You are on page 1of 2

Project Responsible department

PB ABK A2 ABB Ltd.

Replacing

PB ABK A2.CCMMT-01.4.16 kV.Proteccion M-01


C02
Rev. Modification Rel. date Created by Based on

Settings

Group / Parameter Name IED Value PC Value Unit Min Max


MPTTR1: 1
3Ith>M
Operation on
Rated current 0.60 xIn 0.30 2.00
Initial thermal Val 74.0 % 0.0 100.0
Setting Group 1
Overload factor 1.10 1.00 1.20
Alarm thermal value 95.0 % 50.0 100.0
Restart thermal Val 40.0 % 20.0 80.0
Negative Seq factor 6.0 0.0 10.0
Weighting factor p 50.0 % 20.0 100.0
Time constant normal 80 s 80 4000
Time constant start 80 s 80 4000
Time constant stop 80 s 80 8000
Env temperature mode FLC Only
Env temperature Set 40.0 °C -20.0 70.0
Setting Group 2
Overload factor 1.05 1.00 1.20
Alarm thermal value 95.0 % 50.0 100.0
Restart thermal Val 40.0 % 20.0 80.0
Negative Seq factor 6.0 0.0 10.0
Weighting factor p 50.0 % 20.0 100.0
Time constant normal 320 s 80 4000
Time constant start 320 s 80 4000
Time constant stop 500 s 80 8000
Env temperature mode FLC Only
Env temperature Set 40.0 °C -20.0 70.0
Setting Group 3
Overload factor 1.05 1.00 1.20
Alarm thermal value 95.0 % 50.0 100.0
Restart thermal Val 40.0 % 20.0 80.0
Negative Seq factor 6.0 0.0 10.0
Weighting factor p 50.0 % 20.0 100.0
Time constant normal 320 s 80 4000
Time constant start 320 s 80 4000
Time constant stop 500 s 80 8000
Env temperature mode FLC Only
Env temperature Set 40.0 °C -20.0 70.0
Setting Group 4

Project Responsible department

PB ABK A2 ABB Ltd.

Replacing

PB ABK A2.CCMMT-01.4.16 kV.Proteccion M-01


C02
Rev. Modification Rel. date Created by Based on
Project Responsible department

PB ABK A2 ABB Ltd.

Replacing

PB ABK A2.CCMMT-01.4.16 kV.Proteccion M-01


C02
Rev. Modification Rel. date Created by Based on

Group / Parameter Name IED Value PC Value Unit Min Max


Overload factor 1.05 1.00 1.20
Alarm thermal value 95.0 % 50.0 100.0
Restart thermal Val 40.0 % 20.0 80.0
Negative Seq factor 6.0 0.0 10.0
Weighting factor p 50.0 % 20.0 100.0
Time constant normal 320 s 80 4000
Time constant start 320 s 80 4000
Time constant stop 500 s 80 8000
Env temperature mode FLC Only
Env temperature Set 40.0 °C -20.0 70.0
Setting Group 5
Overload factor 1.05 1.00 1.20
Alarm thermal value 95.0 % 50.0 100.0
Restart thermal Val 40.0 % 20.0 80.0
Negative Seq factor 6.0 0.0 10.0
Weighting factor p 50.0 % 20.0 100.0
Time constant normal 320 s 80 4000
Time constant start 320 s 80 4000
Time constant stop 500 s 80 8000
Env temperature mode FLC Only
Env temperature Set 40.0 °C -20.0 70.0
Setting Group 6
Overload factor 1.05 1.00 1.20
Alarm thermal value 95.0 % 50.0 100.0
Restart thermal Val 40.0 % 20.0 80.0
Negative Seq factor 6.0 0.0 10.0
Weighting factor p 50.0 % 20.0 100.0
Time constant normal 320 s 80 4000
Time constant start 320 s 80 4000
Time constant stop 500 s 80 8000
Env temperature mode FLC Only
Env temperature Set 40.0 °C -20.0 70.0