ETAP

Project: Page: 1
Location: 12.6.0H Date: 04-04-2019
Contract: SN:
Engineer: Revision: Base
Study Case: CD
Filename: kablovi Study: Uniform Ampacity

Analysis Results (RW2)


0.00
Conductor Energized Rdc @ Dielectric Conductor
per Conductor Final Temp. Losses Losses Current Temp.
No. Cable ID Conduit/Location ID Cable per Cable µOhm/m Watt/m Yc Ys Watt/m Amp °C

1 Cable1 Loc1 3 3 490.12 0.000 0.001 0.003 21.641 121.24 87.82

2 Cable2 Loc2 3 3 493.43


2.00 0.000 0.001 0.003 21.786 121.24 89.99

3 Cable3 Loc3 3 3 490.12


3.00 0.000 0.001 0.003 21.641 121.24 87.82

Yc = Increment of AC/DC resistance ratio due to AC current skin and proximity effect
Ys = Increment of AC/DC resistance ratio due to losses of circulation and eddy current effect in shield , sheath and armor