LV ACB & MCCB Setting

Station: CMPSS-1
Panel: LV.C1-1,2,3,4,5,6,7,8,9,10

Long Time Protection (L) Short Time Protection (S) Instantaneous (I) Earth Fault Protection
ACB
ACB Rating
Sr.No Tag Number Tripping
In (A) Setting Setting
Unit type Range Setting Value Range Setting Range Setting Value Range Range Setting Range Setting Value
Value Value
(Ir) (Ir) (tr)s Value (tr)s (Isd) (Isd) (tsd) s (Ii) Value (Ii) (A) (A)
(tsd)s (tsd)s
1 C1-1-1B 2000 ET6G 0.4-1 0.80 0.5-24 0.50 1.5-10 6.00 0.1-0.4 0.20 2-15 10.00 500-1200 500.00 0.40
2 C1-6-1B 2000 ET6G 0.4-1 0.80 0.5-24 0.50 1.5-10 6.00 0.1-0.4 0.20 2-15 10.00 500-1200 500.00 0.40
3 LV-DG-1 2000 ET6G 0.4-1 0.98 0.5-24 0.50 1.5-10 4.00 0.1-0.4 0.20 2-15 4.00 500-1200 500.00 0.30

DG ACB setting

Long Time Protection (L) Short Time Protection (S) Instantaneous (I) Earth Fault Protection
ACB
ACB Rating Setting Setting
Sr.No Tag Number Tripping Range Setting Value Range Setting Range Setting Value Range Range Setting Range Setting Value
In (A) Value Value
Unit type (Ir) (Ir) (tr)s Value (tr)s (Isd) (Isd) (tsd) s (Ii) Value (Ii) (A) (A)
(tsd)s (tsd)s
1 DG-ACB 2500 Micr 6.0 0.4-1 1.00 0.5-24 0.5 1.5-10 3.00 0.1-0.4 0.20 2-15 4.00 500-1200 500.00 0.40

DG Control Panel- EMCP Relay


Protection : Overcurrent
Type Configuration : Normal Inverse Curve
Pickup Value: 110%
Time dial: 0.2