Protection Operation Sequence of 315 MVA ICT-2 Failure: 03.01.

2015

Protection Status
Inherent Protections:
Buchholz Relay Operated at 23:33:54:078 hrs. However, the magnitude of differential
current lead to tripping of the Transformer on Differential protection.
Oil Surge Relay There were no damages in the OLTC chamber. Hence Oil Surge relay
was not operated.
PRV PRV was operated at 23:33:53:980 hrs but Transformer was already
tripped on Differential protection at 23:33:53:950 hrs.
External/Electrical Protections:
Differential/ REF Protection Heavy Differential Current was sensed in the Transformer leading to
Immediate Tripping of the Transformer on Differential protection at
23:33:53:950 hrs.
Directional Over current & Relay picked up at 23:33:53:952 hrs and instantaneous trip command
Earth fault protection was generated due to High magnitude current (9.57 kA).However,
main protection, i.e differential had already operated and tripped the
Transformer.

Hence, all associated protections of the Transformer operated satisfactorily.


4B 7UT613_prn

Trip Log - 000147 / 03-01-15


SIMATIC 11:33:53.945 PM - KABUL 400 03.01.15 23:48:35

KABUL 400 30-0-6-12 / KIOSK 4 / 4B 7UT613

MLFB: 7UT61316EB921AB0----0S----------
Parameter set version: V04.62.05
Device path: E:\KABUL400 25-08-14\P7DI\GV\SD\00000039
Author:
Creation date: 06.12.11 00:39:34
Last modified: 03.01.15 23:47:35
Operating mode: Online
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Indications ..........................................................................................................................................................................2
1.1 Trip Log - 000147 / 03-01-15 11:33:53.945 PM - KABUL 400 30-0-6-12 ............................................................................. 2
/ KIOSK 4 / 4B 7UT613/7UT613 V04.63.01

Page 1 of 2
4B 7UT613_prn
Indications
Trip Log - 000147 / 03-01-15
SIMATIC 11:33:53.945 PM - KABUL 400 03.01.15 23:48:35

1 Indications

Trip Log - 000147 / 03-01-15 11:33:53.945 PM - KABUL 400 30-0-6-12


1.1
/ KIOSK 4 / 4B 7UT613/7UT613 V04.63.01
Trip Log - 000147 / 03-01-15 11:33:53.945 PM - KABUL 400 30-0-6-12 / KIOSK 4 / 4B 7UT613/7UT613
V04.63.01
Number Indication Value Date and time Cause State

00301 Power System fault 147 - ON 03.01.2015 23:33:53.945


00302 Fault Event 147 - ON 03.01.2015 23:33:53.945
00501 Relay PICKUP ON 0 ms
05631 Differential protection picked up ON 0 ms
05684 Diff. prot: IDIFF>> L1 (without Tdelay) ON 5 ms
00511 Relay GENERAL TRIP command ON 5 ms
05692 Differential prot.: TRIP by IDIFF>> ON 5 ms
05701 Diff. curr. in L1 at trip without Tdelay 5.77 I/InO 6 ms
05704 Restr.curr. in L1 at trip without Tdelay 5.21 I/InO 6 ms
05702 Diff. curr. in L2 at trip without Tdelay 2.89 I/InO 6 ms
05705 Restr.curr. in L2 at trip without Tdelay 2.79 I/InO 6 ms
05703 Diff. curr. in L3 at trip without Tdelay 2.88 I/InO 6 ms
05706 Restr.curr. in L3 at trip without Tdelay 2.74 I/InO 6 ms
05685 Diff. prot: IDIFF>> L2 (without Tdelay) ON 15 ms
05686 Diff. prot: IDIFF>> L3 (without Tdelay) ON 15 ms
05681 Diff. prot.: IDIFF> L1 (without Tdelay) ON 20 ms
05682 Diff. prot.: IDIFF> L2 (without Tdelay) ON 20 ms
05683 Diff. prot.: IDIFF> L3 (without Tdelay) ON 20 ms
05691 Differential prot.: TRIP by IDIFF> ON 20 ms
05685 Diff. prot: IDIFF>> L2 (without Tdelay) OFF 73 ms
05686 Diff. prot: IDIFF>> L3 (without Tdelay) OFF 73 ms
05684 Diff. prot: IDIFF>> L1 (without Tdelay) OFF 78 ms
05681 Diff. prot.: IDIFF> L1 (without Tdelay) OFF 80 ms
05682 Diff. prot.: IDIFF> L2 (without Tdelay) OFF 80 ms
05683 Diff. prot.: IDIFF> L3 (without Tdelay) OFF 80 ms
05631 Differential protection picked up OFF 155 ms

Page 2 of 2
4B 7SJ622 V4_8_prn

Trip Log - 000103 / 03-01-15


SIMATIC 11:33:53.952 PM - KABUL 400 03.01.15 23:46:57

KABUL 400 30-0-6-12 / KIOSK 4 / 4B 7SJ622 V4.8

MLFB: 7SJ62226EB901FD0----0S----------
Parameter set version: V04.80.05
Device path: E:\KABUL400 25-08-14\P7DI\GV\SD\00000038
Author:
Creation date: 06.12.11 00:39:14
Last modified: 03.01.15 23:45:48
Operating mode: Online
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Indications ..........................................................................................................................................................................2
1.1 Trip Log - 000103 / 03-01-15 11:33:53.952 PM - KABUL 400 30-0-6-12 ............................................................................. 2
/ KIOSK 4 / 4B 7SJ622 V4.8/7SJ622 V04.81.04

Page 1 of 2
4B 7SJ622 V4_8_prn
Indications
Trip Log - 000103 / 03-01-15
SIMATIC 11:33:53.952 PM - KABUL 400 03.01.15 23:46:57

1 Indications

Trip Log - 000103 / 03-01-15 11:33:53.952 PM - KABUL 400 30-0-6-12


1.1
/ KIOSK 4 / 4B 7SJ622 V4.8/7SJ622 V04.81.04
Trip Log - 000103 / 03-01-15 11:33:53.952 PM - KABUL 400 30-0-6-12 / KIOSK 4 / 4B 7SJ622 V4.8/7SJ622
V04.81.04
Number Indication Value Date and time Cause State

00301 Power System fault 103 - ON 03.01.2015 23:33:53.952


00302 Fault Event 103 - ON 03.01.2015 23:33:53.952
00501 Relay PICKUP ON 0 ms
05971 Time Overcurrent 1Phase picked up ON 0 ms
05974 Time Overcurrent 1Phase I> picked up ON 0 ms
00511 Relay GENERAL TRIP command ON 0 ms
05972 Time Overcurrent 1Phase TRIP ON 0 ms
05980 Time Overcurrent 1Phase: I at pick up 450.0 A 0 ms
05975 Time Overcurrent 1Phase I> TRIP ON 0 ms
02691 Directional time overcurrent picked up ON 6 ms
02695 DIR. time overcurrent EARTH picked up ON 6 ms
02692 DIR. time overcurrent Ph L1 picked up ON 6 ms
02670 Ip Directional picked up ON 6 ms
02684 IEp Directional picked up ON 6 ms
02694 DIR. time overcurrent Ph L3 picked up ON 26 ms
00533 Primary fault current IL1 9.57 kA 34 ms
00534 Primary fault current IL2 0.52 kA 34 ms
00535 Primary fault current IL3 0.63 kA 34 ms
02694 DIR. time overcurrent Ph L3 picked up OFF 56 ms
02692 DIR. time overcurrent Ph L1 picked up OFF 85 ms
02670 Ip Directional picked up OFF 85 ms
05974 Time Overcurrent 1Phase I> picked up OFF 85 ms
05971 Time Overcurrent 1Phase picked up OFF 85 ms
02695 DIR. time overcurrent EARTH picked up OFF 95 ms
02684 IEp Directional picked up OFF 95 ms
02691 Directional time overcurrent picked up OFF 95 ms
00301 Power System fault 103 - OFF 03.01.2015 23:33:54.048

Page 2 of 2
KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613 1/3/2015 / 11:33:53 PM.944

Name: KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613


Filename:
C:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2
DIFF OC
Fault start: 1/3/2015 11:33:53 PM.847
Scanning frequency:801 Hz

Cursor 1: 29 ms
Cursor 2: 514 ms
Representation: primary

1/12/2015 / 10:29:01 AMC:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2 DIFF OC
SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613 1/3/2015 / 11:33:53 PM.944

Trigger
1/3/2015
11:33:53 PM.944

iL1-M1/ A
2500

0
-2500 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
t/s
-5000

iL2-M1/ A
2500

-2500 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
-5000

iL3-M1/ A
2500

-2500 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
-5000

3i0-M1/ A
2500
0

-2500 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
-5000

iL1-M2/ A
5000
0
-5000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
t/s
-10000

iL2-M2/ A
5000
0
-5000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
t/s
-10000

iL3-M2/ A
5000
0
-5000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
t/s
-10000

3i0-M2/ A
5000
0
-5000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
t/s
-10000

1/12/2015 / 10:29:01 AMC:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2 DIFF OC
SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613 1/3/2015 / 11:33:53 PM.944

iL1-M3/ A

0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-2000 t/s

iL2-M3/ A

0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-2000 t/s

iL3-M3/ A

0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-2000 t/s

3i0-M3/ A

0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-2000 t/s

i-X3/ A
2500
0
-2500 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-5000 t/s
-7500

uL1/ V
200000
0

-200000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
-400000

uL2/ V
200000
0

-200000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
-400000

uL3/ V
200000
0

-200000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
-400000

u0-calc/ V

0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-100000 t/s

1/12/2015 / 10:29:01 AMC:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2 DIFF OC
SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613 1/3/2015 / 11:33:53 PM.944

uEn/ V
100000
0
-100000 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
-200000
t/s

IDiff-L1/ I/InO

10

5 t/s
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0

IDiff-L2/ I/InO

10

5 t/s
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0

IDiff-L3/ I/InO

10

5 t/s
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0

IRest-L1/ I/InO

10

5 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7


t/s
0

IRest-L2/ I/InO

10

5 t/s
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0

IRest-L3/ I/InO

10

5 t/s
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0

1/12/2015 / 10:29:01 AMC:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2 DIFF OC
SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613 1/3/2015 / 11:33:53 PM.944

Flag Lost
>Trig.Wave.Cap.
FltRecSta
Relay TRIP
Relay PICKUP
Diff picked up
Diff> TRIP
Diff>> TRIP
U/f>> TRIP
U-PH OLTC
V-PH OLTC
W-PH OLTC
M TANK WTI
MAIN TANK1
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
t/s
Measuring Signal Value Phase Extremum DC 2.Harmon. 3.Harmon. 5.Harmon.

uL1 1.87 kV 148.4° -1.407 kV 64.5% 81.7% 58.6% 46.6%


uL2 275 kV 105.6° -381.3 kV 0.4% 0.3% 0.8% 0.4%
uL3 264 kV 5.5° 367.4 kV -0.9% 0.7% 0.9% 0.1%
uEn 32.6 V -170.6° -197.8 V -482.5% 31.9% 28.9% 15.7%
IDiff-L1 16.3 I/InO
IDiff-L2 7.82 I/InO
IDiff-L3 8.67 I/InO
IRest-L1 16.4 I/InO
IRest-L2 8.07 I/InO
IRest-L3 9.21 I/InO
iL1-M1 3.51 kA 158.9° -5.101 kA -3.6% 0.1% 0.3% 0.1%
iL2-M1 70.0 A 178.6° -92.16 A 12.4% 3.3% 4.4% 1.4%
iL3-M1 57.0 A -5.2° 80.64 A -3.2% 4.0% 2.2% 0.8%
3i0-M1 3.52 kA -21.0° 5.108 kA 3.4% 0.1% 0.4% 0.1%
iL1-M2 6.04 kA 158.9° -8.684 kA -2.0% 0.2% 0.1% 0.1%
iL2-M2 581 A -11.4° 891.6 A 13.8% 2.7% 2.2% 0.6%
iL3-M2 590 A -45.3° 758.0 A -18.9% 4.3% 2.6% 0.9%
3i0-M2 4.93 kA -19.4° 7.124 kA 3.0% 0.1% 0.1% 0.1%
iL1-M3 2.09 kA 144.4° -2.721 kA 16.3% 4.5% 2.9% 1.1%
iL2-M3 0.52 kA 116.8° -0.612 kA 65.4% 19.0% 13.1% 4.5%
iL3-M3 0.91 kA -107.0° -2.068 kA -70.7% 21.6% 14.3% 4.9%
3i0-M3 2.35 kA -20.3° 3.288 kA -1.6% 0.1% 0.7% 0.2%
i-X3 4.42 kA 123.1° -8.555 kA 11.9% 11.0% 49.6% 9.2%
u0-calc 115 kV -122.7° -160.7 kV 0.1% 0.6% 0.6% 0.6%

1/12/2015 / 10:29:01 AMC:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2 DIFF OC
SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7UT613 1/3/2015 / 11:33:53 PM.944

1/12/2015 / 10:29:01 AMC:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 DIFF OSC\ICT 2 DIFF OC
SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7SJ622 V4.8 1/3/2015 / 11:33:53 PM.952

Name: KABUL 400 30-0-6-12 KIOSK 4 4B 7SJ622 V4.8


Filename:
C:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 OC DR
Fault start: 1/3/2015 11:33:53 PM.701
Scanning frequency:801 Hz

Cursor 1: 14 ms
Cursor 2: 50 ms
Representation: primary

1/12/2015 / 10:25:50 AM C:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 OC DR


SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7SJ622 V4.8 1/3/2015 / 11:33:53 PM.952

Trigger
1/3/2015
11:33:53 PM.952

iL1/ A

0
-0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-10000 t/s

iL2/ A

0
-0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-10000 t/s

iL3/ A

0
-0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-10000 t/s

iE/ A

0
-0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-10000 t/s

uL1/ V
200000

-200000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15


t/s
-400000

uL2/ V
200000

-200000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15


t/s
-400000

uL3/ V
200000

-200000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15


t/s
-400000

uEn/ V
250000
0
-250000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-500000 t/s

1/12/2015 / 10:25:50 AM C:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 OC DR


SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7SJ622 V4.8 1/3/2015 / 11:33:53 PM.952

iEs/ A
t/s
1000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
0
-1000
-2000
-3000

uL12/ V
250000
0
-250000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-500000 t/s

uL23/ V
250000
0
-250000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-500000 t/s

uL31/ V
250000
0
-250000 -0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
-500000 t/s

>Trig.Wave.Cap.
FltRecSta
Flag Lost
IE>> DIR. TRIP
IE> DIR. TRIP
IEp DIR. TRIP
I>> DIR. TRIP
I> DIR. TRIP
Ip DIR. TRIP
DIR O/C PU
DIR O/C TRIP
Relay PICKUP
Relay TRIP
O/C 1Ph TRIP
O/C 1Ph I> TRIP
O/C1Ph I>> TRIP
OTI MAIN T
BUCHOLTZ T
MT PRV
-0.20 -0.15 -0.10 -0.05 -0.00 0.05 0.10 0.15
t/s

1/12/2015 / 10:25:50 AM C:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 OC DR


SIGRA 4.5
KABUL 400 30-0-6-12 KIOSK 4 4B 7SJ622 V4.8 1/3/2015 / 11:33:53 PM.952

Measuring Signal Value Phase Extremum DC 2.Harmon. 3.Harmon. 5.Harmon.

iL1 9.60 kA 141.3° -13.21 kA 2.8% 0.5% 0.4% 0.4%


iL2 507 A -32.3° 639.8 A -17.8% 4.1% 1.3% 0.6%
iL3 0.66 kA -57.0° 1.008 kA 14.6% 8.9% 4.1% 2.5%
iE 8.47 kA -37.6° 11.61 kA -3.3% 0.2% 0.2% 0.3%
uL1 13.3 kV 137.7° 0.0000 kV 73.1% 39.8% 28.6% 19.4%
uL2 280 kV 89.1° -388.1 kV 2.0% 1.2% 0.7% 0.2%
uL3 265 kV -12.1° 370.0 kV 0.3% 1.0% 0.3% 0.1%
uEn 344 kV 42.7° -486.5 kV 4.7% 2.2% 1.9% 0.8%
iEs 1.75 kA 5.5° -2.621 kA 18.5% 24.1% 15.0% 7.2%
uL12 272 kV -93.0° 385.7 kV 1.5% 1.1% 0.7% 0.8%
uL23 421 kV 127.2° -577.0 kV 1.1% 1.3% 0.4% 0.2%
uL31 276 kV -13.4° 372.4 kV -3.2% 2.3% 1.1% 1.0%

1/12/2015 / 10:25:50 AM C:\DOCUMENTS AND SETTINGS\ADMINISTRATOR\DESKTOP\03.01.15 ICT-2 FAULT DR\ICT-2 OC DR


SIGRA 4.5