DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES

TPG CVT150 - RFQ 012 : 150 KV OUTDOOR CAPACITOR VOLTAGE TRANSFORMER

NO. DESCRIPTION UNIT REQUIRED

Manufacturer to be mentioned
Type of Designation to be mentioned
1 Standard IEC 61869-1; IEC 61869-5
2 Service Condition Outdoor, Tropical Area
3 Nominal voltage kV 150
4 Highest Voltage for equipment (Um) kV 170
5 Rated frequency (Fr) Hz 50
6 Rated primary voltage (Upr) kV 150/√3
7 Rated secondary voltage (Usr) V 115/√3
(110/√3 V especially for East Java and Sulawesi)

RATED INSULATION LEVEL


8 Insulation Class :
- Power frequency withstand voltage kVrms 325
- Lightning impulse withstand voltage kVp 750
- Switching impulse withstand voltage kVp N.A.
9 Creepage distance phase to earth (according to degree of pollution)
Very Heavy Pollution mm/kV 31

GENERAL
10 Rated voltage factor and corresponding rated time, continuous 1.2
11 Rated voltage factor and corresponding rated time, 30 sec. 1.5
12 Dissipation factor of capacitor (tan δ) % ≤0.5
13 Accuracy class :
- for protection 3P
- for instrument and metering 0.5
14 Rated burden :
- for protection VA 15
- for instrument and metering VA 15
- total simultaneous burden VA 30
15 Rated capacitance pF 4000 up to 10000
16 Capacitance tolerance - 5 % to + 10 %
17 Ferro resonance :
- Duration of ferro resonance oscillation s ≤0.5
- Maximum instantaneous error after ferro resonance oscillation % ≤10
18 Suitable for use as coupling capacitor Yes

OTHERS :
19 Insulator material silicon rubber or pocelain
Oil compensation corrosion-proof metallic bellow with pressure relief
20 device
21 Mechanical characteristics : Suitable for mounting line trap minimum 250 kg
a) Average mechanical breaking load N to be mentioned
b) Minimum failing loads :
- tensile loads N to be mentioned
- torsional loads Nm to be mentioned
- cantilever loads N to be mentioned
- compressive loads N to be mentioned
c) Max. electromechanical failing load to be mentioned
d) Max. operating load N to be mentioned
22 Oil level indicator Direct type
23 Secondary terminal box Made from corrosion resistant die cast alluminium,
min.IP54, removable, undrilled, terminal flange with
drainage

24 Earthed terminal one earth terminal


25 Sesmic Condition (Earthquake Factor) (according to seismic map) g ≥ 0,3
PROPOSED AND GUARANTEED (FINAL /
CLARIFIED)

CG Power and Industrial Solutions Limited


CVE 170/750/50
IEC 61869-1; IEC 61869-5
Outdoor, Tropical Area
150
170
50
150/√3
115/√3

325
750
N.A.

31

1.2
1.5
≤0.5

3P
0.5

15
15
30
4400
- 5 % to + 10 %

≤0.5
≤10
Yes

Porcelain
Corrosion-proof Metallic Bellow without
pressure relief device
Suitable for mounting line trap max. 250 kg
10000

2500
N/A
2500
N/A
N/A
N/A
Direct type
Made from corrosion resistant hot dip
galvanized mild steel, min.IP54, removable,
undrilled, terminal flange with drainage

One Earth Terminal


0,5