Professional Documents
Culture Documents
instructions
Belt-driven
screw compressor
S 10 – S 29-2
SF 15 – SF 29-2
separate manuals:
compressor control /
frequency converter
Index
Operating instructions
for the belt-driven
screw compressors
– S 10 (10 Hp)
– S 15 (15 Hp)
– S 20-2 (20 Hp)
– S 24-2 (25 Hp)
– S 29-2 (30 Hp)
– SF 15 (15 Hp)
– SF 24-2 (25 Hp)
– SF 29-2 (30 Hp)
BOGE KOMPRESSOREN
Postfach 10 07 13
D-33507 Bielefeld
Germany
Otto-Boge-Straße 1–7
D-33739 Bielefeld
As of 09 / 2007
No. 596.0860.18
Nominal price: US $ 5.00
Index
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page III
Inhalt.pm6.5 - USA
Index
Part 6:
Appendix
6.1 Flow chart ....................................................................................... 6.1
Air cooled version, standard ............................................................. 6.1
Air cooled version, standard (Series SF 15 – SF 29-2) ..................... 6.2
WARNING!
Nonobservance of the following safety instructions may lead to injuries
and damage to the compressor.
Also observe the generally valid safety and accident prevention regu-
lations in addition to the information in these operating instructions!
Safety instructions for 1. Ensure that no commissioning or maintenance work on the compressor
compressor operation be undertaken until these operating instructions are understood.
2. Only use the compressor for its intended use, as described in these op-
erating instructions.
3. The owner must ensure
– that only appropriately trained and authorized personnel work on this
compressor.
– that the operating, maintenance and repair personnel has been made
fully familiar with all safety instructions, and that they are being ob-
served.
– that the compressor is only operated in a safe operating condition.
4. Avoid any operating method which may impair the safety of the com-
pressor.
5. Do not exceed the limit value for the final compression pressure specified
on the type plate.
6. Do not operate the compressor without the attendant protection and
safety devices.
Do not dismantle any built-in safety devices or put them out of operation.
Ensure that all safety cladding and doors are closed prior to commis-
sioning/starting up the compressor and are not opened during operation.
7. Place the compressor out of operation as described in these operating
instructions, when dismantling the safety cladding or safety devices for
repair or maintenance work. Reattach and close all cladding and safety
devices immediately upon completion of the repair or maintenance work.
8 Only operate the compressor using the additional equipment (options)
recommended or authorized by the manufacturer.
9. Undertake conversions and modifications of the compressor only in
agreement with BOGE, taking all relevant safety regulations into consid-
eration.
The manufacturer is not liable for damages resulting from independent
modifications on the compressor.
10. Never start the compressor when one or serveral parts (e.g. cable, plug)
are damaged, when not in perfect working order, when damage is detected
or suspected.
11. Observe all safety and danger signs directly attached on the compressor!
12. The compressed air/oil receiver is subject to "Druckgeräterichtlinie"
(Recommendation for compressors) and has to be checked in prescribed
intervals.
13. To avoid damages, special precautions have to be taken during (re-) opera-
tion of compressors with frequency control, if the frequency converter
was cut off from the power supply for a longer period of time (> 12 months).
In this case please contact the BOGE-Service.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 1.1
Allgemeines.pm6.5 - USA
General 1.1 General safety instructions
Safety instructions for 1. Ensure that maintenance work is only carried out by appropriately trained
maintenance and repair persons.
of the compressor 2. Ensure that setting work, malfunction rectification and repair are only
carried out by specialists or appropriately trained persons.
3. Prior to maintenance or repair work:
– Switch off main switch.
– Secure main switch against unintentional switch-on.
– Check to ensure that all parts have been isolated.
– Disconnect compressor from compressed air network (relieve or block
pressurized lines).
4. Exercise extreme caution during repair or maintenance work requiring
compressor to be operational.
Ensure that no persons are located in the hazardous area.
5. Ensure that work on the electrical equipment is only undertaken by quali-
fied electricians.
6. Work on voltage carrying parts and devices are not permitted. Exceptions
are governed by the appropriate regulations.
CAUTION
7. Only use original spare parts, compressor oils and operating
materials released by BOGE during repair or maintenance.
8. The operator is required to check the compressor daily for externally vis-
ible damage and defects, and to immediately report any changes (includ-
ing operational behavior).
9. When the automatic restart (Auto-Restart) is activated, the compressor
restarts automatically following a voltage loss.
Only under the condition, that the net pressure is lower than the set
switch-on pressure.
Accident prevention The owner of a compressor plant is required to ensure that it is properly in-
regulations stalled, operated and maintained.
Page 1.2 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Allgemeines.pm6.5 - USA
General 1.1 General safety instructions
WARNING!
Failure to adhere to these recommendations can result in mechanical failure,
property damange and serious injury or death.
All air and water inlet, and air and water discharge pipework to and from the
inlet and discharge port connections must take into account vibration, pul-
sations, temperature, maximum pressure applied, corrosion and chemical
resistance. In addition, it should be noted that lubricated compressors will
discharge some oil into the air stream; therefore, compatibility between dis-
charge piping, system accessories and software must be assured.
For the foregoing reasons, the use of plastic piping, and soldered copper fit-
tings as discharge piping is not recommended. In addition, flexible joints and/
or flex lines can only be considered for such purposes if their specifications
fit the operating parameters of the system.
It is the responsibility of the installer and owner to provide the appropriate
service pipework to and from the machine.
WARNING!
Statement concerning the inadvertent breathing of compressed air
exhaust.
The purchaser/user shall ensure that adequate ventilation and make-up air
are provided if a non-BAP designated compressor supplies air in a confined
area to air consuming devices such as air motors, air tools, solenoids, air
cylinders, air guns, nozzles, etc. The compressed air discharge stream may
contain residual coolants/lubricants/carbon monoxide and condensable
hydrocarbons or other materials which may be hazardous to health with pro-
longed inhalation.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 1.3
Allgemeines.pm6.5 - USA
General 1.2 Introduction
The purpose of these operating instructions is to familiarize the user with the
function and all application possibilities of the compressor.
These operating instructions contain important information on how to operate
the compressor safely, economically and according to its intended use. Ob-
serving these operating instructions will assist in avoiding danger, to reduce
repair costs and downtimes and to increase the reliability and service life of
the compressor. It contains important information concerning the required
maintenance and repair measures, assists in case of malfunctions and con-
tains data concerning spare and wearing parts.
The operating instructions must at all times be made available to the com-
pressor operating personnel at the place of operation.
The operating instructions must be carefully read and applied by all persons
engaged to undertake the following work on the compressor:
– Operation, including fault rectification and daily care
– Maintenance (service, inspection, repair)
– Commissioning
– Transportation
The compressor and its additional equipment must not be installed and
commissioned until the operating instructions are understood.
These operating instructions can be supplemented with instructions on the
basis of existing national regulations concerning accident prevention and
environmental protection.
In the illustrations, the compressor is shown in part without safety cladding
or safety devices for better visualization. However, operation without these
components is prohibited!
WARNING!
Warning is used to indicate the presence of a hazard which can cause se-
vere personal injury, death, or substantial property damage if the warning is
ignored.
CAUTION!
Caution is used to indicate the presence of a hazard which will or can cause
minor personal injury or property damage if the warning is ignored.
NOTICE!
Notice is used to notify people of installation, operation, or maintenance in-
formation which is important but not hazard-related.
Page 1.4 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Allgemeines.pm6.5 - USA
General 1.2 Introduction
NOTICE
Refer to the
Instruction/Operators Manual
before performing any
maintenance.
Warning:
The unit is operated by remote control,
and might start without warning. NOTICE
Frequency converter
Do not operate without
only SF enclosure panels & forklift
covers in place.
Refer to the
Instruction/Operators Manual
before performing any
NOTICE maintenance.
NOTICE
Rotation.
WARNING
Hot surface.
Can cause severe injury.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 1.5
Allgemeines.pm6.5 - USA
General 1.2 Introduction
DANGER
Discharge air.
Can contain carbon monoxide
or other contaminants. Will
cause severe injury or death.
NOTICE
Air discharge.
Prohibited:
Never open the valve before
the air hose (connection to
the compressed air network)
is connected.
NOTICE
Lift here.
WARNING WARNING
WARNING WARNING
Page 1.6 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Allgemeines.pm6.5 - USA
General 1.2 Introduction
Intended use BOGE S series screw compressor, including its additional equipment, is ex-
clusively intended for the compression of air.
The air taken in must not contain any explosive or chemically instable gases
or vapors.
Do not exceed specified final compression temperature.
Inadmissible use Never direct the produced compressed air towards persons. Danger to life!
WARNING!
Statement concerning the use of this equipment for breathing air and/
or aqua lung service. If the model number on this air compressor contains
the letters "BAP", the compressor is suitable for use in breathing air services.
In the absence of such a designation, the compressor is NOT considered as
capable of producing air of breathing quality. For a compressor to be capable
of use in breathing air services it must be fitted with additional specialized
equipment to properly filter and/or purify the air to meet all applicable federal,
state and local laws, rules, regulations and codes, such as, but not limited
to, OSHA 29 CFR 1910.134, Compressed Gas Association Commodity
Specification G-7, 1-1966, Grade D Breathing Air and/or Canadian Standards
Association. Should the Purchaser and/or User fail to add such specialized
equipment and proceeds to use the compressor for breathing air service,
the Purchaser/User assumes all liability resulting therefrom without any re-
sponsibility or liability being assumed by BOGE COMPRESSORS.
The Purchaser is urged to include the above provision in any agreement for
any resale of this compressor.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 1.7
Allgemeines.pm6.5 - USA
General 1.2 Introduction
Transportation BOGE does not accept any liability for breakage or transportation damage.
damage Please inspect the compressor immediately after delivery and direct dam-
age claims to the last carrier – even when the packing is not damaged!
To safeguard claims against the carrier we recommend leaving the machine,
devices and packing material in the same condition as they were in when
the damage was detected.
In the event of any other complaints, please inform us within six days after
arrival of the delivery.
Data Enter the data of your compressor from the type plate or enclosed data
on the type plate sheet in the illustration below. This will ensure that in the event of enquiries,
you will always have the most important data at hand.
Service Please do not hesitate to contact BOGE service if you have any questions.
Please call:
770 - 448 - 5995
In the event of inquiries, always specify the following data of your compres-
sor to prevent any delays:
– Type
– Year of manufacture
– Machine number
NOTICE!
Only BOGE service technicians or persons authorized by BOGE in writing
may repair or alter the compressor during the warranty period. Otherwise all
warranty claims will expire!
Page 1.8 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Allgemeines.pm6.5 - USA
Product description 2.1 Technical data
Dimensions
– Height (super silenced) [inch] 38.5 38.5 45.5 45.5 45.5
– Width [inch] 37 37 47.5 47.5 47.5
– Depth [inch] 27.5 27.5 33.5 33.5 33.5
Weight
– super silenced [lbs.] 463 484 700 803 803
Compressor
max. final compression temperature [°F] 230 230 230 230 230
Volume flow according to
ISO 1217 Part C:
– pmax = 100 psig [cfm] 44 62 94.3 113.5 128.6
– pmax = 115 psig [cfm] 42 58 90.8 107.7 121.8
– pmax = 150 psig [cfm] 38 51 79.1 93.9 109.8
– pmax = 190 psig [cfm] 33 44 67.1 79.8 90.8
Drive motor
Rated power [Hp] 10 15 20 25 30
Rated speed
– 60 Hz [min-1] 3600 3600 3600 3600 3600
Electrical connection
200 / 230 / 200 / 230 / 200 / 230 / 200 / 230 / 200 / 230 /
Mains voltage 1) [V]
460 / 575 460 / 575 460 / 575 460 / 575 460 / 575
Frequency 1) [Hz] 60 60 60 60 60
40 / 40 / 50 / 50 / 70 / 60 / 100 / 70 / 100 / 100 /
Recommended fuse protection (CL RK5) [A]
25 / 15 25 / 20 30 / 30 40 / 30 50 / 40
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 2.1
Produkt.pm6.5 - USA
Product description 2.1 Technical data
Safety valve
Activation pressure at:
– pmax = 100 psig [psig] 160 160 160 160 160
– pmax = 115 psig [psig] 160 160 160 160 160
– pmax = 150 psig [psig] 160 160 160 160 160
– pmax = 190 psig [psig] 203 203 203 203 203
1
) Compressors for other operating pressures Pmin = Pmax minus (–) 14.5 psig.
Page 2.2 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Produkt.pm6.5 - USA
Product description 2.1 Technical data
Dimensions
– Height (super silenced) [inch] 46.5 45.2 45.2
– Width [inch] 37.0 47.5 47.5
– Depth [inch] 27.5 33.5 33.5
Weight
– super silenced [lbs.] 562 803 803
Compressor
max. final compression temperature [°F] 230 230 230
Volume flow according to
ISO 1217 Part C:
– pmax = 100 psig [cfm] 18 – 62 31 – 113 37 – 129
– pmax = 115 psig [cfm] 17 – 58 30 – 108 36 – 122
– pmax = 150 psig [cfm] 14 – 51 22 – 94 31 – 110
– pmax = 190 psig [cfm] 14 – 44 16 – 80 25 – 91
Drive motor
Rated power [Hp] 15 25 30
Rated speed
– 60 Hz [min-1] 3600 3600 3600
Electrical connection
Mains voltage 1) [V] 460 460 460
Frequency 1) [Hz] 60 60 60
Recommended fuse protectoin 2) [A] 30 40 50
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 2.3
Produkt.pm6.5 - USA
Product description 2.1 Technical data
Safety valve
Activation pressure at:
– pmax = 100 psig [psig] 160 160 160
– pmax = 115 psig [psig] 160 160 160
– pmax = 150 psig [psig] 160 160 160
– pmax = 190 psig [psig] 203 203 203
1
) Compressors for other operating pressures Pmin = Pmax minus (–) 14.5 psig.
2
) Specifications as to residual pressure of fan cooling air refer to max. speed.
Page 2.4 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Produkt.pm6.5 - USA
Product description 2.2 Function description
Function principle The air end operates according to the displacement principle. In the housing,
of the air end the main and secondary screws are driven by means of an electric motor
and V-belt.
Both screws have screw-shaped profiles, intermeshing without contact.
Together with the housing wall, these screws form chambers which gradually
reduce in size, seen in air flow direction.
Rotation of the rotors causes the air taken in to be compressed to the final
pressure in the chambers.
During compression oil is continuously injected into the air end. This having
a cooling, sealing and lubricating function.
Air circuit
1
3 4 5
2
8 7 Fig. 2.1:
6
Components of
the air circuit
1 = Intake filter
The intake filter cleans the air suctioned by the air end.
2 = Intake regulator
The intake regulator opens (load operation) or closes (idling operation or
standstill) the suction line depending on the operating condition of the com-
pressor.
3 = Air end
The air end compresses the suctioned air.
4 = Compressed air/oil receiver
The compressed air separates from the oil under the force of gravity in the
compressed air/oil receiver.
5 = Oil separator
The oil separator separates the residual oil contained in the compressed air.
6 = Minimum pressure check valve
The minimum pressure check valve does not open until the system pressure
has increased to 3.5 bar (51 psig). This causes a rapid build-up of the system
pressure and ensures lubrication in the starting phase. Once the compressor
has been switched off, the check valve prevents the compressed air from
flowing back out of the mains line.
7 = Compressed air after-cooler (air and water cooled)
The compressed air is cooled in the compressed air after-cooler, causing the
water contained in the air to condensate.
8 = Stop valve
The screw compressor may be isolated from the mains by means of the stop
valve.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 2.5
Produkt.pm6.5 - USA
Product description 2.2 Function description
Oil circuit The oil injected into the air end has the following function:
– It dissipates the compression heat (cooling).
– It seals the gaps between the screws and between the screws and housing.
– It lubricates the bearings.
5 6
2
4
Fig. 2.2:
Components of the oil circuit
Page 2.6 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Produkt.pm6.5 - USA
Product description 2.3 Compressor control
Network pressure For the compressor, the pressure downstream of the check valve is termed
network pressure. The control system switches the compressor on and off
during operation depending on the network pressure.
Operating states All screw compressor controls are based on three basic operating states:
1. Load operation
– The compressor delivers its speed dependent maximum amount of
compressed air.
– It consumes its maximum energy.
2. Idling operation
– The compressor runs but does not deliver any compressed air.
– It consumes approx. 75% less energy than in load operation.
– When compressed air is required, it switches to load operation with-
out delay.
– Idling operation reduces switching frequencies which can damage the
drive motor, and reduces wear of the system.
3. Standstill ready for operation
– The compressor is standing still but ready for operation.
– When compressed air is required, it switches automatically to load
operation.
Operating modes The two most important operating modes are achieved by combining the
three operating states:
1. Intermittent operation
In intermittent operation the energy balance is perfect.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches
to standstill. It does not consume any energy.
– Once the pressure has dropped to the switch-on pressure pmin the
compressor switches back to load operation.
2. Continuous operation
Continuous operation limits the drive motor switching cycles and reduces
wear to the system.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches
to idling operation.
– Once the pressure has dropped to the switch-on pressure pmin the
compressor switches from idling operation back to load operation.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 2.7
Produkt.pm6.5 - USA
Product description 2.4 Control devices
Operating pressure The operating pressure transmitter controls the operation of the compres-
transmitter sor within the set switching limits.
Note:
Controlled operation If the pressure has dropped below the switch-on pressure Pmin the compres-
sor starts and operates in load operation.
Once the operating pressure Psoll has been exceeded the control is activated
and reduces the speed.
If the pressure has dropped below the operating pressure Psoll the control is
activated and increases th speed.
Upon reaching the switch-off pressure Pmax the compressor switches to idling
operation.
The settings for Pmin and Pmax are effected by the parameterization of the
RATIO.
The setting for Psoll is carried through at the potentiometer -R3 in the switch
cabinet of the compressor.
The serial setting is:
Pmax – 0,3 bar = Psoll
Pmax – 0,4 bar = Pmin
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
Page 2.8 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Produkt.pm6.5 - USA
Product description 2.5 Safety and monitoring devices
General The safety devices guarantee a high degree of operational safety, in connec-
tion with the BOGE monitoring system.
When one of the safety devices responds, the control system reacts as follows:
– The compressor is immediately switched off.
– A flashing fault number in the left field of the display indicates the cause
of the fault.
ATTENTION!
Do not operate the compressor without built-in safety devices.
Do not dismantle the safety devices or put them out of operation.
Safety temperature The safety temperature limiting device switches off the compressor once
limiting device the maximum admissible final compression temperature has been reached.
The compressor does not switch on when dropping below the minimum
temperature.
– While you see the flashing number, press button ↵ (Enter).
Fault is acknowledged.
– Rectify the fault.
– Switch on the compressor (ON button).
Note:
Monitoring the drive The following monitoring devices are standard for BOGE control systems:
and fan motor The drive motor is monitored by PTC resistors.
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 2.9
Produkt.pm6.5 - USA
Product description
Page 2.10 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Produkt.pm6.5 - USA
Installation 3.1 Transportation
General Please observe the generally accepted safety and accident prevention regu-
lations when transporting the compressor. BOGE accepts no liability for dam-
age caused by improper transport!
ATTENTION!
The compressor is delivered filled with oil.
Do not tilt during transport!
Crane conveyance
Only use suitable conveyer slings having a
minimum length of approx. 8 meters.
Position slings at the ends underneath the
base frame of the compressor.
ATTENTION!
Do not subject the safety cladding to force during transportation.
Protect compressor by using wooden spacers (see arrows).
Remove supporting timber beams.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 3.1
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room
Installation, mainte- – Protect compressed air receivers against damage through mechanical
nance conditions and effects (e.g. falling objects).
application for com- – Operate the compressed air receiver and its equipment from a safe location.
pressed air receivers – Adhere to safety areas and safety clearances.
arranged below or – Ensure that the compressed air receiver stands securely. It must not shift
separately or tilt due to external forces. This also includes the additional weight dur-
ing a pressure test!
– Ensure that the compressed air receiver is easily accessible from all sides
(for recurring tests).
– Ensure that the factory label is clearly visible.
– Ensure that compressed air receivers are adequatly protected against
corrosion.
– Only use the compressed air receiver for compressors operating with cut-
in and cut-out mode if the pressure fluctuation range amounts to Δ p ≤ 20 %
of the maximum operating pressure.
Installation surface A level industrial floor without foundation is adequate for the installation of
the compressor. No special fastening elements are required.
Fire protection The following applies to rooms in which compressors with oil injection cool-
ing are to be installed:
– For compressors with motor ratings exceeding 55 Hp, ensure that the
compressor room is equipped with special fire protection.
– Install compressors with motor ratings exceeding 136 Hp in a separate
fire protected room.
Sound protection Only install compressors in workrooms if the sound pressure level of
their measuring surfaces does not exceed 85 dB(A).
Page 3.2 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room
Admissible The compressor room must be clean, dry, cool and free of dust.
environmental
influences Admissible ambient temperatures
Maximum ambient temperature (for air cooling): + 104°F
Minimum ambient temperature: + 41°F
ATTENTION!
Nonobservance of the admissible ambient temperature may lead to the
following problems:
– Compressor will switch off when the admissible final compression
temperature is exceeded or gone below.
– Pipe lines and valves will freeze up at low temperatures.
– Damage due to reduced lubricating ability of compressor oil.
Ventilation If the following instructions are not observed, the admissible final com-
pression temperature may be exceeded.
In this case, compressor will switch off automatically.
Attention!
Arrange compressor intake openings or ducts in such way that dangerous
admixtures (e.g. explosive or chemically unstable materials) cannot be
drawn in.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 3.3
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room
Fans
Ensure that the heated exhaust air is not taken in again.
If necessary, the heated air must be extracted by exhaust fans.
To ensure perfect cooling even at higher temperatures in the summer, the
fans must be designed as follows:
– The fan capacity must be rated approx. 10 – 15% higher than the sum of
the cooling air quantity required for all machines operated in the room.
– For free-standing installation, the cooling air requirement specified in the
table corresponds to the required fan capacity.
Cooling air Please refer to the following table for the cooling air requirements and size
requirements of supply air openings for your compressor. Ensure that flaps and weather
protection grids have the necessary free cross section. It is recommend that
you contact a specialist company for performing the duct construction work
and planning.
Page 3.4 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Aufstellung.pm6.5 - USA
Installation 3.2 Compressor room
Ventilation
possibilities
A B
C D
Condensate The air taken in contains water in form of vapor, which turns into conden-
disposal sation during compression.
ATTENTION!
The condensate contains oil. Never lead it into the public sewage system
without prior treatment.
Strictly observe the effluent disposal laws of your local authorities.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 3.5
Aufstellung.pm6.5 - USA
Installation 3.3 Installation
General BOGE compressor units are supplied ready for connection. Only the work
described in the following paragraphs needs to be carried out during the in-
stallation.
ATTENTION!
Only have the installation work carried out by appropriately trained persons
or specialists.
Page 3.6 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Aufstellung.pm6.5 - USA
Installation 3.3 Installation
Connecting the – Connect the compressor to the compressed air network or a compressed
compressor to the air receiver.
compressed air For this, use a BOGE high pressure hose.
network Do not install a check valve in the pressure line.
The compressor is already equipped with a check valve.
Fig. 3.1:
Remove warm air hood
Note:
ATTENTION!
To avoid damage to the cooler, support the screw connection at the cooler
outlet using a spanner.
2 Electrical connection
Compressed air connection
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 3.7
Aufstellung.pm6.5 - USA
Installation 3.3 Installation
ATTENTION!
Do not loosen or change the sealed nuts for setting the spring tension.
1
1
Note:
Fig. 3.3: Activating the belt tensioning device
Checking the oil level BOGE compressors are supplied with a complete oil filling.
Prior to commissioning/start up, check the oil level as described in chapter
"Maintenance".
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
Page 3.8 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Aufstellung.pm6.5 - USA
Installation 3.4 Electrical connection
Main switch
The customer is responsible to provide the following safety measures:
Compressor plants having a drive motor larger than 4 Hp and current inten-
sities larger than 16 amperes must be equipped with a lockable main switch
and series fuses.
Please refer to the "Technical data" for the design and fuse rating.
Rated voltage
The data of your mains (operating voltage, control voltage, type of current,
frequency, ...) must coincide with the data on the type plate on the switch
cabinet.
In the event of deviations, please contact the BOGE service or your supplier.
Never omit a single safety step! Otherwise, you will risk injuries due to
restarting, electric shock or self-releasing parts.
WARNING!
When the automatic restart (Auto-Restart) is activated, the compressor will
automatically restart following a power failure.
Only under the condition, that the net pressure is lower than the set switch-on
pressure.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 3.9
Aufstellung.pm6.5 - USA
Installation 3.5 Commissioning
Ensure that the rotational direction coincides with the rotational direction
arrow on the air end.
– Switch on the main switch.
– Switch compressor on and immediately off again to check the rotational
direction.
Opening the stop valve Open ball valve on the compressor delivery.
Page 3.10 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Aufstellung.pm6.5 - USA
Installation 3.5 Commissioning
ATTENTION!
Only fill the suction controller with the grade of oil used to operate the com-
pressor.
Never mix different oil grades or brands.
Note:
Fig. 3.4: Suction controller
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 3.11
Aufstellung.pm6.5 - USA
Installation
Page 3.12 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Aufstellung.pm6.5 - USA
Faults 4.1 General
General The tables on the following pages give information on the possible causes
of operating faults and measures for their rectification (please also refer to
operating instructions of the compressor control).
ATTENTION!
Ensure that any work required to rectify faults is only carried out by trained
personnel or specialists.
Ensure that components which have a safety function are only set, repaired
or exchanged by BOGE Service!
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 4.1
Stoerung.pm6.5 - USA
Faults 4.2 General faults
Oil in suction filter Minimum pressure non- Check the minimum pressure check valve and
return valve is leaking replace, if necessary
Suction controller is leaking Check the suction controller and replace,
if necessary
Cut-out performed by Cut-out normally via O-key
emergency-off switch
Excessive oil Drain line is blocked Dismantle and clean drain line
consumption Defective oil separator Check oil separator and replace, if necessary
element
Excessive oil filling Drain off oil
Safety valve blows Operating pressure target Set operating pressure to maximum permissible
value maladjusted pressure of the screw compressor
Defective safety valve Replace safety valve
System pressure does Venting valve does not open Check venting valve and replace, if necessary
not decrease Check valve is leaking Check the check valve and replace, if necessary
when switch-
ing off
Page 4.2 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Stoerung.pm6.5 - USA
Maintenance 5.1 Safety instructions
ATTENTION!
Ensure that maintenance work is only carried out by specialists or appro-
priately trained person.
– Prior to starting any maintenance work, always stop the compressor as
described in these operating instructions prior to removing any safety
cladding or safety devices. Refit the safety cladding or safety devices im-
mediately upon completion of the maintenance work.
– Only use original spare parts, compressor oils and operating materials
released by BOGE for the maintenance work.
– When the automatic restart (Auto-Restart) is activated, the compressor
will start automatically following a voltage loss.
Only under the condition, that the net pressure is lower than the set
switch-on pressure.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.1
Wartung.pm6.5 - USA
Maintenance 5.2 General
Maintenance through Have BOGE-Service check your compressor every 3000 operating hours or
BOGE service annually.
Maintenance agreement
Enter into a maintenance agreement with BOGE.
BOGE service will carry out the proper maintenance on your compres-
sor at regular intervals.This guarantees maximum safety and realiability
of your compressed air supply.
Check or replace
supply air filter on
either side (with SF)
Check / adjust
pressure
Clean com-
Check suction filter pressed air/oil
– Clean filter and cartridge cooler externally
– Change filter cartridge
Change oil filter
Check V-belts
Change oil separator
Oil change
Page 5.2 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.2 General
Maintenance intervals The maintenance intervals specified in the table are based on average oper-
ating and ambient conditions.
Extreme conditions may require shorter maintenance intervals.
Note down any maintenance work in the table on the last page.
This will facilitate trouble shooting for BOGE service.
Oil change
Please change oil and replace oil filter and nozzle with dirt catch after the
first 500 operating hours!
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.3
Wartung.pm6.5 - USA
Maintenance 5.2 General
General
CAUTION: Risk of injury!
information Oil presents a potential danger to health and environment due to their
concerning additives.
the lubricants – Avoid contact with skin and eyes.
used Wear protective gloves made of resistant synthetic material.
Wash yourself thoroughly after contact with oils.
– Do not inhale the fumes or mist.
– Protect your environment.
Ensure that no oil is spilt.
– Fire, naked flames and smoking is strictly prohibited when handling
oil.
Page 5.4 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.2 General
Disposal of ATTENTION!
used The handling and disposal of mineral oils is subject to legal regulations.
operating It is an offense not to ensure correct and safe disposal of old oil!
material Please instruct one of the known service companies to dispose of used
operating materials or deliver them to an authorized disposal point.
ATTENTION!
If the nozzle with dirt catch is soiled the oil consumption may increase sig-
nificantly!
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.5
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
Draining off the Draining: If no automatic condensate darining is fitted, then drain off the
condensate from the condensate at least once a week.
compressed air
The compressor is lubricated with oil. The condensate contains oil and may
receiver not be drained off into the public sewage system!
(option) Pay attention to the pertaining rules and regulations of your local authorities!
Fig. 5.2:
Draining off the condensate manually
Draining off the The fully automatic, electronically controlled condensate separator is
condensate from the equipped with a wear free sensor which monitors the condensate level in
compressed air receiver the integrated collecting basin. As soon as the collecting basin is full, a
solenoid valve opens and the condensate is drained off.
with automatic
condensate Unlike the Konsatronik the fuilly automatic condensate separator operates
without causing any pressure losses. In the event of a malfunction a red
separator LED lights up and a potential-free contact is switched.
(option) Regularly check the function using the additional test switch on the device.
Condensate
Condensate
outlet (to oil-
shut-off valve
water separator)
on receiver
Page 5.6 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
Note:
Fig. 5.4: Change suction filter
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.7
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
Lubricating the As a rule, the bearings of the drive motors are provided with a maintenance
drive motor free permanent lubrication.
The drive motor of some series are equipped with a post-lubricating unit.
bearings
These motors can be easily recognised by the two grease nipples on the
upper side of the housing. In addition, plates on the compressor indicate the
type of motor lubrication.
Drive motors with Under normal operating conditions (coolant temperature max. 105°F,
permanent lubrication continous operation) the bearings are maintenance free for the service
life.
ATTENTION!
Have BOGE service dismantle the bearings and install new bearings once
the specified service life has expired!
Page 5.8 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
The BOGE GM drive system automatically adjusts the V-belt to the correct
V-belt tension in any operating mode.
Thus maintenance of the V-belt drive is limited to the above mentioned work.
Note:
Fig. 5.5: Lifting the motor plate
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.9
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
S 15 / SF 15 7 90
S 15 / SF 15 8 90
S 15 / SF 15 10 90
S 15 / SF 15 13 90
S 20-2 7 90
S 20-2 8 90
blue 1 S 20-2 10 90
S 20-2 13 90
S 24-2 / SF 24-2 7 112
S 24-2 / SF 24-2 8 112
S 24-2 / SF 24-2 10 112
S 24-2 / SF 24-2 13 112
S 29-2 / SF 29-2 7 98
S 29-2 / SF 29-2 8 99
S 29-2 / SF 29-2 10 99
S 29-2 / SF 29-2 13 100
The settings shown in the table are fixed by the manufacturer and may not
be changed. Slight deviations are allowed and compensated by the GM
drive system.
The current settings are also shown on a sticker on the GM drive system.
With special versions the settings on the sticker may deviate from the stan-
dard values.
If the spring is not pre-tensioned at the set measure, the measure must be
reduced until the spring is slightly pretensioned (to prevent the spring clap-
ping).
Page 5.10 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
ATTENTION!
Always use the same oil type when topping up.
Never mix different oil types and brands.
Note:
Fig. 5.6: Checking the oil level, topping up oil
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.11
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
ATTENTION!
Do not use tools to screw in the new oil filter!
You might damage the oil filter or its sealing ring.
A hand tight seating of the oil filter is sufficient.
– Reattach safety warm air hood.
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Subsequently, check the oil filter for leaks once again and tighten by
hand, if necessary (procedure as described above).
Page 5.12 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
Note:
Fig. 5.7: Change oil filter
Changing the Change: – When warning message "8" appears on the control
oil separator system display (RATIO only).
– After 3000 operating hours,
however, no later than after one year.
If the prescribed maintenance intervals are not observed, the oil sepa-
rators might become blocked. In this case, the differential pressure will
increase until the safety valve blows.
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.13
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
ATTENTION!
Do not use tools to screw in the new oil separators!
You might damage the oil separators or their sealing rings.
A hand tight seating of the oil filter is sufficient.
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Subsequently, check the oil filter for leaks once again and tighten by hand,
if necessary (procedure as described above).
Note:
Fig. 5.8: Changing the oil separator
The service life of the oil, the oil filter and oil separators is reduced under the
following conditions:
– When the compressor is operated at extreme ambient temperatures.
– When the intake air is extremely soiled.
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
Page 5.14 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.15
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
ATTENTION!
After each oil change you have to fill a small quantity of oil into the suction
controller before starting the compressor.
For oil quantity and procedure see chapter 3.5 "Commissioning following ex-
tended stoppages".
ATTENTION!
Always fill with the same oil type as previously used.
Never mix different oil types and brands.
The oil circuit must be flushed prior to changing the oil type.
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Conduct trial run.
Flushing the oil circuit Flushing the oil circuit with clean oil becomes necessary:
– When the oil is excessively soiled.
– Prior to changing the oil type.
ATTENTION!
Detailed information as to the flushing with BOGE oils you can obtain from
the following service number.
770 - 448 - 5995
Note:
Fig. 5.12: Flushing the oil circuit
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
Page 5.16 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
ATTENTION!
Do not use any sharp objects for cleaning!
These could damage the cooling unit!
– Blow down the dirt with compressed air in the opposite direction to the
normal cooling air flow. Vacuum out the dirt using an industrial vacuum
cleaner (see Fig.).
– Reattach safety warm air hood.
Note:
Fig. 5.13: Cleaning the compressed air/oil cooling unit
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.17
Wartung.pm6.5 - USA
Maintenance 5.3 Regular maintenance work
Note:
Fig. 5.14: Check safety valve
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
Page 5.18 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Maintenance 5.4 Spare parts and optional equipment
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 5.19
Wartung.pm6.5 - USA
Maintenance
Page 5.20 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Wartung.pm6.5 - USA
Appendix 6.1 Flow chart
Air IN
Compressed
air OUT
1 = Suction filter
3 = Suction filter monitoring (RATIO only)*
4 = Suction controller
5 = Air relief and regulation control valve
6 = Monitoring for rotational direction with double pressure check valve
(RATIO only)*
7 = Drive motor
8 = Air end
9 = Sensor for final compression temperature
10 = Combined compressed air/oil receiver
11 = Oil separator
12 = Safety valve
16 = Thermostatic oil control valve
17 = Oil cooler
18 = Oil filter
19 = Oil filter monitoring (RATIO only)*
21 = Minimum pressure check valve
22 = Compressed air after-cooler
23 = System pressure transmitter (RATIO only)*
24 = Network pressure transmitter
25 = Stop valve, compressed air outlet
27 = Oil drainage
28 = Check valve drainage line
* = Option
BOGE Operating instructions for S 10 – SF 29-2 series screw compressor Page 6.1
Fliess.pm6.5 - USA
Appendix 6.1 Flow chart
Air IN
Compressed air
OUT
1 =
Suction filter
3 =
Suction filter monitoring*
4 =
Suction controller
5 =
Air relief and regulation control valve
6 =
Pressure switch
(for rotational direction, system relief and V-belt monitoring)
7 = Drive motor
8 = Air end
9 = Final compression temperature display and switch
10 = Combined compressed air/oil receiver
11 = Oil separator
12 = Safety valve
14 = System pressure transmitter
16 = Thermostatic oil control valve
17 = Oil cooler
18 = Oil filter
19 = Oil filter monitoring*
21 = Minimum pressure check valve
23 = Network pressure transmitter
24 = Pressure gauge reading in display
25 = Stop valve, compressed air outlet
27 = Stop valve, oil drainage
28 = Throttle with filter
29 = Compresser air refriger. dryer (Series SDF 24-2 – SDF 29-2)
30 = Pressure transmitter speed regulation (network pressure)
* = Option
Page 6.2 BOGE Operating instructions for S 10 – SF 29-2 series screw compressor
Fliess.pm6.5 - USA
Please note the completed maintenance work in the respective columns
Date Operating Line System Tempe- Intake Air intake Oil- Oil- Oil Cooling Motor Com- Remarks
Fliess.pm6.5 - USA
hours pressure pressure rature filter filter filter level separator unit mainte- pressed
* ** cleaning nance air dryer
Appendix
6.2
* R = Cleaning ** K = Check
W = Change W = Change
Page 6.3
Please note the completed maintenance work in the respective columns
Page 6.4
Date Operating Line System Tempe- Intake Air intake Oil- Oil- Oil Cooling Motor Com- Remarks
hours pressure pressure rature filter filter filter level separator unit mainte- pressed
* ** cleaning nance air dryer
Appendix
6.2
List of maintenance and service work
* R = Cleaning ** K = Check
W = Change W = Change