You are on page 1of 1

Sheet1

Calculation Below Using R-Value for one inch of insulation Calculation Below Using R-Value for one inch of insulation

RCA minus Re from above 10.05506331 13.12542182 7.286423074 9.578835444 4.716747019 6.543949049 10.05506331 RCA minus Re from above
Thermal thickness in inches (variable) 1 1 1 1 1 1 1 Thermal thickness in inches (variable)
Total insulation addon to outside diameter (2 x thickness) DI'' 2 2 2 2 2 2 2 Total insulation addon to outside diameter (2 x thickness) DI''
Raceway O.D. from above DC'' 1.163 1.315 1.74 1.9 3.5 3.5 1.163 Raceway O.D. from above DC''
R value for one inch of insulation in BTUth-in / hr-ft*ft-F 3.125 3.125 5.883 5.883 3.125 3.125 3.125 R value for one inch of insulation in BTUth-in / hr-ft*ft-F
693.81 times R-Value to convert to degrees-cm/Watt) 2168.15625 2168.15625 4081.68423 4081.68423 2168.15625 2168.15625 2168.15625 693.81 times R-Value to convert to degrees-cm/Watt)
RI'' thermal ohm feet for insulation 11.30527344 10.44768012 16.27721894 15.2970589 5.107169541 5.107169541 11.30527344 RI'' thermal ohm feet for insulation

Calculation of Re''' for outside thermal insulation Calculation of Re''' for outside thermal insulation
Ds''' outside diameter of thermal barrier 3.163 3.315 3.74 3.9 5.5 5.5 3.163 Ds''' outside diameter of thermal barrier
e''' emissivity .3 for dull, .95 for foil covered) 0.3 0.3 0.3 0.3 0.3 0.3 0.3 e''' emissivity .3 for dull, .95 for foil covered)
Re''' 5.915635564 5.698626631 5.168492867 4.993604682 3.731099038 3.731099038 5.915635564 Re'''

RCA''' (RCA-Re+RI'''+Re''') 27.27597232 29.27172858 28.73213488 29.86949903 13.5550156 15.38221763 27.27597232 RCA''' (RCA-Re+RI'''+Re''')

New ampacity with thermal insulation using R-Value 103.8883418 100.2842544 139.9609115 139.8490595 380.5393007 376.3616671 103.8883418 New ampacity with thermal insulation using R-Value
Thermal Derating Factor with R-Value 80.74% 83.03% 67.16% 78.13% 76.11% 88.32% 80.74% Thermal Derating Factor with R-Value