Professional Documents
Culture Documents
controlled by a 25 kV, 1600 Amps rating vacuum circuit Series reactor of rating 36 kV, 79 Amps is connected on
breaker. neutral side of the capacitor bank. Each capacitor bank
is controlled by a 33 kV, 3-Pole, 1250 Amps rating SF6
AE signals were measured through AEPD hot-stick circuit breaker suitable for direct switching of 20 W A R
mounted individually on 9 capacitors arranged at the 33 kV capacitors.
bottom most row of the bank when the capacitors
were under normal operating voltage of 25 kV. PDs in the above bank were monitored during circuit
Figure 2 shows the mounting of AEPD hot-stick on bxeaker operations. The Client was also interested in the
one of the capacitors. magnitudes of switching transients experienced by the
capacitor bank.
No PDs were observed from the capacitor under the
normal operating condition as shown in Table 1. The arrangement for measuring the switching transient
voltage and current is shown in Figure 3. High voltage
probes, 3 numbers, were connected to RYB phases of
the bank at point of connection of incoming 33 kV
Table 1: Results of AEPD measurement on 25 kV
w. XLPE cable. 3000 Amps CTs were clamped on the heat
shrink terminations of 33 kV XLPE cable. Switching
1 Capacitor I Voltageon I Threshold 1 Measured I transients were recorded during six switching operations
of the Circuit breaker with the help of high voltage
probes and CTs connected to a Power Analyzer (RPM
make and model No. 1656).
Figure 3: Figure 4:
Arrangement for Placement of AEPD
measuring Switching hot-stick on the live
transients at the capacitor container for
Figure 2: Arrangement for measuring AE PD from incoming H V terminals PD measurement.
25 kV Capacitor bank at Railway Traction of a 36 kV capacitor
Substation. bank.
PD measurement on a 36 kV, 6.5 MVAR capacitor The magnitudes of partial discharges in 6 capacitors a~
bank at a 220 kV Receiving Station given in Table 2 along with the magnitude of transient
voltage. The reported AEPD values take into account
The capacitor bank details are as follows: the attenuation of AE signals through capacitor
.
8
Voltage rating of the bank: 36 kV ac
Unit capacitor rating: 6.98 kV / 181 kvar
Total number of capacitors in each bank: 36
dielectric and also along the AEPD hot stick.
A typical transient event recorded during switching 36 kV capacitor bank at 220 kV Receiving station:
operation of the circuit breaker is shown in Figure 5. Capacitor banks in service invariably experience
transient over voltages and currents due to periodic
switching operations of the circuit breaker. Pre-mature
failure of capacitors occurs if (a) the switching
transients are of higher magnitudes than the specified
limits or (b) the capacitors are not designed to
accommodate rated transients. There are several reports
of premature failure of capacitors during switching
operations. One of the serious effects of such over
voltage effects is the occurrence of partial discharges in
capacitor insulation system. At present, there are no
comprehensive diagnostic techniques to assess the
performance of capacitor banks in service particularly
due to switching transients. CPRI has created necessary
facilities for undertaking field measurement at the
request of capacitor industry. At the request of one of
the capacitor users, a 36 kV capacitor bank was tested
on-line for checking its performance during switching
Figure 5 (a): Voltage (rms) recorded during a operation of the circuit breaker.
switching operation of a SF6 circuit breaker.
Figure 5(a) gives voltage (rms.) recorded during a
switching operation of the circuit breaker. The power
anlyzer records system disturbances as EVENT. It can
be observed in Figure 5 (a) that during switching on the
circuit breaker, an event of transient over
voltage(TOV1) and over current has been experienced
by the capacitor bank. The details of TOVl along with
c m n t are shown in Figure 5(b). According to IEC 871
Part 1: 1997, the first peak of transient over voltage
should not exceed 242 times the rated voltage (rms.
value) for a duration of Vi cycle. Hence, for a 33 kV
system, TOV should not exceed 93.3 kV. The maximum
value of TOV recorded is around 93 kV (refer to Table
2). Therefore, switching transients appearing at the 36
kV capacitor bank are within the limits specified in IEC
871 Part 1: 1997.
CONCLUSIONS