Professional Documents
Culture Documents
Abstract--In this paper, a novel simplified probabilistic technique In this paper, the faulty phase is identified using a
is investigated to identify the faulty phase. Estimating the faulty simplified probabilistic method applied on the DWT-based
phase enhances the operation of single-pole autoreclosure which extracting transient features. The algorithm performance is
is applied in Europe countries. The proposed technique is based verified for resistive fault and arcing fault types. The algorithm
on the probability tail functions applied on the standard procedure is depending on standard deviations of DWT detail
deviations of Discrete Wavelet Transforms (DWT) of the phase coefficients of the phase currents. A novel discriminator is
currents. An adaptive setting is proposed to be suitable for investigated to estimate the faulty phase where it is depending
different faulty phase. The setting signal is selected as the on the probability that the phase random transient currents will
maximum standard deviation of the DWT of phase currents. The
exceed a given threshold. This probability is found suitable for
earth faults and phase faults are correctly discriminated.
discriminating between the healthy and faulty phases. A
Validation of the proposed algorithm is verified via ATP/EMTP
simulation. Test results corroborate evidence of the efficacy of practical 400 kV transmission line is simulated in ATP/EMTP
proposed technique. where ATPDraw is used as a graphical interface. The fault
model is incorporated at different locations and the considered
I. INTRODUCTION arcs are implemented using a universal arc representation.
Start
1
i
G= (6)
Currents (ia, ib, ic) Currents at the
u st
measuring node
u st = (u o + r i )l (7)
(ia, ib, ic)
Current (A)
Fig. 3 EMTP network of arcing fault interaction. 0
-2000
B. Earth Faults -4000
1000
-1000
small in magnitude. Also, it is expected a delay due to DWT -2000
usage; however, such delay is depending on the DWT filter -3000
2 0.4
1 0.2
0
0 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 Time (s)
Time (s)
a. At Bus A. a. At Bus A.
1.4
9
P
IB a
StdIB a
8 1.2 P
IB b
StdIB b
P
7 IB c
StdIB c 1
6
0.8
5
4 0.6
3 0.4
2
0.2
1
0
0 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
Time (s)
b. At Bus B. b. At Bus B.
Fig. 6. The standard deviation of DWT detail d1 shown in Fig. 5. Fig. 8. The performance during the arcing fault case at 40 km.
1.4 10
PIA a d1IA a
1.2 PIA b d1IA b
PIA c 5 d1IA c
1
0.8
0
0.6
0.4 -5
0.2
0 -10
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.03 0.032 0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05
Time (s) Time(s)
PIB c d1IB c
1
5
0.8
0
0.6
-5
0.4
-10
0.2
0 -15
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.03 0.032 0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05
Time (s) Time(s)
In Figs. 9.a and b, the initial transients are only localized in 0.8
technique can estimate the fault type is phase fault type as two 0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
discriminators are one while the third one is zero.
d. Discriminator performance at Bus B.
Fig. 9. The performance during the phase fault case at 50 km.
The probability Using Detail level d1
80 1.4
d1IA a PIA a
60
d1IA b 1.2 PIA b
40
d1IA c PIA c
20 1
0 0.8
-20
0.6
-40
-60 0.4
-80
0.2
-100
0.03 0.032 0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05
0
Time(s) 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
a. DWT detail level d1 at Bus A.
150 a. At Bus A.
d1IB a 1.4
d1IB b PIB a
100 1.2
d1IB c PIB b
PIB c
1
50
0.8
0
0.6
-50 0.4
0.2
-100
0.03 0.032 0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05
Time(s) 0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
b. DWT detail level d1 at Bus B.
1.4 b. At Bus B.
PIA a
1.2 PIA b
Fig. 11. The performance during three-phase fault at 50 km.
PIA c
1 The probability Using Detail level d1
1.4
P IA a
0.8
1.2 P IA b
0.6 P IA c
1
0.4
0.8
0.2
0.6
0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
0.4
c. Discriminator performance
The probability Using Detail level d1at Bus A.
1.4 0.2
PIB a
1.2 PIB b 0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
PIB c Time (s)
1
a. At Bus A.
0.8 1.4
P IB a
0.6 1.2 P IB b
P IB c
0.4 1
0.2 0.8
0 0.6
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
0.4
d. Discriminator performance at Bus B.
0.2
Fig. 10. The performance during the phase a-b to ground fault case.
0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time (s)
On the other hand, when the fault is phase a to b to ground
b. At Bus B.
fault, the corresponding performance is shown in Fig. 10. The Fig. 12. The performance during switching of Bus A.
transients are localized in all phases at both Bus A and B as
depicted in Fig. 10.a and b, respectively. In Figs. 10.c and d,
D. Switching
the performance is indicating that the faulty phase is phase c,
however, the discriminator of other phases are not equal. Fig. 12 illustrates the performance during switching case
Therefore, the fault is not phase to ground fault as the security when the switch at Bus A is closed at 32, 36 and 42 ms for
condition is not achieved. phases-a, b and c, respectively. The transients are localized in
For a three-phase fault case occurred at 32 ms and its all phases, however, the probability of the lowest two phases
location is at 50 km, Fig. 11 illustrates the discriminator are not equal. Therefore, these transients are not due to earth
performance where the lowest Discriminators, which are phase faults and the discriminator response could not be taken into
a and b, are not equal. Therefore, the fault is phase type not account. For another switching case where the closing of
earth fault type. breaker poles are simultaneous at 32 ms, the security is also
attained; however, this test case is not presented as the breaker
poles are not practically closing simultaneously.
IV. CONCLUSIONS [4] S. Hanninen, M Lehtonen and U. Pulkkinen “A Probabilistic Method
for Detection and Location of Very High Resistive Earth Faults”
Performance of a simplified probabilistic approach for Electric Power System Research, vol. 54, no. 3, pp. 199-206, June
identifying phase faults has been investigated. The fault 2000.
features have been extracted using DWT. The standard [5] N. Elkalashy, N. Tarhuni and M. Lehtonen “Simplified Probabilistic
Selectivity Technique for Earth Fault Detection in Unearthed MV
deviation of the DWT phase currents has been computed to
Networks” Accepted at IET Transactions on Generation, Transmission
localize the fault transients. The technique performance has and Distribution.
been evaluated considering different fault types; earth and [6] Handbook of Mathematical Functions: With Formulas, Graphs, and
phase faults and considering switching as well. Therefore, Mathematical Tables, edited by Milton Abramowitz and Irene A.
Stegun, Tenth edition, 1972.
sensitive and secure detection of the faulty phase has been [7] Wavelet Toolbox for MATLAB, Math Works 2005.
attained using DWT and probability. [8] L. Prikler and H. Hoildalen, ATPDraw users' manual, SINTEF TR
A4790, Nov. 1998.
V. APPENDIX [9] M. Kizilcay and T. Pniok, “Digital Simulation of Fault Arcs in Power
systems,” Europe Transaction on Electrical Power System, ETEP, vol.
A. DWT 4, no. 3, pp. 55-59, Jan./Feb. 1991.
Wavelets are families of functions generated from one [10] H. Darwish and N. Elkalashy “Universal Arc Representation Using
EMTP,” IEEE Trans. on Power Delivery, Vol. 2, no. 2, pp 774-779,
single function, called the mother wavelet, by means of scaling April 2005.
and translating operations. The scaling operation is used to [11] M. Solanki, Y. Song, S. Potts and A. Perks "Transient protection of
dilate and compress the mother wavelet to obtain the transmission line using wavelet transform" Seventh International
respective high and low frequency information of the function Conference on Developments in Power System Protection,(IEE), pp.
299–302, 9-12 April 2001.
to be analyzed. Then the translation is used to obtain the time
information. In this way, a family of scaled and translated
wavelets is created and it serves as the base for representing U SA_A S A F B R SB_B U
the function to be analyzed [11]. The DWT is in the form:
1 k − nbo aom
DWTψ f (m, k ) =
aom
∑ x(n)ψ (
n aom
) (6)
SW
B. Simulated System
Fig. 13.a illustrates the considered ATPDraw network. It G
contains the transmission system shown in Fig. 2 and the
universal arc representation illustrated in Fig. 3. The
transmission line is represented using a frequency dependent a. ATPDraw network
JMarti model where the configuration is shown in Fig. 13.b.
DC Resistance = 0.036 Ω/km
Thevenin’s equivalent impedances at busses A and B are Outer diameter = 1.46 cm
described using mutual coupled R-L circuit as: the positive
sequence is R1= 1.0185892 Ω and L1= 50.9295 mH, and the At Tower = 30.5 m
Midspan = 23.2 m
zero sequence is R0= 2.0371785 Ω and L0= 101.85891 mH.
Separ= 40 cm
Alpha = 0o
VI. REFERENCES At Tower = 21.63 m NB = 2
Midspan = 9.83 m DC Resistance = 0.0522 Ω/km
[1] N. Elkalashy, H. Darwish, A-M. Taalab, and M. Izzularab, "An Outer diameter = 3.18 cm
Adaptive Single Pole Autoreclosure Based on Zero Sequence Power"
Electric Power Systems Research, vol. 77, no. 5-6, pp. 438-446, April
2007.
[2] Z. Bo, R. Aggarwal, A. Johns, H. Li and Y. Song “A new Approach to
Phase Selection Using Fault Generated High Frequency Noise and
Neural Networks” IEEE Transactions on Power Delivery, Vol. 12, No. 1,
pp. 106-115, Jan. 1997. b. Transmission Line Configuration
[3] P. Silveira, R. Seara and H. Zurn “An Approach Using Wavelet Fig. 13 Simulated Systems.
Transform for Fault Type Identification in Digital Relaying” IEEE
Power Engineering Society Summer Meeting, Edmonton, Alta., Canada,
18-22 July 1999.