You are on page 1of 4

2001 IEEE 7th International Conference on Solid Dielectrics, June 25-29,2001, Eindhoven, the Netherlands 485

ON-LINE DIAGNOSTIC TECHNIQUE FOR MONITORING PARTIALDISCHARGES IN


CAPACITOR BANKS

H N Nagamani S N Moorching Dr. Channakeshava Dr. T Basavaraju


Central Power Research Institute, P B NO. 8066, Bangalore 80, India W C E , Bangalore, India

INTRODUCTION through different insulating media before reaching the


container of the electrical equipment. These signals can
In spite of phenomenal technological developments in be detected by a suitable sensor mounted on the
Capacitor Industry, there are several reports of pre- container of the equipment under test. The output of the
mature failure of capacitors in service. A significant sensor is analyzed using a data acquisition and
number of failures have also been experienced during processing system [3].
laboratory testing. Analysis of such failures has
indicated that majority of the failures can be attributed The principle of AE technique is schematically shown
to partial discharge (PD) phenomenon. So far, no in Figure 1.
technique was available to measure PD in full size Preamplifi
capacitors. Also some of the power utilities have
expressed the need for development of techniques
suitable for on-line condition monitoring of power
capacitors.

Keeping these aspects in view, CPRI has established


facilities for measuring PD in full size capacitors
L-\r Acoustic
Emission
Data Acauisition
&
employing Acoustic technique. Capacitors of rating 750 StressWave Analyzing unit
kvar / 12 kV have been tested successfully for partial
discharges employing this technique. At the request of Electrical
clients, on-line PD measurements on HT capacitor
banks have been carried out [ 1,2]. This paper deals with
two recently investigated case studies. The methodology
employed for acquiring partial discharges from HT Figurel: Basic principle of AE technique (Schematic)
capacitor banks in service is discussed along with
important findings.
ON-LINE PD MEASUREMENT ON CAPACITOR
BANKS
ACOUSTIC EMISSION TECHMQUE FOR PD
MEASUREMENT At the request of two different Clients, on line PD
measurements were performed on HT capacitor banks.
Measurement of partial discharges is one of the PD measurement was carried out with the help of a 4
important diagnostic tools for assessing the condition of channel AE system of model MISTRAS 2001. AE
power equipment. The conventional electrical method
sensor cannot be directly placed on the container of the
for PD detection is well established and is generally capacitor in a capacitor bank as it will be at high
undertaken with adequate electromagnetic shielding. voltage. Therefore, AE signals from the capacitors were
Sensitivity of PD measurement is poor for the high acquired by mounting a hot stick of 66 kV rating on the
capacitance value equipment like power capacitors. The
capacitor container. The hot-stick is made up of AE
limitations of electrical method of PD detection for sensitive material.
equipment in service have resulted in the development
of alternative techniques. More recently, PD detection
PD measurement on a 25 kV, 3 MVAR capacitor
based on acoustic emission (AE) technique is gaining
banks in Railway Traction Substation
importance. The main advantage of this method is that it
is nondestructive, non-invasive and immune to
electromagnetic noise. .
The capacitor bank details are as follows:
Voltage rating of the bank: 25 kV ac
Principal of AE Method: Partial discharge activity is
associated with instantaneous release of energy. A
..
’ Unit capacitor rating: 8 kV / 220 kvar
Total number of capacitors in each bank: 25
Measurement: 24 months after commissioning.
fraction of the released energy heats the material
The bank is of single phase, out-door type with a 13 %
adjacent to the PD location creating a small explosion, Series Reactor connected on HV side. The bank is
which excites a mechanical wave. The waves propagate

0-7803-6352-3/01/$10.00 0 2001 IEEE


486

controlled by a 25 kV, 1600 Amps rating vacuum circuit Series reactor of rating 36 kV, 79 Amps is connected on
breaker. neutral side of the capacitor bank. Each capacitor bank
is controlled by a 33 kV, 3-Pole, 1250 Amps rating SF6
AE signals were measured through AEPD hot-stick circuit breaker suitable for direct switching of 20 W A R
mounted individually on 9 capacitors arranged at the 33 kV capacitors.
bottom most row of the bank when the capacitors
were under normal operating voltage of 25 kV. PDs in the above bank were monitored during circuit
Figure 2 shows the mounting of AEPD hot-stick on bxeaker operations. The Client was also interested in the
one of the capacitors. magnitudes of switching transients experienced by the
capacitor bank.
No PDs were observed from the capacitor under the
normal operating condition as shown in Table 1. The arrangement for measuring the switching transient
voltage and current is shown in Figure 3. High voltage
probes, 3 numbers, were connected to RYB phases of
the bank at point of connection of incoming 33 kV
Table 1: Results of AEPD measurement on 25 kV
w. XLPE cable. 3000 Amps CTs were clamped on the heat
shrink terminations of 33 kV XLPE cable. Switching
1 Capacitor I Voltageon I Threshold 1 Measured I transients were recorded during six switching operations
of the Circuit breaker with the help of high voltage
probes and CTs connected to a Power Analyzer (RPM
make and model No. 1656).

A close view of AEPD hot-stick mounted on one of the


capacitors for monitoring PD is shown in Figure 4.
1
c
54 I 25 kV 40 dB No PD
c55 I 25 kV 40 dB No PD

Figure 3: Figure 4:
Arrangement for Placement of AEPD
measuring Switching hot-stick on the live
transients at the capacitor container for
Figure 2: Arrangement for measuring AE PD from incoming H V terminals PD measurement.
25 kV Capacitor bank at Railway Traction of a 36 kV capacitor
Substation. bank.

PD measurement on a 36 kV, 6.5 MVAR capacitor The magnitudes of partial discharges in 6 capacitors a~
bank at a 220 kV Receiving Station given in Table 2 along with the magnitude of transient
voltage. The reported AEPD values take into account
The capacitor bank details are as follows: the attenuation of AE signals through capacitor

.
8
Voltage rating of the bank: 36 kV ac
Unit capacitor rating: 6.98 kV / 181 kvar
Total number of capacitors in each bank: 36
dielectric and also along the AEPD hot stick.

8 Measurement: 18 months after commissioning.


487

Table 2: Magnitudes AE PD from capacitors during DISCUSSION


switching transients
25 kV capacitor bank at railway traction substation:
Capacitor Transient Threshold AEPD PD from the 25 kV capacitor bank at traction substation
Number voltage for AEPD (max) of railways was monitored during normal operating
voltage. Capacitors were found to be discharge free
under normal operating condition. It may be noted that
voltage appearing on individual capacitors of the above
89 kV 40 dB bank during normal operating conditions will be around
93 kV 40 dB 80 dB 5 kV whereas they are rated for 8 kV. Also, the
c
6 60 kV 40 dB 80 dB capacitor bank was of 2 years old.

A typical transient event recorded during switching 36 kV capacitor bank at 220 kV Receiving station:
operation of the circuit breaker is shown in Figure 5. Capacitor banks in service invariably experience
transient over voltages and currents due to periodic
switching operations of the circuit breaker. Pre-mature
failure of capacitors occurs if (a) the switching
transients are of higher magnitudes than the specified
limits or (b) the capacitors are not designed to
accommodate rated transients. There are several reports
of premature failure of capacitors during switching
operations. One of the serious effects of such over
voltage effects is the occurrence of partial discharges in
capacitor insulation system. At present, there are no
comprehensive diagnostic techniques to assess the
performance of capacitor banks in service particularly
due to switching transients. CPRI has created necessary
facilities for undertaking field measurement at the
request of capacitor industry. At the request of one of
the capacitor users, a 36 kV capacitor bank was tested
on-line for checking its performance during switching
Figure 5 (a): Voltage (rms) recorded during a operation of the circuit breaker.
switching operation of a SF6 circuit breaker.
Figure 5(a) gives voltage (rms.) recorded during a
switching operation of the circuit breaker. The power
anlyzer records system disturbances as EVENT. It can
be observed in Figure 5 (a) that during switching on the
circuit breaker, an event of transient over
voltage(TOV1) and over current has been experienced
by the capacitor bank. The details of TOVl along with
c m n t are shown in Figure 5(b). According to IEC 871
Part 1: 1997, the first peak of transient over voltage
should not exceed 242 times the rated voltage (rms.
value) for a duration of Vi cycle. Hence, for a 33 kV
system, TOV should not exceed 93.3 kV. The maximum
value of TOV recorded is around 93 kV (refer to Table
2). Therefore, switching transients appearing at the 36
kV capacitor bank are within the limits specified in IEC
871 Part 1: 1997.

Before applying the AE technique for field


measurements, it was extensively exercised during
Figure 5 (b): Switching transient voltage (Expanded laboratory testing of HT capacitors. The partial
TOV1). discharges from HT capacitors subjected to switching
transients of magnitude 2.25 Un as per IEC 60871 Part
2: 1999 [4] were monitored employing AE technique.
The magnitude of AE signals from capacitors, which
successfully withstood the transient over- voltage test
were observed to be in the range of 75 to 85 dB.
488

Therefore, the PD activity occurring from capacitors in


33 kV capacitor bank as shown in Table 2, during
switching operation appears to be harmless.

The study conducted was of great practical importance


to the Client as they wanted to check the suitability of
circuit breaker installed for switching ON and OFF the
capacitor bank.

CONCLUSIONS

CPRI has necessary facilities for on-line partial


discharge measurement on Capacitor banks.
Measurement of switching transients, harmonics and
other system disturbances appearing on the capacitor
banks can also be undertaken. Such investigation will be
of great help in (a) diagnosing the condition of the
capacitors in operation, (b) deciding the type of circuit
breakers to be used for capacitor switching operation
and also (c) to assess the performance of capacitor
banks under switching transients.

The proposed AFi technique can be employed as a


diagnostic tool for on-line condition monitoring of
power capacitors as the technique is non destructive,
the instrument is compact, portable and easy to
operate at site as capacitors need not be disconnected
from the capacitor bank.
REFERENCES

[l]“On-Line Measurement of Switching Transients on


Capacitors” H N Nagamani, et al, Seminar on
Capacitors 18-19 Jan, 2001, f i n e , organized by CBIP.
[2] “New Diagnostic Technique for On-Line Condition
Monitoring” - H. N. Nagamani,et al, CPRI,News letter
No. 74 April 2000.
[3]“Acoustic PD detection - Practical application” L E
Lundgaard, Sept/Oct 1992- Vol 8, No. 5, IEEE E1
Magazine.
[4] “A E Technique to assess the performance of HT
Capacitors during Endurance Test as per 1EC-60871-2:
1999”- H. N. Nagamani, et al, Presented at 5”
International Seminar on Capacitors-CAPACIT 2000
during 24” & 11’ March 2000 at New Delhi organized
by IEEMA.

You might also like