LOAD SCHEDULE

CKT. LOAD POWER VOLTAGE CURRENT SIZE OF CONDUCTOR PROTECTION CONDUIT SIZE
NO. DESCRIPTION (VA) (V) (A) AT AF P (mm)
1 9-Lighting Outlet 900 230 3.9 2-2.0 mm2 THHN wires + 15 50 2 13 mm Ø PVC pipe
1-2.0 mm2 (G) THNN wire
2 12-Lighting Outlet 1200 230 5.2 2-2.0 mm2 THHN wires + 15 50 2 13 mm Ø PVC pipe
1-2.0 mm2 (G) THNN wire
3 13-Duplex 2340 230 10.2 2-3.5 mm2 THHN wires + 20 50 2 20 mm Ø PVC pipe
Convenience Outlet 1-3.5 mm2 (G) THNN wire
4 10- Duplex 1800 230 7.8 2-3.5 mm2 THHN wires + 20 50 2 20 mm Ø PVC pipe
Convenience Outlet 1-3.5 mm2 (G) THNN wire
5 Special Outlet 1500 230 6.5 2-5.5 mm2 THHN wires + 30 50 2 20 mm Ø PVC pipe
1-5.5 mm2 (G) THNN wire
6 Refrigerator outlet 746 230 3.2 2-5.5 mm2 THHN wires + 30 50 2 20 mm Ø PVC pipe
1-5.5 mm2 (G) THNN wire
7 Range Outlet 3000 230 13 2-3.5 mm2 THHN wires + 20 50 2 20 mm Ø PVC pipe
1-3.5 mm2 (G) THNN wire
8 ACU 2562 230 11.1 2-5.5 mm2 THHN wires + 30 50 2 20 mm Ø PVC pipe
1-5.5 mm2 (G) THNN wire
9 ACU 2562 230 11.1 2-5.5 mm2 THHN wires + 30 50 2 20 mm Ø PVC pipe
1-5.5 mm2 (G) THNN wire
10 ACU 2562 230 11.1 2-5.5 mm2 THHN wires + 30 50 2 20 mm Ø PVC pipe
1-5.5 mm2 (G) THNN wire
11 SPARE
12 SPARE
TOTAL 19172 83.1

FEEDER CONDUCTOR = 900+1200+2340+1800+1500(1.25)+746(1.25)+3000+(3)(2562)(1.25)/230


= 94.15 A
SERVICE PROTECTION = 900+1200+2340+1800+1500+746(2.5)+3000+2562(3)/230
= 88.22 A
NOTE : USE 2-22 mm2 THW wires + 1-8.0 mm2 (G) THW wire @ 32 mm Ø RSC
: USE 2P, 100 AT INVERSE TIME CIRCUIT BREAKER