Cell Sites AC Power Design

Introduction

The purpose of this document is to standardize the AC power design for


CMPak network for upcoming new sites build out and other upgradation
projects.
Cell Site Power Equipment Lay out

Main CB

Energy Meter

Transformer

Diesel Generator AC DB
ATS (with Class B SPDs)
Rectifier BTS and MW
and BB equipment Tower Mounted
Equipment
AC Power Design (SLD) for Single Sites (Non-Sharing)

Assumptions:
CMPak Site Load = 70 A
Battery Changing (600AH @ 0.3 C) =180 A
Total Load =250 A = 13.5 KW Load on T/F = ~15 KVA

4 Core 4 Core 4 Core Solid Line = Normal Power Cables Connections


16 mm^2 16 mm^2 (Cu) 16 mm^2 (Cu) Dotted Line = Optional In Case DG Installed

M.C.C.B
Energy Meter
100 A
4 Core
Transformer 16 mm^2 (Cu)

T/F Rating =25 KVA


Sanction Load=15KW 4 Core AC Distribution
16 mm^2 (Cu)
Panel To DC Power System

4 Core
16 mm^2 (Cu)

Diesel Genset ATS • AC DB Input Breaker > = 26 A


• AC DB Rectifier Breaker > = 26 A
• Additional Breakers for Lightening and other AC
4 Core load Power Up.
OPTIONAL As per LS Trend ATS To be designed as per 16 mm^2 (Cu)
of the site • Class I&II SPDs (with Uc >= 318V and Surge Current
DG Rating Installed
up to 100KA
DG Rating = @80% Loading For 15 KW Load: • In Case ATS is installed, SPDs will be located before
and p.f = 0.8 • ATS CP Input Breaker > = 26 A ATS in a separate DB.
• ATS DG Input Breaker > = 26 A
• ATS Load Breaker > = 26 A
• Magnetic Contactor >= 25 – 40 A/phase
with Mechanical Interlocking
AC Power Design (SLD) for DC Sharing Site where CMPak is Host (Common DC System)
Assumptions:
CMPak Site Load = 70 A, OMO Site Load = 60 A
Battery Changing (600AH @ 0.2 C) =120 A
Total Load =250 A = 13.5 KW Load on T/F = ~15 KVA

4 Core 4 Core Solid Line = Normal Power Cables Connections


16 mm^2 16 mm^2 (Cu)
Dotted Line = Optional In Case DG Installed

M.C.C.B
Energy Meter
100 A 4 Core
16 mm^2 (Cu)
Transformer

T/F Rating =25 KVA


Sanction Load=15KW 4 Core AC Distribution
16 mm^2 (Cu)
Panel To DC Power System

4 Core
16 mm^2 (Cu)

• AC DB Input Breaker > = 26 A


Diesel Genset ATS • AC DB Rectifier Breaker > = 26 A
• Additional Breakers for Lightening and other
AC load Power Up.
4 Core • Class I&II SPDs (with Uc >= 318V and Surge
DG Rating = @80% Loading ATS To be designed as per 16 mm^2 (Cu) Current upto 100KA.
and p.f = 0.8 DG Rating Installed • In Case ATS is installed, SPDs will be located
before ATS in a separate DB.
For 15 KW Load:
• ATS CP Input Breaker > = 26 A
• ATS DG Input Breaker > = 26 A
• ATS Load Breaker > = 26 A
• Magnetic Contactor >= 25 – 40 A/phase
with Mechanical Interlocking
AC Power Design (SLD) for CP/DG Sharing Site where CMPak is Host (Separate DC Systems for CMPak and OMO)
Assumptions:
CMPak Site Load = 70 A, OMO Site Load = 60 A
Battery Changing (600AH @ 0.2 C) =120 A (CMPAK)
Battery Changing (500AH @ 0.2 C) =100 A (OMO)
Total Load = 350 A = 19.6 KW Total Load on Transformer ~ 21.6 KVA
4 Core 4 Core 4 Core Solid Line = Normal Power Cables Connections
16 mm^2 16 mm^2 (Cu) 16 mm^2 (Cu) Dotted Line = Optional In Case DG Installed

M.C.C.B
Energy Meter
100 A 4 Core
16 mm^2 (Cu)
Transformer

T/F Rating = 25 KVA


Sanction Load = 21 KW 4 Core AC Distribution
16 mm^2 (Cu)
Panel To DC Power System

4 Core
16 mm^2 (Cu)

• AC DB Input Breaker > = 40 A


Diesel Genset ATS • AC DB Rectifier Breaker > = 40 A
• Additional Breakers for Lightening and other
AC load Power Up.
4 Core • Class I&II SPDs (with Uc >= 318V and Surge
DG Rating = @80% Loading ATS To be designed as per 16 mm^2 (Cu) Current up to 100KA
and p.f = 0.8 DG Rating Installed • In Case ATS is installed, SPDs will be located
before ATS in a separate DB.
For 15 KW Load:
• ATS CP Input Breaker > = 40 A
• ATS DG Input Breaker > = 40 A
• ATS Load Breaker > = 40 A
• Magnetic Contactor >= 40 – 45 A/Phase
with Mechanical Interlocking
AC Power Design (SLD) for Indoor Site
Assumptions:
CMPak Site Load = 70 A
Battery Changing (600AH @ 0.3 C) =180 A
Total DC Load =250 A = 13.5 KW ~ 15 KVA
Per AC (2 Ton) Load = 12 A Single Phase = 2.6 KVA/Phase Total Load on Transformer ~ 23 KVA

4 Core 4 Core Solid Line = Normal Power Cables Connections


25 mm^2 16 mm^2 (Cu)
Dotted Line = Optional In Case DG Installed

M.C.C.B
Energy Meter
100 A 4 Core
16 mm^2 (Cu)
Transformer

T/F Rating = 25 KVA


Sanction Load = 22 KW 4 Core AC Distribution
16 mm^2 (Cu)
Panel To DC Power System

4 Core
16 mm^2 (Cu)

• AC DB Input Breaker > = 42 A


• AC DB Rectifier Breaker > = 42 A
Diesel Genset ATS • Additional Breakers for Lightening and
other AC load Power Up.
• Class I&II SPDs (with Uc >= 318V and Surge
4 Core
DG Rating = @80% Loading and ATS To be designed as per 16 mm^2 (Cu) Current upto 100KA
p.f = 0.8 DG Rating Installed • In Case ATS is installed, SPDs will be
located before ATS in a separate DB.
For 15 KW Load:
• ATS CP Input Breaker > = 42 A
• ATS DG Input Breaker > = 42 A
• ATS Load Breaker > = 42 A
• Magnetic Contactor >= 40 – 45
A/phase with Mechanical Interlocking
AC Power Design (SLD) for Indoor Site (PTN (DWDM) with Dual Rectifier)
Assumptions:
CMPak Site Load (Rectifier 1) = 70 A, PTN Site Load (Rectifier 2) = 50 A
Battery Changing Rectifier_1 (600AH @ 0.2 C) =120 A, Battery Charging Rectifier_2 (600AH @ 0.2C)= 120 A
Total DC Load =70+50+180+60 = 360 A= 19.4 KW ~ 21 KVA
Per AC (2 Ton) Load = 12 A, Single Phase Power Required = 2.6 KVA/Phase; Total (Max) Load on Transformer ~ 28.8 KVA

4 Core 4 Core Solid Line = Normal Power Cables Connections


25 mm^2 25 mm^2 (Cu)
Dotted Line = Optional In Case DG Installed

M.C.C.B
Energy Meter
100 A 4 Core
25 mm^2 (Cu)
Transformer

T/F Rating >= 30 KVA


Sanction Load = 25 KW 4 Core AC Distribution
25 mm^2 (Cu)
Panel To DC Power Systems

4 Core
25 mm^2 (Cu)
• AC DB Input Breaker > = 52 A
• AC DB Rectifier Breaker > = 52 A
• Additional Breakers for Lightening and other AC load
Diesel Genset ATS Power Up.
• Class I&II SPDs (with Uc >= 318V and Surge Current upto
4 Core 100KA
DG Rating = @80% Loading and ATS To be designed as per 25 mm^2 (Cu) • In Case ATS is installed, SPDs will be located before ATS in a
p.f = 0.8 DG Rating Installed separate DB.

For 15 KW Load: Important Notes:


• ATS CP Input Breaker > = 52 A 1- All PTN (DWDM) sites will be provided with Type I/II surge protection
• ATS DG Input Breaker > = 52 A of surge current rating of 100KA.
• ATS Load Breaker > = 52 A
• Magnetic Contactor >= 52 A/phase 2- ** New Earth pit will be made on the PTN (DWDM) sites and all DC
with Mechanical Interlocking Power equipment earthing will be done from the new earth pits.
Earthing For PTN/DWDM Sites:
Earthing Requirements For PTN/DWDM Sites and New Physical Sites:

• New Earth Pit is mandatory for all PTN/DWDM sites.


• All DC equipment at the PTN will be grounded with new earth pit whereas AC power components and tower will be grounded from
existing earth pit. AC and DC power earth pits will be differentiated in this way.
• Earth pit will be selected from one of the following methods based on careful analysis of the site (soil test report).
• For All new physical sites earth pits will be part of design.
ATS Power Wiring Diagram

Single ATS Dual ATS (In case of 1+1 DGs)

• All Power cables must be as per the scenario of the site (Single, Sharing, Indoor, PTN) already defined.
• Magnetic Contactors/Breakers rating will be as per scenario of site (Single, Sharing, Indoor, PTN) already defined
• Mechanical Interlocking between contactors is a must along with Electrical Auxiliaries to avoid simultaneous operation of two contactors.
• Control wiring will be designed as per above power diagram.
Work Flow and Responsibility Matrix
AC Power Design Work Flow
Work Flow and Responsibility Matrix
Network Planning

AC Power Design
Site Nominals Finalization for
Start guidelines and Support Site Nominal
a project and Project Scope
to stake holders Type

Existing Operational Site New Physical Site

Site wise working Budget Requirement for Power T/


Bidding Process &
O&M

and requirement F or cable Upgradation/Sanction Opex Budget Implementation as


Contract award to
finalization as per Load Enhancement/Genset Approval per Design
Vendor
design guidelines Upgradation, etc.

YES
Construction
Network

Scope of AC Power to be Site wise working and


Implementation as
included in the New No DG required requirement finalization as
per Design
Physical Sites Scope per design guidelines
Regional Teams

END Acceptance Verification of the work done

Intimation to region for work completion


Important Points
Below mentioned are some important points related to the design;
• AC Power Design is for new physical sites. All new build out sites will follow this design and will not be
applicable on any site already on air. Any existing sites upgradations required will be handled by the
concerned department (O&M) on case to case basis as per existing process in place.
• MCCB (100A) will be 4 pole breaker to protect neutral overcurrent as well.
• If PMT is not installed (e.g. K-Electric, special authority sites, community powered sites etc.) meter to onward
stable power will be used (PMT rating will not be applicable).
• DG and ATS, if mandatory, will be arranged from existing network by O&M and FOPs as per existing DG
relocation criteria.
• For Normal Sites if main power cable (meter to main breaker) is more than 70 meters in length then cable size
(conductor size) need to be re-evaluated before deployment to check for losses. All power cables size in the
design is applicable for up to 70 meters cable length.
• ATS/ ACDB components (circuit breakers, magnetic contactors, SPD’s, etc.) must be verified for proof of
purchase/origin i.e. manufacturer of ATS/DB must provide the proof that these parts are obtained from
authorized dealer or imported from the manufacturer. Vendor must present a quality certificate of the
components from principal for the parts used in the ATS/DB.
• For projects related to existing operational sites O&M will be responsible for AC power upgradations as per
design guidelines and requirement.
• NP will support for any scenario not covered in the design on cases to case basis.
Thanks