PKJ employs a rotary multi-position tap selector. The fixed contacts are mounted on the periphery of an insulated cylinder. Circulating current is limited by the Preventive Auto Transformer (PAT)
PKJ employs a rotary multi-position tap selector. The fixed contacts are mounted on the periphery of an insulated cylinder. Circulating current is limited by the Preventive Auto Transformer (PAT)
PKJ employs a rotary multi-position tap selector. The fixed contacts are mounted on the periphery of an insulated cylinder. Circulating current is limited by the Preventive Auto Transformer (PAT)
Load Tapchanger PKJ III V i r g i n i a Tr a n s f o r m e r C o r p
w w w. v a t r a n s f o r m e r. c o m
INTERNAL CONSTRUCTION FEATURES
THE TAP SELECTOR DRIVE MECHANISM
• PKJ employs a rotary multi-position tap selector. • Enclosed in an air-filled compartment, integral to main tank, • The fixed contacts are mounted on the periphery of an no allignment required. insulated cylinder. • Contains the motor drive with reduction gear, cam switches • When on adjacent contacts, circulating current is limited for controls, and indication devices. by the Preventive Auto Transformer (PAT). • Hinged, lockable sheet metal door. • Contacts move only when carrying no current limiting • Allows observation of the tap position indicator and deterioration of oil quality. operations counter, without opening the door. • Robust construction to reduce stress on the switch and its rollers. • Enclosure withstands NEMA 4 test. • End position limits operated by differential gear system, THE PRE-SELECTOR not a breakable pin. • A three-phase, single-pole, two-way pre-selector switch is provided on the switching cylinder outer periphery. MONITORING BOX • Carries no current at changeover. • PKJ comes with standard built-in features for monitoring many of its own parameters. THE BYPASS SWITCH • Housed in a box in the mechanism chamber, the system • Component of the diverter switch element. verifies that the bottle opening is correct before allowing • Diverter contains the actual current interrupting and the selector to move. making contact. • The monitoring device box also provides a manual check • Bypasses current flow in the vacuum interrupter. button which runs a self-diagnostic test on the monitoring • Mounted on the contact cylinder. system and alerts the operator to any errors. • Driven by a cam mounted on a shaft running parallel to the axis of the switching cylinder. EXTERNAL CONSTRUCTION FEATURES • Same shaft drives the vacuum contactor, to ensure proper timing between the operation of the bypass • Live parts are enclosed in an outdoor, sheet metal tank. switch, and the vacuum contactor is maintained. • Mechanism is integrally mounted on the tank. VACUUM INTERRUPTING ELEMENT • The LTC tank is capable of full vacuum. • Implemented in the form of a vacuum interrupter • Terminal board stems are individually replaceable and (the “bottle”) and driven by the same shaft as the have redundant viton o-rings. bypass switch. • The drive of the bottle is through a cam and latch system which ensures that speeds are accurately REACTOR SWITCHING maintained throughout each phase of opening and closing, independent of the speed of operation of the driving mechanism.
STAGE 1 STAGE 2 STAGE 3 STAGE 4 STAGE 5
OPERATING AT CD OPENS WITH DE (BOTTLE) A MOVES AT NO A MAKES TO DE (BOTTLE) OPERATING AT TAP 1 CE CLOSED OPENS CURRENT CONTACT-2 CLOSES MID TAP CD CONDITION CLOSES TRANSITION TO MID TAP 1-2
STAGE 1 STAGE 2 STAGE 3 STAGE 4 STAGE 5
OPERATING AT CE OPENS WITH DE (BOTTLE) B MOVES AT B MAKES TO DE (BOTTLE) OPERATING AT MID MID TAP CD CLOSED OPENS NO CURRENT CONTACT-2 CLOSES TAP CD CLOSES CONDITION
TRANSITION TO MID TAP 2
Rev1.9.03
VIRGINIA TRANSFORMER CORP
220 Glade View Drive Roanoke, VA 24012 USA (540)345-9892 fax (540)342-7694 Load Tapchanger PKJ III V i r g i n i a Tr a n s f o r m e r C o r p w w w. v a t r a n s f o r m e r. c o m
TAPCHANGER PKJ SPECIFICATION DATA
PKJ meets the following standards: ANSI/IEEE C57.131; Ratings PKJ III ANSI/IEEE C57.12.00-1987; ANSI/IEEE C57.12.10-1988; Operating system voltage 15kV ANSI/IEEE C 57.92-1981; IEC 60214; IS 8468; IS 8478. Insulation of all part to ground for continuous voltage 15kV General data Insulation between phases, for continuous voltage 15kV Design: PKJ is a 3 Phase, Preventive Auto Transformer (center tapped Tapchanger designation PKJ III 1000 PKJ III 1600 reactor) principle, load tapchanger, using vacuum contactor for current Through current 1000A 1600A commutation. Step voltage 1000V Mechanical data Power frequency test voltage/impulse voltage for all live parts to Tank: PKJ is housed in a steel tank, with integral drive mechanism. It is bolted or ground and between phases 34kV/110kvp welded on to the tranformer flange. The Power frequency test voltage/impulse voltage withstand across power switch operates under oil. The drive mechanism chamber is air filled. tapping range 26kV/70kvp Power frequency test voltage/impulse voltage withstand across one tap 15kV/45kvp Size 1854 x 986 x 1386 mm Max number of position (when operated with PAT) 33 (73 x 39 x 54.5 inches) Regulating scheme Reversing Weight (without oil) The oil space withstands full vacuum. Number of taps in regulating winding 9 750 Kg. (1653 pounds) Maximum recovery voltage across reversing switch 20kV Oil filling quantity 960 Ltr. (253 gallons) Maximum number of different voltages obtainable with reversing Time per operation switch and preventive auto transformer 33 Approximately 2 seconds As the design and manufacture of our equipment are subject to constant improvement, the product supplied may Warranty differ in certain details from the specifications and illustrations. Three Year Standard Data is for estimating purposes only and should never be used for construction. Contact factory for actual dimensions, weights and oil volume.
TYPE TESTS DONE ON PKJ III
Test Number Standard Clause Test
1 IEEE C5713.1 6.1 Temperature Rise Test 2 IEEE C5713.1 6.2 Switching Tests 3 IEEE C5713.1 6.3 Short Circuit Test 4 IEEE C5713.1 6.5.1 Mechanical Endurance Test 5 IEEE C5713.1 6.5.2 Sequence Test 6 IEEE C5713.1 6.6 Dielectric Tests 7 IEEE C5713.1 10.3.2 Over Run Test 8 IEC 60529 — Enclosure (NEMA 4) 9 — — 1,000,000 Mechanical Ops.