You are on page 1of 4

Emergency Stop Relays, Safety Gate Monitors

Category 4, EN 954-1
PNOZ X13

Technical Details PNOZ X13

Electrical Data
Supply Voltage 24 VDC
Tolerance
Power Consumption UB
Voltage and Current at the Input and
Reset Circuits and Feedback Control Loop
85 ... 110 %
Approx. 4.5 W
24 VDC, 50 mA
1
Switching Capability in accordance with
EN 60947-4-1, 02/01 AC1: 240 V/8 A/2000 VA
DC1: 24 V/8 A/200 W
EN 60947-5-1, 11/97 AC15: 230 V/5 A; DC13: 24 V/7 A
(DC13: 6 cycles/min.)
Output Contacts 5 safety contacts N/O
1 auxiliary contact N/C
Contact Fuse Protection 10 A quick or 6 A slow
Emergency stop relay and safety (EN 60947-5-1, 11/97)
gate monitor in accordance with Times
VDE 0113 part 1, 11/98, EN 60204-1, Delay-on Energisation Max. 100 ms
12/97 and IEC 204-1, 11/98. Delay-on De-energisation Max. 50 ms
Recovery Time Approx. 1 s
Simultaneity channel1/2 ¥
Features Max. Supply Interruption before Approx. 25 ms
De-energisation
● Input wiring compatible with the Mechanical Data
PNOZ X3
Max. Cross Section of 2 x 1.5 mm2 or 1 x 2.5 mm2
● Dual-channel wiring with
External Conductors Single-core or multi-core
detection of shorts across the
with crimp connectors
input contacts
Dimensions (H x W x D) 87 x 45 x 121 mm
● Monitored manual or automatic
reset can be selected Weight 370 g
● Supply voltage: 24 VDC
Description Operating Modes

Approvals ● 45 mm P-97 housing, DIN Rail ● Single-channel operation


mounting ● Dual-channel operation
● Positive-guided relay outputs: ● Automatic reset
PNOZ X13 – 5 safety contacts N/O ● Monitored manual reset
– 1 auxiliary contact N/C
● ● Connections for
– E-STOP button
– safety gate limit switch

– reset button
● LEDs for power, channel 1,
● channel 2, reset circuit
● Increase in the number of
safety contacts available by
connecting expander modules.

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-249-01/02


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

1-1
Emergency Stop Relays, Safety Gate Monitors

Category 4, EN 954-1
PNOZ X13

Internal Wiring Diagram – Key

UB Reset Input Safety S1/2: E-STOP or safety gate switch


circuit circuit contacts
A2 A1 S33 S34 S14 S13 S11 S12 S31 S32 13 23 33 43 53 61

1
S3: Reset button
- +

CH1 Switch operated


K3
1b
CH2 Gate open
Start K1
1a
Unit
K4 Gate closed
2b

K2
2a

S21 S22 14 24 34 44 54 62
Input
circuit

External Wiring

● Example 1 ● Example 4
Single-channel E-STOP wiring with Single-channel safety gate control
automatic reset. with monitored manual reset.

S11 S31 S21 S13 S11 S21 S31 S33

S1 S1
S3

S12 S32 S22 S14 S12 S22 S32 S34

● Example 2 ● Example 5
Single-channel E-STOP wiring with Dual-channel safety gate control with
monitored manual reset. monitored manual reset.

S11 S31 S21 S33 S21 S11 S33

S1
S1
S3 S22 S3
S31
S2

S12 S32 S22 S34 S32 S12 S34

● Example 3 ● Example 6
Dual-channel E-STOP wiring with Dual-channel safety gate control with
monitored manual reset. automatic reset.

S21 S31 S11 S33 S21 S13 S11

S1
S1
S3 S22
S31

S2

S22 S32 S12 S34 S32 S14 S12

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-249-01/02


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
Emergency Stop Relays, Safety Gate Monitors

Category 4, EN 954-1
PNOZ X13

● Increase in safety contacts


The number of output contacts can
be increased by using expander
modules or relays/contactors with

1
positive-guided contacts.

1L1
13

14

K5 K6

1L2

– Operation with automatic reset.

1L1

K6

K5
S13 S14 13

14

K5 K6

1L2

– Operation with monitored manual


reset.

S21 S31 S11 S33

S1
S3

S22 S32 S12 S34

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-249-01/02


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

1-3
Emergency Stop Relays, Safety Gate Monitors

Category 4, EN 954-1
PNOZ X13

General Technical Data

Unless stated otherwise in the technical details for the specific unit

1
Electrical Data
Frequency Range AC 50 ... 60 Hz
Residual Ripple DC 160 %
Contact Material AgSnO2
Continuous Duty 100 %
Environmental Data
EMC EN 50081-1, 01/92, EN 61000-6-2, 03/00
Vibration in accordance with Frequency: 10 ... 55 Hz,
EN 60068-2-6, 01/00 Amplitude: 0.35 mm
Climatic Suitability DIN IEC 60068-2-3, 12/86
Airgap Creepage DIN VDE 0110 part 1, 04/97
Ambient Temperature -10 ... +55 °C
Storage Temperature -40 ... +85 °C
Mechanical Data
Torque Setting on Connection Terminals 0.6 Nm (screws)
Mounting Position Any
Housing Material Thermoplast Noryl SE 100
Protection Mounting: IP 54
Housing: IP 40
Terminal Range: IP 20

The units were tested in accordance with the relevant standards current at
the time of development.

Order References

Type UB Order No.


PNOZ X13 24 V DC 774 549

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-249-01/02


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de