configured to activate on any
control warning or shutdown fault as well as ready to load, not in auto, common alarm, common warning,
and common shutdown.
Remote E-Stop
For operation of the genset, a short between TB1-15 and TB1-16 must be present. The control enters an
emergency stop mode when the short is removed. Before the genset can be restarted, the control must
be manually reset by re-applying the short and acknowledging the fault. The E-stop circuit contains two
parallel paths. One path is fed into the micro-processor for status processing. The second path is fed
directly into the relay drivers, disabling them when an E-stop is present.
Notes:
J20
J20 Genset Inputs and Outputs J20 is the connection to the PCC1302 board that has
PIN Signal Name
J20 - Genset Connections
Connect To
inputs and outputs for various items and drivers
J20-1
J20-2
Chassis Ground
J20-4 B+ Return
J20-7 B+ Return
J20-9 B+ Input
J20-10 B+ Input
J20-12 B+ Return
J20-13 Relay Coil B+ Supply FSO, Switched B+, Starter Relay Coils
J20-16 NA
J20-19 NA
J20-20 B+ Input
J20-21 B+ Input
J11-2
Oil Pressure Sender (Active) +5 V
ECMs.
Coolant Temperature Sender
J11-12
Return
Oil Pressure
Oil pressure can be sensed with either a 3-wire sender or a 2-wire switch. The sender provides an analog
(0-5VDC) signal to the PCC; the switch is either active or inactive depending on whether appropriate oil
pressure is available to engage the pressure switch. The oil pressure may be monitored by the ECM.
Mag Pickup
The magnetic pickup is used to sense engine speed, and is two-wire. The mag pickup may be monitored
by the ECM.
Glow Plug
This is another low side driver to control the glow plug relay, if the engine requires pre-heating.
Keyswitch
Similar to the Keyswitch in an automobile, this driver must be active in order for the ECM to turn on.
A PCC 1302 control board that is used to control an engine with an ECM will use this communication back-
bone to send information (such as the speed setpoint) to the ECM, and the ECM will send information to
the PCC (such as RPM).
J12
J12 Genset CT Connections J12 is the connection between the PCC1302 board
and the current transformers (CTs) that monitor the
current output of the generator. CTs are polarity
sensitive, and have a dot on one side of them which
must face the source (generator output). In that
sense, the secondaries (wires) are polarity sensitive
as well. Flipping the secondaries is the same as
physically installing the CT backwards.
J12 - Genset CT Connections
PIN Signal Name Connect to
J12-1 CT1 CT1 – X1
J12-2 CT2 CT2 – X1
J12-3 CT3 CT3 – X1
J12-4 CT1 Common CT1 – X2 / X3
J12-5 CT2 Common CT2 – X2 / X3
J12-6 CT3 Common CT3 – X2 / X3
J12 – Connections
• 1 – CT1, connected to CT1 – X1
• 2 – CT2, connected to CT2 – X1
• 3 – CT3, connected to CT3 – X1
• 4 – CT1 Common, connected to CT1 – X2/X3
• 5 – CT2 Common, connected to CT2 – X2/X3
• 6 – CT3 Common, connected to CT3 – X2/X3
Notes:
PIN
J22-1
Signal Name
L1
Connect To
J22-3
L2
L3
600 Vmax L2 Source
Connector
Signal Name Connect To
Pin
J18 J17
J17 J18
J17 is the output from the PCC1302 board to the J18 is the input from the voltage regulation power
alternator excitation system. supply. The PCC 1302 will operate in either a self-
excited (shunt excitation) mode or in PMG
J17 Connections excitation mode. J18 can receive input from either
• 1 – Field + supplies excitation positive to X+ the alternator output, or from phase 1 and 2 of a
(F1) PMG. There are three connector pins; however, only
• 2 – Field - supplies excitation negative to XX- two of them are used. The J18-1 and 2 inputs are
(F2) limited to a maximum input of 240 VAC.
J18 Connections
• 1 – PMG 1/ Shunt L1 (240 VAC max)
• 2 – PMG 2/ Shunt L2 (240 VAC max)
• 3 – N/A
Notes:
J25
J25 Display Connections J25 is the connection between the PCC1302 board
J25 - Display Connections
and the display. The display includes the HMI,
gauges, and E-Stop switch.
PIN Signal Name Connect To
J25 Connections
J25-2 Local E-Stop Normally closed local E-Stop switch
J25-9 B+ Return
J25-11 Auto
2 – PCCNet Data B
J1-2 RS485 (PCCNet) Data B Network Data B
3 – B+ Network Supply
J1-4 PCCNet System Wake Up
TB15 Connections
TB15 - Tools Interface Connections • 1 – Network Power Supply Return
• 2 – N/A
PIN Signal Name Connect to
TB15-1 Return Network Power Supply Return
• 3 – RS-485 Data A
TB15-2 N/A
TB15-3 RS - 485 Data A Network Data A
• 4 – RS-485 Data B
TB15-4 RS - 485 Data B Network Data B
TB15-5 PCCNet System wakeup
Notes:
Activity 4-1
Skills Exercise
Required Materials
• PC 1.X Service Manual w/ Drawings
• Highlighter
Using a highlighter or sticky notes, locate the following connection points to the PC1302 Control Board
1. TB 1
2. J20
3. J11
4. J12
5. J22
6. J17
7. J18
8. J25
9. J1 (HMI)
10. TB15
Using a highlighter find the circuit that the PCC uses to enage the following relays
1. Start Relay
2. Run Relay
3. Switched B+ Relay
Required Materials
• PCC 1302 Simulator Board
• HMI 211
• Common Connector Harness (for simulator)
• Universal Wedge Simulator
Connect the following connectors of the common connector harness to the PCC 1302 board. Use the
drawings in order to verify that all of the wiring is correct on the terminal blocks and connectors.
1. TB 1
2. J20
3. J11
4. J12
5. J22
6. J17
7. J18
8. J25
9. J1 (HMI)
If possible, find the same connectors on an actual generator set, including these other components:
1. Start Relay
2. Run Relay
3. Switched B+ Relay
4. Aux 104
Battery: 27.2VDC
Eng. Temp:73.8°F
Auto
REMOTE START
AUTO
The specific terminology of these menus can change
between different types of Power Command
Eng Hrs: 123.2 MANUAL RUN
Auto Man
Operator Menus
Operator Menus display to the technician many “Read Only” parameters. These can include, but are
obviously not limited to: Genset Voltage, Current, Engine Hours, Speed, Frequency, etc. Operator menus
basically tell the technician the status of the various sensors of the Power Command Control. The
operator menus also allow the technician to operate the generator set by selecting different modes of
operation.
Setup Menus
Setup Menus allow the technician to configure some of the parameters as to how the generator set
operates. These menus are often password protected, so that the customer, or any other untrained
personnel do not have access to them. Setup menus often also are hidden, in that they require a specific
button press combination to access. Setup menu parameters can include: Frequency and voltage
protection thresholds, timers, configurable inputs and outputs, alternator voltage, etc.
Some Power Command Controls have even more protection to some of the Setup Menus that drastically
change the application of the genset.
Notes:
Graphical
Display LED Indicators
This is the common HMI display of the Power Command 1302. The PCC 1302 control board can use two
types of HMIs, the HMI 211 and the HMI 220. When the HMI 211 is used, the collective generator set
control is called the “PC1.1”. When the HMI 220 is used, the collective generator set control is called the
“PC1.2”. This naming convention is used for the 2300 control and 3300 control as well.
The HMI 211 is the display that we will learn in the most depth here in Fundamentals of Power Command
Controls, but the principles of menu navigation, soft push buttons, hard pushbuttons and LED indicators
will carry through to most all of the Power Command Controls that Cummins has to offer.
The HMI 211 has many features that allow the technician to see what the control is doing, as well as input
information into the control to operate the generator set or change configuration.
Graphical Display
The graphical display is used to view all of the different menus of the control system, read fault codes,
and other information.
Off Button
This is also a “hard” pushbutton. Press this button to switch to the off mode. If the genset is running, the
genset will immediately begin its shut-down sequence. This button is also used to acknowledge warning
and shutdown messages after a fault has been corrected.
LED Indicators
The HMI display panel has 6 LED indicators.
• Not in Auto (Red) is lit when the control is not set in Auto Mode.
• Shutdown (Red) is lit when the control detects a shutdown condition. The genset cannot be
started when this lamp is lit. After the condition has been corrected, the lamp can be reset by
pressing the Off button.
• Warning (Amber) is lit whenever the control detects a warning condition. This lamp is
automatically shut off when the warning condition no longer exists.
• Remote Start (Green) is lit when the control is receiving a remote run signal.
• Auto (Green) is lit when the control is in Auto mode.
• Manual Run (Green) is lit when the genset is running after being started in Manual mode.
Operating Modes
The PCC 1302 control is operated by the HMI 211
Off Mode
front panel buttons. There are 5 modes used
Manual/Run Mode regularly by genset operators:
Auto Mode • Off Mode
• Manual/Run Mode
• Auto Mode
• Sleep Mode
• Setup Mode
PCC 2100
HMI 211
Off Mode
The Off Mode is when the generator set is not running, and is not in standby mode. When in Off Mode,
the control does not allow the generator set to start – either by pressing the start button or by receiving a
remote start signal. If the generator set is already running and the technician places the genset into “Off”
mode, the control initiates a normal shutdown sequence.
Manual/Run Mode
The Manual Mode is the mode the operator will select if he/she would like to operate the genset
manually by input to the HMI. In Manual Mode, the remote start signal is ignored. Once in manual mode,
the operator can select Run Mode, and the generator set will start and will continue to run until the
control is put into Off mode.
Auto Mode
When the generator set is in Auto mode, the generator set can be started with a remote signal only.
When in Auto mode, the generator set can start at any time without any operator input (or warning). If
the generator set is running in Auto Mode, and the Off button is pressed or the remote start signal is
removed, the control initiates a normal shutdown sequence.
Auto
REMOTE START
AUTO
MANUAL RUN
between TB15-1 and TB15-5. The control will not
enter Sleep mode if there are any active,
unacknowledged faults or if the control is in Manual
Run mode.
If the second Man button is not pressed within ten seconds of entering Manual mode, the control will
revert to Stop mode.
For older versions of Power Command Controls, such as a PCC 2100 (shown), to put the control into
Manual Mode, you would rotate the O/Man/Auto switch to the Manual Position. This would put the
genset into Manual mode, but not start the genset. To initiate a start sequence, the technician would
then have to press the Manual Run/Stop pushbutton, which will initiate a normal start sequence. Pressing
the Manual Run/Stop pushbutton while the genset is running will begin a normal shut down sequence,
including any cool down timers required.
Pressing the Auto soft buttons while the control is in
Auto Mode Off mode will put the PCC 1302 control in Auto
Auto
mode. In Auto mode, the genset starting and
stopping is controlled automatically by a remote run
signal.
Note: The genset can start at any time while in Auto mode. Never service the genset while it is in Auto
mode. Accidental starting of the genset during troubleshooting can cause severe personal injury or death.
Disable the genset before troubleshooting.
Operator Menus
Engine Status Alternator Status Alternator L-L
Battery: 27.2VDC Power: 15.2 kVA L1-L2: 400 ͠V
Eng. Temp:73.8°F Freq.: 50.1 Hz L2-L3: 398 ͠V
Speed: 1500 RPM L3-L1: 401 ͠V
Eng Hrs: 123.2
Auto Man Auto Man Auto Man
By pressing the soft buttons below the arrow symbols, you can navigate the Operator Menus. The
Operator Menus show read-only data, you cannot change any of the software settings here.
Required Materials
• PC 1.1 Simulator Kit
Instructions:
1. Power up the simulator kit and place in “Off” mode
a. Describe the LEDs on the HMI
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
3. Start the PC1.1 simulator in “Auto” mode using the Remote Start input on the wedge
a. Describe the LEDs on the HMI
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
4. With the simulator running, flip the “Mag Pickup Failure” switch on the wedge
a. Describe the LEDs on the HMI as well as the description on the graphical display
____________________________________________________________________________
____________________________________________________________________________
b. Successfully Reset the fault
Activity 5-2
Skills Exercise
Required Materials
• PC 1.1 Simulator Kit
1. Start the generator set simulator in either “Manual” or “Auto” mode
2. Navigate the Operator Menus of the PC1.1 control and find the following values
Battery: 27.2VDC
Eng. Temp:73.8°F
Auto
REMOTE START
AUTO
The Service Menus are hidden from casual view with
a two-button combination. Press and hold the “Up
Eng Hrs: 123.2 MANUAL RUN
Auto Man
Volts AC
GENSET
:400 the “+” or “-” pushbuttons to increase or decrease
the value. Push the Arrow pushbutton in order to
Hertz :50
No of Phases :3
Phase : Wye
SAVE - + change which parameter you are adjusting. Press
the “Save” pushbutton in order to save your
changes.
Next page
The control system supports automatic engine starting. Primary and backup start disconnects are
achieved by one of three methods; magnetic pickup, battery charging alternator feedback, or main
alternator excitation frequency. When the engine is cranking and begins to run, the PCC control will see
the RPM increase. When the RPM increases to above the start disconnect speed, the PCC deactivates the
start relay, which disengages the starter from the flywheel teeth of the engine.
In general, K1 increases and K2 decreases in value with increasing generator size, but can vary in different
applications.
Notes:
Fueling will be initially set to the Initial Crank Fueling Duty Cycle value and will remain at that value for the
Initial Crank Fueling Period. After this period expires, the fuel command will be ramped at the Crank
Fueling Ramp Rate until the Maximum Crank Fueling limit is reached.
Notes:
Genset Service – Genset pages 11, 12 Genset Service - Genset Submenu, Screen 11
ELECT. GOVERNOR
Once the Governor Enable Engine Speed has been
Gain: 100%
Int: 100%
reached, now the governor is enabled and the PCC
D: 100% enters a closed loop regulation of engine speed.
Adjust ELECT. GOVERNOR
Crank Exit
Fuel DC: 25.0%
Dither Factor: 15 Once again, this is a PID loop that is controlled by a
Proportional, an Integral, and a Derivative
Ramp Time: 0.25
Adjust
• Proportional Gain - The value of GK1 should be adjusted to meet the specification for percent off
rated voltage during a load acceptance, to prevent large voltage overshoots during offloads, and
during engine/alternator startup.
• Integral Gain - The value of GK2 should be adjusted to control the recovery characteristics of the
engine during large load acceptance and rejection transients.
• Dampening – The Dampening factor is used to set basic steady state stability of the engine. Tuning
the Damping factor is an iterative process started by finding the engine load level which produces the
worst steady state engine performance (note: GK1 and GK2 may have to be adjusted first to allow the
engine to be transitioned smoothly into this) and adjusting the dampening factor until the best
performance is observed.
Next page
Notes:
inputs.
Select:
Active Close
Adjust
FAULT INPUT 2
Active State
Select: Each configurable input is essentially the
Active Open
Adjust combination of two wiring points. One is a common,
which is an electrically isolated ground being sent
out to the customer’s piece of equipment or switch.
The “Input” of the configurable input is another
To Inputs 3, 4
point that this common will be inputted back into
113 7/9/2014 Cummins Confidential the control.
That means that there are two states of a configurable input, one where the common is present and one
where the common is not present at the input point.
• Active State Select – Active Open or Active Closed. Select Active Open if the customer wants the
configurable input to be active (and cause a fault, etc.). Active Open means that the configurable fault
will be active when the common is not returned to the input. Active Closed means that the
configurable fault will be active when the common is returned to the input.
Notes:
• Customer Output 1, 2, Map – select the fault code that the customer would like to monitor using a
configurable customer output.
By default, the two configurable relays on the PC 1302 are set to:
• 1540 – Common Warning
• 1541 – Common Shutdown
If the PCC is configured this way, any time there is a warning condition on the PCC, Configurable Output 1
will be active. Also, any time that there is a shutdown condition on the PCC, Configurable Output 2 will be
active.
Now we are at the end of the Genset Service – Customer I/O Submenu.
Press the “Previous Menu” pushbutton on the HMI to return to the previous menu.
Notes:
116 7/9/2014 Cummins Confidential Voltage Calibration for Regulation should be done
before Voltage Calibration for Display.
• Reg Volt Adj - The effect of this trim is inverse on the regulated voltage. Increasing the percentage will
decrease the regulated voltage. Decreasing the percentage will increase the regulated voltage. Adjust
the trim so regulated voltage matches the desired nominal voltage measured with a known calibrated
voltage meter.
For example, the generator set you are going to calibrate is set to produce 3 phase 208 VAC. However, a
calibrated meter reads that it is only producing 206 VAC. The Nominal voltage is set to 208 VAC, and there
are no voltage adjustment trims, and the HMI displays that the generator set is producing 208 VAC. Since
the calibrated meter reads differently, you would change the Voltage Measurement for Regulation trim
until the calibrated meter reads that 208 VAC is being produced.
Notes:
For example, your 3 phase, 208 VAC generator set is producing voltage and frequency and providing load
to a customer. The HMI displays that it is supplying 340 Amps on L1, but a calibrated meter reads that it is
actually supplying 345 Amps on L1. Now, you would calibrate the Current Measurement for Display in
order for the generator set’s HMI to display the accurate reading. Current Measurement for Display does
not change the output of the alternator at all, just the reading on the HMI.
Now we are at the end of the Genset Service – Meter Calibration Submenu.
Press the “Previous Menu” pushbutton on the HMI to return to the previous menu.
Notes:
The most common Cummins annunciator has four custom relays that can be controlled by the PCC1302.
When a specified event becomes active, a message can be sent by the 1302 to the annunciator to turn the
relay on or off. One event per relay is allowed.
There are seven Annunciator submenus that can be used to define three Annunciator Fault Text messages
and four Annunciator Output Maps. You will be able to define three possible customer defined fault
conditions that can be shown on the HMI 211 display. The Annunciator fault text message menus are
used to enter an event type and description.
• Type (Warning, shutdown or event)
• Fault Number (0-655235)
• Description (32 characters max)
Press the “Previous Menu” pushbutton on the HMI to return to the previous menu.
Notes:
• MPU Enable: The Magnetic Pickup Unit measures the RPM of the engine by counting the flywheel
teeth as they go by when the engine is running. Set to Yes if the PCC uses a mag pickup to measure
RPM.
• Flywheel Teeth: This is the number of teeth along the flywheel. The starter motor uses these gear
teeth to rotate the engine at start up, but the MPU also uses them to determine engine speed.
• RPM/Hz Ratio: This is the ratio for nominal engine speed to nominal Hz. For an 1800 RPM 4-pole
alternator producing 60 Hz this ratio will be 30.
Genset Setup - Genset Submenu, Screen 2
• Excitation Source: This is the source of power that the PCC’s AVR circuitry will get in order to regulate
and send back out to the exciter stator for voltage regulation. This can either be “Shunt” which means
self-excited, or “PMG” which means separately excited.
• Excitation/Line Freq. Gain: The excitation, line frequency gain is the multiplier of alternator line
frequency to excitation system frequency.
Notes:
Press the “Previous Menu” pushbutton on the HMI to return to the previous menu.
Notes:
VOLT. PROTECTION The Protection Menu is where you will select all of
the set points for voltage and frequency shutdown
High AC Voltage
Threshold: 115 %
Now we are at the end of the Genset Setup – Voltage Protection Submenu.
Press the “Previous Menu” pushbutton on the HMI to return to the previous menu.
Notes:
fault on Overcurrent.
Now we are at the end of the Genset Setup – Current Protection Submenu.
Press the “Previous Menu” pushbutton on the HMI to return to the previous menu.
By pressing (4) on the Genset Setup Submenu, you
Genset Setup – Engine Protection (4) see the Engine Protection Menu.
133 7/9/2014 Cummins Confidential The Engine Protection Menu consists of 8 screens.
Notes:
Each threshold is associated with the RPM/Hz ratio defined earlier. For a 60 Hz alternator that is running
at 1800 RPM (4-pole), the RPM/Hz ratio is 30. The threshold that the PCC would look at to fault on
Overspeed would be the Overspeed threshold defined at 30, not 20 or 60.
Genset Setup – Eng. Protection Submenu, Screen 3
Genset Setup – Eng. Protection page 3, 4 • Speed/Frequency Fault Threshold – The PCC
ENG. PROTECTION
compares the engine speed (as determined
Speed/Freq Fault
Threshold: 2.0 Hz directly by the MPU) and the engine speed (as
Speed/Freq Fault
Time Delay: 1.5 s indirectly determined by the alternator
frequency).
Adjust
LOP SETUP
LOP Warning
Threshold: 40psi
LOP Warning If they do not match within this defined threshold,
the PCC will produce a Speed/Frequency mismatch
Time Delay: 5 sec
Adjust
Now we are at the end of the Setup Menus – Genset Setup Menus.
Press the “Previous Menu” pushbutton on the HMI and return to the all the way to the main Service
Menus
Notes:
Within the History/About submenu, you are able to view the following data:
• Number of Starts
• Control Hours
• Engine (run) Hours
• Model Number
• Serial Number
• Control Number
• kVA Rating
• Control Part number
• Software Part Number
• Software Version
• Display Part Number
• Display Software Version
• Screen Part number
• Screen Version
History/About - Screen 1
History/About page 1, 2 • Starts – This is a read-only parameter that tells
HISTORY
the operator the number of starts the generator
Starts:
Hours:
592
50.4 starts has made in its lifetime
Control
Hours: 347.5 • Hours – This is a read-only parameter that tells
the operator the amount of hours the generator
Adjust
ABOUT GENSET
Model Number:
Control : set’s engine has in its lifetime
Adjust • Control Hours – This is a read-only parameter
that tells the operator the amount of hours the
PowerCommand Control has been awake in its
Next page lifetime
History/About - Screen 2
• Model Number – This parameter tells the operator the model number of the generator set the
PowerCommand Control is controlling
• Control – This is a parameter that tells the operator the model number of the PCC itself
History/About page 3, 4
ABOUT GENSET
KVA (Standby) History/About - Screen 3
Rating: 25.0 kVA
• kVA (Standby) Rating – This is a read-only
parameter that tells you both what the
Adjust
ABOUT CONTROL
P/N:
S/N:
SW P/N: application of the generator set is (either prime
or standby) and what the kVA rating of the
SW Version:
Adjust
Next page
History/About - Screen 4
• P/N – This is the Part Number of the control board itself
• S/N – This is the Serial Number of that specific control board
• SW P/N – This is the Part number of the software calibration file that is actually loaded onto the
control
• SW Version – This is the Version Number of the software calibration file that is actually loaded onto
the control
These parameters will be helpful when getting help from factory service, as they will need to know what
version of the software you are running on the control.
History/About - Screen 3
History/About page 5 • SW P/N – This is the software part number that
is loaded onto the HMI that the
PowerCommand Control is using
• SCRNE Ver – This is the software version that is
loaded onto the HMI that the PowerCommand
Adjust
ABOUT DISPLAY
SW P/N: 3266811
SCRNE VER:
SCRN VER:
2.26
7.10 Control is using
• SCRN Ver – This is the hardware version of the
DISP DEVICE ID: 68
Adjust
HMI
• DISP DEVICE ID – This number is used by the
InPower Software tool in order to correctly
connect to the display.
141 7/9/2014 Cummins Confidential
These parameters will be helpful when getting help from factory service, as they will need to know what
version of the software you are running on the display.
Press the “Previous Menu” pushbutton on the HMI to return to the main Service Menus
Notes:
Notes:
SERVICE MENU
4) Fault History REMOTE START
The clock operates in 12 hour format with support for AM/PM. The RTC also supports Daylight Savings
Time (DST), The DST logic adds the DST Adjustment time to the current time when the current time is
equal to the DST Start Time. The DST logic subtracts the DST Adjustment time from the current time when
the current time is equal to the DST End Time. To enable DST, the trim Daylight Savings Time Enable
needs to be set to Enabled.
The exercise scheduler is a feature that automatically starts the genset for exercise. This feature prevents
common problems which result from mechanical equipment being not in operation for long periods of
time. In order for the automatic exerciser to work, the control system needs to be in ‘Auto’ mode, the RTC
needs to be set, and the Exercise Scheduler Program needs to be set to Enable.
Notes:
Clock/Exerciser - Screen 1
Clock/Exerciser page 1, 2 • Date – Enter the current date
TIME SETUP
• Time – Enter the current time
Date: ##:##:## These two parameters together make up the Real
mm:dd:yy
Time: ##:## AM Time Clock. This clock is used for the exercise
scheduler feature.
Adjust
Daylight Saving
Adjust
Saving Time:
Enabled
Clock/Exerciser - Screen 2
Adjust: 60 mins
Adjust
Notes:
Clock/Exerciser - Screen 6
• Exercise Duration – Enter the length of time you would like the exercise period to run.
The PCC1302 can be programmed to run only 1 program, which is a repeating event. Furthermore, the
program can be programmed to exercise the genset at rated condition and at ‘No Load’ condition. No
exceptions can be set in PCC1302.
However, other PowerCommand Control types have the capabilities of running multiple different exercise
schedules with numerous exceptions to when it should/should not exercise.
Press the “Previous Menu” pushbutton on the HMI to return to the main Service Menus
By pressing (9) on the First Service Menu, you see
Volt & Hertz Adjust [9] the Volt & Hertz Adjustment Submenu.
Activity 6-1
Skills Exercise
Required Materials
• PC 1.1 Simulator Kit
Using the Setup Menus, configure the PowerCommand Control to the specific application and customer
requests below.
1. Adjust the PCC to have two 10 second crank attempts with 10 seconds of rest between them
before faulting out on fail to start.
2. Add a start delay of 2 seconds and a stop delay of 1 second
3. Configure Configurable Input #1 to shut down the genset when the circuit is closed at the
terminal block
4. Configure Configurable Output #1 to become active when Configurable Input #1 is active
5. Change the Low Battery fault threshold to 22 V
6. Change the Low Coolant Temperature Threshold to 100ºF
7. Set the real-time clock to the correct date and time, and set an exercise schedule to run every
Monday at 8:12AM for 15 minutes
Demonstrate to the instructor that all configurations have been successfully programmed and saved
into your simulator.
L1 L2 L3 N
Field AVR
PMG Amp
Gov.
Actuator
Amp
MPU
Engine
Sensors
and/or
ECM
HMI
153 7/9/2014 Cummins Confidential
Next we will go through an entire starting and stopping sequence and highlight how the subsystems work
together. We will be highlighting and colorizing this visual as subsystems are added to the running system.
Dashboard
The first step of the start sequence is to select which
Stop/Manual/Auto Mode RPM VAC
mode the generator set control is in. This will
Starter FSO Customer change how the generator set will start.
K1 K2
Input Alternator With the HMI, the operator selects Stop, Manual, or
L1 L2 L3 N Auto. The HMI takes operator input and transmits
Field AVR this information to the control. The control then
PMG Amp
accepts this information, and returns information to
Gov. the HMI.
• Off Mode
Actuator
Amp
• Man Mode
MPU
Engine
Sensors
and/or • Auto Mode
ECM
HMI
154 7/9/2014 Cummins Confidential
In Off Mode, the generator cannot be started. The HMI will display the Red “Not in Auto” LED, since the
PCC is not in Auto Mode.
In Man Mode, the generator is waiting for a Manual Run signal. This manual run signal must come from
the operator. The HMI will display the Red “Not in Auto” LED, since the PCC is not in Auto Mode.
In Auto Mode, the generator is waiting for a Remote Start signal. This remote start signal is usually comes
from the customer’s equipment that would be starting the generator set automatically, such as a Building
Management System or Automatic Transfer Switch. The HMI will not display the Red “Not in Auto” LED,
but will display the Green “Auto” LED, since the PCC is in Auto Mode.
Remember that all of the decision making of which LEDs to display is being made by the PCC control
board, not the HMI. The HMI is simply the operator’s window into the control.
Notes:
Manual Idle
In this mode, the operator him/herself puts the generator set into Manual Mode and selects Manual Run.
The genset starts but only ramps up to idle speed in order to warm up. After the idle period is over, or
after the operator selects rated speed, the generator set will then ramp up to rated speed.
Automatic Emergency
In this mode, the PCC control is left in Auto, and receives a remote start signal. The generator set then
begins its normal starting sequence and ramps up to rated speed as soon as possible to assume an
electrical load immediately.
Automatic Non-Emergency.
In this mode, the PCC control is left in Auto, and receives a remote start signal. The generator set begins
its normal starting sequence, however there may be several time delays, including running at idle to warm
up before assuming load.
Notes:
HMI
156 7/9/2014 Cummins Confidential
Dashboard
K1 K2
Input Alternator Once the start signal has been received, the PCC
L1 L2 L3 N may not begin physically cranking the engine
Field AVR because of some pre-start timers.
PMG Amp
HMI
157 7/9/2014 Cummins Confidential
Preheat
Another pre-start timer can be used on some smaller diesel powered generator sets that employ Glow
plugs. Glow plug is used as a Cold starting aid. Glow plugs heat up the air going in for combustion for
Diesel Engine. Glow plugs are used to improve the starting ability of engines and to reduce the white
smoke during cold start. The Preheat timer will enable the glow plugs for a configurable amount of time
before the engine starts cranking.
Dashboard
When the pre-start timers have been exhausted, the
Start Relay Output RPM VAC
PCC control is ready to begin cranking the engine.
Starter FSO Customer
To do this, it activates the Start Relay output.
Input Alternator
K1 K2
HMI
158 7/9/2014 Cummins Confidential
Notes:
proper feedback.
MPU
Engine
Sensors
and/or
ECM
HMI
159 7/9/2014 Cummins Confidential
Dashboard
Once the PCC senses that the engine is cranking, it
Run Signal RPM VAC
will reach a speed to begin fueling. The PCC will
Starter FSO Customer
enable the Run output, which will activate the Run
K1 K2
Input Alternator relay.
L1 L2 L3 N
Field AVR This relay will send battery power to the Fuel
PMG Amp
Shutoff Valve, which opens and sends fuel to the
Gov. intake of the fuel system.
Actuator
Amp
MPU
Engine
Sensors
or
ECM
HMI
160 7/9/2014 Cummins Confidential
Notes:
If the engine does not begin to run, the PCC will not
Cycle Cranking just keep cranking and fueling until the battery is
Crank Cycles
dead. The Power Command has parameters built in
to control the starting. One of these is called Cycle
Cranking.
RPM
A typical configuration will be 3 crank cycles, with a crank period of 15 seconds, and rest period of 15
seconds. Control includes starter protection algorithms to prevent the operator from specifying a starting
sequence that might be damaging.
If the engine does not begin to run within 15 seconds of cranking/fueling, the control will disengage the
crank/run outputs and rest for 15 seconds. The sequence will repeat until the engine starts or the crank
periods have been exhausted.
The fuel from the FSO will eventually need to be
Initial Fueling controlled by an electronic governor. Either the PCC
or the ECM will control the electronic governor with
Governor Enable
Speed is Reached
Crank
DC
pulse width signals.
Ramp Rate
Governor
PID Loop
Fueling will be initially set to the Initial Crank Fueling
Governor Duty Cycle
time
Time On Time Off
By pulsing the DC signal off and on very rapidly, the PCC or ECM can control the fuel rate very closely,
since the short pulses of DC power trying to open the valve will balance the spring force trying to close the
valve.
The more time “On” the valve is in relation to the time “Off”, the farther open the valve will remain, and
more fuel will enter the intake.
The ratio of time ON to total time is called the Duty Cycle, and it is represented as a percentage value.
For example, if the governor duty cycle is 56%, that means that the time On in relation to the time
ON+OFF = 56%.
Primary Start Disconnect is a configurable
Start Disconnect parameter that defines the first way that the PCC
control will disengage the starter. This is usually
Primary Start Disconnect (Engine Inputs)
from an input that senses engine speed directly
Secondary Start Disconnect (Alternator Inputs)
from the engine.
Dashboard
When the PCC enables the Run relay output, the
Start Disconnect Inputs RPM VAC
engine should fire and begin speeding up. At some
Starter FSO Customer
point, the starter is no longer needed. At a certain
K1 K2
Input Alternator point, the PCC will disable the Start output, and the
L1 L2 L3 N engine will be running on fuel/air/ignition alone.
Field AVR
PMG Amp
This point is known as the start disconnect speed.
Gov. The PCC can use a number of inputs to determine
start disconnect, and will employ other inputs as
Actuator
Amp
Even though the PCC is not “trying” to create voltage yet since the generator is not quite yet running, just
the physics of spinning a rotor inside of a stator will develop residual voltage.
Once the primary or secondary start disconnect speeds have been reached, the PCC disables the start
relay output, and the starter solenoid will disengage the starter from the flywheel teeth.
Dashboard
As the engine ramps up to speed during the Initial
Governor Enable RPM VAC
fueling stage, where the PCC isn’t necessarily
Starter FSO Customer
controlling the governor output, just ramping up
K1 K2
Input Alternator fueling, the engine speed will reach a point where
L1 L2 L3 N the Governor Algorithm kicks in.
Field AVR
PMG Amp
When the Governor Enable Engine Speed is reached
Gov. the governor is enabled, the speed setpoint is set to
the sensed engine speed value at this point, and the
Actuator
Amp
The governor ramp time is the time between the engine reaching Governor Enable Engine Speed and
rated (nominal) engine speed. This is a configurable setpoint.
The governor control algorithm was discussed earlier. The governor control feature of the PCC uses a
closed loop PID control algorithm, and allows field tuning of the coefficients. These Coefficients determine
how fast/aggressive the governor will react to changes in engine speed.
Notes:
The output signals from the PCC will usually have to go through some an amplifier. This is because the
PCC control board does not have the current capacity to operate the governor actuator. The PWM signal
is sent to the governor amplifier, which amplifies the signal (or in some cases operates like a “gate” to
mimic a typical PWM signal) to operate the governor actuator.
Dashboard
Once the engine is running at rated speed, the
Field Enable RPM VAC
Automatic Voltage Regulator (AVR) feature of the
Starter FSO Customer
PCC will also bring the alternator voltage up to
K1 K2
Input Alternator rated. This process is similar (and in most cases
Voltage Sensing
L1 L2 L3 N happening simultaneously) to the engine governor
Field AVR control.
PMG Amp Enable
Gov.
Actuator
Amp
MPU
Engine
Sensors
or
ECM
The PWM command to the field coil will be stepped through an AVR Boot Table until the sensed voltage
goes above the value of the AVR Boot Threshold trim and if AVR feature is enabled.
The purpose of the AVR Boot Table is to aid alternator startup whilst preventing overvoltage conditions.
The value of the AVR Boot Table and the AVR Boot Threshold can be set to bring the voltage up both as
quickly and as smoothly as possible, but should already be set in the calibration to their ideal values. The
AVR Boot Table has different values depending on value of the Excitation Source trim.
Essentially, as the alternator is starting up, the excitation is controlled not by an algorithm but by a look
up table.
Notes:
Dashboard
When the AVR startup has been reached, the
Automatic Voltage Regulation RPM VAC
voltage regulation is turned over to the Automatic
Starter FSO Customer
Voltage Regulation algorithm of the PCC 1302.
Input Alternator
K1 K2
Voltage Sensing
L1 L2 L3 N The Automatic Voltage Regulation feature of the
Field AVR PCC uses a closed loop PID control algorithm, and
PMG Amp Control allows field tuning of the coefficients. These
Gov. Coefficients determine how fast/aggressive the AVR
will react to changes in output voltage. The PCC
Actuator
Amp
In some types of PowerCommand Controls, however, just because they are shutdown faults does not
mean that the generator set has to “shut down” immediately. Often, in order to both protect the
alternator and the engine, the PCC will actually open the electrically controlled breaker and allow the
engine to cool down under no load conditions. This prevents damage to the engine and the alternator.
The PCC 1302 has no breaker control, however and will simply shut down immediately.
Over current Warning/Shutdown – Shutdown set to be below alternator damage curve up until maximal
measureable point. Currents above the maximal measureable point shutdown after the HCT Shutdown
Time Delay. Warning level set to half of the shutdown threshold.
Under/Over Frequency - Under frequency default to - 6Hz of the 50 Hz / 60 Hz frequency for 10 seconds
time delays. Over frequency default to + 6Hz of the 50 Hz / 60 Hz frequency for 10 seconds time delays.
Loss Of Sensing AC Voltage Shutdown – Loss of sensing AC voltage detects the loss of voltage sensing or
senses the loss of zero crosses. This fault will also be the primary way to detect short circuit conditions.
Dashboard
While the generator set is running, it is the duty of
Engine Protection RPM VAC
the PowerCommand Control to protect the engine
Starter FSO Customer
from conditions that may be harmful. These
K1 K2
Input Alternator conditions may just be warnings to the operator
L1 L2 L3 N that some operating conditions are outside of an
Field AVR acceptable threshold and maintenance/repairs must
PMG Amp
be done to mitigate them. Others may be more
Gov. urgent, and will force a shutdown of the generator
set altogether.
Actuator
Amp
MPU
Engine
Sensors
or Here are some examples of Engine Protection
ECM
Faults:
171 7/9/2014 Cummins Confidential
Over Speed Shutdown – Engine Over Speed default setting is 115% of the rated engine speed nominal.
Control includes time delays to prevent nuisance shutdown signals.
Low Lube Oil Pressure Warning/Shutdown - Level is preset (configurable with a PC based service tool) to
match the capabilities of the engine used. Control includes time delays to prevent nuisance
warning/shutdown signals.
High Engine Temperature Warning/Shutdown - Level is preset (configurable with PC based service tool)
to match the capabilities of the engine used. Control includes time delays to prevent nuisance
warning/shutdown signals.
Low Coolant Temperature Warning - Indicates that engine temperature may not be high enough for a 10-
second start or proper load pickup. Level is preset (configurable with a PC based service tool) to match
the capabilities of the engine used. Control includes time delays to prevent nuisance warning signals.
Low Battery Voltage Warning - Indicates battery charging system failure by continuously monitoring
battery voltage. Control includes time delays to prevent nuisance warning signals.
High Battery Voltage Warning – Indicates battery charging system is of higher level by continuously
monitoring battery voltage. Control includes time delays to prevent nuisance warning signals.
Weak Battery Voltage Warning - Control system will test the battery bank each time the generator set is
signaled to start, and indicate a warning if the generator set battery indicates impending failure. Control
includes time delays to prevent nuisance warning signals.
Fail to Start (Overcrank) Shutdown. – Control system runs out of crank cycles before the engine starts.
Fail to Crank Shutdown - Control has signaled starter to crank the engine but engine does not rotate.
Cranking Lockout - The control will not allow the starter to attempt to engage or to crank the engine
when the engine is rotating (when control senses the valid engine RPM above the noise threshold value.)
Sensor Failure Indication – Out of range high / low diagnostic logic is provided on the base control to
detect analog sensor or interconnecting wiring failures.
being opened.
MPU
Engine
Sensors
or
ECM
Dashboard
In addition to the protection shut downs, the
Stop Signal Input RPM VAC
generator set will eventually need to shut down
Starter FSO Customer naturally. Shutting the genset down can be done in
K1 K2
Input
(Remote Start
Alternator multiple ways, depending on the start type.
Remote E-Stop) L1 L2 L3 N
Manual Stop
Pressing the manual stop button on the HMI or Operator panel will initiate the shutdown sequence of a
PowerCommand Control started in either Auto or Manual.
It should be noted that if the generator set is shut down properly in Auto Mode (that is, the remote start
command is removed), the PCC will remain in Auto Mode. If the generator set is shut down by an
Emergency Stop, or by a Manual Stop command, the generator set will shut down and enter Off Mode.
Notes:
Dashboard
Similar to the Time Delay Start, there is a
Time Delay Stop RPM VAC
configurable time delay for a stop command before
Starter FSO Customer the PCC will initiate a shutdown sequence. This time
K1 K2
Input Alternator delay is configurable between 0 and 600 seconds
L1 L2 L3 N (default is 0).
Field AVR
PMG Amp Control Time Delay to Stop does not apply to Emergency
Gov. Stops! Emergency Stops, remote and local, will shut
down the generator set immediately.
Actuator
Amp
MPU
Engine
Sensors
or
ECM
HMI
174 7/9/2014 Cummins Confidential
Dashboard
In some types of PowerCommand Controls there are
Cooldown Procedures RPM VAC
built in cool-down procedures that can either be
Starter FSO Customer
configured, or are built in with algorithms.
Input Alternator
K1 K2
There are some types of PowerCommand Controls, however, that do not have this built in functionality
and when the Time Delay to Stop timer runs out, the generator set is put in Off Mode and shuts down
immediately.
Notes:
Depending on the type of PowerCommand Control and its application, there may be more or less, but
fundamentally to shut down a genset:
• The PCC control will disable the Governor Actuator by stopping sending PWM signals to the
Governor Output Module. This will cut fuel off from the engine.
• The PCC control will disable the FSO valve which will stop any more fuel from entering the system.
• The PCC control will disable excitation to the AVR feature
Once shut down, the generator set will remain in “Off” mode if it was shut down with a Manual Off
command. If the generator was stopped in Auto Mode by removing the remote start commands, it will
remain in Auto Mode.
Notes:
Activity 7-1
Skills Exercise
Sequence of Operations Discovery
Required Materials
• PC 1.1 Simulator Kit or running generator set
Instructions:
1. Safely disable a component (listed) of either your generator set simulator or running generator
set.
2. Attempt to start the simulator or generator set either manally or automatically
3. Observe what happens, and answer the questions below about each start attempt
3. Describe the LEDs and fault condition on the HMI (if applicable)
3. Describe the LEDs and fault condition on the HMI (if applicable)
3. Describe the LEDs and fault condition on the HMI (if applicable)
3. Describe the LEDs and fault condition on the HMI (if applicable)
3. Describe the LEDs and fault condition on the HMI (if applicable)
3. Describe the LEDs and fault condition on the HMI (if applicable)
3. Describe the LEDs and fault condition on the HMI (if applicable)
InPower ONAN
For Consumer Controls Customers only. InPower
Onan cannot be used to connect to commercial
PowerCommand genset controls.
InPower Lite
InPower Lite has the ability to connect to all
InPower capable devices and do everything that
InPower Pro can do, except for initial calibration or
update calibration of devices.
InPower Pro
InPower Pro has the capacity to connect to all InPower capable devices, and has full authority to perform
initial calibration and update calibration of devices.
Note that previously, InPower ATS was produced for Wingoal (a Cummins Automatic Transfer Switch
OEM), but that product has since been discontinued.
InPower is used in both commercial and consumer
Devices Supported Cummins products. The following devices are
capable of being calibrated/adjusted via InPower.
InPower Pro has the capacity to connect to all these
devices while the other versions may only be able to
connect to a restricted set of these devices.
Notes:
Adjustments
The main function of InPower is to adjust all of the
parameters of a connected device. Many of these
parameters are the same as were configured using
the service menus of the genset controller, however
there may be additional parameters that are only
able to be adjusted using InPower.
Capture Files
Another useful function of InPower enables the user to take a snapshot of the genset controller’s existing
parameter values loaded to a piece of equipment. This is saved as a local .cap(ture) file located on the
user’s computer. This file can be used to back up a configuration of a genset controller and can later be
uploaded back onto the genset controller to restore to original configuration.
Initial/Update Calibration
InPower Pro can be used to download a calibration file into a service replacement genset control board. A
capture file can be used at the time of initial calibration to reduce the amount of adjustment that may be
required when replacing the control board.
Notes:
RS232
RS232
One end of the cable plugs into the RS232 DB9 port
brainbox
There is an adapter available on the hardware shelf, the Brainbox US-101. When plugged into the USB slot
on your computer, the brainbox automatically installs a driver which assigns a COM port number to the
brain box.
This will essentially create a virtual COM port, and the number will be retained in between uses. For
example, when you plug your brainbox into a USB port for the first time and it assigns itself as COM port
06, each time you plug that USB onto that machine, it will always display as COM06. However, if you were
to plug a different brainbox into your computer, it would assign a different number.
To connect to newer generation of PowerCommand
Connections – RS485 commercial genset controls such as the PC1.X, 2.X,
or 3.X, you will need a Cummins RS485 connection
cable. This cable has a 5 pin terminal block at one
RS485
RS232
This will allow the computer (which uses RS232) to interact w/ the control board (which uses RS485).
Again, if your computer does not have a serial port, a USB to Serial adapter must be used.
Note that some controls may have both a RS232 port and a RS485 port. You may use either to connect to
those controls. It should be noted, however, that the control can only be calibrated from the RS485 port
on these controls.
Notes:
InPower Cable
on the control boards.
Setup – User Setup The User Setup tab in the Setup application allows
the user to set separate users for the InPower
program.
• Read Only users can connect to a device and read all parameter settings, fault information and history
records.
• Read/Write Users have full use of all InPower features, including making adjustments.
• Administrator Users have full use of all InPower features and the ability to establish and maintain user
privileges for all users on this computer.
This tab also allows you to select your Capture File Options. We will discuss more about what a capture
file is shortly. Select the button to Save a Capture File as soon as connected to a controller, and whether
or not you would like the program to ask before saving a capture file.
Notes:
The “Protocol” drop down menu allows the user to select which protocol InPower will use to
communicate with the control. There are several selections, but generally for legacy controls (2100, 3201,
etc.) select “goal” as the protocol and for newer generation controls (1.X, 2.X, 3.X, etc.) select “mon” as
the protocol.
The “Location” dropdown menu allows the user to select how the connection will be made. Select Local
for a direct connection from the PC to the control with an InPower cable.
Click the “Device Setup” button to edit the Device ID, Device Name, and the Device Type.
New Sites need to be created for each type of controller you will be connecting with.
The Communications tab in the Setup application
Setup - Communications allows the user to edit the Communications settings
of InPower.
Notes:
This is a typical window of the InPower Pro V10.0 electronic service tool. This window is used to connect
to different power generation devices, make configuration changes, save changes either to your
computer or to the device itself, etc.
The Menu bar is a set of drop down lists which contain all of the different tools and secondary
applications used to configure or update an InPower supported power generation device.
The Tool bar is a set of buttons of commonly used tools. All of these tools can be found in the menu bar as
well.
The Left window pane is used to navigate the different sites already configured in InPower, as well as
navigate the menu structure of a connected device.
The Right window pane is used to navigate the menu structure of a connected device (or capture file),
read the current settings of selected parameters, as well as actually change the configuration of each
writeable parameter.
Notes:
Port
The Port dropdown menu allows users to connect add a site, Connect/Disconnect from a port, add a site,
find InCal (needed for initial or update calibrations), and exit the program. InPower uses the term port to
refer to a COM port or .cap(ture) file or simulator file. A COM port is the physical connection between the
computer and the InPower supported device. For commercial PowerCommand genset controls, this
connection is made with either a Serial null modem cable or a RS-485 connection cable depending on
which device is being connected.
Device
The Device dropdown menu allows users to connect to and disconnect devices from a device. InPower
uses the term device when referring to the actual genset controller you are attempting to connect to
(through the port). It also allows users to perform read/write such as Saving Adjustments to the controller
after configuration. The device’s parameters can be captured (saved) to a file from this menu as well.
The Device menu can also be used to clear all inactive faults on the device, and create a Comma
Separated Value (CSV) file with All Selected Features of the device’s settings.
When connected to a device with InPower Pro, the user can select Initial Calibration, Update Calibration,
and Update Features as well.
Edit
The edit menu works within the directory of the connected device’s settings and parameters to Find a
specified string of data. The Edit menu can also be used Copy and Paste selected data.
Utilities
This menu is used to download simulator files from an InCal CD. When Universal Simulator Download is
selected, a pop-up menu is displayed allowing you to set the COM port and baud rate. If the InCal CD is
inserted in your local drive, you can navigate to the simulator files(s) you wish to download and then click
on Download.
Simulator files are useful to compare with to look at typical settings in a device. When a user connects to
a simulated device InPower outputs responses and setting you will expect from a certain device.
Notes:
View
This menu is used to view data from the connected device in a Monitor display or Strip Chart display. The
View menu can also be used to access the FIS Fault Tree Main Window, view faults and refresh(update) all
of the parameters displayed in the Value field.
Help
This menu commands are used to find online information about using InPower and Windows. Help is also
used to display Service and Support information and to obtain InPower product and version information.
A separate Help file contains information on consumer device fault codes for marine and RV products.
The menu also allows the user to launch the registration program.
Before any connection is made to a device through a
Left Window Pane – Sites/Menus port of your computer, the left window pane of the
InPower window displays all of the configured Sites
that have been added. These sites are preconfigured
with the port and type of control to be connected.
This sets the protocol that InPower will use when
connecting to a control.
Notes:
In the “Properties” section, enter the COM port number, and enter a Site ID. You can click the blue link in
order to display what COM ports are available. If your brainbox is already plugged in and installed
correctly, the assigned COM port should display.
Click “OK” when finished, the new Site will display in the Left Window Pane.
Note that for each family of controls, you should only have to do this once. Once you have established a
Site for a PCC 1302 control board, through the correct COM port number, you can connect to every PCC
1302 without having to add a new site for each control.
Notes:
Tool Bar
The InPower toolbar has a collection of most frequently used commands that help the user do actions at
the click of a button. Buttons may be added/removed or grayed out of selection, dependent on which
area you are within InPower.
Port Connect Monitor
Connect to a COM port, capture file, or simulator. Allows you to build an excel spread sheet with
parameters for performance testing and diagnostics.
Port Disconnect
Disconnect from a COM port, capture file, or InCal Extractor
simulator. Allows the user to extract new calibrations
downloaded from the InCal website (if available).
Faults
View Faults within a connected device. Save Adjustments
Allows you to save parameter values after editing.
Fault Information Systems
Allows you to see a troubleshooting tree (if Exit
applicable) for specific faults. Exit out of the InPower program.
Refresh Help
Use this to refresh the value of parameters. Launch InPower Help.
Strip Chart
Creates a line graph of parameter values. Useful for
fault diagnostics.
Notes:
195 7/9/2014 Cummins Confidential Other PowerCommand Controls will have different
menu structures.
If this selection was chosen during Setup, a popup
Saving a Capture File window may appear asking whether or not to save a
capture file. Otherwise, a capture file may be saved
by selecting “Capture to File” from the “Device”
drop down menu.
Notes:
Capture Files
Captured files are read-only files that can be viewed after disconnecting the device from InPower. You can
connect to and view these files, but you cannot modify the file contents. Capture files are basically used
to store a copy of a device’s parameter values, History and faults. These capture files can then be used to
compare to a connected device, or used as a template to write the captured settings to another device of
the same type.
Example: The Captured file is from a Genset controller, this file can be written to another (connected)
Genset controller of the same type.
Capture files are generally saved in the hard-drive at
Location of Capture Files the following location (the drive letter may vary
depending on where InPower was installed):
InPower View
File Location
D:\Program Files\Power
Generation\Shared\Captured Files
Notes:
• Compare to a Capture File – Enables the user to compare the settings of a current device to a
captured file (presumably an old set of settings) to see what settings have been changed.
• Drag and Drop – If a user drags and drops a capture file into a connected device it will prompt the
user if they want to revert the settings of the connected device to that of the captured file. This only
works if the captured file and device are of the same type.
• E-mail Capture File – A user can email the capture file to another user. As long as the other user
copies the emailed file to the appropriate location in the hard drive (as discussed in the location
section), they can use the captured file.
Example: PCC 1302 control is behaving irregularly and Technician-A suspects that someone has tampered
with the settings. Technician-A finds out that the previous qualified Technician-B who worked on the
control is at an off-site location. A request is sent to the off-site Technician-B to email the capture file from
the last time the control was worked on. Now Technician-A can use the drag and drop feature to revert the
PCC 1302 control settings to those settings in the emailed capture file. The control should work normally if
the problem was in the incorrect settings.
Notes:
In order to use the Compare function, the device and the capture file should both be connected via a site
location in InPower. Right-click on the device (PCC1302) in the left window pane and select “Compare”. A
Compare Utility screen will pop up with the selected device on one pane and a blank pane next to it. Next,
click and drag the relevant capture file to the empty pane. Now on the left side of the Compare Utility are
all of the parameters of the connected device, and right side is the capture file.
There are a couple of options in the Compare Utility. Click the “Compare” icon on the top left of the pop-
up screen. This will compare all parameters listed for both the connected device and the capture file. The
items displayed in black are identical. The items listed in red are the items that are not the same. Click the
“Filter” icon to filter out the variables that are different, showing only red (different) parameters.
Notes:
To overwrite a connected device’s parameters with the parameters from a previously taken capture file,
first connect to the capture file. Then, connect to the device. Once both are connected successfully, click
and hold the capture file and drag and drop it onto the device.
This feature can be used to copy the entire capture file, individual folders, or specific parameters.
Traditional “copy” and “paste” commands such as “Ctl + C” and “Ctl + V” will work to perform this feature
as well.
A popup menu will appear confirming that you do in fact want to erase all of the parameters on your
connected device and replace them with the parameters in the capture file.
InPower is used to adjust different parameters and
Adjustments settings of devices.
Notes:
Some older versions of PowerCommand Controls also require the control to cycle power in order for the
changes to be saved.
Notes:
The strip chart function in InPower lets you graphically display some (up to 6 max) of the parameters
relevant to a device. In the example shown, the voltage (red), current (dark yellow), and genset power in
kVA (green) will be measured. This will display in real time.
The Strip chart can be accessed by clicking on the Strip chart Icon in the toolbar. To add parameters to the
strip chart, drag and drop the monitor parameters from the InPower window onto the empty space of the
Strip chart. The Strip chart will then begin displaying in real time the value of the parameter. You can
change the values of the maximum and minimum points in the chart so the data is displayed more clearly
by clicking “Properties” in the “Edit” drop down menu. The sampling can be turned on/off via the Toggle
Sampling button in the Strip chart Window toolbar.
Strip charts can also be saved to the disk, and previously saved Strip Charts can be opened by using the
“Save” and “Open” buttons. This does not save the data the Strip Chart was collecting, however, it only
saves the set of parameters that the Strip Chart was monitoring so that you don’t have to repeat this work
if you want to run a similar monitor test later. In order to export the data, you must use a Monitor file.
Notes:
Monitor
The Monitor function in InPower lets you monitor values (up to 6 max) in real time as well as Data log
these values. The sampling rate can be changed so that it takes a sample of the parameter every 0.05
second or 1 second, 1 minute, etc.
The Monitor function can be accessed by clicking on the monitor icon in the toolbar. To add parameters
to it, drag and drop the parameter from the device window similar to the way the Strip Chart was set up.
Once you have all of the parameters that you would like to sample, click the “Sampling” check box and
select your desired Sampling Rate from the dropdown menu. This will begin the sampling of the data in
the window, and if the values are changing, you will see the Value column updating.
Data logging allows the user to log parameter information to a .log file at the selected sampling rate.
Sampling must be enabled in order for the Logging selections to become active. To begin data logging,
click the “Start Logging” button. Data is now being logged to the default Monitor File located at the
default location of D:\Program Files\InPower\Monitor Log Files. Monitor Log Files are named by default
with the date and time. To change either the default location or the default name of the Monitor file, click
the “Browse” button.
When you’ve finished data logging, click “Stop Logging”. If you would just like to view the data and leave
data logging on, click “Generate Report”. This will open the data in Excel.
Monitor Files can also be saved and previously saved monitor files can be opened. This is separate from
data logging. The monitor files are saving the parameters that you drug and dropped into the monitor
window, so that you don’t have to repeat this efforts next time you’d like to run a similar test. For
example, the visual above displays a previously saved AVR test.
Notes:
To generate a report, you first have to select the features that you wish to include in your report. To do
this, navigate the parameters on the left window pane to the folder/features you wish to include. Then,
right click and select “Select Feature”. Then, right click again and select “Prepare CSV file for Feature…”
This will prompt a menu where it will ask you for a location to save the report to and a name. Click “OK”.
This will generate a Comma Separated Value (CSV) file which can be viewed with Excel or Notepad.
The Initial Calibration and Update Calibration
Update InCal features in InPower are very powerful and can be
used to either replace a genset controller or keep an
existing genset controller current with updated
calibrations. But that only works if you have the
most up to date calibration files on your computer.
All To get the most up to date calibration files, you
must go to the InCal website at:
Download
http://cumminspower.com/en/services/software/S
earchandDownload/activeStatus.do
This website allows you to download a zip file of all calibration files for all Cummins Power Generation
products that use InPower calibration files. Or, you can select the specific Model, Systems, or Networks
you are looking for. To download all of the calibration files, select “All” from the Download dropdown
menu and click “Download”
This will download a document called all.zip onto your computer. This can take several minutes
depending on your connection speed.
Notes:
InCal Extractor
This will bring up the InCal extractor window. Click “Browse InCal zip file” and navigate to the .zip file you
downloaded from the InCal website. Make sure that the disk path is correct, for PowerSweep machines
you should extract to the D:\ drive; however this may be different if InPower is installed on a different
drive. Click “Extract”. This will load all of the most current calibration files into a usable form for InPower
to use when performing Update or Initial Calibrations.
The Initial Calibration feature is used to download a
Initial Calibration calibration file into a service replacement genset
control. Initial Calibrations are required when
replacing a control. The use of a capture file can
reduce the amount of adjustment that will be
required. Initial Calibration essentially customizes
the generic Power Command control board with the
very specific set of features of the generator set that
the PCC control will be controlling.
If you did not select a capture file, you will have to select the appropriate features manually. These
features can be found on the Bill of Materials located on QSOL, or on the data plate of the generator set.
Once you have selected all of the features, click “Finish”. This will pop up a dialog box asking if you wish to
calibrate the controller now. Select “Yes” to continue or “No” to cancel. Calibrating the controller at this
point will erase any existing data on the board, so only use Initial Calibration when required.
The calibration file download process can take several minutes to complete. During the download, it is
normal operation for the genset control to display warnings.
Do not hit the “Fault Acknowledge” button during the download, or it may be interrupted.
The Update Calibration feature is used to replace a
Update Calibration current calibration file with a newer version from
the CPG InCal website. The new calibration file is
written over the current calibration file in the
genset baseboard.
Notes:
Check the “Save & Restore” box in order to save the current adjustment trims and settings from the
device and automatically overlay them onto the new calibration file. Click “Finish” to proceed with the
calibration update.
Again, this process can take several minutes to download the new calibration onto the controller, do not
clear any alarms on the control as this may interrupt the calibration download process.
Notes:
Activity 8-1
Skills Exercise
InPower Hands-On
Required Materials
• PC 1.1 Simulator Kit or running generator set
• InPower Service Tool installed on laptop
• Communication Cables
Instructions
Connect w/ InPower
1. Create a Site in InPower to connect to the PCC 1302 board with your communication cables
2. Physically and elctronically connect to the controller
Capture Files
1. Save a capture file
2. Locate the capture file in the folder structure of your computer, and give it to a classmate (while
swapping for their capture file)
3. Save your classmate’s capture file in the appropriate folder on your own computer
4. Connect to that capture file using InPower, and copy it over to yoru connected controller
Strip chart/Monitor File
1. Create a strip chart of the following parameters
a. Frequency, L1-N Voltage, Total kW, AVR Duty clycle
2. Ensure that all of the axis are easy to read and properly scaled
3. Save the Strip Chart parameter list
4. Create a Monitor File using the same parameter list. Sample once per 0.25 seconds.
5. Export a CSV report of those parameters for a startup and shutdown sequence
Initial Calibration
1. Update your InCal contents
2. Perform an Initial Calibration on your connected controller
3. Use your original capture file to set the data plate and overlay parameters
Notes:
DOCUMENT!
221 7/9/2014 Cummins Confidential
DOCUMENT!
Perform Repair
Repair Software or Hardware repair
DOCUMENT!
Notes:
DOCUMENT!
Notes:
Instructions:
1. Use the GATRR Process to investigate the problem with the PowerCommand Control.
2. The Instructor will act as the operator for interviews and questions about symptoms.
3. DOCUMENT each step of the GATRR process below. Full credit will not be given unless
all steps are documented.
Gather
Analyze
Test
Repair
Retest
Note: Instructor or designated helper will act as operator for questions about symptoms
Instructions:
4. Use the GATRR Process to investigate the problem with the PowerCommand Control.
5. The Instructor will act as the operator for interviews and questions about symptoms.
6. DOCUMENT each step of the GATRR process below. Full credit will not be given unless
all steps are documented.
Gather
Analyze
Test
Repair
Retest
Note: Instructor or designated helper will act as operator for questions about symptoms
Instructions:
7. Use the GATRR Process to investigate the problem with the PowerCommand Control.
8. The Instructor will act as the operator for interviews and questions about symptoms.
9. DOCUMENT each step of the GATRR process below. Full credit will not be given unless
all steps are documented.
Gather
Analyze
Test
Repair
Retest
Note: Instructor or designated helper will act as operator for questions about symptoms
www.cummins.com/survey/servicetraining