You are on page 1of 1

LINE DESIGNATION TABLE

LINE DESIGNATION SPECIFICATIONS


OPERATING DESIGN TEST P & ID NOTES REV
SIZE SERV. SPEC No. ORIGIN TERMINATION PRESS TEMP PRESS TEMP PRESS TEMP (Min) TEST PIPE WALL THICK. CORR. MATERIAL RADIO- No. No.
o o o
kPag C kPag C kPag C MEDIUM SCH. mm ALL. (mm) GRADE GRAPHY
Yard Piping
273.1 C2 CP6 002 273.1-C2-CP6-001 273.1-C2-CP6-003/ 004 4,500 10 9,930 38 14,895 10 Water 80 15.09 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0001 3
273.1 C2 CP6 003 273.1-C2-CP6-002 P-1 4,500 10 9,930 38 14,895 10 Water 80 15.09 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0001/2 3/2
273.1 C2 CP6 004 273.1-C2-CP6-002 P-2 4,500 10 9,930 38 14,895 10 Water 80 15.09 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0001/3 3/2
273.1 C2 CP6 013 273.1-C2-CP6-011/ 012 273.1-C2-CP6-0014 9,914 10 9,930 38 14,895 10 Water 80 15.09 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0001 3
60.3 BD CP6 021 273.1-C2-CP6-002 114.3-BD-CP6-020 9,914 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0001/2 3/2
60.3 BD CP6 022 273.1-C2-CP6-013 114.3-BD-CP6-020 9,914 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0001/3 3/2
60.3 FL 01S 015 273.1-C2-CP6-013 (TRV-120) 114.3-FL-01S-040 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0001 3
60.3 FL 01S 016 273.1-C2-CP6-005 (TRV-110) 114.3-FL-01S-040 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0001 3

Pumps P-1
273.1 C2 CP6 011 P-1 273.1-C2-CP6-013 9,914 10 9,930 38 14,895 10 Water 80 15.09 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0002/1 2/3
114.3 BD CP6 020 60.3-BD-CP6-024 114.3-FL-01S-048 4,500 10 9,930 38 14,895 10 Water 80 8.56 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0002/3/5 2/2/0
60.3 BD CP6 023 273.1-C2-CP6-003 60.3-BD-CP6-024 4,500 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0002 2
60.3 BD CP6 024 60.3-DR-CP6-023 114.3-BD-CP6-020 4,500 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0002 2
60.3 BD CP6 025 273.1-C2-CP6-011 60.3-BD-CP6-026 9,914 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0002 2
60.3 BD CP6 026 60.3-BD-CP6-025 114.3-BD-CP6-020 9,914 10 9,930 38 14,895 38 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0002 2
60.3 FL 01S 045 P-1 Seal Plan 76 114.3-FL-01S-040 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0002 2
60.3 FL 01S 042 273.1-C2-CP6-011 (TRV-101) 60.3-FL-01S-044 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0002/5 2/5
60.3 FL 01S 044 60.3-FL-01S-042 114.3-FL-01S-040 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0002/5 2/5

Pump P-2
273.1 C2 CP6 012 P-2 273.1-C2-CP6-013 9,914 10 9,930 38 14,895 10 Water 80 15.09 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0003/1 2/3
60.3 BD CP6 029 273.1-C2-CP6-004 60.3-BD-CP6-030 4,500 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0003 2
60.3 BD CP6 030 60.3-DR-CP6-029 114.3-BD-CP6-020 4,500 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0003 2
60.3 BD CP6 031 273.1-C2-CP6-012 60.3-BD-CP6-032 9,914 10 9,930 38 14,895 10 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0003 2
60.3 BD CP6 032 60.3-BD-CP6-031 114.3-BD-CP6-020 9,914 10 9,930 38 14,895 38 Water 80 5.54 1.5 CSA Z245.1 GRADE 359 CAT II 100% A8003.01-2B Sheet 0003 2
60.3 FL 01S 047 P-2 Seal Plan 76 114.3-FL-01S-040 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0003 2
60.3 FL 01S 043 273.1-C2-CP6-012 (TRV-200) 60.3-FL-01S-046 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0003/5 2/0
60.3 FL 01S 046 60.3-FL-01S-043 114.3-FL-01S-040 500 -70 1,590 38 2,385 10 Water 40 3.91 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0003/5 2/0

Flare Stack (FS-1)


114.3 FL 01S 040 60.3-FL-01S-015 114.3-FL-01S-048 500 -70 1,590 38 2,385 10 Water 10 3.18 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0005 0
114.3 FL 01S 048 114.3-FL-01S-040 FS-1 (NOZZ: 'N1') 500 -70 1,590 38 2,385 10 Water 10 3.18 0 ASME B36.10M A312 TP304L 100% A8003.01-2B Sheet 0005 0

NOTES REVISION DESCRIPTION CHK'D APLXP'D STAMPS ENGINEERING RECORD


1. The 01S specification refers to 01SB02C Rev 1 - ISSUED FOR FIELD HYDROTEST NP PREPARED BY

Arthur Zdziechowski
DATE

9/7/2016
Pembina Prairie Facilities LTD
Rev 0 - ISSUED FOR Review
CHECKED BY DATE
2. Pipeline Riser line materials are per Pembina CP6
Piping Spec. All other line materials are per Pembina
Vantage Booster Pump Station: Carnagh
ENGINEER DATE
CP2 Piping Spec. Please see notes on ISO drawings.
LSD 15-36-009-21 W3M
PROJ. MANAGER DATE
3. All lines have a 100% Radiography Test on welds.
Nathan Pleau 9/7/2016 LINE DESIGNATION TABLE
CLIENT APLXPR. DATE AFE No. DWG No SHEET REV

C/15073 1