PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet

ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos


SPACE CORPORATE BOX-1 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 0 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 184 sft x 12 btu x 0.56 = 1236.53 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 444 sft x 36 (F) x 21 (F) x 1.13 =
Partition 458 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.2 3.5
2131 1483 6.09
98.3 118.5
5.2 3.6

SUMMER MONSOON
BTU BTU
18053.1 10531.0
5681.9 2932.6
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
39128.5 27229.1

3912.8 2722.9
43041.3 29952.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

50054 41514

0.82 0.72

52 52

18.7 18.7

4.2 3.5

2131 1483
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-2 FLOOR AREAS 407 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 407 sft x 5 (F) x 3 (F) x 0.40 =
Floor 407 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 415.344 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1886 1342 5.39
108.3 126.4
4.6 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
814.4 488.6
814.4 488.6
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1772.0 1772.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
34634.2 24645.9

3463.4 2464.6
38097.6 27110.5
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45110 38673

0.80 0.70

52 52

18.7 18.7

3.8 3.2

1886 1342
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-3 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1888 1343 5.39
109.0 127.2
4.6 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
34657.6 24664.8

3465.8 2466.5
38123.4 27131.3
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45136 38693

0.80 0.70

52 52

18.7 18.7

3.8 3.2

1888 1343
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-4 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1888 1343 5.39
109.0 127.2
4.6 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
34657.6 24664.8

3465.8 2466.5
38123.4 27131.3
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45136 38693

0.80 0.70

52 52

18.7 18.7

3.8 3.2

1888 1343
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-5 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1888 1343 5.39
109.0 127.2
4.6 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
34657.6 24664.8

3465.8 2466.5
38123.4 27131.3
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45136 38693

0.80 0.70

52 52

18.7 18.7

3.8 3.2

1888 1343
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-6 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1888 1343 5.39
109.0 127.2
4.6 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
34657.6 24664.8

3465.8 2466.5
38123.4 27131.3
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45136 38693

0.80 0.70

52 52

18.7 18.7

3.8 3.2

1888 1343
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-7 FLOOR AREAS 407 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 693 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 407 sft x 5 (F) x 3 (F) x 0.40 =
Floor 407 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 415.344 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1908 1354 5.45
107.3 125.6
4.7 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8589.9 4433.5
814.4 488.6
814.4 488.6
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1772.0 1772.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
35036.9 24853.7

3503.7 2485.4
38540.6 27339.1
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45553 38901

0.81 0.70

52 52

18.7 18.7

3.8 3.2

1908 1354
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-8 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 260 sft x 12 btu x 0.56 = 1745.69 btu
North/west 79 sft x 123 btu x 0.56 = 5467.42 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 339 sft x 36 (F) x 21 (F) x 1.13 =
Partition 639 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.5 3.9
2347 1736 6.70
90.4 105.5
5.7 4.2

SUMMER MONSOON
BTU BTU
13796.7 8048.1
7918.8 4087.1
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
43085.6 31877.3

4308.6 3187.7
47394.2 35065.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

54407 46627

0.84 0.75

52 52

18.7 18.7

4.5 3.9

2347 1736
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-9 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 78 sft x 123 btu x 0.56 = 5343.16 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 337 sft x 36 (F) x 21 (F) x 1.13 =
Partition 458 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.3 3.8
2214 1664 6.33
95.1 108.9
5.4 4.1

SUMMER MONSOON
BTU BTU
13723.3 8005.3
5681.9 2932.6
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
40651.0 30555.7

4065.1 3055.6
44716.1 33611.2
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

51729 45173

0.83 0.74

52 52

18.7 18.7

4.3 3.8

2214 1664
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-10 FLOOR AREAS 407 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 407 sft x 5 (F) x 3 (F) x 0.40 =
Floor 407 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 415.14 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

3.8 3.2
1886 1342 5.39
108.3 126.3
4.6 3.3

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
814.0 488.4
814.0 488.4
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1771.1 1771.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
34632.5 24644.6

3463.3 2464.5
38095.8 27109.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

45108 38671

0.80 0.70

52 52

18.7 18.7

3.8 3.2

1886 1342
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-11 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 17893.37 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 462 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

5.2 4.7
2728 2249 7.79
79.2 86.3
6.7 5.5

SUMMER MONSOON
BTU BTU
10567.7 6164.5
5726.6 2955.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
50090.3 41288.2

5009.0 4128.8
55099.3 45417.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

62112 56979

0.86 0.80

52 52

18.7 18.7

5.2 4.7

2728 2249
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-12 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 17893.37 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 462 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

5.2 4.7
2728 2249 7.79
79.2 86.3
6.7 5.5

SUMMER MONSOON
BTU BTU
10567.7 6164.5
5726.6 2955.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
50090.3 41288.2

5009.0 4128.8
55099.3 45417.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

62112 56979

0.86 0.80

52 52

18.7 18.7

5.2 4.7

2728 2249
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-13 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 17893.37 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 462 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

5.2 4.7
2728 2249 7.79
79.2 86.3
6.7 5.5

SUMMER MONSOON
BTU BTU
10567.7 6164.5
5726.6 2955.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
50090.3 41288.2

5009.0 4128.8
55099.3 45417.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

62112 56979

0.86 0.80

52 52

18.7 18.7

5.2 4.7

2728 2249
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-14 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 17893.37 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 260 sft x 36 (F) x 21 (F) x 1.13 =
Partition 660 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

5.4 4.9
2862 2318 8.18
75.9 84.3
7.0 5.7

SUMMER MONSOON
BTU BTU
10567.7 6164.5
8187.3 4225.7
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
52551.0 42558.2

5255.1 4255.8
57806.1 46814.0
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

64819 58376

0.86 0.80

52 52

18.7 18.7

5.4 4.9

2862 2318
PROJECT RAJA NAHAR SINGH STADIUM HEIGHT 11 feet
ADDRESS FARIDABAD FLOOR SECOND PEOPLE 30 nos
SPACE CORPORATE BOX-15 FLOOR AREAS 410 sft LIGHT 1.02 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSOON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Difference 36
North/east 182 sft x 12 btu x 0.56 = 1224.41 btu
North/west 0 sft x 123 btu x 0.56 = 17893.37 btu DESIGN CONDITION
South/east 260 sft x 12 btu x 0.56 = 1745.69 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSOON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Difference 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 442 sft x 36 (F) x 21 (F) x 1.13 =
Partition 566 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 410 sft x 5 (F) x 3 (F) x 0.40 =
Floor 410 sft x 5 (F) x 3 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 30 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 300 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 30 nos x 280 btu x =
Light(f) 418.2 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 30 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 150 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 30 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 150 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 150 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

6.1 5.3
3269 2587 9.34
67.4 77.1
8.0 6.3

SUMMER MONSOON
BTU BTU
17979.7 10488.2
7024.1 3625.3
820.0 492.0
820.0 492.0
SUMMER MONSOON
BTU BTU
1166.4 680.4
1166.4 680.4
SUMMER MONSOON
BTU BTU
8400.0 8400.0
1784.1 1784.1
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
60024.2 47505.9

6002.4 4750.6
66026.6 52256.5
SUMMER MONSOON
BTU BTU
216.2 1672.8
108.1 836.4
8100.0 8100.0
0.0 0.0
0.0 0.0
0.0 0.0
8424.4 10609.2
842.4 1060.9
9266.8 11670.1
SUMMER MONSOON
BTU BTU
4957.2 2891.7
919.0 7109.4

293.8 500.1
6170 10501

73039 63819

0.88 0.82

52 52

18.7 18.7

6.1 5.3

3269 2587
PROJECT RAJA NAHAR SINGH STADIUM
ADDRESS FARIDABAD FLOOR SECOND
SPACE PANTRY & TOILETS

CFM REQUIREMENT
NORTH WEST SIDE
VOLUME (C.FT) AIR CHANGES / HOUR CFM
PANTRY 794.4 8 106
L.TOILET 888.9 8 119
G. TOILET 821.1 8 109

SOUTH WEST SIDE


VOLUME (C.FT) AIR CHANGES / HOUR CFM
PANTRY 794.4 8 106
L.TOILET 888.9 8 119
G. TOILET 821.1 8 109